ABB India Limited ELDS-Nashik: 36 KV Vacuum Circuit Breaker

Download as pdf or txt
Download as pdf or txt
You are on page 1of 27
At a glance
Powered by AI
The document provides technical specifications for a vacuum circuit breaker including its rated voltage and current, insulation level, mechanism type, dimensions and other details.

The vacuum circuit breaker has a rated voltage of 36kV, rated current of 62.5kA, short circuit breaking current of 25kA for 3 seconds. It uses a spring charged mechanism and has a control voltage of 230V AC.

The document lists different components used in the circuit breaker like auxiliary plug in relays, terminal blocks, indicators, heaters, toggle switches, limit switches and more along with their makes.

1 2 3 4 5 6 7 8

© Copyright 2019 ABB. All rights reserved.

A ABB India Limited A

ELDS-Nashik FOR EPC CONTRACTS ONLY

36 kV VACUUM CIRCUIT BREAKER


B
CUSTOMER: APTRANSCO B
CUSTOMER PO. NO.:
ABB REF. NO.: BREAKER QUANTITY :
TECHNICAL DETAILS:
STANDARD IEC62271-100
HIGHER SYSTEM VOLTAGE 36 kV
C C
SERVICE VOLTAGE 33 kV
RATED CURRENT 2000 A
RATED FREQUENCY 50 Hz
BASIC INSULATION LEVEL 70 / 170 kVp
SHORT CIRCUIT BREAKING CURRENT 25 kA / 3 SEC
SHORT CIRCUIT MAKING CURRENT 62.5 kAp
D D
MINIMUM CREEPAGE 900 mm
CONTROL VOLTAGE 220 VDC
SPRING CHARGE MOTOR SUPPLY VOLTAGE 230 VAC
AUXILIARY SUPPLY VOLTAGE 230 VAC
PAINT SHADE 631 OF IS 5
ENCLOSURE FABRICATION MATERIAL TYPE MS
E E
Digitally signed by
ENCLOSURE FABRICATION MATERIAL THICKNESS 3 mm JAKKALA JAKKALA DEVANAND
SUPPORT STRUCTURE TYPE CB DEVANAND Date: 2020.12.04
10:51:29 +05'30'
TERMINAL CONNECTOR (REQD. IF ANY) TWIN MOOSE ACSR
Chief Engineer/Construction
MECHANISM TYPE SPRING CHARGE
NOTE: PICTURE IS FOR REFERENCE ONLY. ACTUAL PRODUCT MAY VARY AS PER CONFIGURATION.

F During the installation, commissioning period and the time of operation, client is obliged to follow all instructions and recommendation given by manufacturers of individual instruments installed inside supplied equipment F
Based on Prepared Date Title Order No = K00
Customer: Checked GN Approved VR COMMON DRAWINGS +
APTRANSCO Project name PROJECT TITLE PAGE Doc. No. Lang.
Contractor / Contract No. Page A00
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
© Copyright 2019 ABB. All rights reserved.

Make of Equipments list.


A A
FOR EPC CONTRACTS ONLY

Sr. No. DESCRIPTION MAKE


1 VACUUM CIRCUIT BREAKER & PANEL ABB
2 CLOSING AND TRIPPING COIL IMAX/POWERINST/EQ.
3 AUXILIARY PLUG IN RELAYS ABB / PLA / JYOTI / EQ.
B 4 MCB ABB / SCHNEIDER / HPL / EQ B
5 SELECTOR SWITCHES SWITRON/ SHIRKE/EQ.
6 CONTROL CIRCUIT FUSES COOPER BUSSMANN/ ABB/ EQ.
7 INDICATING LAMP ABB / ESSEN DEINKI / TEKNIC / EQ.
8 AUXILIARY SWITCH SHIRKE /SHUBHADA
9 CABLE / WIRE ROLLIFLEX / POLYCAB / FINOLEX / R.R KABLES / EQ.
10 TERMINAL BLOCKS CONNECTWELL / PHOENIX / ELMEX / EQ.
11 CONNECTING LUGS M.G.ELECTRICAL/ CHETANA/ ECC / DOWELLS / EQ.
C 12 THERMOSTATS APT CONTROLS / VELICO/ EQ. C
13 ILLUMINATION LAMPS-LED HPL / ANCHOR / PHILLIPS / WIPRO / CROMPTON/ EQ
14 HEATERS APT CONTROLS / VELICO / EQ.
15 TOGGLE SWITCH SWITRON/KAYCEE/SHIRKE
16 DOOR OPERATE LIMIT SWITCH SURAJ/KAYCEE/EQ.
17 3 PIN SOCKET FOR AUX. SUPPLY ABB/LEGRAND / ANCHOR / SCHNEIDER
18 SPRING CHARGING MOTOR WUXI
19
D 20 D
21
22
23

SR. NO. SPECIAL POINTS (IF ANY)


STUD TYPE TB TO BE USED

E ALL WIRING IS TO BE DONE BY 2.5 SQ.MM. CONTROL WIRE E


JAKKALA Digitally signed by JAKKALA
DEVANAND
AC : BLACK WIRE, DC : GRAY WIRE, EARTHING: GREEN WIRE TO BE USED
DEVANAND Date: 2020.12.04 10:52:10 +05'30'

Chief Engineer/Construction

NOTE: IF ANY SPECIFIC MAKE EQUIPMENT IS NOT AVAILABLE DURING MANUFACTURING OF BREAKER(S)THEN ALTERNATE MAKE EQUIPMENT WILL BE USED.
F F
Based on Prepared Date Title Order No = K00
Customer: Checked GN Approved VR COMMON DRAWINGS + SLD
APTRANSCO Project name MAKE LIST Doc. No. Lang.
Contractor / Contract No. YN1V300013- Page A01
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SHEET INDEX
© Copyright 2019 ABB. All rights reserved.

A PAGE PAGE NAME REVISION FOR EPC CONTRACTS ONLY A


=H01+LV/1 SHEET INDEX
=H01+LV/2 VBF INTERNAL WIRING
=H01+LV/3 AC SUPPLY CIRCUITS
=H01+LV/4 CLOSING CIRCUIT
=H01+LV/5 TRIPPING CKT
=H01+LV/6 INDICATION CKT
=H01+LV/7 BREAKER SPARE CONTACTS
B =H01+LV/8 SWITCH DET. & SPARE CONTACTS B
=H01+LV/9 GENERAL ARRANGEMENT
=H01+LV/10 Rating Plate
=H01+BOM/1 Parts list
=H01+BOM/2 Parts list
=H01+BOM/3 Parts list
=H01+BOM/4 Parts list
=H01+BOM/5 Parts list
C =H01+BOM/6 Parts list C
=H01+TBPLAN/1 Terminal Strip Overview

D D

E E
JAKKALA Digitally signed by
JAKKALA DEVANAND

DEVANAND Date: 2020.12.04 10:52:28


+05'30'

Chief Engineer/Construction

F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + LV
APTRANSCO Project name SHEET INDEX Doc. No. Lang.
Contractor / Contract No. Page 1
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BREAKER WIRING DIAGRAM NOTE: CB OPEN & SPRING NOT CHARGED


© Copyright 2019 ABB. All rights reserved.

FOR EPC CONTRACTS ONLY


2REA044865A0001, OUTDOOR VACUUM CIRCUIT BREAKER
TYPE : VBF NEW EL3
A A

5/4D

5/7D

7/2D

7/3D

7/4D

7/5D

7/5D
3/2D

5/4D

5/8D

7/2D

7/4D
4/5C

4/6C

7/2B

7/2B

7/4B

7/5B

7/5B

7/6B
4/8B

6/3B

4/7B

7/3B

7/4B

6/4B

5/6E

5/3E
-QAB

-XDB:1 3 5 9 11 12 14 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55

52A-B
29
CB DISCHARGED

CB CHARGED

B 30 B

5 1
LS1

3
LS2

LS2

6 2

-52A-B

-52A-B
4
230 VAC 25 27 19 31 1 3 5 7 9 11 13 15 17 21 23 33 35 37 39 41 43 45 47 49 51
M
26 28 20 32 2 4 6 8 10 12 14 16 18 22 24 34 36 38 40 42 44 46 48 50 52

C 52CC 52TC1 52TC2 C


220 VDC 220 VDC 220 VDC

-XDB:2 4 6 10 13 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56
3/2E

5/7E

6/3C

7/2C

7/2C

7/3C

7/4C

7/4C

7/5C

7/5C

7/6C

6/4C

7/2D

7/2D

7/3D

7/4D

7/4D

7/5D

7/5D

5/6E

5/3E
4/8B

4/7B
4/5D

5/4E

4/6D

D D

DESIGNAT. DESCRIPTION
-M MOTOR FOR THE CLOSING SPRING CHARGING
-LS1, LS2 LIMIT SWITCH OF THE SPRING CHARGING MOTOR
-52CC CLOSE COIL

-52TC1 TRIP COIL-1


E JAKKALA Digitally signed by
JAKKALA DEVANAND
-52TC2
-52A-B
TRIP COIL-2
BREAKER AUXILIARY SWITCH
E

DEVANAND Date: 2020.12.04


10:53:05 +05'30'
NOTE: GROUP MARKER TERMINAL BLOCK TO BE ARRANGED FOR EACH GROUP OF TERMINAL BLOCKS
Chief Engineer/Construction

F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + LV
APTRANSCO Project name VBF INTERNAL WIRING Doc. No. Lang.
Contractor / Contract No. YN1V300013 Page 2
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SPRING CHARGING ILLUMINATION POWER SUPPLY


© Copyright 2019 ABB. All rights reserved.

SPACE HEATER
CIRCUIT CIRCUIT (3 PIN SOCKET)
FOR EPC CONTRACTS ONLY
SPRING CHARGE MOTOR SUPPLY
A A
230 VAC

X6 1 X6 2

H1

H2
1 3
8AC
6A 2 4
MAIN AC
B B
H4
H3

H3

C C
H3 H3
H3

H3

13 13
-SFC6 -SFC7
TOGGLE SWITCH 14 TOGGLE SWITCH 14
13

H9

H13
2/1B
14 11
-QAB -XDB:3 DIS
200 W 23
spring charge motor 12
D -LS1 D

H11
H5

H7

-M
2/1C
M
H11

x1
-XDB:4 x1 -XDS1 -XG3
2/1D 6A PE14
-EA1 23H 3 PIN AC POWER SOCKET
x2
x2
E E
H4

H4

H4

JAKKALA Digitally signed by


JAKKALA DEVANAND

DEVANAND Date: 2020.12.04 10:53:27


+05'30'

Chief Engineer/Construction
F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + LV
APTRANSCO Project name AC SUPPLY CIRCUITS Doc. No. Lang.
Contractor / Contract No. YN1V300013-KA-OG Page 3
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
CB CLOSING CIRCUIT ANTI PUMPING BREAKER CONTACT SPRING CHARGE
CB LOCAL CLOSE
RELAY MULTIPLIER RELAY MULTIPLIER RELAY
© Copyright 2019 ABB. All rights reserved.

FOR EPC CONTRACTS ONLY K1

A A

K1

K1
2/4B 2/1B
-QAB -XDB:21 -XDB:1

-LS2
7
-52A 5
K11 K11
8 6

K11
B 1 5 B
-94 -XDB:22 -XDB:2
4/6E 9
2/4D 2/1D
CLOSING CKT MCB

8CC -X3 6

K19

K21
-X3
J1 K1

K9
ON 2 1
1
-X3 5

K1

K11
220 VDC 1
-X3
1 2
-X3 3

C
ON J2 4 3 K2 2 C
2 -LRSS REMOTE CLOSE
6A
8/6B
-X3 7
2/4B
2 6
K9 -QAB -XDB:15
-94
-X3
K15L
4 2/2B
4/6E 10
-QAB -XDB:5 CRM4(94) 1
-52A

K15R
29
-52B 2
3
30
3
1 2
K7 -XDB:16

K17
4
-52TNC 3 2/4D
-LRSS 4

K17
LS2
D 8/3B 8/6B D
4
K5
-52CC CLOSE
COIL
K13

K17
-XDB:6 A1 A1 A1
2/2D -94 -52AX -88X
A2 A2 A2

K2
K13 -X3 8

E E
K2 K2 K2 K2
5 5 5
1 9 4/5B 1 9 7/7C 1 9 8/5D
6 6 6
2 10 4/6C 2 10 7/7C 2 10 6/4C
7 7 7
JAKKALA Digitally signed by JAKKALA
DEVANAND
3
8
11 3
8
11 7/8C 3
8
11 8/5D

DEVANAND Date: 2020.12.04 10:53:52


+05'30'
4 12 4 12 7/8C 4 12 8/6D

Chief Engineer/Construction
F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + LV
APTRANSCO Project name CLOSING CIRCUIT Doc. No. Lang.
Contractor / Contract No. YN1V300013-KA-OG Page 4
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB TRIP CIRCUIT-2
LOCAL TRIP-2
© Copyright 2019 ABB. All rights reserved.

CB TRIP CIRCUIT-1
LOCAL TRIP-1
K201 K201
K101 K101

K201
A K201 A

K201
-X2 4 -X2 6
-X1 4 6 5
1 -52 TNC
REMOTE PROTECTION
REMOTE PROTECTION TRIP-2 TRIP-2
-52TNC 6
TRIP-1 TRIP-1 -X2 -X2

K225L
8/3B
K101
5 7

K101
2

K125L

K225R
-X1 5 7

K125R
5 7 9 11
-LRSS 1 2 1 2 1 2 1 2

8/6B
6 -LRSS 8 10 -LRSS 12
B -LRSS B
CTD TRIP 8/6B CTD TRIP 8/7B

K123
ISOLATION LINK K201 ISOLATION LINK
8/7B

-X1 -F1 -F2


3 1 2 K123 K123 K123 -X2 3 1 2 K223 K223 K223
4A

K229
4A
K129
TRIP CKT-1 MCB TRIP CKT-2 MCB
-X2 -CA -X2
11 13
-63X2 D2 CTD +VE 32 TO TRIP CKT
-8TC1 32
8TC2 D2 +VE 32 TO TRIP CKT

-X1 63X -X2


C ON J101 2 1 K101 42
ON 2 1 C
1 1 J201 K201
43 33
63X -X1 8 -X2 8
-X1 -X2
ON J102 4 3 K102 ON 4 3 K202
2 6A 2 J202 6A CTD-2
PRE CLOSE-2
220 VDC A1
R4.2 R3.2
PRE CLOSE-1 220 VDC NOT IN ABB SCOPE
-X2 9

K223
K123
-63X -X1 9
A2 31C

K227
D1 R4.1

K127
D D
2/3B 2/3B
14 34 2/3B 2/3B -QAB -XDB:12 14
-QAB -XDB:9 11
31C -VE 19 31
24 44 A1 63X -VE R3.1 25 27 A1 CX
31C -VE -52A -52B
-VE -52A -52B -VE R3.1
-VE
K131

-X2 12 -X2 14 20 32

K231
26 28
8/4D

8/4D

2/7B 2/7B K207

K202
K202
K225
-QAB -XDB:55 K125
K107 -QAB -XDB:53
63X CONTACTS -52TC2
TRIP COIL 2
K102

-52TC1

51 49
-52B
K102

-52B -XDB:13
E -XDB:10
2/3D
E
52 2/3D 50

K202
TRIP COIL 1
-XDB:56 -XDB:54
2/7D
2/7D
K102 -X2 10 JAKKALA Digitally signed by JAKKALA
DEVANAND 220 VDC
-X2 10

DEVANAND Date: 2020.12.04 10:54:11


+05'30'
K202
K102 Chief Engineer/Construction
FOR EPC CONTRACTS ONLY
F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + LV
APTRANSCO Project name TRIPPING CKT Doc. No. Lang.
Contractor / Contract No. YN1V300013-KA-OG Page 5
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
CB SPRING
CB CLOSED CB OPEN
CHARGED
© Copyright 2019 ABB. All rights reserved.

FOR EPC CONTRACTS ONLY


A A
L1

B B
L1

L1

L1
2/4B 2/5B
-QAB -XDB:17 -XDB:37

2 6
3 33 -88X
-52A -52B
4/8E 10
4 34
IND CKT MCB
-XDB:18 -XDB:38
-8IND
C 2/4D 2/5D C
-X4
ON J301 2 1 L1
1
L3

L5
-X4
ON J302 4 3 L2

L7
2 6A

220 VDC

D D

x1 x1 x1
-PFR1 -PFG1 -PFB1
220VDC,RED x2 220VDC,GREEN x2 220VDC, BLUE x2

E E

JAKKALA Digitally signed by JAKKALA


L2 L2 DEVANAND
DEVANAND Date: 2020.12.04 10:54:29 +05'30'

Chief Engineer/Construction

F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + LV
APTRANSCO Project name INDICATION CKT Doc. No. Lang.
Contractor / Contract No. YN1V300013-KA-OG Page 6
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
© Copyright 2019 ABB. All rights reserved.

FOR EPC CONTRACTS ONLY


A A

BREAKER SPARE CONTACTS


-X5 1 -X5 5 -X5 9 -X5 13 -X5 17 -X5 21 -X5 25 -X5 29

U13

U17

U21

U25

U29
U1

U5

U9
2/4B 2/4B 2/4B 2/5B 2/5B 2/5B 2/5B 2/5B
B -QAB -XDB:19 -XDB:23 -XDB:25 -XDB:27 -XDB:29 -XDB:31 -XDB:33 -XDB:35 B

5 9 11 13 15 17 21 23
-52A -52A -52A -52A -52A -52A -52A -52A
-X5 31 -X5 33 35 37
6 10 12 14 16 18 22 24
-X5 -X5

U35

U37
-XDB:20 -XDB:24 -XDB:26 -XDB:28 -XDB:30 -XDB:32 -XDB:34 -XDB:36

U31

U33
2/4D 2/4D 2/4D 2/5D 2/5D 2/5D 2/5D 2/5D

U10

U14

U18

U22

U26

U30
U2

U6

3 7 4 8
1 5 2 6
-X5 2 -X5 6 -X5 10 -X5 14 -X5 18 -X5 22 -X5 26 -X5 30 -52AX -52AX
C -52AX -52AX 4/7E 11 4/7E 12 C
SPARE 4/7E 4/7E CRM4(94) CRM4(94)
CB ON CB ON TO SEMAPHORE CB ON TO CB ON TO CB ON TO 89A I/L 89L I/L 9 10
DIFF. RELAY BACK UP RELAY BCU/BCPU CRM4(94) CRM4(94)
-X5 3 -X5 7 -X5 11 -X5 15 -X5 19 -X5 23 -X5 27

U36

U38
U11

U32

U34
U15

U19

U23

U27
U3

U7

2/6B 2/6B 2/6B 2/6B 2/6B 2/6B 2/6B


-QAB -XDB:39 -XDB:41 -XDB:43 -XDB:45 -XDB:47 -XDB:49 -XDB:51

37 39 41 43 45 47
-X5 32 -X5 34 -X5 36 -X5 38
35 -52B -52B -52B -52B -52B -52B
-52B CB OFF CB OFF CB ON CB ON

36 38 40 42 44 46 48
D D
-XDB:40 -XDB:42 -XDB:44 -XDB:46 -XDB:48 -XDB:50 -XDB:52
2/6D 2/6D 2/6D 2/6D 2/6D 2/6D 2/6D
U4

U12

U16

U20

U24

U28
U8

-X5 4 -X5 8 -X5 12 -X5 16 -X5 20 -X5 24 -X5 28

CB OFF TO SEMAPHORE CB OFF TO CB OFF TO CB OFF TO 89A I/L 89L I/L


CB OFF
DIFF. RELAY BACK UP RELAY BCU/BCPU

E E

JAKKALA Digitally signed by


JAKKALA DEVANAND

DEVANAND Date: 2020.12.04 10:54:47


+05'30'

Chief Engineer/Construction

F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + LV
APTRANSCO Project name BREAKER SPARE CONTACTS Doc. No. Lang.
Contractor / Contract No. YN1V300013-KA-OG Page 7
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

FOR EPC CONTRACTS ONLY


© Copyright 2019 ABB. All rights reserved.

A TRIP-NEUTRAL-CLOSE -52TNC
LOCAL/REMOTE -LRSS A
SELECTOR SWITCH TNC SELECTOR SWITCH SELECTOR SWITCH L/R SELECTOR SWITCH

4/4D
4/3C

5/4B

5/4B

5/7B

5/8B
4/3D
5/4A
2 1 1 3 5 7 9 11 13 15
1 3 1 3 5 7 9 11 2
T N C L R
2 4 6 8 10 12 2 4 6 8 10 12 14 16

B SPRING-RETURN HANDLE WING TYPE LOCKABLE B


1 TRIP 1 LOCAL
PISTOL GRIP
2 NEUTRAL 2 REMOTE
3 CLOSE

C C
-X5 47 -X5 49 -X5 51
-X5 39 CTD SPARE CONTACTS
-X5 41
-X5 43 -X5 45

U49

U51
U41

U47
U39

U43

U45
3 7 4 8
13 15 44 24 1 5
-88X -88X
-LRSS -LRSS -63X2 5/2D -88X 4/8E 11 4/8E 12
8/5A 14 8/5A 16 5/2D 4/8E CRM4(SCX)
34 14 9 CRM4(SCX)
CRM4(SCX)
D D
U40

U46

U50

U52
U48
U44

U46

-X5 40 -X5 42

CB IN CB IN -X5 48 -X5 50 -X5 52


-X5 44 -X5 46
SPRING
LOCAL REMOTE DC FAIL DC HEALTHY DISCHARGED
SPRING SPRING
CHARGED CHARGED
SPARE CONTACTS LR SWITCH
SPRING CHARGE SPARE CONTACTS

E E

JAKKALA Digitally signed by


JAKKALA DEVANAND

DEVANAND Date: 2020.12.04 10:55:04


+05'30'

Chief Engineer/Construction

F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + LV
APTRANSCO Project name SWITCH DET. & SPARE CONTACTS Doc. No. Lang.
Contractor / Contract No. YN1V300013-KA-OG Page 8
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 10
1 2 3 4 5 6 7 8
FOR EPC CONTRACTS ONLY

JAKKALA Digitally signed by


JAKKALA DEVANAND

DEVANAND Date: 2020.12.04


10:55:27 +05'30'

Chief Engineer/Construction
1 2 3 4 5 6 7 8
© Copyright 2019 ABB. All rights reserved.

FOR EPC CONTRACTS ONLY


A A

210

200±0.3 R2
4Holes Ø5.5±0.1

14.7
B B
Letter Height
4mm Serial number: *

3x6
Production year: * IEC62271-100
OVB-VBF36.20.32 VACUUM CIRCUIT BREAKER
Rated Voltage 36 kV
Rated current 2000 A

±0.3
Frequency 50 Hz
Insulation level 70 / 170 kVp

123
113
C Short circuit breaking current C
25 kA

13x5.5
Short circuit withstand current and duration 25 kA / 3 SEC
104.8

Short circuit making current 62.5 kAp


Operating sequence O-0.3s-CO-3Min-CO
Letter Height 220 VDC
3.5mm Closing coil supply voltage
Opening coil supply voltage 220 VDC
Motor supply voltage 230 VAC
Mass(Approx) 450 kg
Instruction manual 1VYN401190-073
D D
MADE IN ABB

PO Number:

5
5 5
10
10
End Customer:

E E

JAKKALA Digitally signed by JAKKALA


DEVANAND

DEVANAND Date: 2020.12.04 10:55:45


+05'30'

Chief Engineer/Construction

F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + LV
APTRANSCO Project name Rating Plate Doc. No. Lang.
Contractor / Contract No. Page 10
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Parts list: H01 FOR EPC CONTRACTS ONLY


© Copyright 2019 ABB. All rights reserved.

OD BREAKER

A DEVICE TAG / PAGE / POSITION MANUFACTURER MATERIAL ORDERING CODE MOUNTING MATERIAL DESCRIPTION Quantity A
FUNCTION LOCATION

APT CONTROLS & APPLIANCES PVT. LTD.,


23H +LV3/4E APT CONTROL GCE0990162P0102 CABINET
Cubicle Space Heater, 100W, 230VAC +/-10% 1
SPACE HEATER

B B
Door Interlock Switch, Ratings:250 VAC,0.25A
DIS +LV3/3D SURAJ 1VYN452305-003 CABINET
Range :Push to OFF,Screw Type Terminal 1
DOOR INTERLOCK SWITCH

MAKE: REPUTED
C -EA1 +LV3/3E REPUTED 1VYN434059-099 CABINET
7 Watt LED Lamp with Clamp. HOLDER 1 C
ILUMINATION LAMP

52CC +LV2/2C Imax 1VYN401001-TG EL MECHANISM 220 VDC/VAC CLOSING/TRIPPING COIL DOMESTIC 1

D D
-52CC

52TC1 +LV2/3C POWERINST 1VCR007335G0003 EL MECHANISM Instantaneous coil MB01 220V DC FOR DOMESTIC BREAKERS 1

-52TC1
E E

52TC2 +LV2/3C POWERINST 1VCR005962G0003 EL MECHANISM Instantaneous coil MB02 220V DC FOR DOMESTIC BREAKERS 1

-52TC2 JAKKALA Digitally signed by JAKKALA


DEVANAND

DEVANAND Date: 2020.12.04 10:56:04


+05'30'

F Chief Engineer/Construction F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + BOM
APTRANSCO Project name Parts list Doc. No. Lang.
Contractor / Contract No. Page 1
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 6
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Parts list: H01 FOR EPC CONTRACTS ONLY


© Copyright 2019 ABB. All rights reserved.

OD BREAKER

A DEVICE TAG / PAGE / POSITION MANUFACTURER MATERIAL ORDERING CODE MOUNTING MATERIAL DESCRIPTION Quantity A
FUNCTION LOCATION

230 VAC SPRING CHARGE MOTOR


M +LV2/1C WUXI 1VCR012079G0004 EL MECHANISM
200 WATT. 1

-M

B B
2REA044865A0001, OUTDOOR VACUUM CIRCUIT BREAKER
-QAB +LV2/1B ABB 2REA044865A0001 PLG
TYPE : VBF NEW EL3 1

MAKE:ABB
C 8AC +LV3/2B ABB 1SYS271112R0064 WIRING PLATE ABB AC MCB SB201 M-C6 NA 1 C
MAIN AC
Aux Voltage : Suitable upto 400V AC 6A

MAKE:ABB
ABB DC MCB SB202-C6DC
8CC +LV4/2C ABB 1SYS252067R0064 WIRING PLATE
ABB, S282UC K2, 6A, MCB 1
CLOSING CKT MCB
2 Pole,6A. Aux Voltage : Suitable upto 440V DC
D D

MAKE:ABB
ABB DC MCB SB202-C6DC
-8IND +LV6/2C ABB 1SYS252067R0064 WIRING PLATE
ABB, S282UC K2, 6A, MCB 1
IND CKT MCB
2 Pole,6A. Aux Voltage : Suitable upto 440V DC

E E
MAKE:ABB
ABB DC MCB SB202-C6DC
-8TC1 +LV5/1C ABB 1SYS252067R0064 WIRING PLATE
ABB, S282UC K2, 6A, MCB 1
TRIP CKT-1 MCB
2 Pole,6A. Aux Voltage : Suitable upto 440V DC
JAKKALA Digitally signed by
JAKKALA DEVANAND

DEVANAND Date: 2020.12.04 10:56:25


+05'30'

F
Chief Engineer/Construction F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + BOM
APTRANSCO Project name Parts list Doc. No. Lang.
Contractor / Contract No. Page 2
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 6
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Parts list: H01


© Copyright 2019 ABB. All rights reserved.

OD BREAKER FOR EPC CONTRACTS ONLY


A DEVICE TAG / PAGE / POSITION MANUFACTURER MATERIAL ORDERING CODE MOUNTING MATERIAL DESCRIPTION Quantity A
FUNCTION LOCATION

MAKE:ABB
ABB DC MCB SB202-C6DC
8TC2 +LV5/5C ABB 1SYS252067R0064 WIRING PLATE
ABB, S282UC K2, 6A, MCB 1
TRIP CKT-2 MCB
2 Pole,6A. Aux Voltage : Suitable upto 440V DC

B B

23 +LV3/4D APT CONTROL IN76350001-2 WIRING PLATE Thermostat,Setting:0-60 deg.centigrade.,15A,220 V 50 Hz 1


THERMOSTAT

CR-M4SS With Base For


C -52AX +LV4/7E ABB-PEENYA 1SVR405613R9000 WIRING PLATE Contacts:4C/O SR 1 C
CB AUXILIARY CONTACT MULTIPLIER
Plug-in Relay, Aux.Voltage:220V DC,

SOCKET,CR-M4SS,FOR-2/4-C/O,STD/SCREW
1SVR405651R3000
-52AX +LV4/7E ABB-PEENYA 1VYN401056-009 WIRING PLATE
BASE FOR CR-M4SS RELAY 1
=
ABB
D D

Holding clamp for CRM relays


CR-MH1 Metal holder for CR-M sockets
-52AX +LV4/7E ABB-PEENYA 1VYN401056-021 WIRING PLATE
1SVR405659R1100 1
=
ABB

E TNC Switch Configuration : 3 Pole 3 Position; 32A E


(3 Contacts to Close in each position )
Mechanism - Spring Return to Neutral (45°+45°)
-52TNC +LV8/2A SHIRKE SC32C0206UBS3P WIRING PLATE Legent Plate Size - 75mm x 75mm. 1
TNC SELECTOR SWITCH
Position Lable - TRIP-NEUTRAL-CLOSE
Handle - Pistol Grip Non-Lockable
Catagory - AC21A : 690 VAC; AC23A : 440 VAC" JAKKALA Digitally signed by
JAKKALA DEVANAND

DEVANAND Date: 2020.12.04 10:56:51


+05'30'

F Chief Engineer/Construction F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + BOM
APTRANSCO Project name Parts list Doc. No. Lang.
Contractor / Contract No. Page 3
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 6
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Parts list: H01


© Copyright 2019 ABB. All rights reserved.

OD BREAKER FOR EPC CONTRACTS ONLY


A DEVICE TAG / PAGE / POSITION MANUFACTURER MATERIAL ORDERING CODE MOUNTING MATERIAL DESCRIPTION Quantity A
FUNCTION LOCATION

CR-M4SS With Base For


-88X +LV4/8E ABB-PEENYA 1SVR405613R9000 WIRING PLATE Contacts:4C/O SR 1
CRM4(SCX) CB SPRING CHARGED MULTIPLIER
Plug-in Relay, Aux.Voltage:220V DC,

B B
SOCKET,CR-M4SS,FOR-2/4-C/O,STD/SCREW
1SVR405651R3000
-88X +LV4/8E ABB-PEENYA 1VYN401056-009 WIRING PLATE
BASE FOR CR-M4SS RELAY 1
=
ABB

Holding clamp for CRM relays


CR-MH1 Metal holder for CR-M sockets
C -88X +LV4/8E ABB-PEENYA 1VYN401056-021 WIRING PLATE
1SVR405659R1100 1 C
=
ABB

CR-M4SS With Base For


-94 +LV4/6E ABB-PEENYA 1SVR405613R9000 WIRING PLATE Contacts:4C/O SR 1
CRM4(94) ANTIPUMPING RELAY
Plug-in Relay, Aux.Voltage:220V DC,
D D

SOCKET,CR-M4SS,FOR-2/4-C/O,STD/SCREW
1SVR405651R3000
-94 +LV4/6E ABB-PEENYA 1VYN401056-009 WIRING PLATE
BASE FOR CR-M4SS RELAY 1
=
ABB

E E
Holding clamp for CRM relays
CR-MH1 Metal holder for CR-M sockets
-94 +LV4/6E ABB-PEENYA 1VYN401056-021 WIRING PLATE
1SVR405659R1100 1
=
ABB
JAKKALA Digitally signed by JAKKALA
DEVANAND

DEVANAND Date: 2020.12.04 10:57:14


+05'30'

F
Chief Engineer/Construction F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + BOM
APTRANSCO Project name Parts list Doc. No. Lang.
Contractor / Contract No. Page 4
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 6
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Parts list: H01


© Copyright 2019 ABB. All rights reserved.

OD BREAKER FOR EPC CONTRACTS ONLY


A DEVICE TAG / PAGE / POSITION MANUFACTURER MATERIAL ORDERING CODE MOUNTING MATERIAL DESCRIPTION Quantity A
FUNCTION LOCATION
Type : Local Remote Switch
Configuration : 4 Pole 2 Position; 32A
(4 Contacts to Close in each position )
-LRSS +LV8/5A SHIRKE SC32D0258UBA9L WIRING PLATE Mechanism -Staput Type (90°) 1
L/R SELECTOR SWITCH
Legent Plate Size - 75mm x 75mm
Position Lable - LOCAL-REMOTE
Handle - Wing Type Lockable.

B B
CL-523B,LED indicating Lamp,Label:Blue
-PFB1 +LV6/4E ABB 1SFA619402R5234 WIRING PLATE
color lens,Suitable for 230V AC 1
CB SPRING CHARGED

CL-520G,LED indicating Lamp,Label:Green


C -PFG1 +LV6/4E ABB 1SFA619402R5202 WIRING PLATE
color lens,Suitable for 220V DC 1 C
CB OPEN

CL-520R,LED indicating Lamp,Label:Red


-PFR1 +LV6/3E ABB 1SFA619402R5201 WIRING PLATE
color lens,Suitable for 220V DC 1
CB CLOSED

D D

MAKE:SWITRON,
-SFC6 +LV3/4C SWITRON 1VYN452150-362 WIRING PLATE
Toggle Switch,10A,240V AC. 1
TOGGLE SWITCH

E E

MAKE:SWITRON,
-SFC7 +LV3/5C SWITRON 1VYN452150-362 WIRING PLATE
Toggle Switch,10A,240V AC. 1
=

JAKKALA Digitally signed by JAKKALA


DEVANAND

DEVANAND Date: 2020.12.04 10:57:35


+05'30'

F
Chief Engineer/Construction F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + BOM
APTRANSCO Project name Parts list Doc. No. Lang.
Contractor / Contract No. Page 5
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 6
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Parts list: H01 FOR EPC CONTRACTS ONLY


© Copyright 2019 ABB. All rights reserved.

OD BREAKER

A DEVICE TAG / PAGE / POSITION MANUFACTURER MATERIAL ORDERING CODE MOUNTING MATERIAL DESCRIPTION Quantity A
FUNCTION LOCATION

-XDS1 +LV3/5E ABB 1SYN880422R0001 WIRING PLATE SNWP3302 2 M Plate 3"X3" for 03 pin socket 1
3 PIN AC POWER SOCKET

B B

-XDS1 +LV3/5E ABB 1SYN880690R0001 WIRING PLATE 06A, 240VAC, 3-PIN SOCKET 1
=

C C

JAKKALA Digitally signed by JAKKALA


DEVANAND

DEVANAND Date: 2020.12.04 10:57:57


+05'30'

D
Chief Engineer/Construction D

E E

F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + BOM
APTRANSCO Project name Parts list Doc. No. Lang.
Contractor / Contract No. Page 6
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 6
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TERMINALS FOR EPC CONTRACTS ONLY


© Copyright 2019 ABB. All rights reserved.

=H01 NOTE:
OD BREAKER
A FIRST TERMINAL OF LAST TERMINAL OF A
STRIP TOTAL QTY. TERMINAL FUNCTION
TAG TERMINAL DIAGRAM TERMINAL DIAGRAM DISCONNECTING TERMINAL BLOCK
TOP SIDE
-X1 1 10 10 TRIP CKT-1

-
-X2 1 14 14 TRIP CKT 2

-X3 1 8 8 CLOSING CKT

B B
-X4 1 2 2 IND. CKT

BOTTOM SIDE
-X5 1 52 52 SPARE CONTACTS OF BREAKER, LR SWITCH, CTD & SPRING CHARGE

-X6 1 2 2 MAIN AC SUPPLY


NON-DISCONNECTING TERMINAL BLOCK
TOP SIDE

C C
-

BOTTOM SIDE

D D
JAKKALA Digitally signed by JAKKALA
DEVANAND

DEVANAND Date: 2020.12.04 10:58:18


+05'30'

Chief Engineer/Construction

E E

F F
Based on Prepared Date Title Order No = H01
Customer: Checked GN Approved VR OD BREAKER + TBPLAN
APTRANSCO Project name Terminal Strip Overview Doc. No. Lang.
Contractor / Contract No. Page 1
Rev. Code Date Name India Ltd., Nashik, ELDS Pages 1
1 2 3 4 5 6 7 8
GUARANTEED TECHNICAL PARTICULARS FOR 33 kV VACUUM CIRCUIT
BREAKERS

S.
No Description 33kV VCBs
1. a) Maker's name country a) ABB India Ltd
of manufacture.
b) Manufacturer's type designation. b) OVB-VBF
2. Applicable Technical Standards IEC 62271-100
3. a) Rated voltage (kV) a) 36
b) Rated Frequency (Hz) b) 50
4. Number of Poles 03
5. Class (Outdoor/Indoor) Outdoor
6. Rated normal current:
a) Under site conditions a) 2000
(Amps)
b) Rated (Amps) b) 2000
7. Rated short circuit breaking current:
a) R.M.S. value of A.C. a) 25kA
component of rated short circuit current (kA)
b), c), d) & e) Please refer type test report
b)Percentage DC component
no. 2050-17
c) Asymmetrical breaking current (including DC
component)
d) Certificate or report no.
e) Oscillogram no.
8. Rated short circuit making current (kA) 62.5kA
9. First Pole to clear factor 1.5
10. Rated transient recovery voltage for terminal faults As per relevant IEC
(kV peak)
11. Rated characteristics for short line faults. As per IEC 62271-100
12. Rated operating sequence . O - 0.3 sec. - CO -3min. – CO
13. Rated duration of short circuit (sec.) 3 sec
14. Rated out of phase breaking current (kA) As per relevant IES
15. Opening time (ms) < 65ms
16. Arcing time (ms)
a) At 10% rated breaking current < 15ms
b) At 25% rated breaking current < 15ms
c) At 50% rated breaking current < 15ms
d) At 100% rated breaking current < 15ms
e) Maximum Arcing time at lowest fault currents < 15ms
17. Break time (ms)
a) At 10% rated breaking current < 65ms
b) At 25% rated breaking current < 65ms

JAKKALA Digitally signed by JAKKALA


DEVANAND
DEVANAND Date: 2020.12.04 10:58:47 +05'30'

Chief Engineer/Construction
c) At 50% rated breaking current < 65ms
d) At 100% rated breaking current < 65ms
e) Maximum break time at lowest fault current < 65ms
18. Closing time (ms) < 85ms
19. Maximum Pole discrepancy time:
a) Opening (ms) <5
b) Closing (ms) <5
20. Rated line charging breaking current (kA) As per relevant IEC
21. Maximum cable charging current
a) On supply side a) As per relevant IEC
b) On line side b) As per relevant IEC
22. Rated small inductive breaking current (kA) As per relevant IEC
23. Max. rise of temperature over ambient temperature for As per relevant IEC
current rating under clause 6.
24. Interrupting capacity based on duty cycle as per clause
11.
a) AC Component (kA) a) As per relevant IEC
b) Percentage D.C. b) As per relevant IEC
Component
25. Latching current (kA) As per IEC 62271-100
26. No of breaks in series per pole One
27. Length of contact travel (mm) 16-20.5 mm Approx.
28. Total length of break per pole (mm) 24mm (max)
29. Rate of contact travel :
a) At tripping (meters/sec.) a) 1.2-1.7 m/sec
b) At closing (meters/sec.) b) 0.8-1.6 m/sec
30. Type of devices, if any, usd to obtain uniform voltage NA
distribution between breaks
31. Recovery voltage distribution between breaks in NA
percent of rated voltage:
a) Single line to ground fault
b) Interruption of short lines
c) Switching off an unloaded
Transformers
32. Type of main contact Spiral Electrode butt. Type
33. Type of arcing-contacts and/or arc control device NA for VCB
34. Material of contacts
a) Main Copper Chromium alloy
b) Arcing
c) Auxiliary
35. Whether contacts are silver plated NO
36. Thickness of silver coating (mm) NA
37. Contact pressure (kg/sq. mm.) 3200 N (approx.)

JAKKALA Digitally signed by JAKKALA


DEVANAND

DEVANAND Date: 2020.12.04 10:59:15


+05'30'

Chief Engineer/Construction
38. Insulation level of the breaker :
a) 1 minute power frequency withstand voltage (kV a) 70KV rms
rms)
b) Switching surge withstand b) Within IEC
test voltage (kV peak)
c) Impulse withstand test voltage (kV peak) c) 170kV Peak
d) Max. dynamic p.f. over voltage withstand (kV d) Within IEC
peak)
39. Minimum clearance in Air (mm)
a) Between Phases (live parts) As per enclosed GA
b) Between live parts and earth
c) Centre to centre distance
between phases
d) The safety boundaries during a breaking
operation for circuit breakers with an external exhaust
for ionized gases or flames
40 Whether the circuit breaker is Trip free
suitable for fixed trip operation
or trip free operation and whether it is provided with a
lock-out device preventing closing of the breaker
41. Method of closing Spring charging motorised
a) Normal
b) Emergency
42. Type of closing mechanism Spring Charged stored
energy mechanism
43. a) Normal voltage of closing a) 220V DC
b) Pick up range, (volts) b) 85 -110%
44. a) Normal voltage of closing a) As per req.
b) Pick up range, (volts) b) 85 -110%
a) Power at normal voltage of closing mechanism, c) 300 Watt
(watts) d) 300 Watt
b) Power at 85% of normal
voltage, (watts)
45. Type of tripping mechanism Spring Charged stored
energy mechanism
46. Normal voltage of tripping coils, (volts) 220V DC
47. a) Power at normal voltage for tripping coils, (watts) a) 300 Watt
b) Power at 70% normal voltage for tripping coils,
(watts) b) 300 Watt

48. Arc duration at 100% (ms) <15 ms


Interruption capacity: NA
a) Opening Arcing time No. of loops and time
including resistor current duration (cycle)

JAKKALA Digitally signed by JAKKALA


DEVANAND

DEVANAND Date: 2020.12.04 10:59:50


+05'30'

Chief Engineer/Construction
Resistor current duration, (cycle) As per IEC 62271-100
Total length of the arc, (mm)
Max. length of the arc, (mm)

Total interrupting time measured from instant


of trip coil energisation to arc extinction of resistor <100 ms approx
current (cycles).

b) Closing time measured from instant of


application of power to closing device upto arcing <120 ms approx
contacts touching, (cycles).
49. Critical current (current giving the longest arc when a Not Applicable
break takes place) (kA)
50. a) Recovery voltage when circuit breaker tested at As per IEC 62271-100
100% rated breaking capacity, (kV inst.)
b) Rate of rise of re-striking voltage at breaking
i) for 30% breaking capacity, (kV/Micro. sec.)
ii) for 100% breaking capacity, (kV/Micro. sec.)
c) Maximum over voltage factor of the circuit
breaker when switching off.
i) Unloaded transformers.
ii) Loaded transformer
iii) Open circuited lines
51. When switching of synchronous systems: As per IEC 62271-100
a) Max. current (kA)
b) Max. contacts of 1 pole
(kV)
52. No. of openings the circuit breaker is capable of
performing without inspection, replacement of
contacts or other main parts.
a) at 50% rated current a) 10000
b) at 100% rated current b) 10000
c) at current corresponding to c) 100
50% rated breaking capacity
d) at current corresponding to 100% rated breaking d) 30
capacity
53. a) Weight of complete circuit breaker (kg.) a) 450kg (approx..)
b) Impact loading for foundation design, to include b) 14 KN
deed load plus impact value on opening at maximum
interrupting ratings, in terms of equivalent static load,
(kg.)
c) Overall dimensions: c) As per enclosed GA drawing
Height (mm)
Width (mm)

JAKKALA Digitally signed by JAKKALA


DEVANAND

DEVANAND Date: 2020.12.04 11:00:15


+05'30'

Chief Engineer/Construction
Length (mm)

54. Porcelain:
a) Make a) CJI/RCPL/PCPL/VM/IEC/WSI/EQ

b) Type b) Porcelain/Hollow
c) Descriptive pamphlet c) 1VYN301101-CH
No.
d) Weight (kg.) d) 32 Approx.
e) Transport dimensions, e) As per enclosed GA
(mm)
f) Height above floor, f) 4500 Max.
required to remove
porcelain, (mm)
g) Class C
g) Insulation class
h) One minute dry power h) 70
frequency withstand,
kV (r.m.s.) i) As per IEC
i) 10 seconds wet power
frequency withstand,
kV (peak) j) 70 kVrms
j) Flash over voltage,
(kV)
k) Full wave impulse k) 170 kV peak
withstand voltage kV
(peak)
l) Switching surge l) Not Applicable
withstand voltage kV
(peak)
m) Corona discharge m) Not Applicable
voltage, (kV r.m.s.)
n) Nature of the dielectric n) Ceramic
o) Creepage distance, o) 900 mm
total protected (mm) Protected. Creepage is as per relevant IEC

p) Volume of insulating p) 8.3 Ltr


medium per porcelain,
(liters)
q) Permissible safe q) 7500 NM
cantilever loading on
installed porcelain
(kg.m.)

JAKKALA Digitally signed by JAKKALA


DEVANAND
DEVANAND Date: 2020.12.04 11:00:54 +05'30'

Chief Engineer/Construction
55. Operating mechanism :
a)Mechanically operated a) Mechanically Operated
or pneumatically or
hydraulically operated.
b) For stored energy b) Spring Stored Energy Mechanism
mechanism :
1. Spring charging motor
i) Rating kW
ii) Voltage V i) 600 Watt (Approx.)
iii) Power ii) 230VAC
frequency withstand iii) 2.5kV / 1 min
voltage kV.
iv) 15 Sec (max)
iv) Time required for the motor to charge
the spring fully (secs.)

v) Power required at the normal control v) 600 Watt (Approx.)


voltage to charge the spring - Watts. vi) As per relevant IEC
vi) Specification
reference.

2.Spring closing/opening
i) Number of springs i) 1 No each
ii) Type ii) Spiral
iii) Number of turns iii) As per manufacturer design
iv) Guage iv) As per manufacturer design
v) External diameter mm. v) As per manufacturer design
vi) Stiffness vi) As per manufacturer design

vii) Material vii) As per manufacturer design


viii) Force developed in full charged position. viii) As per manufacturer design
ix) Specification reference. ix) As per manufacturer design

56. Pneumatic equipment for pneumatically operated Not Applicable


breakers.
a) Type
b) Manufacturers type
designation
c) Air Compressor
i) Type
ii) Make
iii) Capacity in

JAKKALA Digitally signed by JAKKALA


DEVANAND
DEVANAND Date: 2020.12.04 11:01:23 +05'30'

Chief Engineer/Construction
liters/min.
d) Compressor motor:
i) HP rating
ii) Rated voltage and frequency
iii) Limits of voltage and frequency variation for
satisfactory operation of compressor motor
iv) No. of phases
v) Speed (r.p.m.)
vi) Temp. of insulation.
vii) Class of insulation.

e) Safety, valve opens on receiver kg/sq.cm.

f) Compressor start at kg/sq.cm.

g) Compressor stops at kg/sq.cm.


h) Alarm switch on receiver closes at kg/sq.cm.

i) Lockout switch on receiver operates at

i) kg/sq.cm. for closing


ii) kg/sq.cm. for opening
iii) kg/sq.cm. for auto re-closure duty

j) Time of air compressor to charge the


reservoirs:

i) From atmospheric to pressure indicated in (g)


above, (minutes)

ii) From pressure indicated in (g) above to that in (h)


above (minutes)
57. Rated pressure of SF6 gas in the circuit breaker Not Applicable
(kg/sq.cm)
58. Rated pressure of SF6 gas in the gas cylinders Not Applicable
(kg./sq.cm.)
59. Quantity of SF6 gas required per single pole unit (kg.) Not Applicable
(3 pole unit for 145 kV)
60. Quantity of SF6 gas per cylinder (kg.) Not Applicable
61. Weight of empty cylinder (kg.) Not Applicable
62. Quantity of absorbent required per pole (kg.) Not Applicable
63. Recommended interval for renewal of absorbent in Not Applicable
case of outdoor circuit breakers operating in tropical
conditions.

JAKKALA Digitally signed by JAKKALA


DEVANAND

DEVANAND Date: 2020.12.04 11:01:58


+05'30'

Chief Engineer/Construction
64. Chemical composition of absorbent Not Applicable
65. Quantity of absorbent covered in the scope of Not Applicable
supply (including spare quantity) (kg.)
66. Limits of gas pressure for pressure operation of Not Applicable
circuit breaker (kg./sq.cm.)
67. Pressure and temperature at which the temperature Not Applicable
compensated gas pressure switch
a) alarm (kg./sq.cm., deg.C)
b) Cut off (kg/sq.cm. deg.C)
68. Name of SF6 supplier and country of origin Not Applicable
69. Quantity of SF6 gas supplied for Not Applicable
a) Actual use in breakers (kg.)
b) As spare (kg.)
Not Applicable
70. Chemical composition of gas:
a) Qty. of air by weight (ppm)
b)Qty. of H20 by weight (ppm)
c)Qty. of CF4 by weight (ppm)
d) Qty of free acid by weight (ppm)
72. No. of auxiliary contacts provided
a) Those close when breaker is closed. a) 08
b) Those open when breaker is closed. b) 08
c) Those adjustable with respect to the position c) NO
of main contacts.
d) Continuous rating of contacts. d) 2A
e) Breaking capacity of contacts. e) 10A
73. Whether the equipment covered by this Bid have Yes
been fully type tested and if so, whether the copies of
the type test cert. enclosed to the bid offer.

Name of the firm : M/s ABB India Ltd


.
Signature of Bidder :

Designation & Seal :

Date :

JAKKALA Digitally signed by


JAKKALA DEVANAND

DEVANAND Date: 2020.12.04 11:02:28


+05'30'

Chief Engineer/Construction