Dsine MCCB Catalogue
Dsine MCCB Catalogue
Dsine MCCB Catalogue
Moulded Case
Circuit Breakers
Stability: Activated
Up and Running, Uninterrupted 1
In every industry, big or small, electrical power supply is The dsine range, a new generation of MCCBs, is a
critical. Even a few seconds of interruption or instability combination of state-of-the-art design and modern
can result in huge financial losses, even loss of life. We user-friendly features. It also boasts a wide choice of
have little or no control over the nature or stability of protective releases, ergonomics, aesthetics and
power supply. The unpredictable nature of power compactness. The range, designed to meet the
makes it important to take appropriate steps for the changing needs of users after extensive analysis and user
protection and safety of your organisation’s employees feedback, can satisfy the most demanding system
and equipment. requirements.
In line with this objective, Larsen & Toubro presents Complemented by a wide array of accessories, the dsine
dsine – a highly advanced and sophisticated range of range offers comprehensive solutions to customer
Moulded Case Circuit Breakers (MCCBs). applications ensuring operational safety, reliability and
versatility.
Moulded Case
Circuit Breakers
Moulded Case
Circuit Breakers
Versatility: Downloaded
Paper Industry
Sugar Industry
Oil Industry
Gas Industry
Meeting Diverse Demands 5
Industries
Every industry is unique, and so are its requirements. MCCBs with high breaking capacities cater to high
Industries as diverse as paper, sugar, oil & gas have voltage applications such as windmills and mines. They
different sets of needs. Thankfully, dsine MCCBs, are compact so the panel builder can optimise panel
available in various current ranges (20A to 1250A), are size. They are thoroughly factory-tested with adequate
designed to efficiently handle such diversity. quality controls in place. Moreover, since these MCCBs
are designed to handle high-value capacitive inrush
Our Thermal Magnetic as well as Microprocessor-based
currents, no nuisance tripping is observed in APFC
releases with various breaking capacities cater to
panels. Motor loads being most vital, our design team
multiple industrial needs. Built with the latest
has also developed special dsine-M series for motor
technology, dsine MCCBs deliver optimum efficiency
back-up protection ranging from 32A to 630A.
even in the most adverse environmental conditions.
Efficiency: Initiated
Paving The Path to Progress 7
Building Sector
Today, efficient energy management holds the key to Choose from a variety of communication protocols
growth and development in any sector. Moreover, in including MODBUS RTU and Bluetooth available with
most sectors, such as the building sector, energy our new MATRIX releases. In today’s world of high-end
management has become mandatory. Our new range of residential buildings or commercial malls, our motorised
dsine MATRIX releases with advanced technology is dsine MCCBs with the fastest changeover from mains to
specially designed with energy management in mind. DG in less than 300 milliseconds are indeed the most
reliable choice. Our Auto Source Transfer System has
MTX3.0 releases with power metering and
almost eliminated the risk of loss of data.
communication capabilities are ideal for remote
annunciation in Data Centers and IT Parks.
Performance: Delivered
Delivering Unparalleled Results 9
Infrastructure
Monitoring and controlling electrical installations at As power supply is critical for airports and hospitals, our
places like airports, hospitals etc. demands high-end, dsine MCCBs with ASTS offer changeovers in less than
reliable solutions. MATRIX releases are built precisely for 300 milliseconds coupled with a variety of other
such purposes. protections in case of under voltage, phase unbalance,
etc.
Communication capable MATRIX releases with power
and energy metering help in modernisation. These A variety of settings in MATRIX releases helps in choosing
releases are made compatible with HMI (Human Machine the correct selection for fault clearing, while trip & event
Interface) and DCS (Data Control System). recording with MATRIX releases helps in analysing the
faults in detail.
Our dsine MCCBs are shipped to Europe, Africa, Australia, Middle East,
South East Asia, China and America. In India, we have the largest stockist
network with over 700 stockists. To find the ideal dsine MCCB suitable for
your requirements, turn the page.
INDEX
Overview
Product Data
Accessories
Characteristic Curves
Wiring Diagrams
Dimensions
Overview
n Range 16
n
Standards & Approvals 18
n
Structure & Features 19
n
Marking & Configuration 20
n
Trip Units 21
Accessories
n 22
16 Range
State-of-the-art design, user-friendly features and a wide spectrum of protection releases form the hallmarks of the
dsine range. Also recognised for its ergonomics, aesthetics and compactness, it belongs to a new generation of
MCCBs. Specially designed and developed for extreme tropical conditions, it promises reliable performance at high
ambient and humid environment.
dsine, unfailingly, caters to the ever-evolving needs of customers, derived after in-depth analysis and customer
feedback. Because we understand our customers' requirements and demands, our contemporary range of MCCBs
never fall short of ensuring complete customer satisfaction. Moreover, complemented by a host of accessories, the
dsine range delivers comprehensive solutions to customer applications ensuring operational safety, reliability and
versatility.
Range 17
Features
Range
Æ available from 20A to 1250A
Available
Æ in 3 pole & 4 pole
Range of 25kA / 36kA / 50kA / 70kA / 100kA breaking capacities
Æ
Microprocessor and Thermal-Magnetic based protection releases
Æ
MCCBs for Motor backup protection
Æ
MCCBs for Distribution and SD versions
Æ
Suitable for DC application
Æ
Manual, Rotary or Motorised versions
Æ
Wide range of common Internal and External accessories
Æ
RoHS complaint
Æ
DN0
Rated Current 20, 25, 32, 40, 50, 63, 80, 100, 125*A
Release Thermal-Magnetic
DN1
Rated Current 125, 160, 200, 250A
Release Thermal-Magnetic
DN2
Rated Current 63, 80, 100, 125, 160, 200, 250A 40, 63, 100, 160, 250A
Release Thermal-Magnetic Microprocessor
DN3B
Rated Current 320, 400A
Release Thermal-Magnetic
DN3
Rated Current 320, 400, 500, 630A 400, 630A
Release Thermal-Magnetic Microprocessor
DN4
Rated Current 800, 1000, 1250A
Release Microprocessor
* Available only in DN0-D
NABL
NABL accreditation is a formal recognition of the technical competence of testing,
calibration or medical laboratory for a specific task following ISO/IEC 17025:2005 Standard.
Accredited laboratories have the responsibility of satisfying the criteria of laboratory
accreditation at all times, which are verified during Surveillance and Re-assessment visits by
NABL. Further the accredited laboratories should prove their technical competence by
satisfactory participation in recognized Proficiency Testing Programmes.
L&T’s Switchgear Testing Lab is NABL accredited subject to continued satisfactory
compliance to above standard & additional requirements of NABL.
All dsine range of MCCBs are tested in L&T's NABL accredited Switchgear Testing Lab.
marking
A CE marking is a European marking of conformity that indicates a product complies with
the essential requirements of the applicable European laws or directives with respect to
safety, health and environment and consumer protection. Generally, this conformity to the
applicable directives is done through self-declaration and is required on products in the
countries of the European Economic Area (EEA) to facilitate trade among the member
countries. The manufacturer or their authorized representative established in the EEA is
responsible for affixing the CE marking to their product. The CE marking provides a means
for a manufacturer to demonstrate that a product complies with a common set of laws
required by all countries in the EEA to allow free movement of trade within the EEA
countries.
L&T’s dsine range of MCCBs conform to the Low voltage directive 73/23/EEC as amended
by directive 93/68/EEC, provided if it is used in the application for which it is made and is
installed and maintained in accordance with professional practices with relevant installation
standards and operating instructions.
Terminal Connections
Standard Characteristics
}Uimp: Impulse withstand voltage
}Ue: Rated operational voltage
}Icu: Rated Ultimate breaking Utilization Category
capacity Brand
}Ics: Rated Service breaking capacity Frame Size
Symbol of suitability
Standards for Isolation
Mark
Indication of Closed (I/ON)
Company Logo
Operating Knob
Release
Current Rating of MCCB
Release Settings "Push to Trip" button
Release name
Terminal Shroud
Trip Units 21
Variable Thermal,
Fixed Magnetic
(DN0, DN1, DN3B)
Thermal Magnetic
Variable Thermal, Variable Magnetic (DN2, DN3)
Releases
Inst
Microprocessor
Releases
Inst
Magnetic Release
DN3-M
Isolator
22 Accessories
1 Spreader Terminals
2 Phase Barriers
3 Undervoltage Release
4 Shunt Release
5 Auxiliary Contact 12
13 Communication Module
16
14 Voltage Module
15 Display Module 4 3
16 External Neutral CT
(with Adaptor Kit)
8
23
15
14
13
6 7
5
11
10
9
Product Data
MCCBs for Power Distribution
n 26
- Technical Datasheet
MCCBs for Motor & Isolator
n 28
- Motor Backup Protection
- Isolator Application
MCCBs for DC & Capacitor Application
n 29
- DC Application
- Capacitor Application
n
Protection Releases for MCCBs 30
- Thermal Magnetic Release
- Microprocessor Release
n
MCCBs for Auto Source Transfer Application 42
- Auto Source Transfer Application
26 MCCBs for Power Distribution
Technical Datasheet
Frame 100A 125A 250A 250A
DN0-100 DN0-125 DN1-250 DN2-250
Type
C D D C N D N S
TM/MP
Release TM TM TM (MTX1.0/2.0/3.0)
20, 25, 32, 125, 160, 40, 63, 80,
Current Range In (A) 40, 50, 63, 125 100, 125, 160,
200, 250
80, 100 200, 250
Poles 3/4 3/4 3/4 3/4
Impulse withstand Voltage Uimp (kV) 8 8 8 8
Rated Operational Voltage Ue (V) (MAX) 600 600 600 690
Rated Insulation Voltage Ui (V) 800 800 800 800
Utilization Category A A A A
Standard
240 VAC 40 65 65 65 65 50 70 100
415 VAC/440 VAC ^ 25 36 36 25 50 36 50 70
480 VAC/500 VAC 10 10 10 10 10 25 36 42
Icu(kA)
Rated 550 VAC 8 8 8 8 8 18 25 36
Short 600 VAC 5 5 5 5 5 16 18 22
Circuit 690 VAC - - - - - 10 15 20
Breaking
Capacity 240 VAC 100% 50% 50% 50% 50% 100% 100% 100%
415 VAC/440 VAC 100% 50% 50% 100% 50% 100% 100% 100%
480 VAC/500 VAC 100% 50% 50% 50% 50% 100% 100% 100%
Ics as % Icu
550 VAC 100% 50% 50% 50% 50% 100% 100% 100%
600 VAC 100% 50% 50% 50% 50% 100% 100% 100%
690 VAC - - - - - 50% 50% 50%
Mechanical 40000 40000 15000 25000
Life
Electrical @1.0 In* 12000 8000 4000 10000 10000
Making Capacity (kA) 52.5 75.6 75.6 52.5 105 75.6 105 154
Operating Frequency (Hz)
Total Opening Time
Finger-proof Terminals
Suitable for Isolation
IP class
Pollution Degree
Load Line Bias
Ambient Temperature
Storage Temperature
Mounting Positions in Vertical Plane
3-Pole 75 x 60 x 130 105 x 60 x 165 105 x 96 x 179
Dimensions (WxDxH) mm
4-Pole 100 x 60 x 130 140 x 60 x 165 140 x 96 x 179
Weight (kg) (3/4 Pole) 0.8/1.1 0.73/1 0.73/1 1.55/2 2.5/3.3
Auxiliary Contact
Trip Alarm Contact 1 C/O or 2 C/O
A
INTERNAL Auxiliary & Trip Alarm Contact
C
C Shunt Release 240/415 V AC 50 Hz
E Under Voltage Release
S Rotary Operating Mechanism (Direct/Extended) ü ü ü
S Electrical Operating Mechanism û û ü
O Mechanical Interlock Kit û û ü
R Spreader T erminals ü ü ü
I EXTERNAL
Key lock ü ü ü
E Neutral CT with Adaptor kit û û
S
Current Metering Module û û
Display, Communication and Voltage Module û û
40, 63,
100, 160, 320, 400 320, 400 500, 630 400, 630 800, 1000, 1250
250
3/4 3/4 3/4 3/4
8 8 8 8
690 690 690 690
800 800 800 800
A A A A
IS/IEC60947-2, IEC60947-2 & EN60947-2
100 100 50 50 70 100 50 70 100 100 70 100 100
80 100 36 36 50 70 36 50 70 100 50 70 100
65 65 25 25 36 42 25 36 42 65 25 36 65
36 36 15 15 20 25 15 20 25 50 20 25 50
22 36 12 12 18 22 12 18 22 50 16 20 50
20 36 5 8 15 20 8 10 15 50 10 18 50
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
100% 50% 100% 100% 100% 100% 100% 100% 100% 50% 100% 100% 50%
100% 50% 100% 100% 100% 100% 100% 100% 100% 50% 100% 100% 50%
50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50%
25000 10000 15000 15000 15000 20000
10000* 4000 4000 4000 4000* 3000*
176 220 75.6 75.6 105 154 75.6 105 154 220 105 154 220
50 / 60
<10msec <20msec
Yes
Yes
IP40
III
NO
-5OC to 55OC
-35OC to 70OC
Vertical and 90 deg in both directions
140 x 111 x 205 140 x 111.5 x 266 140 x 111.5 x 266 210 x 143 x 370
184 x 111 x 205 183.5 x 111.5 x 266 183.5 x 111.5 x 266 278 x 143 x 370
4.0/5.0 5.5/7.2 6/7.8 6.3/8 17 / 22
1 C/O or 2 C/O
1 C/O
1 C/O + 1 C/O
110 / 415 V AC 50 Hz, 110 / 220 V DC, 24 V DC $
240 V AC 50 Hz
ü ü
#
û ü û
û ü û
ü û
ü ü
Available for 3P MCCBs with MTX2.0 & MTX3.0 release only ü
Available for MTX2.0 release for current metering only @
Available for MTX3.0 release for Communication & Power metering
Note:
• Any two internal accessories can be mounted at a time
• V version MCCBs, to be used with extended ROM only
• Separate earth fault module required for earth fault protection using TM releases
• Icu: Rated ultimate short-circuit breaking capacity
Ics: Rated service short-circuit breaking capacity
• Reference temperature 40OC & 50OC
28 MCCBs for Motor & Isolator
Isolator Application
dsine MCCBs with Switch Disconnector version offer solution for switching various loads such as UPS, Battery Banks
etc. with various advantages. These MCCBs differ from regular MCCBs only in terms of absence of protection trip
units. These MCCBs can be used for following applications for isolation purpose:
• For local isolation- such as very close to Motor load
• Generally used at the incoming of any sub-distribution
• As an Isolator for Bus coupler
• As an automatic switch
• For switching applications of motors with VFDs, soft starters
SD MCCBs are always backed up by the Short Circuit Protection Device (SCPD) to protect downstream
loads/installations against short circuit. Our dsine SD MCCBs offer following advantages.
• Suitable for Positive isolation
• Available with 3P & 4P versions
• Can be used with Under Voltage Protection
• Remote tripping through Shunt release
• Motor operated MCCBs
• Status feedback possible
Following are the specifications of SD MCCBs
DC Application
DC power distribution is an upcoming technology in this modern era due to its most rigorous network power
applications such as
• AC-DC Power System
• DC-DC Converter Systems
• DC-AC Inverter Systems
• DC UPS
• Batteries & Accessories
• Solution to alternative energy-Solar Power
We offer dsine MCCBs for the protection of DC systems in variety of current ratings from 20A-630A, voltage ratings
upto 750V and various breaking capacities ranging from 5kA to 36kA.
250 V DC 20 20 20 30 36 20 30 36 25 20 30 36
Icu (kA rms) 500 V DC 15 15 15 20 25 15 20 25 10 15 20 25
750 V DC - - 10 15 20 10 15 20 - 10 15 20
Type of connection 3P in series
L/R (msec) <15msec
*Available only in DN0-125D
Switching of DC currents is much severe phenomenon than switching AC currents due to non occurrence of natural zero.
Hence DC MCCBs are desired to give less breaking capacity than AC MCCBs for the same voltage & currents.
Note: Suitable for Thermal Magnetic release only
Capacitor Application
For any APFC panel, MCCBs are required for short circuit protection, overload protection and for isolation of
capacitors. MCCB selection for capacitive load is tricky because of heavy inrush current, high overload capacity and
continuous full load. These inherent traits of a capacitor, complicates the selection process. The selection should be
such that the MCCB should not nuisance trip during inrush current and should withstand continuous flow of
overload current.
Whenever we use MCCB in an APFC panel, proper measures need to be taken against the ill effects of the inrush
current. Normally the inrush current (more than 100 times the rated capacitor current) will remain for a few micro-
seconds and will not be sensed by the MCCB. However the contacts of MCCB may repel and bounce because of the
current limiting feature, causing micro-arcs between the contacts of MCCB. This multiple bounce can result in
premature failure of MCCB contacts. In order to reduce the magnitude of the peak inrush current, MCCBs must be
used along with capacitor duty contactors or inrush current limiting reactors.
The maximum permissible current in a capacitor branch is 1.46 times the rated current. This factor is comprised of the
following:
1. Harmonics overload and over voltage – 30%
2. Capacitance tolerance – 10%
3. Frequency variation – 2%
Hence adequate care needs to be taken while selecting switching & protection devices for capacitor applications. It is
always advised to limit the switching inrush current within safe limits. For this, MCCB ratings should be chosen at
least 1.5 to 2 times of capacitor rated current along with Capacitor Duty Contactors.
30 Protection Release for MCCBs
Thermal-Magnetic Release
Features of Thermal-Magnetic Release
Adjustable
Æ overload settings
Fixed /
Æ Adjustable short circuit settings
True RMS
Æ sensing Settings
“Push
Æ to Trip” button Protection
DN0 & DN1 DN2 & DN3 DN3B
Microprocessor Release
Features of MTX1.0
Overload
Æ Protection with inverse time delay
Adjustable
Æ Trip class
Short
Æ Circuit Protection with selectable
time delay
Provision
Æ of Thermal memory defeat
Provision
Æ for release testing
Overload
Æ indication
Power
Æ ON LED
Self powered
Æ
True RMS
Æ sensing
“Push
Æ to Trip” button
MTX1.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 5%
Time delay, tr (Inverse) 10s at 6Ir, 3s at 6Ir, 10s at 7.2Ir, 3s at 7.2Ir
Protection mode ON / OFF
Thermal memory Enable / Disable
Short Circuit
Current setting, Is (Is = x Ir) 1.5, 2.5, 4.0, 5.5, 6.5, 8.0Ir
Time delay, ts Instantaneous / 100ms
Protection mode ON / OFF
Note: • Factory Settings - O/L: 100%In, Curves: 6Ir@10s, Thermal Memory: Off, S/C: 5.5Ir @ Instantaneous
• Release provides in-built instantaneous override protection fixed @ 10In
* Refer page 51
Protection Release for MCCBs 31
Microprocessor Release
Features of MTX2.0
Overload
Æ Protection with inverse time delay
Adjustable
Æ Trip class
Short
Æ Circuit Protection with selectable
time delay
Inbuilt
Æ Earth fault and Neutral overload
Inst
protection
Provision
Æ of Thermal memory defeat
Provision
Æ for release testing
Overload
Æ indication
Power
Æ ON LED
Panel
Æ mounted O-LED display for current metering
Self powered
Æ
True RMS
Æ sensing
“Push
Æ to Trip” button
Latest
Æ trip record
MTX2.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 5%
Time delay, tr (Inverse) 10s at 6Ir, 3s at 6Ir, 10s at 7.2Ir, 3s at 7.2Ir
Protection mode ON / OFF
Thermal memory Enable / Disable
Overload (Neutral)
Current setting, IN (IN = x Ir) 50%, 100% and 150%Ir
Time delay, tN 200ms / Same as overload
Protection mode ON / OFF
Short Circuit
Current setting, Is (Is = x Ir) 1.5, 2.5, 4.0, 5.5, 6.5, 8.0Ir
Time delay, ts Instantaneous / 100ms
Protection mode ON / OFF
Earth Fault
Current setting, Ig (Ig = x In) 20% to 50%In in steps of 10%
Time delay, tg 100ms / 200ms
Protection mode ON / OFF
Note: • Factory Settings - O/L: 100%In, Curves: 6Ir @10s, S/C: 5.5Ir @ Instantaneous, Thermal Memory: Off, E/F: Off, Neutral: Off.
• Release provides in-built instantaneous override protection fixed @ 10In
32 Protection Release for MCCBs
Power
Supply
Module
Metering Module
Port with
Æ Polarized Connector
MTX2.0 release with metering port is implemented with poka-yoke
technology using polarized connector to ensure correct insertion of
metering harness, thus avoiding unnecessary errors.
Digital Current
Æ Metering
MTX releases are designed with protection class CTs
which measure true RMS values. Inbuilt current
metering does not require separate CTs hence
maintenance is easy.
O-LED Display
Æ
O-LED display allows the operator a wide viewing
angle.
O-LEDs showing current metering has got faster
response time and also consumes less power, hence
saves energy. It has better contrast ratio as well.
Display Module
Protection Release for MCCBs 33
@6Ir
Inst
3s
10s
@7.2Ir
2 3 1
Inbuilt Earth
Æ Fault Protection 1
Inbuilt earth fault protection function does not require any separate trip coil & external CBCT, thus saving panel
space, cost & improving the overall hygiene. Earth fault protection limits expenses by preventing damage to other
equipment.
Thermal Memory
Æ 2
Thermal memory protects the system from thermal stresses generated by cumulative heating caused by cyclic
overload conditions thus allowing the system to return to a safe operating temperature. This function also allows
an optimization of cables or bus bar protection in case of low amplitude repetitive faults. Advance tripping
increases the overall life and eliminates the production downtime incase of severe faults.
DIP Switches
Æ
DIP switches are provided on front side of the release for easy operations. These switches give you quicker option
to precisely change selection, offering high life.
Trip Indication
Æ 4
Improves uptime and productivity by setting alarms for unbalanced loads so that proactive measures can be taken
to avoid overload conditions. Also, cause of fault (Short circuit and earth fault) can be indicated on the release as
per below table.
Self Powered
Æ
MTX releases do not need any external power supply hence require no extra devices and wires to power up.
The release power up with 30% loading with a power ON LED
@6Ir
Inst
3s
Overload Protection, (Ir = x In)
10s
@7.2Ir
0.4 0.4 0.4 0.4 0.4 0.4 0.4
DIP Switch
r
r
Position
r
r
q q q q q q q
DIP Switch
r
r
Position
r
r
q q q q q q q
Thermal Memory
0.4 0.4
DIP Switch
r
Position
r
q q
Setting Bypass ON
Overload Curves
DIP Switch
r
Position
r
q q q q
DIP Switch
Inst
Inst
Inst
Inst
Inst
Inst
Inst
Position
Inst
Position
DIP Switch
Position
0.2 0.2
DIP Switch
Position
Ir * Ir * Ir * Ir *
DIP Switch
Position
0.5
1.0
0.5
1.0
0.5
1.0
0.5
1.0
Ir * Ir *
DIP Switch
Position
0.5
1.0
0.5
1.0
Microprocessor Release
Features of MTX3.0
Overload
Æ Protection with inverse time delay
2 4
I t, I t,
Æ SI, LI-VI based over load curves
Short Circuit Protection with selectable time delay
Æ
Instantaneous protection with fine settings
Æ
Advanced current and voltage based protection function
Æ
Protection against current unbalance and single phasing
Æ
Comprehensive current, power and energy metering
Æ
Inbuilt Earth fault and Neutral overload protection
Æ
Provision of Thermal memory defeat
Æ
Panel mounted O-LED display
Æ
Communication through MODBUS RTU
Æ
Pre-trip alarms
Æ
True RMS sensing
Æ
Power on LED
Æ Inst
MTX3.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 1%*
Time delay, tr (Inverse) 0.5s to 30s in steps of 0.1s*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Ir in steps of 1%*
Thermal memory Enable/Disable
Overload (Neutral)
Current setting, IN (IN = x Ir) 50% to 150% Ir in steps of 1%*
Time delay, tN 0.2s / same as overload*
Protection mode ON / OFF
Short Circuit
Current setting, Is (Is = x Ir) 1.5 to 8 Ir in steps of 0.1*
Time delay, ts 100ms, 200ms, 300ms, 400ms*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Is in steps of 1%*
Instantaneous
Current setting, Ii (Ii = x In) 1.5 to 8 In in steps of 0.1*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Ii in steps of 1%*
Earth Fault
Current setting, Ig (Ig = x In) 10%* to 50% In in steps of 5%*
Time delay, tg 100ms to 500ms in steps of 50ms*
Protection mode ON / OFF
* Can be set using communication and display module
Note: • Factory Settings - Address:0000, O/L: 100%In, Curves: 6Ir @10s, S/C: 5.5Ir @ Instantaneous, Thermal Memory: Off, E/F: Off, Neutral:
Off.
• Release provides in-built instantaneous override protection fixed @ 10In
Protection Release for MCCBs 37
Voltage Protection
Under Voltage
Voltage setting (V) Vuv (Vuv = x Un) 45 to 80% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 110 to 150% Vuv in steps of 1%
Over Voltage
Voltage setting (V) Vov (Vov = x Un) 105 to 150% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90%Vov in steps of 1%
Voltage Unbalance
Voltage setting (V) 5 to 20% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Residual Voltage
Voltage setting (V) 5 to 40% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Frequency Protection
Under Frequency
Frequency setting (Hz) F-0.5 to F-5.0 in steps of 0.5
Time delay (s) 0.1 to 30 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set freq in steps of 1%
Over Frequency
Frequency setting (Hz) F+0.5 to F+5.0 in steps of 0.5
Time delay (s) 0.1 to 30 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set freq in steps of 1%
38 Protection Release for MCCBs
Power Protection
Reverse Power
Power setting (W) PR 1 to 5000kW in steps of 1kW
Time delay (s) 0.5 to 60 in steps of 0.5
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% PR in steps of 1%
Lead Pf
Pf setting 0.5 to 0.99 in steps of 1%
Time delay (ms) 100 to 500 in steps of 1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Lag Pf
Pf setting 0.5 to 0.99 in steps of 1%
Time delay (ms) 100 to 500 in steps of 1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Other Protections
MD Active
Demand settings 1 to 5000kW in steps of 1kW
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
MD Reactive
Demand settings 1 to 5000kVAr in steps of 1kVAr
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
MD Apparent
Demand settings 1 to 5000kVA in steps of 1kVA
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Phase Sequence
Phase seq setting 123 or 132
Time delay (s) 1 to 5 in steps of 0.1
Protection mode ON / OFF
THD Current
Current setting (A) 5 to 50%Ir in steps of 1%
Time delay (s) 5 to 15 in steps of 5
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
THD Voltage
Voltage setting (V) 5 to 50% Un in steps of 1%
Time delay (s) 5 to 15 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Protection Release for MCCBs 39
Power Supply
Module
Voltage
Display Module
Module
3 ph 4 wire
Communication AC supply
Module
Advanced
Æ Current and Voltage based protections
• Reverse Phase:
This function detects the phase reversal of current from the
set sequence. It is especially important in motor feeder
applications
• Reverse Power:
One can set the direction of power flow in a system from
source to load and in case the direction of power flow
reverses, the reverse power protection can be activated to
trip the system. This is especially important in a DG set or in a
ring mains system.
Power Quality
Æ Control
MTX3.0 release measures the frequency, power factor and offers
protection against leading and lagging values thereby assisting in
maintaining the power quality. This release measures THD of
current & voltage and gives an alarm / trip in case it exceeds the
set thresholds.
Communication
Æ Capable
Convertor
Laptop or HMI (RS485 to RS232)
Most advanced release of MTX series, MTX3.0 is communication capable on MODBUS RTU network. Using MODBUS
com module the MCCB release can be connected to a Personal Computer. The metering values can be read remotely.
The settings configuration on the other hand can both be read and changed remotely. These releases are also made
compatible with HMI (Human Machine Interface) & DCS (Data Control Systems)
Protection Release for MCCBs 41
Multi-looping
Æ
Laptop or HMI
Convertor
(RS485 to RS232)
A single display module can be used to connect upto 15 MCCBs with MTX3.0 release through MODBUS network.
Highly reliable data yet extremely simple looping reduces operational headaches and enhances remote accessibility.
Maintenance Functionality
Æ
MTX3.0 release can store last 10 trip records & last 10 event records which can be used for the system analysis
later on. These recorded values can be viewed from display unit as well as PC.
AuXC-2000 Controller
There are many electrical services which are required to be powered up always. Interruption of supply to these kinds
of services is not desired. These loads are part of any industry, hospital, school, commercial buildings, shopping malls,
name any place of importance. These loads can be firefighting system, emergency lighting, control stations, CCTV,
emergency pumps, security system etc. L&T’s micro-processor based Automatic Transfer Controller
AuXC-2000along with L&T switchgear is the answer to all auto source transfer requirements.
Changeover Conditions
All the conditions which can help establish whether a power source is or is not suitable are defined by the
user through setting following parameters
Parameter Description
Minimum voltage One or more phases too low
Maximum voltage One or more phases too high
Phase loss Threshold below which the unit intervention is quicker than with a normal decrease.
Asymmetry (unbalance) Phases within the Maximum-Minimum range but too different from each other
Minimum frequency Too low frequency
Maximum frequency Too high frequency
Phase sequence Reverse rotation of phases
Insulation type Single between OUT4-5 and OUT 6-7 OUT6 and OUT 7 outputs: terminals 28,29,30
Double toward the remaining groups Contact type 2 x 1 NO + contact common
Rated insulation voltage Ui 250V~ AC1 - 8A 250V~
Rated current DC1 - 8A 30V=
Single Double AC15 -1.5A 250V~
Rated impulse withstand voltage Uimp 4kV Uimp 6kV Max rated voltage 300V~
Power frequency withstand voltage 1.5kV 3kV Mechanical / electrical endurance 1x107 / 1x105 ops
Line 1 and Line 2 voltage inputs: terminals 1-4 and 5-8 Maximum current at contact common 10A
Maximum rated voltage Ue 100…480V~ L-L (277VAC L-N) Connections
Measuring range 50…576V~ L-L (333V~L-N) Terminal type Plug-in / removable
Frequency range 45-65Hz Cable cross section (min... max) 0.2-2.5 mm² (24... 12 AWG)
Measuring method True RMS Tightening torque 0.56 Nm (5 lbin)
Measuring input impedance > 0.5MW L-N > 1,0MW L-L Housing
Single-phase, two-phase, Version Flushmount
three-phase with or without
Wiring mode neutral or balanced Material Polycarbonate
three-phase system. Degree of protection IP40 on front / IP20 terminals
Ambient operating conditions Weight 680g
O
Operating temperature +70 c -30..... *Notice: this product has been designed for environment A. Use of this product in
Vibration resistance -30... +80OC environment B may cause unwanted electromagnetic disturbances in which case the
user may be required to take adequate mitigation measures.
Climatic sequence <80% (IEC/EN 60068-2-78)
Shock resistance 2
Measurement category 3
Overvoltage category III
Maximum pollution degree Z/ABDM (IEC/EN 60068-2-61)
Relative humidity 15g (IEC/EN 60068-2-27)
Storage temperature 0.7g (IEC/EN 60068-2-6)
Accessories
Internal Accessories
n 46
- Auxiliary Contact
- Trip Alarm Contact
- Auxiliary Trip Alarm Contact
- Shunt Release
- Under Voltage Release
n
External Accessories 47
- Rotary Operating Mechanism
- Mechanical Interlocking Kit
- Keylock
- Spreader Terminals
- External Neutral CT
- Stored Energy Electrically Operated
Mechanism
- MTX Modules
- MCCB Enclosure
- Earth Fault Module
46 Accessories
Internal Accessories
Shunt Release
It allows opening of MCCB by means of an electrical command. Operation of the release is guaranteed for a voltage
between 70% and 110% of the rated power supply voltage value Ue, both in AC & DC.
UV Release
The Under-voltage release causes the MCCB to trip if the operational voltage falls to a value between 35% and 70%
of its rated voltage or not applied. UV release mechanically locks the closing mechanism of MCCB & makes it
impossible to close on under-voltage or no voltage, both manually & electrically. With the under-voltage release de-
energized, it is not possible to close the MCCB. UV release can also be used for interlocking schemes (for DG
synchronization, paralleling of transformers etc) also.
External Accessories
Rotary Operating Mechanism
Rotary operating mechanism (ROM) for dsine MCCBs are available in
direct & extended versions.
Spreader Terminal
• Available for enhancing termination capacity
• Made of silver plated copper
$ 30mm on request
Specifications AC DC
Input 85-265V 125-300V
#
Output 1 - 200mA at 24V DC
Output 2 - 650mA at 24V DC
#
For using Output 1, Output 2 should be loaded
Æ
Current Metering Module for MTX2.0
It consists of 2 parts viz. Metering module & Display module. Metering module collects the data from the release and
sends the same to the Display module. The panel mounted O-LED Display module shows various parameters viz. 3
phase currents, neutral and ground fault currents, if any. We can also view last trip records.
50 Accessories
Æ
Voltage Module for MTX3.0
This accessory when connected to MTX 3.0 release in DN2/DN3/DN4
frames is able to provide the various measurements of the electrical values
of the plant like voltage, power, energy & frequency . It can be mounted
just beside the MCCB on a DIN plate. Its operating temperature is -25O C
O
to 70 C
Æ
Display Module for MTX3.0
It is a panel mounted O-LED display unit that can be integrated with
MTX3.0 release . It has one navigation key, a select button & an exit
button. Provision for taking D+, D- from this module is also provided.
You can simultaneously view parameters remotely & on display. Its
O O
operating temperature is -25 C to 70 C and consumption is 12mA
Æ
MTX Test Kit
• Universal Test Kit for all MTX releases
• Simulation of overload, short-circuit & earth fault
• Single phase AC supply
MCCB Enclosure
Æ
New Range of MCCB enclosures, Size I suitable for DN0 frame and Size II for
DN1 frame. These standalone enclosures not only provides ample space for
cable termination but are also superior in aesthetics.
• Conforms to IEC 62208, IEC 62262 and IEC 60529
• Common Enclosure for 3P/4P MCCBs
• RoHS compliant
• IP30 Protection & IK08 Protection
• Inbuilt Neutral Link for TPN systems
• Mounting Holes on the back plate
• Louvers for better heat dissipation
Earth Fault Module GF11 Note: MCCBs need to be fitted with 110 V / 240 V AC shunt
GF11 is suitable upto 800A MCCBs release for Earth Fault Module operation.
Technical Data
Specification Type GF1 / GF2 / GF11
Current Setting Range, Is (Is=x In) 10% to 50%In in steps of 10%
Auxiliary Supply 240V AC ±20%
Time Delay (ms) 100 / 200ms Field selectable
Pick-up Accuracy ±10% Is
1 NO contact manual reset Type
Output Contact
contact rating 5A 240V AC
a) Power On LED
Indication b) Trip LED (manual reset)
Operating Temperature +10oC to +55oC
2 kV 50Hz for one minute across independent circuit
Insulation 1 kV 50Hz for one minute across open contacts
Mounting Base plate mounting type
GF1 - 110 x 32
Window for Cable / Busbar entry (mm2)
GF2 - 165 x 61.5
Weight (kg) GF1 - 1.2, GF2 - 2.2, GF11 - 0.9
Note: For wiring diagram, please refer page no. 61
Characteristic Curves
Thermal Magnetic Release
n 54
DN0
}
DN1
}
DN2
}
DN3B
}
DN3
}
Microprocessor Release
n 55
}M TX1.0-2.0 (O/L curves)
- I2T at 6Ir, 7.2Ir
Thermal-Magnetic Release
1000 1000
100 100
10 10
Trip Time (s)
9In 9In
0.1 0.1
t<10ms t<10ms
0.01 0.01
0.001 0.001
10-1 1 10 102 103 10-1 1 10 102 103
Current multiples (xIn) Current multiples (xIn)
10 10
Trip Time (s)
10
6-10In
6-10In
1 9In
1 1
0.001
0.001 0.001
10-1 1 10 102 103 10-1 1 10 102 103 10
-1
1 10 10
2 3
10
Current multiples (xIn) Current multiples (xIn) Current multiples (xIn)
Microprocessor Release
2
MTX1.0 / 2.0 - DN2 / DN3 / DN4 (O/L curves - I t)
2 2
I T @ 6Ir I T @ 7.2Ir
10000 10000
1000 1000
Trip Time (s)
10 10
10s
10s
3s
1 3s 1
0.1 0.1
1 10 1 10
Current multiples (xIr) Current multiples (xIr)
10 100 100
Trip Time (s)
30s
1 10 30s 10 20s
30s
20s 10s
20s
10s
10s 5s
5s 3s
0.1 5s 1 3s 1
3s
Microprocessor Release
4
MTX3.0 - DN2 / DN3 / DN4 (O/L curves - I t)
4 4 4
I T @ 1.5Ir I T @ 6Ir I T @7.2Ir
1000 100000 100000
10000 10000
100
1000 1000
10
Trip Time (s)
1
10 10 30s
30s 18s
30s
18s 18s 10s
0.1 10s 6s
10s 1 1
6s 3s
6s 3s
3s
0.01 0.1 0.1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)
30s 30s
24s 24s
30s
Trip Time (s)
Trip Time (s)
24s
12s 12s
10 10 10
12s
4s 4s
4s
1 1 1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)
Characteristic Curves 57
Microprocessor Release
MTX3.0 - DN2 / DN3 / DN4
(O/L curves - Long Inverse / Very Inverse)
LI-VI @ 1.5Ir LI-VI @ 6Ir LI-VI @ 7.2Ir
100 1000 1000
10 100 100
Trip Time (s)
4s
4s
4s
0.1 1 1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)
400ms 500ms
300ms
Invs
OFF*
200ms 200ms 200ms
Trip Time (s)
Inst
For MTX3.0 only For MTX3.0 only *: IDMT disable in case of MTX3.0
K2 K1
K1 K2
K1
K2
K1
K2
OUT 1
OUT 2
OUT1 - OUT7
B300 / 250V~ 8A AC1 / 1A 30V= PILOT DUTY
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
COM
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
INP 1
INP 2
INP 3
INP 4
INP 5
INP 6
COM
MCCB 1 MCCB 2
CONTROL CONNECTIONS CONTROL CONNECTIONS
RECTIFIER
L
3
AUX.
SUPPLY
N
4 240 Vac
TO LOAD
GF11
FROM MCCB
240 Vac
R Y B N RELAY 1
MCCB
2 SHUNT
S1 RELEASE
SENSING
CIRCUIT
S2 5
S1
CT Sec.
S2 RECTIFIER L
3
S1 AUX
SUPPLY
S2
4 240 Vac
N
S1
S2
TO LOAD
62 Wiring Diagrams
Display Module
Metering
Module
MTX2.0 Release
Inst
to other
MTX2.0
24 Vdc 24 Vdc
+ - + -
Auxiliary
Power Supply
Module
L 240 Vac
50 Hz
N
Wiring Diagrams 63
Laptop / SCADA
System
D+ Convertor
D-
RS485 RS232
+Vs
Gnd
Communication
Module Voltage Module
MTX3.0 Release
Inst
3 Phase
415 Vac Supply
+ - + -
24 Vdc 24 Vdc
Auxiliary
Power Supply
Module
L 240 Vac
50 Hz
N
Dimensions
Dimensions of MCCB
n 66
DN0
}
DN1
}
DN2
}
DN3B
}
DN3
}
DN4
}
Dimensions of Accessory
n 72
Rotary Operating Mechanism
}
Stored Energy Electrically
}
Operated Mechanism
Panel Mounted Key Lock
}
Mechanical Interlock Kit
}
External Neutral CTs
}
MTX Modules
}
Auto Source Transfer Switch: AuXC-2000
}
Earth Fault Modules
}
Size I Enclosure for DN0 MCCB
}
Size II Enclosure for DN1 MCCB
}
66 Dimensions of MCCB
DN0-125 MCCB
86
64
60
20 2
75 (3P) MCCB MOUNTING HOLES
M3 SCREW 6 Nos.
32
25 25 25 12.5
10
25 25
50.5 50.5
61.5
25.5
58
48.5
13.5
52
75
2.25 27.25
116.4
17
112
130
112
46
39
N N CUT OUT 1
45
38
CUT OUT 2
29.5
76
101
25 25 25
32.2
11
32
28
28
10
61.5
58
13.5
75
17
172.2
194.2
172.2
194.2
N
45
38
30.2
32.2
2
22 22 20
35 35 35 35 35
92 127.2
DIN rail kit
DN1-250 MCCB
MCCB MOUNTING
HOLES 6 Nos.
105 (3P) 93.7
141
35 35 35 17.5 64.5
60
35 35
17.5 17.5
58.6
78.65
95.7
126
145
165
126
46
N
N
45
88 53
70.5 70.5
35 35 35 Mounting &
140 (4P) Door Cut-out Details
46
47.5
38
78.65
95.7
221
147
257
221
257
N
45
250A
47.5
46
35 4
54.5 54.5 35 18
144 54 54 54
197
DN2-250 MCCB
25.5 60.5
89.27
72.7
61
CUT OUT
157
163
157
179
46.5
N
45
86
35 35 35
140 (4P) Mounting &
Door Cut-out Details
48
38
38
89.27
72.7
239
275
239
275
N
45
41
48
35 35 4
54 54 54 A
54.5 54.5
144 197
DN3B-400 MCCB
MCCB
MOUNTING HOLES
M5 SCREW 6 Nos.
44.50 44.50
140
139.5 (3P) 115
52.50
44.5 44.5 44.5 25.25 110
38.25 82.75
CUT OUT
68
98
176
79
182
205
176
77
121
Ø10.5
23
Ø10.5
56.5
45
45
68
98
272
318
272
318
N
77
56.5
40 40 5
63.5 63.5 63 61.5 63 26.5
167 227.5
DN3-400/630 MCCB
180
143 MCCB MOUNTING HOLES
140 (3P) 120 M5 SCREW 6 Nos.
43,5 43,5 43,5 26,5 103 43,5 43,5
104
38.75
82.25
CUT OUT
82,7
224
234
266
224
77
78
N
121
43,5 43,5
Mounting &
183.5 (4P) Door Cut-out Details
23
Ø10.5 5
Ø10.5
F
C
104
D
D
E
77
N
F
40 40
62,5 62,5 62 60,5 62 B
165 224,5
Type DN3-400 DN3-630
Recommended cat nos. A 39 43
for DN3 spreaders B 37* 39#
Rating 3P 4P C 45 55
D 324 344
400A ST98065OOOO ST98066OOOO
E 370 390
630A ST98054OOOO CM92004OOOO
F 52 62
* 38 for MTX
# 38 for 500A TM
DN4-800/1000/1250 MCCB
MCCB
210 (3P)
197 MOUNTING HOLES
68 68 68 143 M5 SCREW 6 Nos.
68 68
132.5
109.5
57 125
198.5
105
107
330
370
326
326
N
CUT OUT
182
24
71 68 68 71
Mounting &
180
Door Cut-out Details
278 (4P)
85
132.5
105
370
510
N
85
15
60 24 60 24 46
B B 198
3P Frame 4P Frame
3/4P Frame
Type A B C D Type A B C D
Type Y
800A 98 256 6 38 800A 88 324 6 28
N version 46
1000A 98 256 12 38 1000A 88 324 12 28
S version 42
1250A 86 232 20 26 1250A 80 300 20 20
L5
L4
L3
N
L2
L1 68
Mounting &
Door Cut-out Details
L2 Ø51
450 Ø76
L3
N Ø4
Type L1 L L2 L3
DN0 169 L1 - 119 7.5 69.5
L
DN1 169 L1 - 119 24.5 81.7
DN2 202 L1 - 152 27 84
L = Length of Shaft Required DN3 233 L1 - 183 39 122
for Panel Depth L1 DN3B 233 L1 - 183 39 92
Total Length of Shaft =275mm DN4 302 L1 - 252 69 170
18.7
= =
Door
Cut-out
94
157
N ON TRIP
T
156
= =
94
DN3 264
Mounting 43.5
holes for MCCB 256
= =
Door
62.1
45 49
94
Door
Cut-out
224
94
N ON TRIP
Cut-out for
136
Handle Assembly
68
68
12
Cut-out for
Panel Mounted Key Lock Ø29
2.2
58 52
Mounting &
Door Cut-out Details
Note: Panel Mounted key lock can be used only with extended ROM All dimensions are in mm
74 Dimensions of Accessories
DN2
372
Ø10 Mounting Holes
41.5 141 141
35
10
149
209
239
177
141 141 Holes for Breaker Mounting
Mounting Details
DN3
152
21
55
316
266
346
446
DN2/DN3
K
L
B
C
D
G
H
J
Bottom Bottom
Side Side
ØF
Frame A B C D E F
DN2 250A 93 59 47 81 35 10.2
Adaptor Terminal
DN3 400A 93.5 58 46 81.5 40 13
DN3 630A 93.5 58 46 81.5 40 10.5
ON
TRIP
Frame G H J K L M OFF
DN2 250A 77 153 189 26 4 55 Bottom
Side
DN3 400A 63.5 153.5 199.5 39 5 60
DN3 630A 63.5 173.5 219.5 39 5 60
Note: • Adaptor Terminals shown are not available with product >M
• Kindly refer accessories data for ordering separately
• Circuit Breaker shown for reference only All dimensions are in mm
76 Dimensions of Accessories
DN4
M P
H
G
K
D
A
Bottom Bottom
Side Side
ØF
E
DN4 A B C D E F G
800A 132 88.5 73.5 117 60 12.5 92
1000A 132 88.5 73.5 117 60 12.5 92
1250A 132 88.5 73.5 117 60 12.5 92
DN4 H J K L M P
MTX Modules
Display Module
36
44.5
51
10
96
44.5
91.5
91.5
Voltage/Communication/Metering Module
3
73.3
73.3
81
87
3
23
14.3 60
Door Cut-out
23 65
Details
144
138
35
8.5 274.5 60
24 110
108
105.5
Cable / Busbar entry
71.5
71.5
Cable / Busbar entry (165 mm x 61.5 mm)
32
(110 mm x 32 mm)
5
20
175 15 54
158 50
USE M6 SCREW 30
195
74
96
30
Terminal
Block 90 90
= =
175
USE M4 SCREW
Terminal Block
GF2
GF1
108
158 50
195
Terminals for external CT
secondary connection
30
175
USE M4 SCREW
186.5
197.5
222.6
543
179.5
178.3
58
91
110
97
118.1 67.9
337
84
289.2
301.8
348.8
830
322.2
295.8
84
150 106.2
111.2
All dimensions are in mm
80 Notes
Notes 81
82 Notes
Aimed at maximizing productivity, conserving energy, minimizing costs and enhancing safety, our
Electrical & Automation training programmes have benefitted over 1.35 Lakh professionals in the
last 28 years. These training programmes are highly beneficial as they provide right exposure and
impart knowledge on selection, installation, maintenance and testing of Electrical & Automation
Products.
Please contact any of the training centres for participation and detailed training programme schedule.