Moulded Case
Circuit Breakers
Stability: Activated
Up and Running, Uninterrupted 1
In every industry, big or small, electrical power supply The dsine range, a new generation of MCCBs, is a
is critical. Even a few seconds of interruption or combination of state-of-the-art design and modern
instability can result in huge financial losses, even loss user-friendly features. It also boasts a wide choice of
of life. We have little or no control over the nature or protective releases, ergonomics, aesthetics and
stability of power supply. The unpredictable nature of compactness. The range, designed to meet the
power makes it important to take appropriate steps changing needs of users after extensive analysis and
for the protection and safety of your organisations user feedback, can satisfy the most demanding
employees and equipment. system requirements.
In line with this objective, Larsen & Toubro presents Complemented by a wide array of accessories, the
dsine a highly advanced and sophisticated range of dsine range offers comprehensive solutions to
Moulded Case Circuit Breakers (MCCBs). customer applications ensuring operational safety,
reliability and versatility.
Moulded Case
Circuit Breakers
Moulded Case
Circuit Breakers
Versatility: Downloaded
Paper Industry
Sugar Industry
Oil Industry
Gas Industry
Meeting Diverse Demands 5
Industries
Every industry is unique, and so are its requirements. MCCBs with high breaking capacities cater to high
Industries as diverse as paper, sugar, oil & gas have voltage applications such as windmills and mines.
different sets of needs. Thankfully, dsine MCCBs, They are compact so the panel builder can optimise
available in various current ranges (20A to 1250A), panel size. They are thoroughly factory-tested with
are designed to efficiently handle such diversity. adequate quality controls in place. Moreover, since
these MCCBs are designed to handle high-value
Our Thermal Magnetic as well as Microprocessor-
capacitive inrush currents, no nuisance tripping is
based releases with various breaking capacities cater
to multiple industrial needs. Built with the latest observed in APFC panels. Motor loads being most
technology, dsine MCCBs deliver optimum efficiency vital, our design team has also developed special
even in the most adverse environmental conditions. dsine-M series for motor back-up protection ranging
from 32A to 630A.
Efficiency: Initiated
Paving The Path to Progress 7
Building Sector
Today, efficient energy management holds the key to Choose from a variety of communication protocols
growth and development in any sector. Moreover, in including MODBUS RTU and Bluetooth available with
most sectors, such as the building sector, energy our new MATRIX releases. In todays world of high-
management has become mandatory. Our new range end residential buildings or commercial malls, our
of dsine MATRIX releases with advanced technology motorised dsine MCCBs with the fastest changeover
is specially designed with energy management in from mains to DG in less than 300 milliseconds are
mind. indeed the most reliable choice. Our Auto Source
Transfer System has almost eliminated the risk of loss
MTX3.0 releases with power metering and
of data.
communication capabilities are ideal for remote
annunciation in Data Centres and IT Parks.
Performance: Delivered
Delivering Unparalleled Results 9
Infrastructure
Monitoring and controlling electrical installations at As power supply is critical for airports and hospitals,
places like airports, hospitals etc. demands high-end, our dsine MCCBs with ASTS offer changeovers in less
reliable solutions. MATRIX releases are built precisely than 300 milliseconds coupled with a variety of other
for such purposes. protections in case of under voltage, phase
unbalance, etc.
Communication capable MATRIX releases with
power and energy metering help in modernisation. A variety of settings in MATRIX releases helps in
These releases are made compatible with HMI choosing the correct selection for fault clearing,
(Human Machine Interface) and DCS (Data Control while trip & event recording with MATRIX releases
System). helps in analysing the faults in detail.
Our dsine MCCBs are shipped to Europe, Africa, Australia, Middle East,
South East Asia, China and America. In India, we have the largest
stockist network with over 700 stockists. To find the ideal dsine MCCB
suitable for your requirements, turn the page.
INDEX
Overview
Product Data
Accessories
Characteristic Curves
Wiring Diagrams
Dimensions
Overview
n Range 16
n
Standards & Approvals 18
n
Structure & Features 19
n
Marking & Configuration 20
n
Trip Units 21
n
Accessories 22
16 Range
State-of-the-art design, user-friendly features and a wide spectrum of protection releases form the hallmarks
of the dsine range. Also recognised for its ergonomics, aesthetics and compactness, it belongs to a new
generation of MCCBs. Specially designed and developed for extreme tropical conditions, it promises reliable
performance at high ambient and humid environment.
dsine, unfailingly, caters to the ever-evolving needs of customers, derived after in-depth analysis and customer
feedback. Because we understand our customers' requirements and demands, our contemporary range of
MCCBs never fall short of ensuring complete customer satisfaction. Moreover, complemented by a host of
accessories, the dsine range delivers comprehensive solutions to customer applications ensuring operational
safety, reliability and versatility.
Range 17
Features
Range
available from 20A to 1250A
Available
in 3 pole & 4 pole
Range of 25kA / 36kA / 50kA / 70kA / 100kA breaking capacities
DN0
Rated Current 20, 25, 32, 40, 50, 63, 80, 100, 125*A
Release Thermal-Magnetic
DN1
Rated Current 125, 160, 200, 250A
Release Thermal-Magnetic
DN2
Rated Current 63, 80, 100, 125, 160, 200, 250A 40, 63, 100, 160, 250A
Release Thermal-Magnetic Microprocessor
DN3B
Rated Current 320, 400A
Release Thermal-Magnetic
DN3
Rated Current 320, 400, 500, 630A 400, 630A
Release Thermal-Magnetic Microprocessor
DN4
Rated Current 800, 1000, 1250A
Release Microprocessor
* Available only in DN0-D
NABL
NABL accreditation is a formal recognition of the technical competence of testing,
calibration or medical laboratory for a specific task following ISO/IEC 17025:2005
Standard. Accredited laboratories have the responsibility of satisfying the criteria of
laboratory accreditation at all times, which are verified during Surveillance and Re-
assessment visits by NABL. Further the accredited laboratories should prove their
technical competence by satisfactory participation in recognized Proficiency Testing
Programmes.
L&Ts Switchgear Testing Lab is NABL accredited subject to continued satisfactory
compliance to above standard & additional requirements of NABL.
All dsine range of MCCBs are tested in L&T's NABL accredited Switchgear Testing Lab.
marking
A CE marking is a European marking of conformity that indicates a product complies
with the essential requirements of the applicable European laws or directives with
respect to safety, health and environment and consumer protection. Generally, this
conformity to the applicable directives is done through self-declaration and is required
on products in the countries of the European Economic Area (EEA) to facilitate trade
among the member countries. The manufacturer or their authorized representative
established in the EEA is responsible for affixing the CE marking to their product. The
CE marking provides a means for a manufacturer to demonstrate that a product
complies with a common set of laws required by all countries in the EEA to allow free
movement of trade within the EEA countries.
L&Ts dsine range of MCCBs conform to the Low voltage directive 73/23/EEC as
amended by directive 93/68/EEC, provided if it is used in the application for which it is
made and is installed and maintained in accordance with professional practices with
relevant installation standards and operating instructions.
Terminal Connections
Standard Characteristics
}Uimp: Impulse withstand voltage
}Ue: Rated operational voltage
}Icu: Rated Ultimate breaking Utilization Category
capacity Brand
}Ics: Rated Service breaking capacity Frame Size
Symbol of suitability
Standards for Isolation
Mark
Indication of Closed (I/ON)
Company Logo
Operating Knob
Release
Current Rating of MCCB
Release Settings "Push to Trip" button
Release name
Terminal Shroud
Trip Units 21
Variable Thermal,
Fixed Magnetic
(DN0, DN1, DN3B)
Thermal Magnetic
Variable Thermal, Variable Magnetic (DN2, DN3)
Releases
Inst
Microprocessor
Releases
Inst
In 630 A
Magnetic Release
DN3-M
Isolator
22 Accessories
1 Spreader Terminals
2 Phase Barriers
3 Undervoltage Release
4 Shunt Release
5 Auxiliary Contact 12
13 Communication Module
16
14 Voltage Module
15 Display Module 4 3
16 External Neutral CT
(with Adaptor Kit)
8
23
15
14
13
6 7
5
11
10
9
Product Data
MCCBs for Power Distribution 26
Technical Datasheet
Motor Backup Protection
Isolator Application
MCCBs for DC Applications
Protection Releases
MCCBs for Different Applications 42
Auto Source Transfer Application
26 MCCBs for Power Distribution 27
Technical Datasheet
Frame 100A 125A 250A 250A 400A 400A 630A 1250A
DN0-100 DN0-125 DN1-250 DN2-250 DN3B-400 DN3-400 DN3-630 DN4-1250
Type
C D D C N D N S H V D D N S D N S V N S V
TM/MP MP (MTX MP (MTX
Release TM TM TM (MTX1.0/2.0/3.0) TM TM/MP (MTX1.0/2.0/3.0) TM/MP (MTX1.0/2.0/3.0) MP (MTX1.0/2.0/3.0)
1.0/2.0/3.0) 1.0/2.0/3.0)
20, 25, 32, 125, 160, 40, 63, 80, 40, 63,
Current Range In (A) 40, 50, 63, 125 100, 125, 160, 100, 160, 320, 400 320, 400 500, 630 400, 630 800, 1000, 1250
200, 250
80, 100 200, 250 250
Poles 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Impulse withstand Voltage Uimp (kV) 6 6 6 8 8 8 8 8
Rated Operational Voltage Ue (V) (MAX) 600 600 600 690 690 690 690 690
Rated Insulation Voltage Ui (V) 690 690 690 800 800 800 800 800
Utilization Category A A A A A A A A
Standard IS/IEC60947-2, IEC60947-2 & EN60947-2
240 VAC 40 65 65 65 65 50 70 100 - - 50 50 70 100 50 70 100 - 70 100 -
415 VAC 25 36 36 25 50 36 50 70 80 100 36 36 50 70 36 50 70 100 50 70 100
Icu(kA) 480 VAC 10 10 10 10 10 25 36 42 65 65 25 25 36 42 25 36 42 65 25 36 65
Rated 550 VAC 8 8 8 8 8 18 25 36 - - 15 15 20 25 15 20 25 - 20 25 -
Short 600 VAC 5 5 5 5 5 16 18 22 - - 12 12 18 22 12 18 22 - 16 20 -
Circuit 690 VAC - - - - - - - - - 36 - - - - - - - 50 - - 50
Breaking
Capacity 240 VAC 100% 50% 50% 50% 50% 100% 100% 100% - - 100% 100% 100% 100% 100% 100% 100% - 100% 100% 100%
Ics as % Icu 415 VAC 100% 50% 50% 100% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
480 VAC 100% 50% 50% 50% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
550 VAC 100% 50% 50% 50% 50% 100% 100% 100% - - 100% 100% 100% 100% 100% 100% 100% - 100% 100% -
600 VAC 100% 50% 50% 50% 50% 100% 100% 100% - - 100% 100% 100% 100% 100% 100% 100% - 100% 100% -
690 VAC - - - - - - - - 50% - - - - - - - 50% - - 50%
Mechanical 40000 40000 10000 25000 25000 10000 15000 15000 15000 20000
Life
Electrical @1.0 In 4000 2500 3000 10000 10000* 4000 4000 4000 4000* 3000*
Making Capacity (kA) 52.5 75.6 75.6 52.5 105 75.6 105 154 176 220 75.6 75.6 105 154 75.6 105 154 220 105 154 220
Operating Frequency (Hz) 50 / 60
Total Opening Time <10msec <20msec
Finger-proof Terminals Yes
Suitable for Isolation Yes
IP class IP40
Pollution Degree III
Load Line Bias NO
Ambient Temperature -5OC to 55OC
O O
Storage Temperature -35 C to 70 C
Mounting Positions in Vertical Plane Vertical and 90 deg in both directions
3-Pole 75 x 60 x 130 105 x 60 X 165 105 x 96 x 179 140 x 111 x 205 140 x 111.5 x 266 140 x 111.5 x 266 210 x 143 x 370
Dimensions (WxDxH) mm
4-Pole 100 x 60 x 130 140 x 60 X 165 140 x 96 x 179 184 x 111 x 205 183.5 x 111.5 x 266 183.5 x 111.5 x 266 278 x 143 x 370
Weight (kg) (3/4 Pole) 0.8/1.1 0.73/1 0.73/1 1.55/2 2.5/3.3 4.0/5.0 5.5/7.2 6/7.8 6.3/8 17 / 22
Auxiliary Contact 1 C/O or 2 C/O
Trip Alarm Contact 1 C/O or 2 C/O 1 C/O
A
INTERNAL Auxiliary & Trip Alarm Contact 1 C/O + 1 C/O
C
C Shunt Release 240/415 V AC 50 Hz 110 / 415 V AC 50 Hz, 110 / 220 V DC, 24 V DC $
E Under Voltage Release 240 V AC 50 Hz
S Rotary Operating Mechanism (Direct/Extended)
S Electrical Operating Mechanism
#
O Mechanical Interlock Kit
R Spreader Terminals
I EXTERNAL
Key lock
E Neutral CT with Adaptor kit Available for 3P MCCBs with MTX2.0 & MTX3.0 release only
S
Current Metering Module Available for MTX2.0 release for current metering only @
Display, Communication and Voltage Module Available for MTX3.0 release for Communication & Power metering
$ : 'NO' of control contactor to be connected in series for 220V DC, 24V DC Note:
@: Contains display module & metering module, separate cable required for connection Any two internal accessories can be mounted at a time
V version MCCBs, to be used with extended ROM only
#: Only Extended ROM available Separate earth fault module required for earth fault protection using TM releases
* : at 415V Icu: Rated ultimate short-circuit breaking capacity
DN2 - 1500 @ 690V Ics: Rated service short-circuit
O
breaking
O
capacity
DN3 - 1000 @ 690V Reference temperature 40 C & 50 C
DN4 - 800A - 2500 @ 415V
28 MCCBs for Motor & Isolator
Isolator Application
dsine MCCBs with Switch Disconnector version offer solution for switching various loads such as UPS, Battery
Banks etc. with various advantages. These MCCBs differ from regular MCCBs only in terms of absence of
protection trip units. These MCCBs can be used for following applications for isolation purpose:
For local isolation- such as very close to Motor load
Generally used at the incoming of any sub-distribution
As an Isolator for Bus coupler
As an automatic switch
For switching applications of motors with VFDs, soft starters
SD MCCBs are always backed up by the Short Circuit Protection Device (SCPD) to protect downstream
loads/installations against short circuit. Our dsine SD MCCBs offer following advantages.
Suitable for Positive isolation
Available with 3P & 4P versions
Can be used with Under Voltage Protection
Remote tripping through Shunt release
Motor operated MCCBs
Status feedback possible
Following are the specifications of SD MCCBs
DC power distribution is an upcoming technology in this modern era due to its most rigorous network power
applications such as
AC-DC Power System
DC-DC Converter Systems
DC-AC Inverter Systems
DC UPS
Batteries & Accessories
Solution to alternative energy-Solar Power
We offer dsine MCCBs for the protection of DC systems in variety of current ratings from 20A-630A, voltage
ratings upto 750V and various breaking capacities ranging from 5kA to 36kA.
250 V DC 20 20 20 30 36 20 30 36 25 20 30 36
Icu (kA rms) 500 V DC 15 15 15 20 25 15 20 25 10 15 20 25
750 V DC - - 10 15 20 10 15 20 - 10 15 20
Type of connection 3P in series
L/R (msec) <15msec
*Available only in DN0-125D
Switching of DC currents is much severe phenomenon than switching AC currents due to non occurrence
of natural zero. Hence DC MCCBs are desired to give less breaking capacity than AC MCCBs for the same
voltage & currents. As per the earthing of the system, we recommend following connections for breaking
the fault currents.
+ + LOAD + LOAD
250/500V
250/500V
250/500V
- LOAD - -
Thermal-Magnetic Release
Features of Thermal-Magnetic Release
Adjustable
overload settings
Fixed
/ Adjustable short circuit settings
True RMS
sensing Settings
Protection
Push
to Trip button DN0 & DN1 DN2 & DN3 DN3B
Microprocessor Release
Features of MTX1.0
Overload Protection with inverse time delay
Adjustable Trip class
Short Circuit Protection with selectable
time delay
Provision of Thermal memory defeat
Provision for release testing
Overload indication
Power ON LED
Self powered
True RMS sensing
Push to Trip button
MTX1.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 5%
Time delay, tr (Inverse) 10s at 6Ir, 3s at 6Ir, 10s at 7.2Ir, 3s at 7.2Ir
Protection mode ON / OFF
Thermal memory Enable / Disable
Short Circuit
Current setting, Is (Is = x Ir) 1.5, 2.5, 4.0, 5.5, 6.5, 8.0Ir
Time delay, ts Instantaneous / 100ms
Protection mode ON / OFF
Note: Factory Settings - O/L: 100%In, Curves: 6Ir@10s, Thermal Memory: Off, S/C: 5.5Ir @ Instantaneous
Release provides in-built instantaneous override protection fixed @ 10In
* Refer page 51
Protection Release for MCCBs 31
Microprocessor Release
Features of MTX2.0
Inst
protection
Overload indication
Power ON LED
Self powered
MTX2.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 5%
Time delay, tr (Inverse) 10s at 6Ir, 3s at 6Ir, 10s at 7.2Ir, 3s at 7.2Ir
Protection mode ON / OFF
Thermal memory Enable / Disable
Overload (Neutral)
Current setting, IN (IN = x Ir) 50%, 100% and 150%Ir
Time delay, tN 200ms / Same as overload
Protection mode ON / OFF
Short Circuit
Current setting, Is (Is = x Ir) 1.5, 2.5, 4.0, 5.5, 6.5, 8.0Ir
Time delay, ts Instantaneous / 100ms
Protection mode ON / OFF
Earth Fault
Current setting, Ig (Ig = x In) 20% to 50%In in steps of 10%
Time delay, tg 100ms / 200ms
Protection mode ON / OFF
Note: Factory Settings - O/L: 100%In, Curves: 6Ir @10s, S/C: 5.5Ir @ Instantaneous, Thermal Memory: Off, E/F: Off, Neutral: Off.
Release provides in-built instantaneous override protection fixed @ 10In
32 Protection Release for MCCBs
Power
Supply
Module
Metering Module
O-LED Display
O-LED display allows the operator a wide viewing
angle.
O-LEDs showing current metering has got faster
response time and also consumes less power,
hence saves energy. It has better contrast ratio as
well. Display Module
Protection Release for MCCBs 33
@6Ir
Inst
3s
10s
@7.2Ir
2 3 1
Thermal Memory 2
Thermal memory protects the system from thermal stresses generated by cumulative heating caused by
cyclic overload conditions thus allowing the system to return to a safe operating temperature. This function
also allows an optimization of cables or bus bar protection in case of low amplitude repetitive faults.
Advance tripping increases the overall life and eliminates the production downtime incase of severe faults.
DIP Switches
DIP switches are provided on front side of the release for easy operations. These switches give you quicker
option to precisely change selection, offering high life.
Overload Indication 4
Improves uptime and productivity by setting alarms for unbalanced loads so that proactive measures can
be taken to avoid overload conditions.
Self Powered
MTX releases do not need any external power supply hence require no extra devices and wires to power up.
Note: For wiring diagram, please refer page no. 62
34 Protection Release for MCCBs
@6Ir
Inst
Overload Protection, (Ir = x In)
3s
10s
@7.2Ir
0.4 0.4 0.4 0.4 0.4 0.4 0.4
DIP Switch
r
r
Position
q
r
q
r
r
q
r
q
r
q
r
q
r
Setting Bypass 40% 45% 50% 55% 60% 65%
DIP Switch
r
r
Position
q
r
q
r
q
r
q
r
q
r
q
r
q
r
Setting 70% 75% 80% 85% 90% 95% 100%
Thermal Memory
0.4 0.4
DIP Switch
r
Position
q
r
q
r
Setting Bypass ON
Overload Curves
DIP Switch
r
Position
q
r
q
r
q
r
q
r
DIP Switch
Inst
Inst
Inst
Inst
Inst
Inst
Inst
Position
Inst
Position
DIP Switch
Position
0.2 0.2
DIP Switch
Position
Ir * Ir * Ir * Ir *
DIP Switch
Position
0.5
1.0
0.5
1.0
0.5
1.0
0.5
1.0
Ir * Ir *
DIP Switch
Position
0.5
1.0
0.5
1.0
Microprocessor Release
Features of MTX3.0
Overload
Protection with inverse time delay
2 4
I t, I t, SI, LI-VI based over load curves
Pre-trip alarms
Inst
Power on LED
Self powered
MTX3.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 1%*
Time delay, tr (Inverse) 0.5s to 30s in steps of 0.1s*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Ir in steps of 1%*
Thermal memory Enable/Disable
Overload (Neutral)
Current setting, IN (IN = x Ir) 50% to 150% Ir in steps of 1%*
Time delay, tN 0.2s / same as overload
Protection mode ON / OFF
Short Circuit
Current setting, Is (Is = x Ir) 1.5 to 8 Ir in steps of 0.1*
Time delay, ts 100ms, 200ms, 300ms, 400ms*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Is in steps of 1%*
Instantaneous
Current setting, Ii (Ii = x In) 1.5 to 8 In in steps of 0.1*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Ii in steps of 1%*
Earth Fault
Current setting, Ig (Ig = x In) 10% to 50% In in steps of 5%*
Time delay, tg 100ms to 500ms in steps of 50ms*
Protection mode ON / OFF
* Can be set using display module
Note: Factory Settings - Address:0000, O/L: 100%In, Curves: 6Ir @10s, S/C: 5.5Ir @ Instantaneous, Thermal Memory: Off, E/F: Off,
Neutral: Off.
Release provides in-built instantaneous override protection fixed @ 10In
Protection Release for MCCBs 37
Voltage Protection
Under Voltage
Voltage setting (V) Vuv (Vuv = x Un) 45 to 80% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 110 to 150% Vuv in steps of 1%
Over Voltage
Voltage setting (V) Vov (Vov = x Un) 105 to 150% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90%Vov in steps of 1%
Voltage Unbalance
Voltage setting (V) 5 to 20% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Residual Voltage
Voltage setting (V) 5 to 40% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Frequency Protection
Under Frequency
Frequency setting (Hz) F-0.5 to F-5.0 in steps of 0.5
Time delay (s) 0.1 to 30 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set freq in steps of 1%
Over Frequency
Frequency setting (Hz) F+0.5 to F+5.0 in steps of 0.5
Time delay (s) 0.1 to 30 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set freq in steps of 1%
38 Protection Release for MCCBs
Power Protection
Reverse Power
Power setting (W) PR 1 to 5000kW in steps of 1kW
Time delay (s) 0.5 to 60 in steps of 0.5
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% PR in steps of 1%
Lead Pf
Pf setting 0.5 to 0.99 in steps of 1%
Time delay (ms) 100 to 500 in steps of 1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Lag Pf
Pf setting 0.5 to 0.99 in steps of 1%
Time delay (ms) 100 to 500 in steps of 1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Other Protections
MD Active
Demand settings 1 to 5000kW in steps of 1kW
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
MD Reactive
Demand settings 1 to 5000kVAr in steps of 1kVAr
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
MD Apparent
Demand settings 1 to 5000kVA in steps of 1kVA
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Phase Sequence
Phase seq setting 123 or 132
Time delay (s) 1 to 5 in steps of 0.1
Protection mode ON / OFF
THD Current
Current setting (A) 5 to 50%Ir in steps of 1%
Time delay (s) 5 to 15 in steps of 5
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
THD Voltage
Voltage setting (V) 5 to 50% Un in steps of 1%
Time delay (s) 5 to 15 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Protection Release for MCCBs 39
release, in addition to current & voltage measurement, active, reactive and apparent energy &
power can also be measured. This would enable monitoring energy at individual feeder level and
thus help in implementing effective energy management practices in the plant. Moreover, using
communication module, different parameters reading can be viewed on display module.
Power Supply
Module
Voltage
Display Module
Module
3 ph 4 wire
Communication AC supply
Module
Communication Capable
Convertor
Laptop or HMI (RS485 to RS232)
Most advanced release of MTX series, MTX3.0 is communication capable on MODBUS RTU network. Using
MODBUS com module the MCCB release can be connected to a Personal Computer. The metering values can be
read remotely. The settings configuration on the other hand can both be read and changed remotely. These
releases are also made compatible with HMI (Human Machine Interface) & DCS (Data Control Systems)
Protection Release for MCCBs 41
Multi-looping
Laptop or HMI
Convertor
(RS485 to RS232)
A single display module can be used to connect upto 15 MCCBs with MTX3.0 release through MODBUS
network. Highly reliable data yet extremely simple looping reduces operational headaches and enhances
remote accessibility.
Maintenance Functionality
MTX3.0 release can store last 10 trip records & last 10 event records which can be used for the system
analysis later on. These recorded values can be viewed from display unit as well as PC.
+
AuXC-1000
Key Features:
Utility-to-utility, utility-to-generator or generator-to-generator changeover possible
Three-phase, two-phase or single-phase voltage controls
Controls of minimum voltage, maximum voltage, phase loss, asymmetry, minimum frequency,
maximum frequency, with independent enable and delay
Voltage thresholds with programmable hysteresis
Manual control of Circuit Breakers
Main line failure simulation
Communication Capable
Front display for monitoring the system voltage and frequency and for onsite controller programming
Six programmable inputs and five programmable outputs
Front test feature to simulate the operation of the diesel generator set
Status indication through 22 LEDs
Flush mounting arrangement
+
AuXC-1000L
With the new AuXC-1000L controller in addition to its predecessor, ASTS has become a lot simpler & easier.
Some of the salient features of the controller are as follows:
Utility-to-utility, utility-to-generator changeover facility
Single supply input from battery supply 12-48V DC
Display to view main and secondary line parameters
15 status LED indicators
6 programmable digital inputs
3 programmable relay outputs
RS232 communication interface
Modbus RTU and Modbus-ASCII communication protocols
Status display of circuit breakers
Emergency demand supervision parameter programming for stand by generator sets
Event logging
Alarm code & description display
The automatic transfer takes place through AuXC-1000L / AuXC-1000 whenever following conditions are
predefined by the user
System Voltage not in line with programmed limits
The need to have a very reliable power source
The need to use the most economical power source
These controllers are compatible with U-POWER OMEGA range of Electrical ACBs, dsine range of Motorized
MCCBs and MCX range of contactors.
Accessories
Internal Accessories 46
- Auxiliary Contact
- Trip Alarm Contact
- Auxiliary Trip Alarm Contact
- Shunt Release
- Under Voltage Release
External Accessories 47
- Rotary Operating Mechanism
- Mechanical Interlocking Kit
- Keylock
- Spreader Terminals
- Terminal Shrouds
- External Neutral CT
- Stored Energy Electrically Operated
Mechanism
- MTX Modules
- Earth Fault Module
46 Accessories
Internal Accessories
Shunt Release
It allows opening of MCCB by means of an electrical command. Operation of the release is guaranteed for a
voltage between 70% and 110% of the rated power supply voltage value Ue, both in AC & DC.
UV Release
The Under-voltage release causes the MCCB to trip if the operational voltage falls to a value between 35% and
70% of its rated voltage or not applied. UV release mechanically locks the closing mechanism of MCCB & makes
it impossible to close on under-voltage or no voltage, both manually & electrically. With the under-voltage
release de-energized, it is not possible to close the MCCB. UV release can also be used for interlocking schemes
(for DG synchronization, paralleling of transformers etc) also.
External Accessories
Rotary Operating Mechanism
Rotary operating mechanism (ROM) for dsine MCCBs are available in direct &
extended versions.
Spreader Terminal
Available for enhancing termination capacity
Made of silver plated copper
$ 30mm on request
Specifications AC DC
Input 85-265V 125-300V
Output 1 - 650mA at 24V DC
#
Output 2 - 200mA at 24V DC
#
For using Output 2, Output 1 should be loaded
Current Metering Module for MTX2.0
It consists of 2 parts viz. Metering module & Display module. Metering module collects the data from the
release and sends the same to the Display module. The panel mounted O-LED Display module shows
various parameters viz. 3 phase currents, neutral and ground fault currents, if any. We can also view last trip
records.
Communication Module for MTX3.0
The Communication module is solutions for connecting dsine
MCCBs to Modbus network for remote supervision and
control of circuit breaker. It is suitable for the MTX3.0 electronic
trip units across DN2/DN3/DN4 frames. It is available with DIN
rail mounting facility. 2 LEDs in front fo the module indicates
The Power LED - the presence of auxiliary power supply to
the module
The Data LED - transmission of data
Its operating temperature is -25O C to 70O C and consumption is 43mA
Voltage Module for MTX3.0
This accessory when connected to MTX 3.0 release in DN2/DN3/DN4
frames is able to provide the various measurements of the electrical
values of the plant. It has to be mounted just beside the MCCB on a
O O
DIN plate. Its operating temperature is -25 C to 70 C.
Display Module for MTX3.0
It is a panel mounted O-LED display unit that can be integrated with
MTX3.0 release in DN2/DN3/DN4 frames. It has one navigation key, a
select button a an exit button. Its operating temperature is
O O
-25 C to 70 C and consumption is 12mA
MTX Test Kit
Universal Test Kit for all MTX releases
Simulation of overload, short-circuit & earth fault
Single phase AC supply
Earth Fault Module GF11 Note: MCCBs need to be fitted with 110 V / 240 V AC shunt
GF11 is suitable upto 800A MCCBs release for Earth Fault Module operation.
Technical Data
Specification Type GF1 / GF2 / GF11
Current Setting Range, Is (Is=x In) 10% to 50%In in steps of 10%
Auxiliary Supply 240V AC 20%
Time Delay (ms) 100 / 200ms Field selectable
Pick-up Accuracy 10% Is
1 NO contact manual reset Type
Output Contact
contact rating 5A 240V AC
a) Power On LED
Indication b) Trip LED (manual reset)
Operating Temperature +10oC to +55oC
2 kV 50Hz for one minute across independent circuit
Insulation 1 kV 50Hz for one minute across open contacts
Mounting Base plate mounting type
2 GF1 - 110 x 32
Window for Cable / Busbar entry (mm )
GF2 - 165 x 61.5
Weight (kg) GF1 - 1.2, GF2 - 2.2, GF11 - 0.9
n
Microprocessor Release
55
}MTX1.0-2.0 (O/L curves)
- I2T at 6Ir, 7.2Ir
}
MTX3.0 (O/L curves)
- I2T at 1.5Ir, 6Ir, 7.2Ir
4
- I T at 1.5Ir, 6Ir, 7.2Ir
- SI at 1.5Ir, 6Ir, 7.2Ir
- LI-VI at 1.5Ir, 6Ir, 7.2Ir
- Short circuit, Earth fault & Neutral
curves For MTX1.0-2.0-3.0
54 Characteristic Curves
Thermal-Magnetic Release
1000 1000
100 100
Trip Time (s)
10 10
9In 9In
0.1 0.1
t<10ms t<10ms
0.01 0.01
0.001 0.001
10-1 1 10 102 103 10-1 1 10 102 103
Current multiples (xIn) Current multiples (xIn)
10 10
Trip Time (s)
10
6-10In
6-10In
1 9In
1 1
0.001
0.001 0.001
10-1 1 10 102 103 10-1 1 10 102 103 10-1 1 10 102 103
Current multiples (xIn) Current multiples (xIn) Current multiples (xIn)
Microprocessor Release
2
MTX1.0 / 2.0 - DN2 / DN3 / DN4 (O/L curves - I t)
2 2
I T @ 6Ir I T @ 7.2Ir
10000 10000
1000 1000
Trip Time (s)
10 10
10s
10s
3s
1 3s 1
0.1 0.1
1 10 1 10
Current multiples (xIr) Current multiples (xIr)
2
MTX3.0 - DN2 / DN3 / DN4 (O/L curves - I t)
I T @ 6Ir
2 2 2
I T @ 1.5Ir I T @ 7.2Ir
1000 10000 10000
10 100 100
Trip Time (s)
30s
1 10 30s 10 20s
30s
20s 10s
20s
10s
10s 5s
5s 3s
0.1 5s 1 3s 1
3s
Microprocessor Release
4
MTX3.0 - DN2 / DN3 / DN4 (O/L curves - I t)
4 4 4
I T @ 1.5Ir I T @ 6Ir I T @7.2Ir
1000 100000 100000
10000 10000
100
1000 1000
10
Trip Time (s)
1
10 10 30s
30s 18s
30s
18s 18s 10s
0.1 10s 6s
10s 1 1
6s 3s
6s 3s
3s
0.01 0.1 0.1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)
30s 30s
24s 24s
30s
Trip Time (s)
Trip Time (s)
24s
12s 12s
10 10 10
12s
4s 4s
4s
1 1 1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)
Characteristic Curves 57
Microprocessor Release
MTX3.0 - DN2 / DN3 / DN4
(O/L curves - Long Inverse / Very Inverse)
LI-VI @ 1.5Ir LI-VI @ 6Ir LI-VI @ 7.2Ir
100 1000 1000
10 100 100
Trip Time (s)
4s
4s
4s
0.1 1 1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)
400ms 500ms
300ms
Invs
OFF*
200ms 200ms 200ms
Trip Time (s)
Inst
For MTX3.0 only For MTX3.0 only *: IDMT disable in case of MTX3.0
QF2
9.1
9.2
9.3
9.4
AuXc - 1000
Q1 Q2 K2 K2 K1 K1 DC
DIGITAL INPUT S SUPPLY
7.1
7.2
1.1
1.2
1.3
2.1
2.2
2.3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
5.1
5.2
5.3
K1 K2
_ _
+
K2 K1
L1 L2 L3 N
LOAD
Parameter setting
for the wiring diagram in picture.
Terminal Parameter code Setting
1.1 P6.01 OP.1 Circuit Breaker
1.3 P6.02 CL.1 (Q1, Q2) 1 3 4 2 1 3 4 2
POWER SUPPLY
POWER SUPPLY
2.1 P6.03 OP.2
INTERLOCK
INTERLOCK
Contactors COMMON
COMMON
OPENING
OPENING
CLOSING
CLOSING
2.3 P6.04 CL.2
STATUS
STATUS
TRIP
TRIP
4.1 P5.01 Fb.1 Mechanical
4.2 P5.02 Fb.2 Interlocking 5
WITHDRAWN
5
WITHDRAWN
3.1
3.2
3.3
3.4
3.5
2.1
2.2
2.3
2.4
2.5
2.6
L
DUALPOWERSUPPLY OUT
N
L1 L2 L3 N
LOAD
Parameter setting
for the wiring diagram in picture.
Terminal Parameter code Setting
4.1 P6.1.1 OP.1 Circuit Breaker 1 3 4 2 1 3 4 2
4.3 P6.2.1 CL.1 (Q1, Q2)
POWER SUPPLY
POWER SUPPLY
INTERLOCK
COMMON
COMMON
Contactors
OPENING
OPENING
CLOSING
CLOSING
STATUS
STATUS
TRIP
RECTIFIER
L
3
AUX.
SUPPLY
N
4 240 Vac
TO LOAD
GF11
FROM MCCB
240 Vac
R Y B N RELAY 1
MCCB
2 SHUNT
S1 RELEASE
SENSING
CIRCUIT
S2 5
S1
CT Sec.
S2 RECTIFIER L
3
S1 AUX
SUPPLY
S2
4 240 Vac
N
S1
S2
TO LOAD
62 Wiring Diagrams
Display Module
Metering
Module
MTX2.0 Release
Inst
to other
MTX2.0
24 Vdc 24 Vdc
+ - + -
Auxiliary
Power Supply
Module
L 240 Vac
N 50 Hz
Wiring Diagrams 63
Display Module
Communication
Module Voltage Module
MTX3.0 Release
Inst
D+ Convertor
D- 3 Phase
RS485 RS232
+Vs 415 Vac Supply
Gnd
+ - + -
24 Vdc 24 Vdc
Laptop / SCADA
System
Auxiliary
Power Supply
Module
L 240 Vac
50 Hz
N
Dimensions
n
Dimensions of MCCB
}
DN0
}
DN1
}
DN2
}
DN3B
}
DN3
}
DN4
n
Dimensions of Accessory
}
Rotary Operating Mechanism
}
Stored Energy Electrically
Operated Mechanism
}
Panel Mounted Key Lock
}
Mechanical Interlock Kit
}
External Neutral CTs
}
MTX Modules
}
Auto Source Transfer Switch: AuXC-1000
and AuXC-1000L
}
Earth Fault Modules
}
Terminal Shrouds
66 Dimensions of MCCB
DN0-125 MCCB
86
64
60
20 2
75 (3P) MCCB MOUNTING HOLES
M3 SCREW 6 Nos.
32
25 25 25 12.5
10
25 25
50.5 50.5
61.5
25.5
48.5
58
13.5
52
75
2.25 27.25
116.4
17
112
130
112
46
39
N N CUT OUT 1
45
38
CUT OUT 2
29.5
76
101
25 25 25
32.2
11
32
28
28
10
61.5
58
13.5
75
17
172.2
194.2
172.2
194.2
N
45
38
30.2
32.2
2
22 22 20
35 35 35 35 35
92 127.2
DIN rail kit
DN1-250 MCCB
MCCB MOUNTING
HOLES 6 Nos.
105 (3P) 93.7
141
35 35 35 17.5 64.5
60
35 35
17.5 17.5
58.6
78.65
95.7
126
145
165
126
46
N
45
88 53
70.5 70.5
35 35 35 Mounting &
140 (4P) Door Cut-out Details
46
47.5
38
78.65
95.7
221
147
257
221
257
N
45
47.5
46
35 4
54.5 54.5 35 18
144 54 54 54
197
DN2-250 MCCB
25.5 60.5
89.27
72.7
61
CUT OUT
157
163
157
179
46.5
N
45
86
35 35 35
140 (4P) Mounting &
Door Cut-out Details
48
38
38
89.27
72.7
239
275
239
275
N
45
41
48
35 35 4
54 54 54 A
54.5 54.5
144 197
DN3B-400 MCCB
MCCB
MOUNTING HOLES
M5 SCREW 6 Nos.
44.50 44.50
140
139.5 (3P) 115
52.50
44.5 44.5 44.5 25.25 110
38.25 82.75
CUT OUT
68
98
176
79
182
205
176
77
121
13
13
56.5
45
45
68
98
272
318
272
318
N
77
56.5
40 40 5
63.5 63.5 63 61.5 63 26.5
167 227.5
DN3-400/630 MCCB
180
143 MCCB MOUNTING HOLES
140 (3P) 120 M5 SCREW 6 Nos.
43,5 43,5 43,5 26,5 103 43,5 43,5
104
38.75
82.25
CUT OUT
82,7
224
234
266
224
77
78
N
121
43,5 43,5
Mounting &
183.5 (4P) Door Cut-out Details
23
10.5 5
10.5
F
C
104
D
D
E
77
N
F
40 40
62,5 62,5 62 60,5 62 B
165 224,5
* 38 for MTX
# 38 for 500A TM
DN4-800/1000/1250 MCCB
MCCB
210 (3P)
197 MOUNTING HOLES
68 68 68 143 M5 SCREW 6 Nos.
68 68
132.5
109.5
198.5
57 125
105
107
330
370
326
326
N
CUT OUT
182
24
71 68 68 71
Mounting &
180
Door Cut-out Details
278 (4P)
85
132.5
105
370
510
N
85
24
15
60 24 60 46
B B 198
3P Frame 4P Frame
3/4P Frame
Type A B C D Type A B C D
Type Y
800A 98 256 6 38 800A 88 324 6 28
N version 46
1000A 98 256 12 38 1000A 88 324 12 28
S version 42
1250A 86 232 20 26 1250A 80 300 20 20
L5
L4
L3
N
L2
L1 68
Mounting &
Door Cut-out Details
L2 51
450 76
L3
N 4
Type L1 L L2 L3
DN0 169 L1 - 119 7.5 69.5
L
DN1 169 L1 - 119 24.5 81.7
DN2 202 L1 - 152 27 84
L = Length of Shaft Required DN3 233 L1 - 183 39 122
for Panel Depth L1 DN3B 233 L1 - 183 39 92
Total Length of Shaft =275mm DN4 302 L1 - 252 69 170
18.7
== 237.5
Door
Cut-out
94
157
N ON TRIP
156
= =
94
DN3 264
Mounting 43.5
holes for MCCB 256
= =
Door
62.1
45 49
94
Door
Cut-out
224
94
N ON TRIP
Cut-out for
136
Handle Assembly
68
68
12
Cut-out for
Panel Mounted Key Lock 29
2.2
58 52
Mounting &
Door Cut-out Details
Note: Panel Mounted key lock can be used only with extended ROM All dimensions are in mm
74 Dimensions of Accessories
DN2
372
10 Mounting Holes
41.5 141 141
35
10
149
209
239
177
141 141 Holes for Breaker Mounting
Mounting Details
DN3
10 Mounting Holes
436
53 161 161 53 56
22.5
152.5
316
346
266
Mounting Details
DN2/DN3
K
L
B
C
D
G
H
J
Bottom Bottom
Side Side
Frame A B C D E F
ON
TRIP
Frame G H J K L M OFF
Bottom
DN2 250A 77 153 189 26 4 55 Side
Note: Adaptor Terminals shown are not available with product >M
Kindly refer accessories data for ordering separately
Circuit Breaker shown for reference only All dimensions are in mm
76 Dimensions of Accessories
DN4
M P
H
G
K
D
J
A
Bottom Bottom
Side Side
F
E
DN4 A B C D E F G
800A 132 88.5 73.5 117 60 12.5 92
DN4 H J K L M P
800A 24 302 272 80 47 6
Bottom
Side
1000A 24 302 272 80 47 12
MTX Modules
Display Module
36
44.5
51
10
96
44.5
91.5
91.5
Voltage/Communication/Metering Module
3
73.3
73.3
81
87
3
23
14.3 60
Door Cut-out
23 65
Details
C
A
Type A B C
AuXC - 1000 144 79 138.5
AuXC - 1000L 96 82 92
8.5 274.5 60
24 110
105.5
108
71.5
Cable / Busbar entry
71.5
Cable / Busbar entry (165 mm x 61.5 mm)
32
(110 mm x 32 mm)
5
20
175 15 54
158 50
USE M6 SCREW 30
195
74
96
30
Terminal
Block 90 90
= =
175
USE M4 SCREW
Terminal Block
GF2
GF1
108
158 50
195
Terminals for external CT
secondary connection
30
175
USE M4 SCREW