Solutions for diverse application.

Moulded Case
Circuit Breakers
Stability: Activated
Up and Running, Uninterrupted 1

In every industry, big or small, electrical power supply The dsine range, a new generation of MCCBs, is a
is critical. Even a few seconds of interruption or combination of state-of-the-art design and modern
instability can result in huge financial losses, even loss user-friendly features. It also boasts a wide choice of
of life. We have little or no control over the nature or protective releases, ergonomics, aesthetics and
stability of power supply. The unpredictable nature of compactness. The range, designed to meet the
power makes it important to take appropriate steps changing needs of users after extensive analysis and
for the protection and safety of your organisations user feedback, can satisfy the most demanding
employees and equipment. system requirements.

In line with this objective, Larsen & Toubro presents Complemented by a wide array of accessories, the
dsine a highly advanced and sophisticated range of dsine range offers comprehensive solutions to
Moulded Case Circuit Breakers (MCCBs). customer applications ensuring operational safety,
reliability and versatility.

Moulded Case
Circuit Breakers

L&T Turning technology to your advantage


Over the last five decades, L&T has earned a place selection, installation and effective after-sales
among the worlds leading manufacturers of Low service, across the country.
Voltage Switchgear with the scale, sophistication and
L&T is one of the first companies to introduce MCCBs
range to meet global benchmarks.
in India. Over the years, we have developed our
In keeping with our leadership position in the Indian products to meet the ever-evolving demands of the
market, we also provide expert assistance in product market.
Obstacles: Deleted
Overcoming Challenges 3

Original Equipment Manufacturers (OEMs)


For Original Equipment Manufacturers (OEMs), every offer neutral and earth fault protection with 3P
moment poses a new challenge. The dsine range of MCCBs. Equipped with common accessories for the
MCCBs has been created keeping this in mind. Built in entire range, these MCCBs assure excellent savings by
accordance with the highest technical standards, reducing your inventory costs.
dsine MCCBs assure reliable and maintenance-free Whats more, our experienced sales & service team is
operation. They have been designed to adapt to just a call away. Our team is adept at handling
changes and overcome the challenges of your day-to- queries and complaints and is trained to offer you
day operations. techno-commercial solutions on time, every time.
Besides being available in 4P version to serve OEMs, After all, forging long-term associations has always
such as DG sets, dsine MCCBs come with an external been the cornerstone of our business.
neutral CT for the microprocessor-based version to

Moulded Case
Circuit Breakers
Versatility: Downloaded

Paper Industry

Sugar Industry

Oil Industry

Gas Industry
Meeting Diverse Demands 5

Industries
Every industry is unique, and so are its requirements. MCCBs with high breaking capacities cater to high
Industries as diverse as paper, sugar, oil & gas have voltage applications such as windmills and mines.
different sets of needs. Thankfully, dsine MCCBs, They are compact so the panel builder can optimise
available in various current ranges (20A to 1250A), panel size. They are thoroughly factory-tested with
are designed to efficiently handle such diversity. adequate quality controls in place. Moreover, since
these MCCBs are designed to handle high-value
Our Thermal Magnetic as well as Microprocessor-
capacitive inrush currents, no nuisance tripping is
based releases with various breaking capacities cater
to multiple industrial needs. Built with the latest observed in APFC panels. Motor loads being most
technology, dsine MCCBs deliver optimum efficiency vital, our design team has also developed special
even in the most adverse environmental conditions. dsine-M series for motor back-up protection ranging
from 32A to 630A.
Efficiency: Initiated
Paving The Path to Progress 7

Building Sector
Today, efficient energy management holds the key to Choose from a variety of communication protocols
growth and development in any sector. Moreover, in including MODBUS RTU and Bluetooth available with
most sectors, such as the building sector, energy our new MATRIX releases. In todays world of high-
management has become mandatory. Our new range end residential buildings or commercial malls, our
of dsine MATRIX releases with advanced technology motorised dsine MCCBs with the fastest changeover
is specially designed with energy management in from mains to DG in less than 300 milliseconds are
mind. indeed the most reliable choice. Our Auto Source
Transfer System has almost eliminated the risk of loss
MTX3.0 releases with power metering and
of data.
communication capabilities are ideal for remote
annunciation in Data Centres and IT Parks.
Performance: Delivered
Delivering Unparalleled Results 9

DC Systems, UPS, Battery Chargers


Unlike AC breaking, DC breaking is a critical They are also available for lower DC voltages such as
phenomenon that causes severe damage. Thats why, battery chargers.
we offer DC MCCBs from the dsine family. A range
The SD (Switch Disconnector) version of dsine MCCBs
that has been designed and developed specially for
can be used at the incoming and outgoing terminals
DC applications such as UPS and battery chargers. of UPS for isolation. Our SD is designed to withstand
Choose from a wide range of DC voltages (up to high currents without compromising on Service
500V) and DC breaking capacities (up to 36kA) Performance.
available as per various application requirements.
Reliability: Ensured
Soaring High with Consistency 11

Infrastructure
Monitoring and controlling electrical installations at As power supply is critical for airports and hospitals,
places like airports, hospitals etc. demands high-end, our dsine MCCBs with ASTS offer changeovers in less
reliable solutions. MATRIX releases are built precisely than 300 milliseconds coupled with a variety of other
for such purposes. protections in case of under voltage, phase
unbalance, etc.
Communication capable MATRIX releases with
power and energy metering help in modernisation. A variety of settings in MATRIX releases helps in
These releases are made compatible with HMI choosing the correct selection for fault clearing,
(Human Machine Interface) and DCS (Data Control while trip & event recording with MATRIX releases
System). helps in analysing the faults in detail.

Our dsine MCCBs are shipped to Europe, Africa, Australia, Middle East,
South East Asia, China and America. In India, we have the largest
stockist network with over 700 stockists. To find the ideal dsine MCCB
suitable for your requirements, turn the page.
INDEX
Overview

Product Data

Accessories

Characteristic Curves

Wiring Diagrams

Dimensions
Overview
n Range 16
n
Standards & Approvals 18
n
Structure & Features 19
n
Marking & Configuration 20
n
Trip Units 21
n
Accessories 22
16 Range

DN4 DN3 DN2 DN1 DN0

State-of-the-art design, user-friendly features and a wide spectrum of protection releases form the hallmarks
of the dsine range. Also recognised for its ergonomics, aesthetics and compactness, it belongs to a new
generation of MCCBs. Specially designed and developed for extreme tropical conditions, it promises reliable
performance at high ambient and humid environment.
dsine, unfailingly, caters to the ever-evolving needs of customers, derived after in-depth analysis and customer
feedback. Because we understand our customers' requirements and demands, our contemporary range of
MCCBs never fall short of ensuring complete customer satisfaction. Moreover, complemented by a host of
accessories, the dsine range delivers comprehensive solutions to customer applications ensuring operational
safety, reliability and versatility.
Range 17

Features
Range
available from 20A to 1250A
Available
in 3 pole & 4 pole
Range of 25kA / 36kA / 50kA / 70kA / 100kA breaking capacities

Microprocessor and Thermal-Magnetic based protection releases

MCCBs for Motor backup protection

MCCBs for Distribution and SD versions

Suitable for DC application

Manual, Rotary or Motorised versions

Wide range of common Internal and External accessories

DN0
Rated Current 20, 25, 32, 40, 50, 63, 80, 100, 125*A
Release Thermal-Magnetic
DN1
Rated Current 125, 160, 200, 250A
Release Thermal-Magnetic
DN2
Rated Current 63, 80, 100, 125, 160, 200, 250A 40, 63, 100, 160, 250A
Release Thermal-Magnetic Microprocessor
DN3B
Rated Current 320, 400A
Release Thermal-Magnetic
DN3
Rated Current 320, 400, 500, 630A 400, 630A
Release Thermal-Magnetic Microprocessor
DN4
Rated Current 800, 1000, 1250A
Release Microprocessor
* Available only in DN0-D

Breaking Capacities (Icu)


18 Standards & Approvals

range of MCCBs and Accessories comply with following


international standards
IEC 60947-1, EN 60947-1, IS/IEC 60947-1
Low-voltage switchgear and controlgear, Part 1: General Rules
IEC 60947-2, EN 60947-2, IS/IEC 60947-2
Low-voltage switchgear and controlgear, Part 2: Circuit-breakers
IEC 60947-3, EN 60947-3, IS/IEC 60947-3
Low-voltage switchgear and controlgear, Part 3: Switches, disconnectors,
switch-disconnectors and fuse combination units
IEC 60947-4, EN 60947-4, IS/IEC 60947-4
Low-voltage switchgear and controlgear, Part 4: Contactors and Motor-starters
Third party certificates (ERDA/CPRI) available for dsine range of MCCBs

NABL
NABL accreditation is a formal recognition of the technical competence of testing,
calibration or medical laboratory for a specific task following ISO/IEC 17025:2005
Standard. Accredited laboratories have the responsibility of satisfying the criteria of
laboratory accreditation at all times, which are verified during Surveillance and Re-
assessment visits by NABL. Further the accredited laboratories should prove their
technical competence by satisfactory participation in recognized Proficiency Testing
Programmes.
L&Ts Switchgear Testing Lab is NABL accredited subject to continued satisfactory
compliance to above standard & additional requirements of NABL.
All dsine range of MCCBs are tested in L&T's NABL accredited Switchgear Testing Lab.

marking
A CE marking is a European marking of conformity that indicates a product complies
with the essential requirements of the applicable European laws or directives with
respect to safety, health and environment and consumer protection. Generally, this
conformity to the applicable directives is done through self-declaration and is required
on products in the countries of the European Economic Area (EEA) to facilitate trade
among the member countries. The manufacturer or their authorized representative
established in the EEA is responsible for affixing the CE marking to their product. The
CE marking provides a means for a manufacturer to demonstrate that a product
complies with a common set of laws required by all countries in the EEA to allow free
movement of trade within the EEA countries.
L&Ts dsine range of MCCBs conform to the Low voltage directive 73/23/EEC as
amended by directive 93/68/EEC, provided if it is used in the application for which it is
made and is installed and maintained in accordance with professional practices with
relevant installation standards and operating instructions.

IECEE CB SCHEME DEKRA (KEMA) certified


The IECEE CB SCHEME is a multilateral agreement among participating countries and
certification organizations. A manufacturer utilizing a CB test certificate issued by one
of the accepted National Certification Bodies (NCBs) can obtain certification marks of
the latter, within their scope of adherence, in the countries where the accepted NCBs
are located.
L&Ts dsine range of MCCBs are certified for IECEE CB scheme by DEKRA (KEMA) which
is a world renowned organisation with a heritage of 150 years in testing, inspections &
certification, risk management and verification.
Structure & Features 19

Low Watt Loss


The entire current carrying
path is optimally designed to
achieve low watt loss Arc Chutes
Silver contacts offer low Arc chutes are designed for
contact resistance thus helping efficient and faster arc
in low watt loss quenching

Current Limiting MCCBs


The unique speed contact
MCCB Mechanism system with current limiting
Quick make, quick break & trip feature accelerates the
free mechanism opening of contacts during
short circuit resulting in very
low let through energy

Positive Isolation Knob


Indicates the true position of Designed for better grip
the contacts - ensures
operator safety Indicates "ON", OFF" and
TRIP" position of MCCB

No Load Line Bias Release


Either side of MCCB terminals Thermal & Microprocessor
can be used as load or line based releases are available
20 Marking & Configuration

Terminal Connections

Standard Characteristics
}Uimp: Impulse withstand voltage
}Ue: Rated operational voltage
}Icu: Rated Ultimate breaking Utilization Category
capacity Brand
}Ics: Rated Service breaking capacity Frame Size
Symbol of suitability
Standards for Isolation
Mark
Indication of Closed (I/ON)
Company Logo

Operating Knob

Indication of Open (O/OFF)

Release
Current Rating of MCCB
Release Settings "Push to Trip" button

Release name

Terminal Shroud
Trip Units 21

Variable Thermal,
Fixed Magnetic
(DN0, DN1, DN3B)

Thermal Magnetic
Variable Thermal, Variable Magnetic (DN2, DN3)
Releases

MTX1.0 with LSI (DN2, DN3, DN4)

MTX2.0 with LSING + Current Metering (DN2, DN3, DN4)

Inst

Microprocessor
Releases

MTX3.0 with LSING + Communication capable +


Power Metering (DN2, DN3, DN4)

Inst

Motor Protection Release (DN0, DN1, DN2, DN3 -


Magnetic Protection only)

In 630 A
Magnetic Release

DN3-M

Switch Disconnector (DN0, DN2, DN3, DN4)

Isolator
22 Accessories

1 Spreader Terminals

2 Phase Barriers

3 Undervoltage Release

4 Shunt Release

5 Auxiliary Contact 12

6 Trip Alarm Contact

7 Auxiliary + Trip Alarm Contact

8 Direct Rotary Handle

9 Extended Rotary Handle

10 Panel Mounted Keylock

11 Stored Energy Electrically Operated Mechanism

12 Mechanical Interlock Kit

13 Communication Module
16
14 Voltage Module

15 Display Module 4 3

16 External Neutral CT
(with Adaptor Kit)

8
23

15
14
13

6 7
5

11
10
9
Product Data
MCCBs for Power Distribution 26
Technical Datasheet
Motor Backup Protection
Isolator Application
MCCBs for DC Applications
Protection Releases
MCCBs for Different Applications 42
Auto Source Transfer Application
26 MCCBs for Power Distribution 27

Technical Datasheet
Frame 100A 125A 250A 250A 400A 400A 630A 1250A
DN0-100 DN0-125 DN1-250 DN2-250 DN3B-400 DN3-400 DN3-630 DN4-1250
Type
C D D C N D N S H V D D N S D N S V N S V
TM/MP MP (MTX MP (MTX
Release TM TM TM (MTX1.0/2.0/3.0) TM TM/MP (MTX1.0/2.0/3.0) TM/MP (MTX1.0/2.0/3.0) MP (MTX1.0/2.0/3.0)
1.0/2.0/3.0) 1.0/2.0/3.0)
20, 25, 32, 125, 160, 40, 63, 80, 40, 63,
Current Range In (A) 40, 50, 63, 125 100, 125, 160, 100, 160, 320, 400 320, 400 500, 630 400, 630 800, 1000, 1250
200, 250
80, 100 200, 250 250
Poles 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Impulse withstand Voltage Uimp (kV) 6 6 6 8 8 8 8 8
Rated Operational Voltage Ue (V) (MAX) 600 600 600 690 690 690 690 690
Rated Insulation Voltage Ui (V) 690 690 690 800 800 800 800 800
Utilization Category A A A A A A A A
Standard IS/IEC60947-2, IEC60947-2 & EN60947-2
240 VAC 40 65 65 65 65 50 70 100 - - 50 50 70 100 50 70 100 - 70 100 -
415 VAC 25 36 36 25 50 36 50 70 80 100 36 36 50 70 36 50 70 100 50 70 100
Icu(kA) 480 VAC 10 10 10 10 10 25 36 42 65 65 25 25 36 42 25 36 42 65 25 36 65
Rated 550 VAC 8 8 8 8 8 18 25 36 - - 15 15 20 25 15 20 25 - 20 25 -
Short 600 VAC 5 5 5 5 5 16 18 22 - - 12 12 18 22 12 18 22 - 16 20 -
Circuit 690 VAC - - - - - - - - - 36 - - - - - - - 50 - - 50
Breaking
Capacity 240 VAC 100% 50% 50% 50% 50% 100% 100% 100% - - 100% 100% 100% 100% 100% 100% 100% - 100% 100% 100%
Ics as % Icu 415 VAC 100% 50% 50% 100% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
480 VAC 100% 50% 50% 50% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
550 VAC 100% 50% 50% 50% 50% 100% 100% 100% - - 100% 100% 100% 100% 100% 100% 100% - 100% 100% -
600 VAC 100% 50% 50% 50% 50% 100% 100% 100% - - 100% 100% 100% 100% 100% 100% 100% - 100% 100% -
690 VAC - - - - - - - - 50% - - - - - - - 50% - - 50%
Mechanical 40000 40000 10000 25000 25000 10000 15000 15000 15000 20000
Life
Electrical @1.0 In 4000 2500 3000 10000 10000* 4000 4000 4000 4000* 3000*
Making Capacity (kA) 52.5 75.6 75.6 52.5 105 75.6 105 154 176 220 75.6 75.6 105 154 75.6 105 154 220 105 154 220
Operating Frequency (Hz) 50 / 60
Total Opening Time <10msec <20msec
Finger-proof Terminals Yes
Suitable for Isolation Yes
IP class IP40
Pollution Degree III
Load Line Bias NO
Ambient Temperature -5OC to 55OC
O O
Storage Temperature -35 C to 70 C
Mounting Positions in Vertical Plane Vertical and 90 deg in both directions
3-Pole 75 x 60 x 130 105 x 60 X 165 105 x 96 x 179 140 x 111 x 205 140 x 111.5 x 266 140 x 111.5 x 266 210 x 143 x 370
Dimensions (WxDxH) mm
4-Pole 100 x 60 x 130 140 x 60 X 165 140 x 96 x 179 184 x 111 x 205 183.5 x 111.5 x 266 183.5 x 111.5 x 266 278 x 143 x 370
Weight (kg) (3/4 Pole) 0.8/1.1 0.73/1 0.73/1 1.55/2 2.5/3.3 4.0/5.0 5.5/7.2 6/7.8 6.3/8 17 / 22
Auxiliary Contact 1 C/O or 2 C/O
Trip Alarm Contact 1 C/O or 2 C/O 1 C/O
A
INTERNAL Auxiliary & Trip Alarm Contact 1 C/O + 1 C/O
C
C Shunt Release 240/415 V AC 50 Hz 110 / 415 V AC 50 Hz, 110 / 220 V DC, 24 V DC $
E Under Voltage Release 240 V AC 50 Hz
S Rotary Operating Mechanism (Direct/Extended)
S Electrical Operating Mechanism
#
O Mechanical Interlock Kit
R Spreader Terminals
I EXTERNAL
Key lock
E Neutral CT with Adaptor kit Available for 3P MCCBs with MTX2.0 & MTX3.0 release only
S
Current Metering Module Available for MTX2.0 release for current metering only @
Display, Communication and Voltage Module Available for MTX3.0 release for Communication & Power metering

$ : 'NO' of control contactor to be connected in series for 220V DC, 24V DC Note:
@: Contains display module & metering module, separate cable required for connection Any two internal accessories can be mounted at a time
V version MCCBs, to be used with extended ROM only
#: Only Extended ROM available Separate earth fault module required for earth fault protection using TM releases
* : at 415V Icu: Rated ultimate short-circuit breaking capacity
DN2 - 1500 @ 690V Ics: Rated service short-circuit
O
breaking
O
capacity
DN3 - 1000 @ 690V Reference temperature 40 C & 50 C
DN4 - 800A - 2500 @ 415V
28 MCCBs for Motor & Isolator

Motor Backup Protection


AC induction motors are the vital elements in any
production process and hence constitute majority
of loads in Industry and other installations. The M
version MCCBs in dsine range are developed
specially to give short circuit protection for all types DN3-M
of motors. Selection of MCCB using our type 2
charts give reliable performance of the motors.

Frame 100A 160A 250A 400A 630A


DN0-100 DN1-160 DN2-250 DN3-400 DN3-630
Type
M M M MH M M MV
Current range (A) 32-100 100-160 100-250 32-250 320-400 500-630 320-630
Poles 3 3 3 3 3 3 3
400 / 415 V 50 50 50 80 50 50 100
Icu (kA) 480 V - - 36 65 36 36 65
Rated 690 V - - 15 - 15 10 50
Short 50 50 50 80 50 50 100
415 V
Circuit Iq (kA)
Breaking 480 V - - - 65 - - 65
Capacity 400 / 415 V 25% 25% 100% 100% 100% 100% 100%
Ics as % Icu 480 V - - 100% 100% 100% 100% 100%
690 V - - 100% - 100% 100% 50%
Magnetic Setting 9In 10In 6-10In*
Note: MV version MCCBs to be used with extended ROM only.

Isolator Application
dsine MCCBs with Switch Disconnector version offer solution for switching various loads such as UPS, Battery
Banks etc. with various advantages. These MCCBs differ from regular MCCBs only in terms of absence of
protection trip units. These MCCBs can be used for following applications for isolation purpose:
For local isolation- such as very close to Motor load
Generally used at the incoming of any sub-distribution
As an Isolator for Bus coupler
As an automatic switch
For switching applications of motors with VFDs, soft starters
SD MCCBs are always backed up by the Short Circuit Protection Device (SCPD) to protect downstream
loads/installations against short circuit. Our dsine SD MCCBs offer following advantages.
Suitable for Positive isolation
Available with 3P & 4P versions
Can be used with Under Voltage Protection
Remote tripping through Shunt release
Motor operated MCCBs
Status feedback possible
Following are the specifications of SD MCCBs

Frame 160A 250A 400A 400A 630A 800A 1000A 1250A


Type DN0-160SD DN2-250SD DN3B-400SD DN3-400SD DN3-630SD DN4-1250SD
Current Range (A) 32-160 100-250 320-400 320-400 500-630 800 1000 1250
Poles 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
ICW (kA) 2 3.6 5.5 5.5 7.6 10 12 15
Duration (sec) 1 1 1 1 1 1 0.5 0.1

Note: Icw - Rated short-time withstand current


* To be set at 10In only
MCCBs for DC Applications 29

DC power distribution is an upcoming technology in this modern era due to its most rigorous network power
applications such as
AC-DC Power System
DC-DC Converter Systems
DC-AC Inverter Systems
DC UPS
Batteries & Accessories
Solution to alternative energy-Solar Power
We offer dsine MCCBs for the protection of DC systems in variety of current ratings from 20A-630A, voltage
ratings upto 750V and various breaking capacities ranging from 5kA to 36kA.

Frame DN0-125* DN1-250 DN2-250 DN3-400 DN3B-400 DN3-630


Type C D C N D N S D N S D D N S
Release TM
Poles 3 or 4
20, 25, 32, 125, 160, 63, 80, 100, 125,
Rated current In (A) 40, 50, 63, 320, 400 320, 400 500, 630
80, 100, 125 200, 250 160, 200, 250

250 V DC 20 20 20 30 36 20 30 36 25 20 30 36
Icu (kA rms) 500 V DC 15 15 15 20 25 15 20 25 10 15 20 25
750 V DC - - 10 15 20 10 15 20 - 10 15 20
Type of connection 3P in series
L/R (msec) <15msec
*Available only in DN0-125D

Switching of DC currents is much severe phenomenon than switching AC currents due to non occurrence
of natural zero. Hence DC MCCBs are desired to give less breaking capacity than AC MCCBs for the same
voltage & currents. As per the earthing of the system, we recommend following connections for breaking
the fault currents.

Earthed system Earthed system Insulated system


Any one polarity is earthed Midpoint of the system is earthed No earthing

No. of poles required to No. of poles required to No. of poles required to


perform the break must perform the break must perform the break can be
be in series on one polarity be on both the polarities shared between two polarities

+ + LOAD + LOAD
250/500V

250/500V

250/500V

- LOAD - -

Note: Suitable for Thermal Magnetic release only


30 Protection Release for MCCBs

Thermal-Magnetic Release
Features of Thermal-Magnetic Release
Adjustable
overload settings
Fixed
/ Adjustable short circuit settings
True RMS
sensing Settings
Protection
Push
to Trip button DN0 & DN1 DN2 & DN3 DN3B

Overload 80% - 100%In 80% - 100%In 80% - 100%In

Short Circuit 9In (fixed) 6 - 10In 9In (fixed)

Earth fault External GF Module required*

Microprocessor Release
Features of MTX1.0

Overload Protection with inverse time delay

Adjustable Trip class

Short Circuit Protection with selectable
time delay

Provision of Thermal memory defeat

Provision for release testing

Overload indication

Power ON LED

Self powered

True RMS sensing

Push to Trip button

MTX1.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 5%
Time delay, tr (Inverse) 10s at 6Ir, 3s at 6Ir, 10s at 7.2Ir, 3s at 7.2Ir
Protection mode ON / OFF
Thermal memory Enable / Disable
Short Circuit
Current setting, Is (Is = x Ir) 1.5, 2.5, 4.0, 5.5, 6.5, 8.0Ir
Time delay, ts Instantaneous / 100ms
Protection mode ON / OFF
Note: Factory Settings - O/L: 100%In, Curves: 6Ir@10s, Thermal Memory: Off, S/C: 5.5Ir @ Instantaneous
Release provides in-built instantaneous override protection fixed @ 10In
* Refer page 51
Protection Release for MCCBs 31

Microprocessor Release
Features of MTX2.0

Overload Protection with inverse time delay

Adjustable Trip class

Short Circuit Protection with selectable


time delay

Inbuilt Earth fault and Neutral overload

Inst
protection

Provision of Thermal memory defeat

Provision for release testing

Overload indication

Power ON LED

Panel mounted O-LED display for current metering

Self powered

True RMS sensing

Push to Trip button

Latest trip record

MTX2.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 5%
Time delay, tr (Inverse) 10s at 6Ir, 3s at 6Ir, 10s at 7.2Ir, 3s at 7.2Ir
Protection mode ON / OFF
Thermal memory Enable / Disable
Overload (Neutral)
Current setting, IN (IN = x Ir) 50%, 100% and 150%Ir
Time delay, tN 200ms / Same as overload
Protection mode ON / OFF
Short Circuit
Current setting, Is (Is = x Ir) 1.5, 2.5, 4.0, 5.5, 6.5, 8.0Ir
Time delay, ts Instantaneous / 100ms
Protection mode ON / OFF
Earth Fault
Current setting, Ig (Ig = x In) 20% to 50%In in steps of 10%
Time delay, tg 100ms / 200ms
Protection mode ON / OFF
Note: Factory Settings - O/L: 100%In, Curves: 6Ir @10s, S/C: 5.5Ir @ Instantaneous, Thermal Memory: Off, E/F: Off, Neutral: Off.
Release provides in-built instantaneous override protection fixed @ 10In
32 Protection Release for MCCBs

Advanced features of MTX2.0


Panel Mounted Display for Current Metering &
Trip Record
System currents & latest trip record can be viewed with panel
door closed.

Power
Supply
Module

Metering Module

Port with Polarized Connector


MTX2.0 release with metering port is implemented with poka-
yoke technology using polarized connector to ensure correct
insertion of metering harness, thus avoiding unnecessary
errors.

Digital Current Metering


MTX releases are designed with protection class
CTs which measure true RMS values. Inbuilt
current metering does not require separate CTs
hence maintenance is easy.

O-LED Display
O-LED display allows the operator a wide viewing
angle.
O-LEDs showing current metering has got faster
response time and also consumes less power,
hence saves energy. It has better contrast ratio as
well. Display Module
Protection Release for MCCBs 33

@6Ir

Inst
3s
10s
@7.2Ir

2 3 1

Inbuilt Earth Fault Protection 1


Inbuilt earth fault protection function does not require any separate trip coil & external CBCT, thus saving
panel space, cost & improving the overall hygiene. Earth fault protection limits expenses by preventing
damage to other equipment.

Thermal Memory 2
Thermal memory protects the system from thermal stresses generated by cumulative heating caused by
cyclic overload conditions thus allowing the system to return to a safe operating temperature. This function
also allows an optimization of cables or bus bar protection in case of low amplitude repetitive faults.
Advance tripping increases the overall life and eliminates the production downtime incase of severe faults.

Multiple Trip Class 3


Enhances adjustability for better enhanced coordination with other devices to achieve correct motor
switching and ensures protection of the starter elements in order to guarantee the plant safety.

Precise Selection of Parameters


Overload & short circuit settings with minimum step change helps to maintain balance between nuisance
tripping and optimal protection resulting in high continuity of service and reduced call back periods. MTX
release can be adapted to specific requirements of OEM or end-user.

DIP Switches
DIP switches are provided on front side of the release for easy operations. These switches give you quicker
option to precisely change selection, offering high life.

Overload Indication 4
Improves uptime and productivity by setting alarms for unbalanced loads so that proactive measures can
be taken to avoid overload conditions.

% of Ir Overload LED indication


30% Green LED
85% Faster blinking of green LED
115% Sequential ON/OFF of green LED

Self Powered
MTX releases do not need any external power supply hence require no extra devices and wires to power up.
Note: For wiring diagram, please refer page no. 62
34 Protection Release for MCCBs

Various Protection Settings

@6Ir

Inst
Overload Protection, (Ir = x In)

3s
10s
@7.2Ir
0.4 0.4 0.4 0.4 0.4 0.4 0.4

DIP Switch
r

r
Position
q
r

q
r

r
q

r
q

r
q

r
q

r
Setting Bypass 40% 45% 50% 55% 60% 65%

0.4 0.4 0.4 0.4 0.4 0.4 0.4

DIP Switch
r

r
Position
q
r

q
r

q
r

q
r
q

r
q

r
q

r
Setting 70% 75% 80% 85% 90% 95% 100%

Thermal Memory

0.4 0.4

DIP Switch
r

Position
q
r

q
r

Setting Bypass ON

Overload Curves

0.4 0.4 0.4 0.4

DIP Switch
r

Position
q
r

q
r

q
r

q
r

Setting 3s @ 6Ir 10s @ 6Ir 3s @ 7.2Ir 10s @ 7.2Ir

Short Circuit Setting, (Is = x Ir)

DIP Switch
Inst

Inst

Inst

Inst

Inst

Inst

Inst

Position

Setting Bypass 1.5 2.5 4.0 5.5 6.5 8.0


Protection Release for MCCBs 35

Time Delay for Short Circuit Protection

DIP Switch Inst

Inst
Position

Setting Instantaneous 100ms

Earth Fault Setting, (Ig= x In)

0.2 0.2 0.2 0.2 0.2

DIP Switch
Position

Setting Bypass 20% 30% 40% 50%

Time Delay for Earth Fault Protection

0.2 0.2

DIP Switch
Position

Setting 100ms 200ms

Neutral Setting, (IN = x Ir)

Ir * Ir * Ir * Ir *

DIP Switch
Position
0.5
1.0

0.5
1.0

0.5
1.0

0.5
1.0

Setting Bypass 50% 100% 150%*

Time Delay for Neutral Protection

Ir * Ir *

DIP Switch
Position
0.5
1.0

0.5
1.0

Setting 200ms Follows O/L Curve

* With maximum overload setting Ir=0.65In


36 Protection Release for MCCBs

Microprocessor Release
Features of MTX3.0
Overload
Protection with inverse time delay
2 4
I t, I t, SI, LI-VI based over load curves

Short Circuit Protection with selectable time delay


Instantaneous protection with fine settings


Advanced current and voltage based protection function


Protection against current unbalance and single phasing


Comprehensive current, power and energy metering


Inbuilt Earth fault and Neutral overload protection


Provision of Thermal memory defeat


Panel mounted O-LED display


Communication through MODBUS RTU


Pre-trip alarms
Inst

True RMS sensing


Power on LED

Push to Trip button


Self powered

MTX3.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 1%*
Time delay, tr (Inverse) 0.5s to 30s in steps of 0.1s*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Ir in steps of 1%*
Thermal memory Enable/Disable
Overload (Neutral)
Current setting, IN (IN = x Ir) 50% to 150% Ir in steps of 1%*
Time delay, tN 0.2s / same as overload
Protection mode ON / OFF
Short Circuit
Current setting, Is (Is = x Ir) 1.5 to 8 Ir in steps of 0.1*
Time delay, ts 100ms, 200ms, 300ms, 400ms*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Is in steps of 1%*
Instantaneous
Current setting, Ii (Ii = x In) 1.5 to 8 In in steps of 0.1*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Ii in steps of 1%*
Earth Fault
Current setting, Ig (Ig = x In) 10% to 50% In in steps of 5%*
Time delay, tg 100ms to 500ms in steps of 50ms*
Protection mode ON / OFF
* Can be set using display module
Note: Factory Settings - Address:0000, O/L: 100%In, Curves: 6Ir @10s, S/C: 5.5Ir @ Instantaneous, Thermal Memory: Off, E/F: Off,
Neutral: Off.
Release provides in-built instantaneous override protection fixed @ 10In
Protection Release for MCCBs 37

MTX3.0 Additional features with Display Module


Current Protection
Under Current
Current setting (A) Iui (Iui = x Ir) 20 to 85% Ir in steps of 1%
Time delay (s) 1 to 255 in steps of 1
Protection mode ON / OFF
Preset trip alarm setting 110% to 150% Iui in steps of 1%
Current Unbalance
Current setting (A) 30 to 90% Ir in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%

Voltage Protection
Under Voltage
Voltage setting (V) Vuv (Vuv = x Un) 45 to 80% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 110 to 150% Vuv in steps of 1%
Over Voltage
Voltage setting (V) Vov (Vov = x Un) 105 to 150% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90%Vov in steps of 1%
Voltage Unbalance
Voltage setting (V) 5 to 20% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Residual Voltage
Voltage setting (V) 5 to 40% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%

Frequency Protection
Under Frequency
Frequency setting (Hz) F-0.5 to F-5.0 in steps of 0.5
Time delay (s) 0.1 to 30 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set freq in steps of 1%
Over Frequency
Frequency setting (Hz) F+0.5 to F+5.0 in steps of 0.5
Time delay (s) 0.1 to 30 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set freq in steps of 1%
38 Protection Release for MCCBs

Power Protection
Reverse Power
Power setting (W) PR 1 to 5000kW in steps of 1kW
Time delay (s) 0.5 to 60 in steps of 0.5
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% PR in steps of 1%
Lead Pf
Pf setting 0.5 to 0.99 in steps of 1%
Time delay (ms) 100 to 500 in steps of 1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Lag Pf
Pf setting 0.5 to 0.99 in steps of 1%
Time delay (ms) 100 to 500 in steps of 1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%

Other Protections
MD Active
Demand settings 1 to 5000kW in steps of 1kW
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
MD Reactive
Demand settings 1 to 5000kVAr in steps of 1kVAr
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
MD Apparent
Demand settings 1 to 5000kVA in steps of 1kVA
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Phase Sequence
Phase seq setting 123 or 132
Time delay (s) 1 to 5 in steps of 0.1
Protection mode ON / OFF
THD Current
Current setting (A) 5 to 50%Ir in steps of 1%
Time delay (s) 5 to 15 in steps of 5
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
THD Voltage
Voltage setting (V) 5 to 50% Un in steps of 1%
Time delay (s) 5 to 15 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Protection Release for MCCBs 39

Metering & Display


Current Phase, Neutral & Earth
Voltage Phase & Line
Frequency & power factor True RMS
Power Active, Reactive & Apparent
Energy Active, Reactive & Apparent
Maximum demand Active, Reactive & Apparent
THD Current and voltage
Communication
Protocol MODBUS RTU
History
Trip history Last 10 trip records with non volatile memory
Event history Last 10 event records with non volatile memory

Advanced Features of MTX3.0


Energy & Power Measurement
One of the first steps towards energy efficiency is energy ana power measurement. In MTX 3.0

release, in addition to current & voltage measurement, active, reactive and apparent energy &
power can also be measured. This would enable monitoring energy at individual feeder level and
thus help in implementing effective energy management practices in the plant. Moreover, using
communication module, different parameters reading can be viewed on display module.

MCCB with MTX3.0 release

Power Supply
Module

Voltage
Display Module
Module
3 ph 4 wire
Communication AC supply
Module

Energy and Power management functionality using voltage module


40 Protection Release for MCCBs

Advanced Current and Voltage based protections


Reverse Phase:
This function detects the phase reversal of current from
the set sequence. It is especially important in motor
feeder applications
Reverse Power:
One can set the direction of power flow in a system from
source to load and in case the direction of power flow
reverses, the reverse power protection can be activated to
trip the system. This is especially important in a DG set or
in a ring mains system.

Power Quality Control


MTX3.0 release measures the frequency, power factor and
offers protection against leading and lagging values thereby
assisting in maintaining the power quality. This release
measures THD of current & voltage and gives an alarm / trip
in case it exceeds the set thresholds.

Communication Capable

Convertor
Laptop or HMI (RS485 to RS232)

Most advanced release of MTX series, MTX3.0 is communication capable on MODBUS RTU network. Using
MODBUS com module the MCCB release can be connected to a Personal Computer. The metering values can be
read remotely. The settings configuration on the other hand can both be read and changed remotely. These
releases are also made compatible with HMI (Human Machine Interface) & DCS (Data Control Systems)
Protection Release for MCCBs 41

Multi-looping

Laptop or HMI

Convertor
(RS485 to RS232)

MODBUS Communication through MODBUS looping

A single display module can be used to connect upto 15 MCCBs with MTX3.0 release through MODBUS
network. Highly reliable data yet extremely simple looping reduces operational headaches and enhances
remote accessibility.

Maintenance Functionality
MTX3.0 release can store last 10 trip records & last 10 event records which can be used for the system
analysis later on. These recorded values can be viewed from display unit as well as PC.

Note: For wiring diagram, please refer page no. 63


42 MCCBs for Different Applications

Auto Source Transfer Application


In this modern era of automation, ASTS (Automatic Source Transfer Systems) are very widely used in many
places such as commercial buildings, IT parks for quick changeovers and also in Utilities for uninterrupted
supplies for critical loads.
These solutions can give you optimum energy management.
ASTS solution basically consists of
Motorised MCCBs
Mechanical Interlocking device (usually a base plate)
Automatic Transfer Controller
ASTS with AuXC-1000 controller
The AuXC-1000 controller brings simplicity and flexibility to an auto source transfer system. It has been
developed to control and supervise the automatic or manual transfer of a utility load from a principal power
supply source to a stand-by and vice-versa. It sets a new benchmark in Auto Source Transfer Switch Controller
technology. It includes all the necessary features to supervise and control power supply sources, composed by
energy distribution systems or generating sets, and the relative transfer equipment, such as contactors,
motorized moulded case circuit breakers and air circuit breakers.

+
AuXC-1000

MIL with Base Plate & EOM

Key Features:
Utility-to-utility, utility-to-generator or generator-to-generator changeover possible
Three-phase, two-phase or single-phase voltage controls
Controls of minimum voltage, maximum voltage, phase loss, asymmetry, minimum frequency,
maximum frequency, with independent enable and delay
Voltage thresholds with programmable hysteresis
Manual control of Circuit Breakers
Main line failure simulation
Communication Capable
Front display for monitoring the system voltage and frequency and for onsite controller programming
Six programmable inputs and five programmable outputs
Front test feature to simulate the operation of the diesel generator set
Status indication through 22 LEDs
Flush mounting arrangement

Note: For wiring diagram, please refer page no.60


MCCBs for Different Applications 43

ASTS with AuXC-1000L Controller Smarter, Simpler, Easier

+
AuXC-1000L

MIL with Base Plate & EOM

With the new AuXC-1000L controller in addition to its predecessor, ASTS has become a lot simpler & easier.
Some of the salient features of the controller are as follows:
Utility-to-utility, utility-to-generator changeover facility
Single supply input from battery supply 12-48V DC
Display to view main and secondary line parameters
15 status LED indicators
6 programmable digital inputs
3 programmable relay outputs
RS232 communication interface
Modbus RTU and Modbus-ASCII communication protocols
Status display of circuit breakers
Emergency demand supervision parameter programming for stand by generator sets
Event logging
Alarm code & description display

The automatic transfer takes place through AuXC-1000L / AuXC-1000 whenever following conditions are
predefined by the user
System Voltage not in line with programmed limits
The need to have a very reliable power source
The need to use the most economical power source

These controllers are compatible with U-POWER OMEGA range of Electrical ACBs, dsine range of Motorized
MCCBs and MCX range of contactors.
Accessories
Internal Accessories 46
- Auxiliary Contact
- Trip Alarm Contact
- Auxiliary Trip Alarm Contact
- Shunt Release
- Under Voltage Release

External Accessories 47
- Rotary Operating Mechanism
- Mechanical Interlocking Kit
- Keylock
- Spreader Terminals
- Terminal Shrouds
- External Neutral CT
- Stored Energy Electrically Operated
Mechanism
- MTX Modules
- Earth Fault Module
46 Accessories

Internal Accessories

dsine range of MCCBs are offered with snap-fit type, easily


installable internal accessories. There is no need to open main
cover and no live parts are accessed during installation. TAC,
Aux+TAC to be fitted in the right cavity & under voltage
release to be fitted in left cavity.
Double Insulation: The internal accessories are housed in
insulated casings to ensure first level of insulation. When the front
cover is opened for the fixing of internal accessories, the MCCB is
totally insulated ensuring the double insulation.

MCCB with mid cover opened & Internal


accessories fitted Auxiliary Contact TAC Shunt Release UV Release

Internal Accessories Contacts/Supply Voltage Frame Cavity


DN0, DN1 Right
1 C/O
DN2, DN3, DN3B, DN4 Right/Left
Auxiliary Contact
DN0, DN1 Right
2 C/O
DN2, DN3, DN3B, DN4 Right/Left
DN0, DN1 Right
1 C/O
Trip Alarm Contact DN2, DN3, DN3B, DN4 Right
2 C/O DN0, DN1 Right
DN0, DN1 Right
Auxiliary + Trip Alarm Contact 1 C/O + 1 C/O
DN2, DN3, DN3B, DN4 Right
240/415V AC 50Hz DN0, DN1 Left
Shunt Release
110/415V AC 50Hz, 110/220V, 24V DC DN2, DN3, DN3B, DN4 Right/Left
DN0, DN1
Under Voltage Release 240V AC DN2, DN3, DN3B Left
DN4

Shunt Release
It allows opening of MCCB by means of an electrical command. Operation of the release is guaranteed for a
voltage between 70% and 110% of the rated power supply voltage value Ue, both in AC & DC.

Frame Operational Voltage Power Consumption


DN0 / DN1 240 / 415V AC, 50Hz 1500VA
110 - 415V AC, 50Hz 1500VA
DN2 / DN3 /
110 / 220V DC 85W
DN3B / DN4
24V DC 10W
Accessories 47

UV Release
The Under-voltage release causes the MCCB to trip if the operational voltage falls to a value between 35% and
70% of its rated voltage or not applied. UV release mechanically locks the closing mechanism of MCCB & makes
it impossible to close on under-voltage or no voltage, both manually & electrically. With the under-voltage
release de-energized, it is not possible to close the MCCB. UV release can also be used for interlocking schemes
(for DG synchronization, paralleling of transformers etc) also.

Frame Operational Voltage Power consumption


DN0 / DN1 240V AC, 50Hz 5VA
DN2 / DN3 / DN3B 240V AC, 50Hz 5VA
DN4 240V AC, 50Hz 5VA

External Accessories
Rotary Operating Mechanism
Rotary operating mechanism (ROM) for dsine MCCBs are available in direct &
extended versions.

1. Direct Rotary Handle (MCCB mounted)


Available for entire family of dsine MCCBs
In built pad locking feature

Direct Rotary Handle


2. Extended Rotary Handle (Panel Mounted) (MCCB mounted)
ROM mounts directly on MCCB without removal of mid cover
Clear ON/OFF/TRIP indication
Clear view of MCCB rating label
Direct access to Push to Trip button
IP 54 degree of protection with
extended rotary handle
Unique coupling to allow 3mm tolerance
Door interlock in ON position,
with defeat facility
Door interlock in OFF condition
with padlock feature Panel Door Mounted
Extended
Auto restoration of door interlock Rotary Handle: Key lock (To be used along
External keylock for mechanical interlocking Panel Mounted with Extended Rotary Handles)

Mechanical Interlocking Schemes


1. Mechanical Interlocking Kit:
Two MCCBs can be interlocked using base plate mechanism,
in side-by-side configuration.
Features

For 3P & 4P versions


For DN2 & DN3 frames
Site fittable
MIL with Base Plate
48 Accessories

2. Mechanical Interlocking using Key Locks: I/C or B/C Key Lock


For mechanical interlocking through extended 2 l/C Any 1 type of lock for both MCCBs
rotary operating mechanism, a panel mounted
2 I/C and 1 B/C Lock 1 and Lock 2 for I/C and Lock 12 for B/C
key lock is available. The selection of the key
lock as per the table: 3 I/C and 2 B/C Locks 1, 2, 3 for I/Cs and Locks 12, 23 for B/Cs

Key Lock Selection: I/C1 I/C2 I/C3

Type of lock Exclusively operable by key nos.


Incommers
1 1 Lock 1 Lock 2 Lock 3 (I/C)
2 2
3 3 Bus couplers
Lock 12 Lock 23 (B/C)
12 1, 2 & 12
B/C1 B/C2
23 2, 3 & 23

Spreader Terminal
Available for enhancing termination capacity
Made of silver plated copper

Terminal capacity without spreader terminals


Rating (A) 16-100 125-250 320-630 800-1250
2 2 2 2
dsine Frame Cable (mm ) Link(mm) Cable (mm ) Link(mm) Cable (mm ) Link(mm) Cable (mm ) Link(mm)
DN0 35 17
DN1 120 26
DN2 95 25
DN3 120 27$
DN3B* 185 32
DN4 - 2 x 40

$ 30mm on request

Terminal capacity with spreader terminals


Rating (A) 16-100 125-250 320-630 800-1250
2 2 2 2
dsine Frame Cable (mm ) Link (mm) Cable (mm ) Link (mm) Cable (mm ) Link (mm) Cable (mm ) Link (mm)
DN0 50 22
DN1 185 35
DN2 185 35
DN3 2 x 240 2 x 40
DN3B* 2 x 240 2 x 40
DN4 2 x 300 2 x 60

* DN3B available in 320A and 400A only


Note: Phase barriers are supplied along with MCCBs ; Copper termination recommended for enhanced performance
Accessories 49

External Neutral CTs


Used to provide neutral protection to 3P MCCBs in 3 phase 4 wire system
Available for 3P MCCBs with MTX2.0 & 3.0 releases
Adapters for NCT available

Stored Energy Electrically Operated Mechanism


ON / OFF & Charged/Discharged indication
Foolproof mounting
Selector switch for Auto/Manual operation
Padlock facility for locking in OFF position (3 nos. locks)
Higher mechanical & electrical endurance
Back up fuse for extended motor protection
Easy access to the protection setting on MCCB
True indication for ON/OFF & Trip

Specification DN2 DN3


Operating voltage (V AC) 240V AC 240V AC
Operating voltage (%) 85-110% 85-110%
Closing time (ms) 60 90
Opening time (ms) 300 450
Power consumption (VA) 350 500
Life / No. of operations 16000 15000
2
Door cut out (mm ) 96 x 96 96 x 96
IP protection, on the front IP30 IP30
Operating frequency 2/min 1/min
Min. control impulse time (ms)* 300 450

Power Supply (PS) Module


PS module is used to power ON dsine MTX modules when
auxiliary 24Vdc supply is not available.

Specifications AC DC
Input 85-265V 125-300V
Output 1 - 650mA at 24V DC
#
Output 2 - 200mA at 24V DC

#
For using Output 2, Output 1 should be loaded

Note: For wiring diagram, please refer page no. 63


* At rated voltage
50 Accessories


Current Metering Module for MTX2.0
It consists of 2 parts viz. Metering module & Display module. Metering module collects the data from the
release and sends the same to the Display module. The panel mounted O-LED Display module shows
various parameters viz. 3 phase currents, neutral and ground fault currents, if any. We can also view last trip
records.


Communication Module for MTX3.0
The Communication module is solutions for connecting dsine
MCCBs to Modbus network for remote supervision and
control of circuit breaker. It is suitable for the MTX3.0 electronic
trip units across DN2/DN3/DN4 frames. It is available with DIN
rail mounting facility. 2 LEDs in front fo the module indicates
The Power LED - the presence of auxiliary power supply to
the module
The Data LED - transmission of data
Its operating temperature is -25O C to 70O C and consumption is 43mA


Voltage Module for MTX3.0
This accessory when connected to MTX 3.0 release in DN2/DN3/DN4
frames is able to provide the various measurements of the electrical
values of the plant. It has to be mounted just beside the MCCB on a
O O
DIN plate. Its operating temperature is -25 C to 70 C.


Display Module for MTX3.0
It is a panel mounted O-LED display unit that can be integrated with
MTX3.0 release in DN2/DN3/DN4 frames. It has one navigation key, a
select button a an exit button. Its operating temperature is
O O
-25 C to 70 C and consumption is 12mA

The module displays wide range of parameters as follows


Phase current, ground current, earth leakage current
Phase / Line voltage
Active / Reactive / Apparent Power
Power factor, Frequency
Energy
Maximum demand
THD


MTX Test Kit
Universal Test Kit for all MTX releases
Simulation of overload, short-circuit & earth fault
Single phase AC supply

Note: For wiring diagram, please refer page no. 63


Accessories 51

Earth Fault Module


Earth Fault Modules Type GF1, GF2 and GF11. Features:
These modules are to be used with MCCBs for
earth fault protection. The principle of operation is Compact in size
based on detection of the residual current in the
Solid state design.
system. They combine safety and versatility,
conforming to the high performance standards, Built-in moulded CBCT for GF1 & GF2.
the characteristic of all L&T products. External CTs are to be used for GF11.
Suitable for both 3 phase 3 wire & 3 Phase 4
wire systems. In case of 3 phase 4 wire
system, the neutral cable/twisted link should
also be passed through the CBCT along with
the 3 phase links / cables.
Built-in test facility.
Earth Fault Module GF1
GF1 is suitable upto 200A MCCBs Selection facility for nominal current rating (In).
Earth fault setting is adjustable from 10% to
50% of set current
Selectable trip times (100 ms, 200 ms).
Earth Fault Module GF2 Manual reset for positive fault
GF2 is suitable upto 250A-400A MCCBs acknowledgment.
Potential free NO contact to trip MCCB
(through 240 V shunt release).
Window dimensions suitable for
Cable connection only in GF1 and GF2.

Earth Fault Module GF11 Note: MCCBs need to be fitted with 110 V / 240 V AC shunt
GF11 is suitable upto 800A MCCBs release for Earth Fault Module operation.

Technical Data
Specification Type GF1 / GF2 / GF11
Current Setting Range, Is (Is=x In) 10% to 50%In in steps of 10%
Auxiliary Supply 240V AC 20%
Time Delay (ms) 100 / 200ms Field selectable
Pick-up Accuracy 10% Is
1 NO contact manual reset Type
Output Contact
contact rating 5A 240V AC
a) Power On LED
Indication b) Trip LED (manual reset)
Operating Temperature +10oC to +55oC
2 kV 50Hz for one minute across independent circuit
Insulation 1 kV 50Hz for one minute across open contacts
Mounting Base plate mounting type
2 GF1 - 110 x 32
Window for Cable / Busbar entry (mm )
GF2 - 165 x 61.5
Weight (kg) GF1 - 1.2, GF2 - 2.2, GF11 - 0.9

Note: For wiring diagram, please refer page no. 61


Characteristic Curves
n
Thermal Magnetic Release 54
DN0
}
DN1
}
DN2
}
DN3B
}
DN3
}

n
Microprocessor Release
55
}MTX1.0-2.0 (O/L curves)
- I2T at 6Ir, 7.2Ir

}
MTX3.0 (O/L curves)
- I2T at 1.5Ir, 6Ir, 7.2Ir
4
- I T at 1.5Ir, 6Ir, 7.2Ir
- SI at 1.5Ir, 6Ir, 7.2Ir
- LI-VI at 1.5Ir, 6Ir, 7.2Ir
- Short circuit, Earth fault & Neutral
curves For MTX1.0-2.0-3.0
54 Characteristic Curves

Thermal-Magnetic Release

DN0 MCCB DN1 MCCB


10000 10000

1000 1000

100 100
Trip Time (s)

10 10

Trip Time (s)


1 1

9In 9In
0.1 0.1

t<10ms t<10ms
0.01 0.01

0.001 0.001
10-1 1 10 102 103 10-1 1 10 102 103
Current multiples (xIn) Current multiples (xIn)

DN2 MCCB DN3B MCCB DN3 MCCB


10000 10000 10000

1000 1000 1000

100 100 100

10 10
Trip Time (s)

Trip Time (s)


Trip Time (s)

10
6-10In
6-10In
1 9In
1 1

0.1 0.1 0.1

t<10ms t<10 ms t<10ms


0.01 0.01 0.01

0.001
0.001 0.001
10-1 1 10 102 103 10-1 1 10 102 103 10-1 1 10 102 103
Current multiples (xIn) Current multiples (xIn) Current multiples (xIn)

Note: Curves are Ir based till overload zone.


Characteristic Curves 55

Microprocessor Release
2
MTX1.0 / 2.0 - DN2 / DN3 / DN4 (O/L curves - I t)

2 2
I T @ 6Ir I T @ 7.2Ir
10000 10000

1000 1000
Trip Time (s)

Trip Time (s)


100 100

10 10
10s
10s

3s
1 3s 1

0.1 0.1
1 10 1 10
Current multiples (xIr) Current multiples (xIr)

2
MTX3.0 - DN2 / DN3 / DN4 (O/L curves - I t)

I T @ 6Ir
2 2 2
I T @ 1.5Ir I T @ 7.2Ir
1000 10000 10000

100 1000 1000

10 100 100
Trip Time (s)

Trip Time (s)

Trip Time (s)

30s
1 10 30s 10 20s
30s
20s 10s
20s
10s
10s 5s
5s 3s
0.1 5s 1 3s 1
3s

0.01 0.1 0.1


1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)
56 Characteristic Curves

Microprocessor Release

4
MTX3.0 - DN2 / DN3 / DN4 (O/L curves - I t)
4 4 4
I T @ 1.5Ir I T @ 6Ir I T @7.2Ir
1000 100000 100000

10000 10000
100

1000 1000
10
Trip Time (s)

Trip Time (s)

Trip Time (s)


100 100

1
10 10 30s
30s 18s
30s
18s 18s 10s
0.1 10s 6s
10s 1 1
6s 3s
6s 3s
3s
0.01 0.1 0.1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)

MTX3.0 - DN2 / DN3 / DN4 (O/L curves - Short Inverse)

SI @1.5Ir SI @ 6Ir SI @ 7.2Ir


100 100 100

30s 30s
24s 24s
30s
Trip Time (s)
Trip Time (s)

Trip Time (s)

24s
12s 12s
10 10 10

12s

4s 4s

4s

1 1 1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)
Characteristic Curves 57

Microprocessor Release
MTX3.0 - DN2 / DN3 / DN4
(O/L curves - Long Inverse / Very Inverse)
LI-VI @ 1.5Ir LI-VI @ 6Ir LI-VI @ 7.2Ir
100 1000 1000

10 100 100
Trip Time (s)

Trip Time (s)

Trip Time (s)


30s
30s
24s 30s 24s
24s
1 12s 10 10
12s
12s

4s
4s
4s

0.1 1 1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)

MTX1.0* / 2.0 / 3.0 (S/C, E/F & Neutral Curves)


Short Circuit Curves Earth Fault Curves Neutral Curves
1 1 1

400ms 500ms
300ms
Invs
OFF*
200ms 200ms 200ms
Trip Time (s)

Trip Time (s)

Trip Time (s)

0.1 100ms 0.1 100ms 0.1

Inst

0.01 0.01 0.01


1 1.5 8 10 0.1 0.2 0.5 1 0.1 0.5 11.5 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)

For MTX3.0 only For MTX3.0 only *: IDMT disable in case of MTX3.0

* Only Short Circuit setting available in MTX1.0


Under Short Circuit fault conditions, MCCBs will clear the fault in less then 10 msec
Wiring Diagrams
n
Motorised Circuit Breakers Control 60
through AuXC - 1000 & AuXC - 1000L
n
Earth Fault Modules 61
n
MTX2.0 with Current Metering Module 62
n
MTX3.0 with Communication 63
through Modbus
60 Wiring Diagrams

Motorised Circuit Breakers Control through AuXC - 1000


LINE 1 LINE 2
L1 L2 L3 N L1 L2 L3 N
QF1
8.1
8.2 RS232
8.3
8.4

QF2
9.1
9.2
9.3
9.4
AuXc - 1000
Q1 Q2 K2 K2 K1 K1 DC
DIGITAL INPUT S SUPPLY
7.1
7.2

1.1
1.2
1.3
2.1
2.2
2.3

3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8

4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8

5.1
5.2
5.3
K1 K2

_ _
+

K2 K1
L1 L2 L3 N
LOAD
Parameter setting
for the wiring diagram in picture.
Terminal Parameter code Setting
1.1 P6.01 OP.1 Circuit Breaker
1.3 P6.02 CL.1 (Q1, Q2) 1 3 4 2 1 3 4 2

POWER SUPPLY

POWER SUPPLY
2.1 P6.03 OP.2

INTERLOCK

INTERLOCK
Contactors COMMON

COMMON
OPENING

OPENING
CLOSING

CLOSING
2.3 P6.04 CL.2

STATUS

STATUS
TRIP

TRIP
4.1 P5.01 Fb.1 Mechanical
4.2 P5.02 Fb.2 Interlocking 5
WITHDRAWN
5
WITHDRAWN

4.3 P5.03 Tr.1


4.4 P5.04 Tr.2 MCB SE-EOM Q1 SE-EOM Q2

Motorised Circuit Breakers Control through AuXC - 1000L


LINE1 LINE2
L1 L2 L3 N L1 L2 L3 N
QF1
6.1 L1
6.2 L2 RS232
LINE1
6.3 L3
6.4 N

QF2 AuXC - 1000L


7.1 L1
7.2 L2 LINE2
7.3 L3
7.4 N
LINE1 LINE2 AUX
Q1 Q2 DC
DIGITAL INPUT S SUPPLY
L N L N L N L N
LINE1 LINE2
1.1
1.2
4.1
4.2
4.3
5.1
5.2
5.3

3.1
3.2
3.3
3.4
3.5

2.1
2.2
2.3
2.4
2.5
2.6

L
DUALPOWERSUPPLY OUT
N

L1 L2 L3 N
LOAD

Parameter setting
for the wiring diagram in picture.
Terminal Parameter code Setting
4.1 P6.1.1 OP.1 Circuit Breaker 1 3 4 2 1 3 4 2
4.3 P6.2.1 CL.1 (Q1, Q2)
POWER SUPPLY

POWER SUPPLY

5.1 P6.3.1 OP.2


INTERLOCK

INTERLOCK
COMMON

COMMON

Contactors
OPENING

OPENING
CLOSING

CLOSING
STATUS

STATUS

5.3 P6.4.1 CL.2


TRIP

TRIP

2.1 P5.1.1 Fb.1 Mechanical


5 5
2.2 P5.2.1 Fb.2 Interlocking
2.3 P5.3.1 Tr.1
2.4 P5.4.1 Tr.2 MCB
Wiring Diagrams 61

Earth Fault Modules

GF1 & GF2

FROM MCCB 240 Vac


R Y B N
SENSING
1
CIRCUIT MCCB
RELAY SHUNT
2
RELEASE

RECTIFIER
L
3
AUX.
SUPPLY
N
4 240 Vac
TO LOAD

GF11

FROM MCCB
240 Vac
R Y B N RELAY 1
MCCB
2 SHUNT
S1 RELEASE
SENSING
CIRCUIT
S2 5
S1
CT Sec.
S2 RECTIFIER L
3
S1 AUX
SUPPLY
S2
4 240 Vac
N
S1

S2

TO LOAD
62 Wiring Diagrams

MTX2.0 with Current Metering Module

Display Module

Metering
Module

MTX2.0 Release

Inst
to other
MTX2.0

24 Vdc 24 Vdc
+ - + -

Auxiliary
Power Supply
Module

L 240 Vac
N 50 Hz
Wiring Diagrams 63

MTX3.0 with Communication through Modbus

Display Module

Communication
Module Voltage Module

MTX3.0 Release

Inst

D+ Convertor
D- 3 Phase
RS485 RS232
+Vs 415 Vac Supply
Gnd
+ - + -
24 Vdc 24 Vdc
Laptop / SCADA
System
Auxiliary
Power Supply
Module

L 240 Vac
50 Hz
N
Dimensions
n
Dimensions of MCCB
}
DN0
}
DN1
}
DN2
}
DN3B
}
DN3
}
DN4

n
Dimensions of Accessory
}
Rotary Operating Mechanism
}
Stored Energy Electrically
Operated Mechanism
}
Panel Mounted Key Lock
}
Mechanical Interlock Kit
}
External Neutral CTs
}
MTX Modules
}
Auto Source Transfer Switch: AuXC-1000
and AuXC-1000L
}
Earth Fault Modules
}
Terminal Shrouds
66 Dimensions of MCCB

DN0-125 MCCB
86
64
60
20 2
75 (3P) MCCB MOUNTING HOLES
M3 SCREW 6 Nos.

32
25 25 25 12.5
10
25 25

50.5 50.5

61.5
25.5

48.5
58
13.5

52
75
2.25 27.25
116.4

17
112

130

112
46
39
N N CUT OUT 1

45
38
CUT OUT 2
29.5
76
101
25 25 25
32.2

100 (4P) Mounting &


Door Cut-out Details
2
20

DIN rail kit

DN0-125 with Spreader Links 86


64
60
8.5 13 13 13 20 2
13 13
9
11

11

32
28

28

10

61.5
58
13.5

75
17
172.2
194.2

172.2
194.2

N
45
38
30.2

32.2

2
22 22 20
35 35 35 35 35
92 127.2
DIN rail kit

Recommended cat. nos.


for DN0 spreaders
Current 3P 4P
upto 100A CM97785OOOO CM97921OOOO
125A CM90687OOLO CM90688OOLO
Note: Spreaders are available as spare
It is recommended to use spreader links for enhancing termination capacity
Frame size is same for DN0 / DN0-SD / DN0-M All dimensions are in mm
Dimensions of MCCB 67

DN1-250 MCCB

MCCB MOUNTING
HOLES 6 Nos.
105 (3P) 93.7
141
35 35 35 17.5 64.5
60
35 35
17.5 17.5

58.6
78.65
95.7

126
145
165
126

46
N

45
88 53

70.5 70.5

35 35 35 Mounting &
140 (4P) Door Cut-out Details

DN1-250 with Spreader Links 93.7


64.5
19 19 19 60
4
10.2 18
10.2 19.5 19.5
18
18

46
47.5
38

78.65
95.7
221
147

257
221
257

N
45
47.5

46

35 4
54.5 54.5 35 18
144 54 54 54
197

Recommended cat. nos.


for DN1 spreaders
3P 4P
ST98053OOOO CM92007OOOO

Note: Spreaders are available as spare


It is recommended to use spreader links for enhancing termination capacity
Frame size is same for DN1 / DN1-M All dimensions are in mm
68 Dimensions of MCCB

DN2-250 MCCB

105 (3P) MCCB


119.57 MOUNTING HOLES
35 35 35 17.5 M4 SCREW 6 Nos.
96.5
8 35 35

25.5 60.5

89.27
72.7

61
CUT OUT

157
163
157

179

46.5
N
45
86

35 35 35
140 (4P) Mounting &
Door Cut-out Details

DN2-250 with Spreader Links 119.57


96.5
19 19 19 28.65
19.5 19.5 4
10.2 10.2
18
18

48
38
38

89.27
72.7
239
275
239
275

N
45
41

48

35 35 4
54 54 54 A
54.5 54.5
144 197

Rating Dimension (A)


Recommended cat. nos. 125-250A TM 26
for DN2 spreaders
63-100A TM 25.5
3P 4P 32-50A TM 26.25
ST98053OOOO CM92007OOOO MTX breakers 28

Note: Spreaders are available as spare


It is recommended to use spreader links for enhancing termination capacity
Frame size is same for DN2 / DN2-SD / DN2-M All dimensions are in mm
Dimensions of MCCB 69

DN3B-400 MCCB

MCCB
MOUNTING HOLES
M5 SCREW 6 Nos.
44.50 44.50
140
139.5 (3P) 115

52.50
44.5 44.5 44.5 25.25 110
38.25 82.75

CUT OUT

68
98

176
79
182
205
176

77
121

44.5 44.5 47.5


184 (4P)
Mounting &
Door Cut-out Details

DN3B-400 with Spreader Links


140
115
110
26.5
23.5 23.5 23 21.5 23 5
23
23

13
13
56.5
45
45

68
98
272

318
272
318

N
77
56.5

40 40 5
63.5 63.5 63 61.5 63 26.5
167 227.5

Recommended cat nos.


for DN3B spreaders
3P 4P
ST98065OOOO ST98066OOOO

Note: Spreaders are available as spare


It is recommended to use spreader links for enhancing termination capacity
Frame size is same for DN3B / DN3B-SD All dimensions are in mm
70 Dimensions of MCCB

DN3-400/630 MCCB
180
143 MCCB MOUNTING HOLES
140 (3P) 120 M5 SCREW 6 Nos.
43,5 43,5 43,5 26,5 103 43,5 43,5

104

38.75

82.25
CUT OUT

82,7
224
234
266
224

77

78
N

121

43,5 43,5
Mounting &
183.5 (4P) Door Cut-out Details

DN3-400/630 with Spreader Links 180


143
120
103
22,5 22,5 22 20,5 22 A
23

23

10.5 5
10.5

F
C

104
D

D
E

77
N

F
40 40
62,5 62,5 62 60,5 62 B
165 224,5

Type DN3-400 DN3-630


Recommended cat nos. A 39 43
for DN3 spreaders B 37* 39#
Rating 3P 4P C 45 55
D 324 344
400A ST98065OOOO ST98066OOOO
E 370 390
630A ST98054OOOO CM92004OOOO
F 52 62

* 38 for MTX
# 38 for 500A TM

Note: Spreaders are available as spare


It is recommended to use spreader links for enhancing termination capacity All dimensions are in mm
Frame size is same for DN3 / DN3-SD / DN3-M
Dimensions of MCCB 71

DN4-800/1000/1250 MCCB
MCCB
210 (3P)
197 MOUNTING HOLES
68 68 68 143 M5 SCREW 6 Nos.
68 68

132.5

109.5
198.5
57 125

105

107
330
370
326

326
N
CUT OUT
182

24
71 68 68 71
Mounting &
180
Door Cut-out Details
278 (4P)

DN4-800/1000/1250 with Spreader Links

12.5 A A 12.5 143


A A A
D Y
15
D
C

85

132.5
105
370
510

N
85

24
15

60 24 60 46
B B 198

3P Frame 4P Frame
3/4P Frame
Type A B C D Type A B C D
Type Y
800A 98 256 6 38 800A 88 324 6 28
N version 46
1000A 98 256 12 38 1000A 88 324 12 28
S version 42
1250A 86 232 20 26 1250A 80 300 20 20

Recommended cat nos. for DN4 spreaders


Rating 3P 4P
800A CM91161OOUO ST90362OOOO
1000A CM91161OOVO CM90064OOVO
1250A CM91161OOAO ST98058OOOO

Note: Spreaders are available as spare


It is recommended to use spreader links for enhancing termination capacity All dimensions are in mm
Frame size is same for DN4 / DN4-SD
72 Dimensions of Accessories

Rotary Operating Mechanism (ROM)


Direct ROM Door Cut-out Detail

L5

L4
L3
N

L2

L1 68
Mounting &
Door Cut-out Details

L1 = Mounting Depth Type L1 L2 L3 L4 L5


L2/L3 = Panel Cut-out DN0 96.5 58 52 43.5 37
L4/L5 = Breaker Mounting Refer DN1 96.5 73 52 56.5 54
DN2 122 96 63 53 66
DN3 146 121 87 78 82
DN3B 146 121 87 49 82.5

Extended ROM Door Cut-out Detail

L2 51
450 76
L3

N 4

L1=Minimum Panel Depth suggested 68


Mounting & Door Cut-out Details

Type L1 L L2 L3
DN0 169 L1 - 119 7.5 69.5
L
DN1 169 L1 - 119 24.5 81.7
DN2 202 L1 - 152 27 84
L = Length of Shaft Required DN3 233 L1 - 183 39 122
for Panel Depth L1 DN3B 233 L1 - 183 39 92
Total Length of Shaft =275mm DN4 302 L1 - 252 69 170

All dimensions are in mm


Dimensions of Accessories 73

MCCB with Stored Energy Electrically


Operated Mechanism (SE-EOM)
DN2
245.5
35 Door

18.7
== 237.5

Door
Cut-out

94
157

N ON TRIP

156

= =
94

DN3 264
Mounting 43.5
holes for MCCB 256
= =

Door
62.1

45 49
94

Door
Cut-out
224

94

N ON TRIP

Panel Mounted Key Lock


Type 1 / 2 / 3 / 12 / 23
72 48.5
2 Holes, 4.2
76
50
50
450

Cut-out for
136

Handle Assembly
68
68

12

Cut-out for
Panel Mounted Key Lock 29
2.2

58 52
Mounting &
Door Cut-out Details
Note: Panel Mounted key lock can be used only with extended ROM All dimensions are in mm
74 Dimensions of Accessories

Mechanical Interlocking Kit

DN2

372
10 Mounting Holes
41.5 141 141
35
10

149

209
239

177
141 141 Holes for Breaker Mounting

Mounting Details

DN3

10 Mounting Holes
436
53 161 161 53 56
22.5

152.5
316
346

266

161 161 Holes for Breaker Mounting

Mounting Details

All dimensions are in mm


Dimensions of Accessories 75

External Neutral CTs

DN2/DN3
K
L

B
C
D

G
H
J

Bottom Bottom
Side Side

Frame A B C D E F

DN2 250A 93 59 47 81 35 10.2


Adaptor Terminal
DN3 400A 93.5 58 46 81.5 40 13
DN3 630A 93.5 58 46 81.5 40 10.5

ON
TRIP
Frame G H J K L M OFF
Bottom
DN2 250A 77 153 189 26 4 55 Side

DN3 400A 63.5 153.5 199.5 39 5 60


DN3 630A 63.5 173.5 219.5 39 5 60

Note: Adaptor Terminals shown are not available with product >M
Kindly refer accessories data for ordering separately
Circuit Breaker shown for reference only All dimensions are in mm
76 Dimensions of Accessories

External Neutral CTs

DN4
M P
H

G
K
D

J
A

Bottom Bottom
Side Side

F
E

DN4 A B C D E F G
800A 132 88.5 73.5 117 60 12.5 92

1000A 132 88.5 73.5 117 60 12.5 92

1250A 132 88.5 73.5 117 60 12.5 92

DN4 H J K L M P
800A 24 302 272 80 47 6
Bottom
Side
1000A 24 302 272 80 47 12

1250A 24 302 272 80 47 20

Note: Adaptor Terminals shown are not available with product


Kindly refer accessories data for ordering separately
Circuit Breaker shown for reference only
>L
Special Note: Adaptor Terminals for DN4 range of product are not symmetrical.
Kindly ensure proper orientation in assembly as shown in figure. All dimensions are in mm
Dimensions of Accessories 77

MTX Modules
Display Module
36

44.5
51
10
96

44.5

91.5

91.5

Door Cut-out Details

Voltage/Communication/Metering Module
3

73.3

73.3
81

87
3

23
14.3 60
Door Cut-out
23 65
Details

All dimensions are in mm


78 Dimensions of Accessories

Auto Source Transfer Switch:


AuXC-1000 and AuXC-1000L
A 94 C
B

C
A

Type A B C
AuXC - 1000 144 79 138.5
AuXC - 1000L 96 82 92

Earth Fault Modules - GF1, GF2, GF11


Terminal Block

8.5 274.5 60

24 110

105.5
108

71.5
Cable / Busbar entry

71.5
Cable / Busbar entry (165 mm x 61.5 mm)
32

(110 mm x 32 mm)

5
20

175 15 54
158 50
USE M6 SCREW 30
195

74
96
30

Terminal
Block 90 90
= =
175
USE M4 SCREW
Terminal Block
GF2
GF1
108

158 50

195
Terminals for external CT
secondary connection
30

175
USE M4 SCREW

GF11 All dimensions are in mm


Notes 79
80 Notes
Aimed at maximizing productivity, conserving energy, minimizing costs and enhancing safety, our
Electrical & Automation training programmes have benefitted over 1.35 Lakh professionals in the
last 28 years. These training programmes are highly beneficial as they provide right exposure and
impart knowledge on selection, installation, maintenance and testing of Electrical & Automation
Products.

So gain the advantage and go the extra mile with:


? 22 courses on contemporary topics
? Courses applicable to all switchgear brands
? Training Centers in Pune, Lucknow, Coonoor, Vadodara, Delhi & Kolkata
? Blend of theory and practical experience

The typical training programmes cover:


? Low Voltage & Medium Voltage Switchgear
? Switchboard Electrical Design
? AC Drives & Building Management Solutions
? Protective Relays, Earthing, Reactive Power Management & Harmonics
? Energy Conservation & Management

Please contact any of the training centres for participation and detailed training programme schedule.

Pune Lucknow Coonoor


Larsen & Toubro Limited Larsen & Toubro Limited Larsen & Toubro Limited
Switchgear Training Centre, Switchgear Training Centre, Switchgear Training Centre,
T-156/157, MIDC C - 6 & 7, UPSIDC Ooty-Coonoor Main Road
Bhosari, Pune - 411 026 P. O. Sarojininagar, Lucknow - 226 008 Yellanahalli P.O., The Nilgiris - 643 243
Tel: 020 2712 0037 / 2712 0653 Tel: 0522 247 6015 / 97944 54455 Tel. : 0423 251 7107
Fax: 020 2712 2933 Fax: 0522 247 6015 Fax : 0423 251 7158
E-mail: [email protected] E-mail: [email protected] E-mail: [email protected]

Vadodara Delhi Kolkata


Larsen & Toubro Limited Larsen & Toubro Ltd Larsen & Toubro Limited
Switchgear Training Centre Switchgear Training Centre Switchgear Training Centre
Behind L&T Knowledge City, 32, Shivaji Marg, 4th Floor, 3B, Shakespeare Sarani,
Near Village Ankhol, Near Motinagar Metro Station, Kolkata - 700071
Vadodara - 390019 New Delhi - 110015 Tel: 033 42005975 / 42005978
Tel: 0265 2457805 Tel: 011 41419515 / 41419695 / 41419500 E-mail: [email protected]
E-mail: [email protected] Fax: 011 41419600
E-mail: [email protected]
Electrical Standard Products (ESP) Offices:

HEAD OFFICE Khairasol, Degaul Avenue L&T Business Park,


L&T Business Park, Durgapur 713 212 Tower 'B' / 5th Floor
Tower 'B' / 3rd Floor Tel: 0343-2540448 / 2540449 / 2540443 Saki Vihar Road, Powai
Saki Vihar Road, Powai Fax: 0343-2540442 Mumbai 400 072
Mumbai 400 072 e-mail: [email protected] Tel: 022-67052874 / 2737 / 1156
Tel: 022-67053229 Fax: 022-67051112
Fax: 022-67051112 5, Milanpur Road, Bamuni Maidan e-mail: [email protected]
e-mail: [email protected] Guwahati 781 021
Tel: +91 8876554410 / 8876554417 12, Shivaji Nagar
BRANCH OFFICES Fax: 361-2551308 North Ambajhari Road
501, Sakar Complex I e-mail: [email protected] Nagpur 440 010
Opp. Gandhigram Rly. Station Tel: 0712-2260012 / 6606421
Ashram Road II Floor, Vasantha Chambers Fax: 2260030 / 6606434
Ahmedabad 380 009
5-10-173, Fateh Maidan Road e-mail: [email protected]
Tel: 079-66304006-11
Hyderabad 500 004
Fax: 079-66304025
e-mail: [email protected] Tel: 040-67015052 32, Shivaji Marg
Fax: 040-23296468 P. O. Box 6223
38, Cubbon Road, P. O. Box 5098 e-mail: [email protected] New Delhi 110 015
Bengaluru 560 001 Tel: 011-41419514 / 5 / 6
Tel: 080-25020100 / 25020324 Monarch Building, 1st Floor Fax: 011-41419600
Fax: 080-25580525 D-236 & 237, Amrapali Marg e-mail: [email protected]
e-mail: [email protected] Vaishali Nagar
Jaipur 302 021 L&T House
131/1, Zone II Tel: 0141-4385914 to 18 P. O. Box 119
Maharana Pratap Nagar Fax: 0141-4385925 191/1, Dhole Patil Road
Bhopal 462 011 e-mail: [email protected] Pune 411 001
Tel: 0755-3080511 / 05 / 08 / 13 / 17 / 19 Tel: 020-66033395 / 66033279
Fax: 0755-3080502 Akashdeep Plaza, 2nd Floor Fax: 020-26164048 / 26164910
e-mail: [email protected] P. O. Golmuri e-mail: [email protected]
Jamshedpur 831 003
Plot No. 559, Annapurna Complex Jharkhand Crystal Tower,
Lewis Road Tel: 0657-2312205 / 38 4th Floor, G. E. Road
Bhubaneswar 751 014 Fax: 0657-2341250 Telibandha
Tel: 0674-6451342 / 2436690 / 2436696 e-mail: [email protected] Raipur - 492 006
Fax: 0674-2537309 Tel: 0771-4283214
e-mail: [email protected] Skybright Bldg; M. G. Road e-mail: [email protected]
Ravipuram Junction, Ernakulam
Aspire Towers, 4th Floor Kochi 682 016 3rd Floor
Plot No. 55, Phase-I Tel: 0484-4409420 / 4 / 5 / 7 Vishwakarma Chambers
Industrial & Business Park Fax: 0484-4409426 Majura Gate, Ring Road
Chandigarh-160 002
e-mail: [email protected] Surat 395 002
Tel: 0172-4646840 / 41 / 42 / 46 / 53
Fax: 0172-4646802 Tel: 0261-2473726
Email: [email protected] 3-B, Shakespeare Sarani Fax: 0261-2477078
Kolkata 700 071 e-mail: [email protected]
L&T Construction Campus Tel: 033-42005982
TC-1 Building, II Floor Fax: 033-22821025 / 7587 Radhadaya Complex
Mount-Poonamallee Road e-mail: [email protected] Old Padra Road
Manapakkam Near Charotar Society
Chennai 600 089 A28, Indira Nagar, Faizabad Road Vadodara 390 007
Tel: 044-2270 6800 Lucknow 226 016 Tel: 0265-6613610 / 1 / 2
Fax: 044-22706940 Tel: 0522-4929905 / 04 Fax: 0265-2336184
e-mail: [email protected] Fax: 0522-2311671 e-mail: [email protected]
e-mail: [email protected]
67, Appuswamy Road Door No. 49-38-14/3/2, 1st floor,
Post Bag 7156 No: 73, Karpaga Nagar, 8th Street NGGO's Colony, Akkayyapalem,
Opp. Nirmala College K. Pudur Visakhapatnam - 530 016
Coimbatore 641 045 Madurai 625 007 Tel: 0891-2791126 / 2711125
Tel: 0422-2588120 / 1 / 5 Tel: 0452-2567405 / 2561068 / 2561657 Fax: 0891-2791100
Fax: 0422-2588148 Fax: 0452-2567552 Email: [email protected]
e-mail: [email protected] e-mail: [email protected]

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Larsen & Toubro Limited, Electrical Standard Products


Powai Campus, Mumbai 400 072

Customer Interaction Center (CIC)


BSNL / MTNL (toll free) : 1800 233 5858 Reliance (toll free) : 1800 200 5858
Tel : 022 6774 5858, Fax : 022 6774 5859
E-mail : [email protected] / Website www.Lntebg.com

Registered Office: L&T House, N. M. Marg, Ballard Estate, Mumbai 400 001, INDIA CIN: L99999MH1946PLC004768

SP 50584 R7

You might also like