Solutions for diverse application.

Moulded Case
Circuit Breakers
Stability: Activated
Up and Running, Uninterrupted 1

In every industry, big or small, electrical power supply is The dsine range, a new generation of MCCBs, is a
critical. Even a few seconds of interruption or instability combination of state-of-the-art design and modern
can result in huge financial losses, even loss of life. We user-friendly features. It also boasts a wide choice of
have little or no control over the nature or stability of protective releases, ergonomics, aesthetics and
power supply. The unpredictable nature of power compactness. The range, designed to meet the
makes it important to take appropriate steps for the changing needs of users after extensive analysis and user
protection and safety of your organisation’s employees feedback, can satisfy the most demanding system
and equipment. requirements.
In line with this objective, Larsen & Toubro presents Complemented by a wide array of accessories, the dsine
dsine – a highly advanced and sophisticated range of range offers comprehensive solutions to customer
Moulded Case Circuit Breakers (MCCBs). applications ensuring operational safety, reliability and
versatility.

Moulded Case
Circuit Breakers

L&T – Turning technology to your advantage


Over the last five decades, L&T has earned a place among selection, installation and effective after-sales service,
the world’s leading manufacturers of Low Voltage across the country.
Switchgear with the scale, sophistication and range to L&T is one of the first companies to introduce MCCBs in
meet global benchmarks. India. Over the years, we have developed our products to
In keeping with our leadership position in the Indian meet the ever-evolving demands of the market.
market, we also provide expert assistance in product
Obstacles: Deleted
Overcoming Challenges 3

Original Equipment Manufacturers (OEMs)


For Original Equipment Manufacturers (OEMs), every and earth fault protection with 3P MCCBs. Equipped with
moment poses a new challenge. The dsine range of common accessories for the entire range, these MCCBs
MCCBs has been created keeping this in mind. Built in assure excellent savings by reducing your inventory costs.
accordance with the highest technical standards, dsine What’s more, our experienced sales & service team is just
MCCBs assure reliable and maintenance-free operation. a call away. Our team is adept at handling queries and
They have been designed to adapt to changes and complaints and is trained to offer you techno-commercial
overcome the challenges of your day-to-day operations. solutions… on time, every time.
Besides being available in 4P version to serve OEMs, such
After all, forging long-term associations has always been
as DG sets, dsine MCCBs come with an external neutral
the cornerstone of our business.
CT for the microprocessor-based version to offer neutral

Moulded Case
Circuit Breakers
Versatility: Downloaded

Paper Industry

Sugar Industry

Oil Industry

Gas Industry
Meeting Diverse Demands 5

Industries
Every industry is unique, and so are its requirements. MCCBs with high breaking capacities cater to high
Industries as diverse as paper, sugar, oil & gas have voltage applications such as windmills and mines. They
different sets of needs. Thankfully, dsine MCCBs, are compact so the panel builder can optimise panel
available in various current ranges (20A to 1250A), are size. They are thoroughly factory-tested with adequate
designed to efficiently handle such diversity. quality controls in place. Moreover, since these MCCBs
are designed to handle high-value capacitive inrush
Our Thermal Magnetic as well as Microprocessor-based
currents, no nuisance tripping is observed in APFC
releases with various breaking capacities cater to
panels. Motor loads being most vital, our design team
multiple industrial needs. Built with the latest
has also developed special dsine-M series for motor
technology, dsine MCCBs deliver optimum efficiency
back-up protection ranging from 32A to 630A.
even in the most adverse environmental conditions.
Efficiency: Initiated
Paving The Path to Progress 7

Building Sector
Today, efficient energy management holds the key to Choose from a variety of communication protocols
growth and development in any sector. Moreover, in including MODBUS RTU and Bluetooth available with
most sectors, such as the building sector, energy our new MATRIX releases. In today’s world of high-end
management has become mandatory. Our new range of residential buildings or commercial malls, our motorised
dsine MATRIX releases with advanced technology is dsine MCCBs with the fastest changeover from mains to
specially designed with energy management in mind. DG in less than 300 milliseconds are indeed the most
reliable choice. Our Auto Source Transfer System has
MTX3.0 releases with power metering and
almost eliminated the risk of loss of data.
communication capabilities are ideal for remote
annunciation in Data Centers and IT Parks.
Performance: Delivered
Delivering Unparalleled Results 9

DC Systems, UPS, Battery Chargers


Unlike AC breaking, DC breaking is a critical They are also available for lower DC voltages such as
phenomenon that causes severe damage. That’s why, we battery chargers.
offer DC MCCBs from the dsine family. A range that has
The SD (Switch Disconnector) version of dsine MCCBs can
been designed and developed specially for DC
be used at the incoming and outgoing terminals of UPS
applications such as UPS and battery chargers.
for isolation. Our SD is designed to withstand high
Choose from a wide range of DC voltages (up to 500V) currents without compromising on Service Performance.
and DC breaking capacities (up to 36kA) available as per
various application requirements.
Reliability: Ensured
Soaring High with Consistency 11

Infrastructure
Monitoring and controlling electrical installations at As power supply is critical for airports and hospitals, our
places like airports, hospitals etc. demands high-end, dsine MCCBs with ASTS offer changeovers in less than
reliable solutions. MATRIX releases are built precisely for 300 milliseconds coupled with a variety of other
such purposes. protections in case of under voltage, phase unbalance,
etc.
Communication capable MATRIX releases with power
and energy metering help in modernisation. These A variety of settings in MATRIX releases helps in choosing
releases are made compatible with HMI (Human Machine the correct selection for fault clearing, while trip & event
Interface) and DCS (Data Control System). recording with MATRIX releases helps in analysing the
faults in detail.

Our dsine MCCBs are shipped to Europe, Africa, Australia, Middle East,
South East Asia, China and America. In India, we have the largest stockist
network with over 700 stockists. To find the ideal dsine MCCB suitable for
your requirements, turn the page.
INDEX
Overview

Product Data

Accessories

Characteristic Curves

Wiring Diagrams

Dimensions
Overview
n Range 16
n
Standards & Approvals 18
n
Structure & Features 19
n
Marking & Configuration 20
n
Trip Units 21
Accessories
n 22
16 Range

DN4 DN3 DN2 DN1 DN0

State-of-the-art design, user-friendly features and a wide spectrum of protection releases form the hallmarks of the
dsine range. Also recognised for its ergonomics, aesthetics and compactness, it belongs to a new generation of
MCCBs. Specially designed and developed for extreme tropical conditions, it promises reliable performance at high
ambient and humid environment.
dsine, unfailingly, caters to the ever-evolving needs of customers, derived after in-depth analysis and customer
feedback. Because we understand our customers' requirements and demands, our contemporary range of MCCBs
never fall short of ensuring complete customer satisfaction. Moreover, complemented by a host of accessories, the
dsine range delivers comprehensive solutions to customer applications ensuring operational safety, reliability and
versatility.
Range 17

Features
Range
Æ available from 20A to 1250A
Available
Æ in 3 pole & 4 pole
Range of 25kA / 36kA / 50kA / 70kA / 100kA breaking capacities
Æ
Microprocessor and Thermal-Magnetic based protection releases
Æ
MCCBs for Motor backup protection
Æ
MCCBs for Distribution and SD versions
Æ
Suitable for DC application
Æ
Manual, Rotary or Motorised versions
Æ
Wide range of common Internal and External accessories
Æ
RoHS complaint
Æ

DN0
Rated Current 20, 25, 32, 40, 50, 63, 80, 100, 125*A
Release Thermal-Magnetic
DN1
Rated Current 125, 160, 200, 250A
Release Thermal-Magnetic
DN2
Rated Current 63, 80, 100, 125, 160, 200, 250A 40, 63, 100, 160, 250A
Release Thermal-Magnetic Microprocessor
DN3B
Rated Current 320, 400A
Release Thermal-Magnetic
DN3
Rated Current 320, 400, 500, 630A 400, 630A
Release Thermal-Magnetic Microprocessor
DN4
Rated Current 800, 1000, 1250A
Release Microprocessor
* Available only in DN0-D

Breaking Capacities (Ic u )


18 Standards & Approvals

range of MCCBs and Accessories comply with following


international standards
• IEC 60947-1, EN 60947-1, IS/IEC 60947-1
Low-voltage switchgear and controlgear, Part 1: General Rules
• IEC 60947-2, EN 60947-2, IS/IEC 60947-2
Low-voltage switchgear and controlgear, Part 2: Circuit-breakers
• IEC 60947-3, EN 60947-3, IS/IEC 60947-3
Low-voltage switchgear and controlgear, Part 3: Switches, disconnectors,
switch-disconnectors and fuse combination units
• IEC 60947-4, EN 60947-4, IS/IEC 60947-4
Low-voltage switchgear and controlgear, Part 4: Contactors and Motor-starters
Third party certificates (ERDA/CPRI) available for dsine range of MCCBs

NABL
NABL accreditation is a formal recognition of the technical competence of testing,
calibration or medical laboratory for a specific task following ISO/IEC 17025:2005 Standard.
Accredited laboratories have the responsibility of satisfying the criteria of laboratory
accreditation at all times, which are verified during Surveillance and Re-assessment visits by
NABL. Further the accredited laboratories should prove their technical competence by
satisfactory participation in recognized Proficiency Testing Programmes.
L&T’s Switchgear Testing Lab is NABL accredited subject to continued satisfactory
compliance to above standard & additional requirements of NABL.
All dsine range of MCCBs are tested in L&T's NABL accredited Switchgear Testing Lab.

marking
A CE marking is a European marking of conformity that indicates a product complies with
the essential requirements of the applicable European laws or directives with respect to
safety, health and environment and consumer protection. Generally, this conformity to the
applicable directives is done through self-declaration and is required on products in the
countries of the European Economic Area (EEA) to facilitate trade among the member
countries. The manufacturer or their authorized representative established in the EEA is
responsible for affixing the CE marking to their product. The CE marking provides a means
for a manufacturer to demonstrate that a product complies with a common set of laws
required by all countries in the EEA to allow free movement of trade within the EEA
countries.
L&T’s dsine range of MCCBs conform to the Low voltage directive 73/23/EEC as amended
by directive 93/68/EEC, provided if it is used in the application for which it is made and is
installed and maintained in accordance with professional practices with relevant installation
standards and operating instructions.

IECEE CB SCHEME – DEKRA (KEMA) certified


The IECEE CB SCHEME is a multilateral agreement among participating countries and
certification organizations. A manufacturer utilizing a CB test certificate issued by one of the
accepted National Certification Bodies (NCBs) can obtain certification marks of the latter,
within their scope of adherence, in the countries where the accepted NCBs are located.
L&T’s dsine range of MCCBs are certified for IECEE CB scheme by DEKRA (KEMA) which is a
world renowned organisation with a heritage of 150 years in testing, inspections &
certification, risk management and verification.
Structure & Features 19

Low Watt Loss


• The entire current carrying
path is optimally designed to
achieve low watt loss Arc Chutes
• Silver contacts offer low • Arc chutes are designed for
contact resistance thus helping efficient and faster arc
in low watt loss quenching

Current Limiting MCCBs


• The unique speed contact
MCCB Mechanism system with current limiting
• Quick make, quick break & trip feature accelerates the
free mechanism opening of contacts during
short circuit resulting in very
low let through energy

Positive Isolation Front Fascia


• Indicates the true position of • Knob designed for better grip
the contacts - ensures
operator safety • Indicates “ON", “OFF" and
“TRIP" position of MCCB

No Load Line Bias Release


• Either side of MCCB terminals • Thermal & Microprocessor
can be used as load or line based releases are available
20 Marking & Configuration

Terminal Connections

Standard Characteristics
}Uimp: Impulse withstand voltage
}Ue: Rated operational voltage
}Icu: Rated Ultimate breaking Utilization Category
capacity Brand
}Ics: Rated Service breaking capacity Frame Size
Symbol of suitability
Standards for Isolation
Mark
Indication of Closed (I/ON)
Company Logo

Operating Knob

Indication of Open (O/OFF)

Release
Current Rating of MCCB
Release Settings "Push to Trip" button

Release name

Terminal Shroud
Trip Units 21

Variable Thermal,
Fixed Magnetic
(DN0, DN1, DN3B)

Thermal Magnetic
Variable Thermal, Variable Magnetic (DN2, DN3)
Releases

MTX1.0 with LSI (DN2, DN3, DN4)

MTX2.0 with LSING + Current Metering (DN2, DN3, DN4)

Inst

Microprocessor
Releases

MTX3.0 with LSING + Communication capable +


Power Metering (DN2, DN3, DN4)

Inst

Motor Protection Release (DN0, DN1, DN2, DN3 -


Magnetic Protection only)

Magnetic Release

DN3-M

Switch Disconnector (DN0, DN2, DN3, DN4)

Isolator
22 Accessories

1 Spreader Terminals

2 Phase Barriers

3 Undervoltage Release

4 Shunt Release

5 Auxiliary Contact 12

6 Trip Alarm Contact

7 Auxiliary + Trip Alarm Contact

8 Direct Rotary Handle

9 Extended Rotary Handle

10 Panel Mounted Keylock

11 Stored Energy Electrically Operated Mechanism

12 Mechanical Interlock Kit

13 Communication Module
16
14 Voltage Module

15 Display Module 4 3

16 External Neutral CT
(with Adaptor Kit)

* For Enclosure please refer page no. 50


1

8
23

15
14
13

6 7
5

11
10
9
Product Data
MCCBs for Power Distribution
n 26
- Technical Datasheet
MCCBs for Motor & Isolator
n 28
- Motor Backup Protection
- Isolator Application
MCCBs for DC & Capacitor Application
n 29
- DC Application
- Capacitor Application
n
Protection Releases for MCCBs 30
- Thermal Magnetic Release
- Microprocessor Release
n
MCCBs for Auto Source Transfer Application 42
- Auto Source Transfer Application
26 MCCBs for Power Distribution

Technical Datasheet
Frame 100A 125A 250A 250A
DN0-100 DN0-125 DN1-250 DN2-250
Type
C D D C N D N S
TM/MP
Release TM TM TM (MTX1.0/2.0/3.0)
20, 25, 32, 125, 160, 40, 63, 80,
Current Range In (A) 40, 50, 63, 125 100, 125, 160,
200, 250
80, 100 200, 250
Poles 3/4 3/4 3/4 3/4
Impulse withstand Voltage Uimp (kV) 8 8 8 8
Rated Operational Voltage Ue (V) (MAX) 600 600 600 690
Rated Insulation Voltage Ui (V) 800 800 800 800
Utilization Category A A A A
Standard
240 VAC 40 65 65 65 65 50 70 100
415 VAC/440 VAC ^ 25 36 36 25 50 36 50 70
480 VAC/500 VAC 10 10 10 10 10 25 36 42
Icu(kA)
Rated 550 VAC 8 8 8 8 8 18 25 36
Short 600 VAC 5 5 5 5 5 16 18 22
Circuit 690 VAC - - - - - 10 15 20
Breaking
Capacity 240 VAC 100% 50% 50% 50% 50% 100% 100% 100%
415 VAC/440 VAC 100% 50% 50% 100% 50% 100% 100% 100%
480 VAC/500 VAC 100% 50% 50% 50% 50% 100% 100% 100%
Ics as % Icu
550 VAC 100% 50% 50% 50% 50% 100% 100% 100%
600 VAC 100% 50% 50% 50% 50% 100% 100% 100%
690 VAC - - - - - 50% 50% 50%
Mechanical 40000 40000 15000 25000
Life
Electrical @1.0 In* 12000 8000 4000 10000 10000
Making Capacity (kA) 52.5 75.6 75.6 52.5 105 75.6 105 154
Operating Frequency (Hz)
Total Opening Time
Finger-proof Terminals
Suitable for Isolation
IP class
Pollution Degree
Load Line Bias
Ambient Temperature
Storage Temperature
Mounting Positions in Vertical Plane
3-Pole 75 x 60 x 130 105 x 60 x 165 105 x 96 x 179
Dimensions (WxDxH) mm
4-Pole 100 x 60 x 130 140 x 60 x 165 140 x 96 x 179
Weight (kg) (3/4 Pole) 0.8/1.1 0.73/1 0.73/1 1.55/2 2.5/3.3
Auxiliary Contact
Trip Alarm Contact 1 C/O or 2 C/O
A
INTERNAL Auxiliary & Trip Alarm Contact
C
C Shunt Release 240/415 V AC 50 Hz
E Under Voltage Release
S Rotary Operating Mechanism (Direct/Extended) ü ü ü
S Electrical Operating Mechanism û û ü
O Mechanical Interlock Kit û û ü
R Spreader T erminals ü ü ü
I EXTERNAL
Key lock ü ü ü
E Neutral CT with Adaptor kit û û
S
Current Metering Module û û
Display, Communication and Voltage Module û û

$ : 'NO' of control contactor to be connected in series for 220V DC, 24V DC


@: Contains display module & metering module, separate cable required for connection
# : Only Extended ROM available
^ : 440V AC reduce breaking capacity for DN0 & DN1
* : at 415V
DN2 - 1500 @ 690V
DN3 - 1000 @ 690V
DN4N - 800A - 2500 @ 415V
DN4S - 800A - 5000 @ 415V
27

400A 400A 630A 1250A


DN3B-400 DN3-400 DN3-630 DN4-1250
H V D N S D N S V N S V
MP (MTX TM/MP (MTX1.0/2.0/3.0) TM/MP (MTX1.0/2.0/3.0) MP (MTX1.0/2.0/3.0)
1.0/2.0/3.0) TM

40, 63,
100, 160, 320, 400 320, 400 500, 630 400, 630 800, 1000, 1250
250
3/4 3/4 3/4 3/4
8 8 8 8
690 690 690 690
800 800 800 800
A A A A
IS/IEC60947-2, IEC60947-2 & EN60947-2
100 100 50 50 70 100 50 70 100 100 70 100 100
80 100 36 36 50 70 36 50 70 100 50 70 100
65 65 25 25 36 42 25 36 42 65 25 36 65
36 36 15 15 20 25 15 20 25 50 20 25 50
22 36 12 12 18 22 12 18 22 50 16 20 50
20 36 5 8 15 20 8 10 15 50 10 18 50
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
100% 50% 100% 100% 100% 100% 100% 100% 100% 50% 100% 100% 50%
100% 50% 100% 100% 100% 100% 100% 100% 100% 50% 100% 100% 50%
50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50% 50%
25000 10000 15000 15000 15000 20000
10000* 4000 4000 4000 4000* 3000*
176 220 75.6 75.6 105 154 75.6 105 154 220 105 154 220
50 / 60
<10msec <20msec
Yes
Yes
IP40
III
NO
-5OC to 55OC
-35OC to 70OC
Vertical and 90 deg in both directions
140 x 111 x 205 140 x 111.5 x 266 140 x 111.5 x 266 210 x 143 x 370
184 x 111 x 205 183.5 x 111.5 x 266 183.5 x 111.5 x 266 278 x 143 x 370
4.0/5.0 5.5/7.2 6/7.8 6.3/8 17 / 22
1 C/O or 2 C/O
1 C/O
1 C/O + 1 C/O
110 / 415 V AC 50 Hz, 110 / 220 V DC, 24 V DC $
240 V AC 50 Hz
ü ü
#
û ü û
û ü û
ü û
ü ü
Available for 3P MCCBs with MTX2.0 & MTX3.0 release only ü
Available for MTX2.0 release for current metering only @
Available for MTX3.0 release for Communication & Power metering

Note:
• Any two internal accessories can be mounted at a time
• V version MCCBs, to be used with extended ROM only
• Separate earth fault module required for earth fault protection using TM releases
• Icu: Rated ultimate short-circuit breaking capacity
Ics: Rated service short-circuit breaking capacity
• Reference temperature 40OC & 50OC
28 MCCBs for Motor & Isolator

Motor Backup Protection


AC induction motors are the vital elements in any
production process and hence constitute majority of
loads in Industry and other installations. The M version
MCCBs in dsine range are developed specially to give
short circuit protection for all types of motors. DN3-M
Selection of MCCB using our type 2 charts give reliable
performance of the motors.

Frame 100A 160A 250A 400A 630A


DN0-100 DN1-160 DN2-250 DN3-400 DN3-630
Type
M M M MH M M MV
Current range (A) 32-100 100-160 100-250 63-250 320-400 500-630 320-630
Poles 3 3 3 3 3 3 3
400 / 415 V 50 50 50 80 50 50 100
Icu (kA) 480 V 10 10 36 65 36 36 65
Rated 690 V - - 15 20 15 10 50
Short 50 50 50 80 50 50 100
415 V
Circuit Iq (kA)
Breaking 480 V - - - 65 - - 65
Capacity 400 / 415 V 25% 50% 100% 100% 100% 100% 100%
Ics as % Icu 480 V 25% 50% 100% 100% 100% 100% 100%
690 V - - 100% 100% 100% 100% 50%
Magnetic Setting 9In 10In 10In
Note: MV version MCCBs to be used with extended ROM only.

Isolator Application
dsine MCCBs with Switch Disconnector version offer solution for switching various loads such as UPS, Battery Banks
etc. with various advantages. These MCCBs differ from regular MCCBs only in terms of absence of protection trip
units. These MCCBs can be used for following applications for isolation purpose:
• For local isolation- such as very close to Motor load
• Generally used at the incoming of any sub-distribution
• As an Isolator for Bus coupler
• As an automatic switch
• For switching applications of motors with VFDs, soft starters
SD MCCBs are always backed up by the Short Circuit Protection Device (SCPD) to protect downstream
loads/installations against short circuit. Our dsine SD MCCBs offer following advantages.
• Suitable for Positive isolation
• Available with 3P & 4P versions
• Can be used with Under Voltage Protection
• Remote tripping through Shunt release
• Motor operated MCCBs
• Status feedback possible
Following are the specifications of SD MCCBs

Frame 160A 250A 400A 400A 630A 800A 1000A 1250A


Type DN0-160SD DN2-250SD DN3B-400SD DN3-400SD DN3-630SD DN4-1250SD
Current Range (A) 32-160 100-250 320-400 320-400 500-630 800 1000 1250
Poles 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
ICW (kA) 2 3.6 5.5 5.5 7.6 10 12 15
Duration (sec) 1 1 1 1 1 1 0.5 0.1

Note: Icw - Rated short-time withstand current


MCCBs for DC & Capacitor Application 29

DC Application
DC power distribution is an upcoming technology in this modern era due to its most rigorous network power
applications such as
• AC-DC Power System
• DC-DC Converter Systems
• DC-AC Inverter Systems
• DC UPS
• Batteries & Accessories
• Solution to alternative energy-Solar Power
We offer dsine MCCBs for the protection of DC systems in variety of current ratings from 20A-630A, voltage ratings
upto 750V and various breaking capacities ranging from 5kA to 36kA.

Frame DN0-125* DN1-250 DN2-250 DN3-400 DN3B-400 DN3-630


Type C D C N D N S D N S D D N S
Release TM
Poles 3 or 4
20, 25, 32, 125, 160, 63, 80, 100, 125,
Rated current In (A) 40, 50, 63, 320, 400 320, 400 500, 630
80, 100, 125 200, 250 160, 200, 250

250 V DC 20 20 20 30 36 20 30 36 25 20 30 36
Icu (kA rms) 500 V DC 15 15 15 20 25 15 20 25 10 15 20 25
750 V DC - - 10 15 20 10 15 20 - 10 15 20
Type of connection 3P in series
L/R (msec) <15msec
*Available only in DN0-125D

Switching of DC currents is much severe phenomenon than switching AC currents due to non occurrence of natural zero.
Hence DC MCCBs are desired to give less breaking capacity than AC MCCBs for the same voltage & currents.
Note: Suitable for Thermal Magnetic release only

Capacitor Application
For any APFC panel, MCCBs are required for short circuit protection, overload protection and for isolation of
capacitors. MCCB selection for capacitive load is tricky because of heavy inrush current, high overload capacity and
continuous full load. These inherent traits of a capacitor, complicates the selection process. The selection should be
such that the MCCB should not nuisance trip during inrush current and should withstand continuous flow of
overload current.
Whenever we use MCCB in an APFC panel, proper measures need to be taken against the ill effects of the inrush
current. Normally the inrush current (more than 100 times the rated capacitor current) will remain for a few micro-
seconds and will not be sensed by the MCCB. However the contacts of MCCB may repel and bounce because of the
current limiting feature, causing micro-arcs between the contacts of MCCB. This multiple bounce can result in
premature failure of MCCB contacts. In order to reduce the magnitude of the peak inrush current, MCCBs must be
used along with capacitor duty contactors or inrush current limiting reactors.
The maximum permissible current in a capacitor branch is 1.46 times the rated current. This factor is comprised of the
following:
1. Harmonics overload and over voltage – 30%
2. Capacitance tolerance – 10%
3. Frequency variation – 2%
Hence adequate care needs to be taken while selecting switching & protection devices for capacitor applications. It is
always advised to limit the switching inrush current within safe limits. For this, MCCB ratings should be chosen at
least 1.5 to 2 times of capacitor rated current along with Capacitor Duty Contactors.
30 Protection Release for MCCBs

Thermal-Magnetic Release
Features of Thermal-Magnetic Release
Adjustable
Æ overload settings
Fixed /
Æ Adjustable short circuit settings
True RMS
Æ sensing Settings
“Push
Æ to Trip” button Protection
DN0 & DN1 DN2 & DN3 DN3B

Overload 80% - 100%In 80% - 100%In 80% - 100%In

Short Circuit 9In (fixed) 6 - 10In 9In (fixed)

Earth fault External GF Module required*

Microprocessor Release
Features of MTX1.0
Overload
Æ Protection with inverse time delay
Adjustable
Æ Trip class
Short
Æ Circuit Protection with selectable
time delay
Provision
Æ of Thermal memory defeat
Provision
Æ for release testing
Overload
Æ indication
Power
Æ ON LED
Self powered
Æ

True RMS
Æ sensing
“Push
Æ to Trip” button

MTX1.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 5%
Time delay, tr (Inverse) 10s at 6Ir, 3s at 6Ir, 10s at 7.2Ir, 3s at 7.2Ir
Protection mode ON / OFF
Thermal memory Enable / Disable
Short Circuit
Current setting, Is (Is = x Ir) 1.5, 2.5, 4.0, 5.5, 6.5, 8.0Ir
Time delay, ts Instantaneous / 100ms
Protection mode ON / OFF
Note: • Factory Settings - O/L: 100%In, Curves: 6Ir@10s, Thermal Memory: Off, S/C: 5.5Ir @ Instantaneous
• Release provides in-built instantaneous override protection fixed @ 10In
* Refer page 51
Protection Release for MCCBs 31

Microprocessor Release
Features of MTX2.0
Overload
Æ Protection with inverse time delay
Adjustable
Æ Trip class
Short
Æ Circuit Protection with selectable
time delay
Inbuilt
Æ Earth fault and Neutral overload

Inst
protection
Provision
Æ of Thermal memory defeat
Provision
Æ for release testing
Overload
Æ indication
Power
Æ ON LED
Panel
Æ mounted O-LED display for current metering
Self powered
Æ

True RMS
Æ sensing
“Push
Æ to Trip” button
Latest
Æ trip record

MTX2.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 5%
Time delay, tr (Inverse) 10s at 6Ir, 3s at 6Ir, 10s at 7.2Ir, 3s at 7.2Ir
Protection mode ON / OFF
Thermal memory Enable / Disable
Overload (Neutral)
Current setting, IN (IN = x Ir) 50%, 100% and 150%Ir
Time delay, tN 200ms / Same as overload
Protection mode ON / OFF
Short Circuit
Current setting, Is (Is = x Ir) 1.5, 2.5, 4.0, 5.5, 6.5, 8.0Ir
Time delay, ts Instantaneous / 100ms
Protection mode ON / OFF
Earth Fault
Current setting, Ig (Ig = x In) 20% to 50%In in steps of 10%
Time delay, tg 100ms / 200ms
Protection mode ON / OFF
Note: • Factory Settings - O/L: 100%In, Curves: 6Ir @10s, S/C: 5.5Ir @ Instantaneous, Thermal Memory: Off, E/F: Off, Neutral: Off.
• Release provides in-built instantaneous override protection fixed @ 10In
32 Protection Release for MCCBs

Advanced features of MTX2.0


Panel Mounted
Æ Display for Current Metering &
Trip Record
System currents & latest trip record can be viewed with panel
door closed.

Power
Supply
Module

Metering Module

Port with
Æ Polarized Connector
MTX2.0 release with metering port is implemented with poka-yoke
technology using polarized connector to ensure correct insertion of
metering harness, thus avoiding unnecessary errors.

Digital Current
Æ Metering
MTX releases are designed with protection class CTs
which measure true RMS values. Inbuilt current
metering does not require separate CTs hence
maintenance is easy.

O-LED Display
Æ
O-LED display allows the operator a wide viewing
angle.
O-LEDs showing current metering has got faster
response time and also consumes less power, hence
saves energy. It has better contrast ratio as well.
Display Module
Protection Release for MCCBs 33

@6Ir

Inst
3s
10s
@7.2Ir

2 3 1

Inbuilt Earth
Æ Fault Protection 1
Inbuilt earth fault protection function does not require any separate trip coil & external CBCT, thus saving panel
space, cost & improving the overall hygiene. Earth fault protection limits expenses by preventing damage to other
equipment.

Thermal Memory
Æ 2
Thermal memory protects the system from thermal stresses generated by cumulative heating caused by cyclic
overload conditions thus allowing the system to return to a safe operating temperature. This function also allows
an optimization of cables or bus bar protection in case of low amplitude repetitive faults. Advance tripping
increases the overall life and eliminates the production downtime incase of severe faults.

Multiple Trip Class


Æ 3
Enhances adjustability for better enhanced coordination with other devices to achieve correct motor switching
and ensures protection of the starter elements in order to guarantee the plant safety.

Precise Selection of Parameters


Æ
Overload & short circuit settings with minimum step change helps to maintain balance between nuisance tripping
and optimal protection resulting in high continuity of service and reduced call back periods. MTX release can be
adapted to specific requirements of OEM or end-user.

DIP Switches
Æ
DIP switches are provided on front side of the release for easy operations. These switches give you quicker option
to precisely change selection, offering high life.

Trip Indication
Æ 4
Improves uptime and productivity by setting alarms for unbalanced loads so that proactive measures can be taken
to avoid overload conditions. Also, cause of fault (Short circuit and earth fault) can be indicated on the release as
per below table.

% of Ir Overload LED indication LED Fault Indication


80% Slow blinking of green LED Fault MTX1.0 MTX2.0/MTX3.0
115% Faster blinking of green LED Short Circuit OFF-ON-OFF-ON-OFF-OFF-OFF-OFF OFF-ON-OFF-ON-OFF-OFF-OFF-OFF
Earth Fault – ON-OFF-ON-OFF-ON-ON-ON-ON
Note: This sequence will continue till Aux Power is connected. One ON/OFF blink is of 0.5 sec.

Self Powered
Æ
MTX releases do not need any external power supply hence require no extra devices and wires to power up.
The release power up with 30% loading with a power ON LED

Note: For wiring diagram, please refer page no. 62


34 Protection Release for MCCBs

Various Protection Settings

@6Ir

Inst
3s
Overload Protection, (Ir = x In)

10s
@7.2Ir
0.4 0.4 0.4 0.4 0.4 0.4 0.4

DIP Switch
r

r
Position
r

r
q q q q q q q

Setting Bypass 40% 45% 50% 55% 60% 65%

0.4 0.4 0.4 0.4 0.4 0.4 0.4

DIP Switch
r

r
Position
r

r
q q q q q q q

Setting 70% 75% 80% 85% 90% 95% 100%

Thermal Memory

0.4 0.4

DIP Switch
r

Position
r

q q

Setting Bypass ON

Overload Curves

0.4 0.4 0.4 0.4

DIP Switch
r

Position
r

q q q q

Setting 3s @ 6Ir 10s @ 6Ir 3s @ 7.2Ir 10s @ 7.2Ir

Short Circuit Setting, (Is = x Ir)

DIP Switch
Inst

Inst

Inst

Inst

Inst

Inst

Inst

Position

Setting Bypass 1.5 2.5 4.0 5.5 6.5 8.0


Protection Release for MCCBs 35

Time Delay for Short Circuit Protection

DIP Switch Inst

Inst
Position

Setting Instantaneous 100ms

Earth Fault Setting, (Ig= x In)

0.2 0.2 0.2 0.2 0.2

DIP Switch
Position

Setting Bypass 20% 30% 40% 50%

Time Delay for Earth Fault Protection

0.2 0.2

DIP Switch
Position

Setting 100ms 200ms

Neutral Setting, (IN = x Ir)

Ir * Ir * Ir * Ir *

DIP Switch
Position
0.5
1.0

0.5
1.0

0.5
1.0

0.5
1.0

Setting Bypass 50% 100% 150%*

Time Delay for Neutral Protection

Ir * Ir *

DIP Switch
Position
0.5
1.0

0.5
1.0

Setting 200ms Follows O/L Curve

* With maximum overload setting Ir=0.65In


36 Protection Release for MCCBs

Microprocessor Release
Features of MTX3.0
Overload
Æ Protection with inverse time delay
2 4
I t, I t,
Æ SI, LI-VI based over load curves
Short Circuit Protection with selectable time delay
Æ
Instantaneous protection with fine settings
Æ
Advanced current and voltage based protection function
Æ
Protection against current unbalance and single phasing
Æ
Comprehensive current, power and energy metering
Æ
Inbuilt Earth fault and Neutral overload protection
Æ
Provision of Thermal memory defeat
Æ
Panel mounted O-LED display
Æ
Communication through MODBUS RTU
Æ
Pre-trip alarms
Æ
True RMS sensing
Æ
Power on LED
Æ Inst

“Push to Trip” button


Æ
Self powered
Æ

MTX3.0
Rated Current, In From 40 to 1250A
Overload (Phase)
Current setting, Ir (Ir = x In) 40% to 100%In in steps of 1%*
Time delay, tr (Inverse) 0.5s to 30s in steps of 0.1s*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Ir in steps of 1%*
Thermal memory Enable/Disable
Overload (Neutral)
Current setting, IN (IN = x Ir) 50% to 150% Ir in steps of 1%*
Time delay, tN 0.2s / same as overload*
Protection mode ON / OFF
Short Circuit
Current setting, Is (Is = x Ir) 1.5 to 8 Ir in steps of 0.1*
Time delay, ts 100ms, 200ms, 300ms, 400ms*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Is in steps of 1%*
Instantaneous
Current setting, Ii (Ii = x In) 1.5 to 8 In in steps of 0.1*
Protection mode ON / OFF
Preset trip alarm setting 50% to 90% Ii in steps of 1%*
Earth Fault
Current setting, Ig (Ig = x In) 10%* to 50% In in steps of 5%*
Time delay, tg 100ms to 500ms in steps of 50ms*
Protection mode ON / OFF
* Can be set using communication and display module
Note: • Factory Settings - Address:0000, O/L: 100%In, Curves: 6Ir @10s, S/C: 5.5Ir @ Instantaneous, Thermal Memory: Off, E/F: Off, Neutral:
Off.
• Release provides in-built instantaneous override protection fixed @ 10In
Protection Release for MCCBs 37

MTX3.0 Additional features with Display Module


Current Protection
Under Current
Current setting (A) Iui (Iui = x Ir) 20 to 85% Ir in steps of 1%
Time delay (s) 1 to 255 in steps of 1
Protection mode ON / OFF
Preset trip alarm setting 110% to 150% Iui in steps of 1%
Current Unbalance
Current setting (A) 30 to 90% Ir in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%

Voltage Protection
Under Voltage
Voltage setting (V) Vuv (Vuv = x Un) 45 to 80% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 110 to 150% Vuv in steps of 1%
Over Voltage
Voltage setting (V) Vov (Vov = x Un) 105 to 150% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90%Vov in steps of 1%
Voltage Unbalance
Voltage setting (V) 5 to 20% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Residual Voltage
Voltage setting (V) 5 to 40% Un in steps of 1%
Time delay (s) 0.5 to 60 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%

Frequency Protection
Under Frequency
Frequency setting (Hz) F-0.5 to F-5.0 in steps of 0.5
Time delay (s) 0.1 to 30 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set freq in steps of 1%
Over Frequency
Frequency setting (Hz) F+0.5 to F+5.0 in steps of 0.5
Time delay (s) 0.1 to 30 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set freq in steps of 1%
38 Protection Release for MCCBs

Power Protection
Reverse Power
Power setting (W) PR 1 to 5000kW in steps of 1kW
Time delay (s) 0.5 to 60 in steps of 0.5
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% PR in steps of 1%
Lead Pf
Pf setting 0.5 to 0.99 in steps of 1%
Time delay (ms) 100 to 500 in steps of 1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Lag Pf
Pf setting 0.5 to 0.99 in steps of 1%
Time delay (ms) 100 to 500 in steps of 1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%

Other Protections
MD Active
Demand settings 1 to 5000kW in steps of 1kW
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
MD Reactive
Demand settings 1 to 5000kVAr in steps of 1kVAr
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
MD Apparent
Demand settings 1 to 5000kVA in steps of 1kVA
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Phase Sequence
Phase seq setting 123 or 132
Time delay (s) 1 to 5 in steps of 0.1
Protection mode ON / OFF
THD Current
Current setting (A) 5 to 50%Ir in steps of 1%
Time delay (s) 5 to 15 in steps of 5
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
THD Voltage
Voltage setting (V) 5 to 50% Un in steps of 1%
Time delay (s) 5 to 15 in steps of 0.1
Protection mode ON / OFF
Preset trip alarm setting 50 to 90% of set value in steps of 1%
Protection Release for MCCBs 39

Metering & Display


Current Phase, Neutral & Earth
Voltage Phase & Line
Frequency & power factor True RMS
Power Active, Reactive & Apparent
Energy Active, Reactive & Apparent
Maximum demand Active, Reactive & Apparent
THD Current and voltage
Communication
Protocol MODBUS RTU
History
Trip history Last 10 trip records with non volatile memory
Event history Last 10 event records with non volatile memory

Advanced Features of MTX3.0


Energy & Power Measurement
One of the first steps towards energy efficiency is energy ana power measurement. In MTX 3.0 release, in addition
Æ
to current & voltage measurement, active, reactive and apparent energy & power can also be measured. This would
enable monitoring energy at individual feeder level and thus help in implementing effective energy management
practices in the plant. Moreover, using communication module, different parameters reading can be viewed on
display module.

MCCB with MTX3.0 release

Power Supply
Module

Voltage
Display Module
Module
3 ph 4 wire
Communication AC supply
Module

Energy and Power management functionality using voltage module


40 Protection Release for MCCBs

Advanced
Æ Current and Voltage based protections
• Reverse Phase:
This function detects the phase reversal of current from the
set sequence. It is especially important in motor feeder
applications
• Reverse Power:
One can set the direction of power flow in a system from
source to load and in case the direction of power flow
reverses, the reverse power protection can be activated to
trip the system. This is especially important in a DG set or in a
ring mains system.

Power Quality
Æ Control
MTX3.0 release measures the frequency, power factor and offers
protection against leading and lagging values thereby assisting in
maintaining the power quality. This release measures THD of
current & voltage and gives an alarm / trip in case it exceeds the
set thresholds.

Communication
Æ Capable

Convertor
Laptop or HMI (RS485 to RS232)

Most advanced release of MTX series, MTX3.0 is communication capable on MODBUS RTU network. Using MODBUS
com module the MCCB release can be connected to a Personal Computer. The metering values can be read remotely.
The settings configuration on the other hand can both be read and changed remotely. These releases are also made
compatible with HMI (Human Machine Interface) & DCS (Data Control Systems)
Protection Release for MCCBs 41

Multi-looping
Æ

Laptop or HMI

Convertor
(RS485 to RS232)

MODBUS Communication through MODBUS looping

A single display module can be used to connect upto 15 MCCBs with MTX3.0 release through MODBUS network.
Highly reliable data yet extremely simple looping reduces operational headaches and enhances remote accessibility.

Maintenance Functionality
Æ
MTX3.0 release can store last 10 trip records & last 10 event records which can be used for the system analysis
later on. These recorded values can be viewed from display unit as well as PC.

Note: For wiring diagram, please refer page no. 63


42 MCCBs for Auto Source Transfer Application

AuXC-2000 Controller
There are many electrical services which are required to be powered up always. Interruption of supply to these kinds
of services is not desired. These loads are part of any industry, hospital, school, commercial buildings, shopping malls,
name any place of importance. These loads can be firefighting system, emergency lighting, control stations, CCTV,
emergency pumps, security system etc. L&T’s micro-processor based Automatic Transfer Controller
AuXC-2000along with L&T switchgear is the answer to all auto source transfer requirements.

Changeover Conditions
All the conditions which can help establish whether a power source is or is not suitable are defined by the
user through setting following parameters
Parameter Description
Minimum voltage One or more phases too low
Maximum voltage One or more phases too high
Phase loss Threshold below which the unit intervention is quicker than with a normal decrease.
Asymmetry (unbalance) Phases within the Maximum-Minimum range but too different from each other
Minimum frequency Too low frequency
Maximum frequency Too high frequency
Phase sequence Reverse rotation of phases

Intuitive user interface Password access to prevent any unauthorized


• 5 keys membrane keypad for parameters setting. access
• 128x80 pixel, Backlight LCD screen with 4 Grey levels. • The password is used to enable or lock the
access to setting menu and to commands menu.
Status at a glance
• 4 LEDs for plant synoptic (source line and breakers status). Generator setup
• 2 LEDs for alarm presence and AUTO mode active. • Management of generator set start-stop &\
cooling cycle
Flexibility to suit side conditions • Management of automatic test for generators
• Suitable for switching between Utility-Utility or with emergency and rotation.
Utility-Genset or Genset-Genset
• Selectability between auto and manual mode of switching Failure simulation
• Enabling and disabling of priority supply. • Test the changeover setup without
• Settable transition time for all events connecting actual load
• Selectability between Open before presence of secondary
supply (OBP) & open after presence of secondary supply EJP (Effacement Jours Pointe) function
(OAP) available • Switch from the main supply to standby
power for the duration of a tariff period with
Programmable digital inputs, outputs & alarms to higher prices.
control changeover device
• 6 programmable digital inputs (negative). Event Logger
• 6 + 1 digital outputs: • Storage of last 100 events.
- 6 relays with NO contact 8A 250VAC
- 1 relays with changeover contact 8A 250VAC
• 18 alarms (4 user programmable alarms)
MCCBs for Auto Source Transfer Application 43

AC Supply : terminals 13, 14 Measuring accuracy


Rated voltage Us 100 - 240V~ Mains and generator voltage ±0.25% f.s. ±1digit

Operating voltage range 90 -264V~ Real time clock


93.5 - 300V= Energy storage Back-up capacitors
Frequency 45 - 66Hz Operating time without supply voltage About 5 minites
Power consumption/dissipation 3.8W - 9.5VA Digital inputs: terminals 15 - 20

≤50ms (110V~ ) Input type Negative


Immunity time for microbreakings
≤250ms (220V~ ) Current input 8mA
£
Recommended fuses F1A (fast) Input “low” voltage 2,2
£
Insulation voltage Input “high” voltage 3,4
³
AC Supply Input delay 50ms
³
Rated insulation voltage Ui 250V~ OUT1 and OUT 2 outputs: terminals 9,10 e 11,12
Rated impulse withstand voltage Uimp 6kV Contact type 2 x 1 NO
Power frequency withstand voltage 3kV AC1 - 8A 250V~
Rated current DC1 - 8A 30V=
Line 1 and Line 2 voltage inputs AC15 -1.5A 250V~
Rated insulation voltage Ui 480V~ Max rated voltage 300V~
Rated impulse withstand voltage Uimp 6kV Mechanical / electrical endurance 1x107 / 1x105 ops
Power frequency withstand voltage 3.8kV OUT3 output: terminals 22, 23, 24
OUT1 and OUT 2 outputs Contact type 1 changeover
Single between OUT1 and OUT 2 AC1 - 8A 250V~
Insulation type Rated current DC1 - 8A 30V=
Double toward the remaining groups AC15 -1.5A 250V~
Rated insulation voltage Ui 250V~ Max rated voltage 300V~
Single Double Mechanical / electrical endurance 1x107 / 1x105 ops
Rated impulse withstand voltage Uimp 4kV Uimp 6kV OUT4 and OUT 5 outputs: terminals 25,26,27
Power frequency withstand voltage 1.5kV 3kV Contact type 2 x 1 NO + contact common
OUT 3 output AC1 - 8A 250V~
Rated current DC1 - 8A 30V=
Rated insulation voltage Ui 250V~ AC15 -1.5A 250V~
Rated impulse withstand voltage Uimp 6kV Max rated voltage 300V~
Power frequency withstand voltage 3kV Mechanical / electrical endurance 1x107 / 1x105 ops
OUT4-5 and OUT 6-7 outputs Maximum current at contact common 10A

Insulation type Single between OUT4-5 and OUT 6-7 OUT6 and OUT 7 outputs: terminals 28,29,30
Double toward the remaining groups Contact type 2 x 1 NO + contact common
Rated insulation voltage Ui 250V~ AC1 - 8A 250V~
Rated current DC1 - 8A 30V=
Single Double AC15 -1.5A 250V~
Rated impulse withstand voltage Uimp 4kV Uimp 6kV Max rated voltage 300V~
Power frequency withstand voltage 1.5kV 3kV Mechanical / electrical endurance 1x107 / 1x105 ops
Line 1 and Line 2 voltage inputs: terminals 1-4 and 5-8 Maximum current at contact common 10A
Maximum rated voltage Ue 100…480V~ L-L (277VAC L-N) Connections
Measuring range 50…576V~ L-L (333V~L-N) Terminal type Plug-in / removable
Frequency range 45-65Hz Cable cross section (min... max) 0.2-2.5 mm² (24... 12 AWG)
Measuring method True RMS Tightening torque 0.56 Nm (5 lbin)
Measuring input impedance > 0.5MW L-N > 1,0MW L-L Housing
Single-phase, two-phase, Version Flushmount
three-phase with or without
Wiring mode neutral or balanced Material Polycarbonate
three-phase system. Degree of protection IP40 on front / IP20 terminals
Ambient operating conditions Weight 680g
O
Operating temperature +70 c -30..... *Notice: this product has been designed for environment A. Use of this product in
Vibration resistance -30... +80OC environment B may cause unwanted electromagnetic disturbances in which case the
user may be required to take adequate mitigation measures.
Climatic sequence <80% (IEC/EN 60068-2-78)
Shock resistance 2
Measurement category 3
Overvoltage category III
Maximum pollution degree Z/ABDM (IEC/EN 60068-2-61)
Relative humidity 15g (IEC/EN 60068-2-27)
Storage temperature 0.7g (IEC/EN 60068-2-6)
Accessories
Internal Accessories
n 46
- Auxiliary Contact
- Trip Alarm Contact
- Auxiliary Trip Alarm Contact
- Shunt Release
- Under Voltage Release

n
External Accessories 47
- Rotary Operating Mechanism
- Mechanical Interlocking Kit
- Keylock
- Spreader Terminals
- External Neutral CT
- Stored Energy Electrically Operated
Mechanism
- MTX Modules
- MCCB Enclosure
- Earth Fault Module
46 Accessories

Internal Accessories

dsine range of MCCBs are offered with snap-fit type, easily


installable internal accessories. There is no need to open main
cover and no live parts are accessed during installation. TAC,
Aux+TAC to be fitted in the right cavity & under voltage release
to be fitted in left cavity.
Double Insulation: The internal accessories are housed in insulated
casings to ensure first level of insulation. When the front cover is
opened for the fixing of internal accessories, the MCCB is totally
insulated ensuring the double insulation.

MCCB with mid cover opened & Internal


accessories fitted Auxiliary Contact TAC Shunt Release UV Release

Internal Accessories Contacts/Supply Voltage Frame Cavity


DN0, DN1 Right
1 C/O
DN2, DN3, DN3B, DN4 Right/Left
Auxiliary Contact
DN0, DN1 Right
2 C/O
DN2, DN3, DN3B, DN4 Right/Left
DN0, DN1 Right
1 C/O
Trip Alarm Contact DN2, DN3, DN3B, DN4 Right
2 C/O DN0, DN1 Right
DN0, DN1 Right
Auxiliary + Trip Alarm Contact 1 C/O + 1 C/O
DN2, DN3, DN3B, DN4 Right
240/415V AC 50Hz DN0, DN1 Left
Shunt Release
110/415V AC 50Hz, 110/220V, 24V DC DN2, DN3, DN3B, DN4 Right/Left
DN0, DN1
Under Voltage Release 240V AC DN2, DN3, DN3B Left
DN4

Shunt Release
It allows opening of MCCB by means of an electrical command. Operation of the release is guaranteed for a voltage
between 70% and 110% of the rated power supply voltage value Ue, both in AC & DC.

Frame Operational Voltage Power Consumption


DN0 / DN1 240 / 415V AC, 50Hz 1500VA
110 - 415V AC, 50Hz 1500VA
DN2 / DN3 /
110 / 220V DC 85W
DN3B / DN4
24V DC 10W
Accessories 47

UV Release
The Under-voltage release causes the MCCB to trip if the operational voltage falls to a value between 35% and 70%
of its rated voltage or not applied. UV release mechanically locks the closing mechanism of MCCB & makes it
impossible to close on under-voltage or no voltage, both manually & electrically. With the under-voltage release de-
energized, it is not possible to close the MCCB. UV release can also be used for interlocking schemes (for DG
synchronization, paralleling of transformers etc) also.

Frame Operational Voltage Power consumption


DN0 / DN1 240V AC, 50Hz 5VA
DN2 / DN3 / DN3B 240V AC, 50Hz 5VA
DN4 240V AC, 50Hz 5VA

External Accessories
Rotary Operating Mechanism
Rotary operating mechanism (ROM) for dsine MCCBs are available in
direct & extended versions.

1. Direct Rotary Handle (MCCB mounted)


• Available for entire family of dsine MCCBs
• In built pad locking feature

2. Extended Rotary Handle (Panel Mounted) Direct Rotary Handle


(MCCB mounted)
• ROM mounts directly on MCCB without removal of mid cover
• Clear ON/OFF/TRIP indication
• Clear view of MCCB rating label
• Direct access to “Push to Trip” button
• IP 54 degree of protection with
extended rotary handle
• Unique coupling to allow ±3mm tolerance
• Door interlock in ON position,
with defeat facility
• Door interlock in OFF condition
with padlock feature
• Auto restoration of door interlock Extended Panel Door Mounted
• External keylock for mechanical interlocking Rotary Handle: Key lock (To be used along
Panel Mounted with Extended Rotary Handles)

Mechanical Interlocking Schemes


1. Mechanical Interlocking Kit:
Two MCCBs can be interlocked using base plate mechanism, in
side-by-side configuration.
Features
Æ

• For 3P & 4P versions


• For DN2 & Dn3 frames
• Site fittable
MIL with Base Plate
48 Accessories

2. Mechanical Interlocking using Key Locks: Key Lock


I/C or B/C
For mechanical interlocking through extended 2 l/C Any 1 type of lock for both MCCBs
rotary operating mechanism, a panel mounted
2 I/C and 1 B/C Lock 1 and Lock 2 for I/C and Lock 12 for B/C
key lock is available. The selection of the key
lock as per the table: 3 I/C and 2 B/C Locks 1, 2, 3 for I/Cs and Locks 12, 23 for B/Cs

Key Lock Selection: I/C1 I/C2 I/C3

Type of lock Exclusively operable by key nos. Incommers


1 1 Lock 1 Lock 2 Lock 3 (I/C)
2 2
Bus couplers
3 3
Lock 12 Lock 23 (B/C)
12 1, 2 & 12
B/C1 B/C2
23 2, 3 & 23

Spreader Terminal
• Available for enhancing termination capacity
• Made of silver plated copper

Terminal capacity without spreader terminals


Rating (A) 16-100 125-250 320-630 800-1250
2 2 2 2
dsine Frame Cable (mm ) Link(mm) Cable (mm ) Link(mm) Cable (mm ) Link(mm) Cable (mm ) Link(mm)
DN0 35 17
DN1 120 26
DN2 95 25
DN3 120 27$
DN3B* 185 32
DN4 - 2 x 40

$ 30mm on request

Terminal capacity with spreader terminals


Rating (A) 16-100 125-250 320-630 800-1250
2 2 2
dsine Frame Cable (mm ) Link (mm) Cable (mm ) Link (mm) Cable (mm ) Link (mm) Cable (mm2) Link (mm)
DN0 50 22
DN1 185 35
DN2 185 35
DN3 2 x 240 2 x 40
DN3B* 2 x 240 2 x 40
DN4 2 x 300 2 x 60

* DN3B available in 320A and 400A only


Note: Phase barriers are supplied along with MCCBs ; Copper termination recommended for enhanced performance
Accessories 49

External Neutral CTs


• Used to provide neutral & earth fault protection to 3P MCCBs in 3 phase
4 wire system
• Available for 3P MCCBs with MTX2.0 & 3.0 releases
• Adapters for NCT available

Stored Energy Electrically Operated Mechanism


• ON / OFF & Charged/Discharged indication
• Foolproof mounting
• Selector switch for Auto/Manual operation
• Padlock facility for locking in OFF position (3 nos. locks)
• Higher mechanical & electrical endurance
• Back up fuse for extended motor protection
• Easy access to the protection setting on MCCB
• True indication for ON/OFF & Trip

Specification DN2 DN3 DN4


Operating voltage (V AC) 240V AC 240V AC 240V AC
Operating voltage (%) 85-110% 85-110% 85-110%
Closing time (ms) 60 90 100
Opening time (ms) 300 450 1000
Power consumption (VA) 350 500 400
Life / No. of operations 16000 15000 8000
Door cut out (mm2) 96 x 96 96 x 96 130 x 146
IP protection, on the front IP30 IP30 IP30
Operating frequency 2/min 1/min 1/min
Min. control impulse time (ms)* 800 800 800
Note: For wiring diagram, please refer page no. 62
* At rated voltage

Power Supply (PS) Module


PS module is used to power ON dsine MTX modules when auxiliary 24Vdc
supply is not available.

Specifications AC DC
Input 85-265V 125-300V
#
Output 1 - 200mA at 24V DC
Output 2 - 650mA at 24V DC
#
For using Output 1, Output 2 should be loaded

Æ
Current Metering Module for MTX2.0
It consists of 2 parts viz. Metering module & Display module. Metering module collects the data from the release and
sends the same to the Display module. The panel mounted O-LED Display module shows various parameters viz. 3
phase currents, neutral and ground fault currents, if any. We can also view last trip records.
50 Accessories

Communication Module for MTX3.0


Æ
The Communication module is solution for connecting dsine MCCBs to
Modbus network for remote supervision and control of circuit breaker. It
is suitable for the MTX3.0 electronic trip units across DN2/DN3/DN4
frames. It is available with DIN rail mounting facility. 2 LEDs in front of the
module indicates
• The Power LED - the presence of auxiliary power supply to
the module
• The Data LED - transmission of data
O O
Its operating temperature is -25 C to 70 C and consumption is 43mA

Æ
Voltage Module for MTX3.0
This accessory when connected to MTX 3.0 release in DN2/DN3/DN4
frames is able to provide the various measurements of the electrical values
of the plant like voltage, power, energy & frequency . It can be mounted
just beside the MCCB on a DIN plate. Its operating temperature is -25O C
O
to 70 C

Æ
Display Module for MTX3.0
It is a panel mounted O-LED display unit that can be integrated with
MTX3.0 release . It has one navigation key, a select button & an exit
button. Provision for taking D+, D- from this module is also provided.
You can simultaneously view parameters remotely & on display. Its
O O
operating temperature is -25 C to 70 C and consumption is 12mA

The module displays wide range of parameters as follows


• Phase current, ground current, earth leakage current
• Phase / Line voltage
• Active / Reactive / Apparent Power
• Power factor, Frequency
• Energy
• Maximum demand
• THD

Æ
MTX Test Kit
• Universal Test Kit for all MTX releases
• Simulation of overload, short-circuit & earth fault
• Single phase AC supply

MCCB Enclosure
Æ
New Range of MCCB enclosures, Size I suitable for DN0 frame and Size II for
DN1 frame. These standalone enclosures not only provides ample space for
cable termination but are also superior in aesthetics.
• Conforms to IEC 62208, IEC 62262 and IEC 60529
• Common Enclosure for 3P/4P MCCBs
• RoHS compliant
• IP30 Protection & IK08 Protection
• Inbuilt Neutral Link for TPN systems
• Mounting Holes on the back plate
• Louvers for better heat dissipation

Enclosure Height (mm) Width (mm) Depth (mm)


Size I 543 198 97
Size II 830 337 111.2

Note: For wiring diagram of modules, please refer page no. 63


Accessories 51

Earth Fault Module


Earth Fault Modules Type GF1, GF2 and GF11. These Features:
modules are to be used with MCCBs for earth fault
protection. The principle of operation is based on • Compact in size
detection of the residual current in the system. They • Solid state design
combine safety and versatility, conforming to the high
performance standards, the characteristic of all L&T • Built-in moulded CBCT for GF1 & GF2.
products. External CTs are to be used for GF11
• Suitable for both 3 phase 3 wire & 3 Phase 4
wire systems. In case of 3 phase 4 wire system,
the neutral cable/twisted link should also be
passed through the CBCT along with the 3
phase links / cables
• Built-in test facility
Earth Fault Module GF1 • Selection facility for nominal current rating (In)
GF1 is suitable upto 200A MCCBs
• Earth fault setting is adjustable from 10% to
50% of set current
• Selectable trip times (100 ms, 200 ms)
• Manual reset for positive fault
Earth Fault Module GF2 acknowledgment
GF2 is suitable upto 200A-400A MCCBs • Potential free NO contact to trip MCCB
(through 240 V shunt release)
• Window dimensions suitable for
Cable connection only in GF1 and GF2

Earth Fault Module GF11 Note: MCCBs need to be fitted with 110 V / 240 V AC shunt
GF11 is suitable upto 800A MCCBs release for Earth Fault Module operation.

Technical Data
Specification Type GF1 / GF2 / GF11
Current Setting Range, Is (Is=x In) 10% to 50%In in steps of 10%
Auxiliary Supply 240V AC ±20%
Time Delay (ms) 100 / 200ms Field selectable
Pick-up Accuracy ±10% Is
1 NO contact manual reset Type
Output Contact
contact rating 5A 240V AC
a) Power On LED
Indication b) Trip LED (manual reset)
Operating Temperature +10oC to +55oC
2 kV 50Hz for one minute across independent circuit
Insulation 1 kV 50Hz for one minute across open contacts
Mounting Base plate mounting type
GF1 - 110 x 32
Window for Cable / Busbar entry (mm2)
GF2 - 165 x 61.5
Weight (kg) GF1 - 1.2, GF2 - 2.2, GF11 - 0.9
Note: For wiring diagram, please refer page no. 61
Characteristic Curves
Thermal Magnetic Release
n 54
DN0
}
DN1
}
DN2
}
DN3B
}
DN3
}

Microprocessor Release
n 55
}M TX1.0-2.0 (O/L curves)
- I2T at 6Ir, 7.2Ir

MTX3.0 (O/L curves)


}
2
- I T at 1.5Ir, 6Ir, 7.2Ir
- I4T at 1.5Ir, 6Ir, 7.2Ir
- SI at 1.5Ir, 6Ir, 7.2Ir
- LI-VI at 1.5Ir, 6Ir, 7.2Ir
- Short circuit, Earth fault & Neutral
curves For MTX1.0-2.0-3.0
54 Characteristic Curves

Thermal-Magnetic Release

DN0 MCCB DN1 MCCB


10000 10000

1000 1000

100 100

10 10
Trip Time (s)

Trip Time (s)


1 1

9In 9In
0.1 0.1

t<10ms t<10ms
0.01 0.01

0.001 0.001
10-1 1 10 102 103 10-1 1 10 102 103
Current multiples (xIn) Current multiples (xIn)

DN2 MCCB DN3B MCCB DN3 MCCB


10000 10000 10000

1000 1000 1000

100 100 100

10 10
Trip Time (s)

Trip Time (s)


Trip Time (s)

10
6-10In
6-10In
1 9In
1 1

0.1 0.1 0.1

t<10ms t<10 ms t<10ms


0.01 0.01 0.01

0.001
0.001 0.001
10-1 1 10 102 103 10-1 1 10 102 103 10
-1
1 10 10
2 3
10
Current multiples (xIn) Current multiples (xIn) Current multiples (xIn)

Note: Curves are Ir based till overload zone.


Characteristic Curves 55

Microprocessor Release
2
MTX1.0 / 2.0 - DN2 / DN3 / DN4 (O/L curves - I t)

2 2
I T @ 6Ir I T @ 7.2Ir
10000 10000

1000 1000
Trip Time (s)

Trip Time (s)


100 100

10 10
10s
10s

3s
1 3s 1

0.1 0.1
1 10 1 10
Current multiples (xIr) Current multiples (xIr)

MTX3.0 - DN2 / DN3 / DN4 (O/L curves - I 2t)

I 2 T @ 1.5Ir I 2 T @ 6Ir I 2 T @ 7.2Ir


1000 10000 10000

100 1000 1000

10 100 100
Trip Time (s)

Trip Time (s)

Trip Time (s)

30s
1 10 30s 10 20s
30s
20s 10s
20s
10s
10s 5s
5s 3s
0.1 5s 1 3s 1
3s

0.01 0.1 0.1


1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)
56 Characteristic Curves

Microprocessor Release

4
MTX3.0 - DN2 / DN3 / DN4 (O/L curves - I t)
4 4 4
I T @ 1.5Ir I T @ 6Ir I T @7.2Ir
1000 100000 100000

10000 10000
100

1000 1000
10
Trip Time (s)

Trip Time (s)

Trip Time (s)


100 100

1
10 10 30s
30s 18s
30s
18s 18s 10s
0.1 10s 6s
10s 1 1
6s 3s
6s 3s
3s
0.01 0.1 0.1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)

MTX3.0 - DN2 / DN3 / DN4 (O/L curves - Short Inverse)

SI @1.5Ir SI @ 6Ir SI @ 7.2Ir


100 100 100

30s 30s
24s 24s
30s
Trip Time (s)
Trip Time (s)

Trip Time (s)

24s
12s 12s
10 10 10

12s

4s 4s

4s

1 1 1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)
Characteristic Curves 57

Microprocessor Release
MTX3.0 - DN2 / DN3 / DN4
(O/L curves - Long Inverse / Very Inverse)
LI-VI @ 1.5Ir LI-VI @ 6Ir LI-VI @ 7.2Ir
100 1000 1000

10 100 100
Trip Time (s)

Trip Time (s)

Trip Time (s)


30s
30s
24s 30s 24s
24s
1 12s 10 10
12s
12s

4s
4s
4s

0.1 1 1
1 10 1 10 1 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)

MTX1.0* / 2.0 / 3.0 (S/C, E/F & Neutral Curves)


Short Circuit Curves Earth Fault Curves Neutral Curves
1 1 1

400ms 500ms
300ms
Invs
OFF*
200ms 200ms 200ms
Trip Time (s)

Trip Time (s)

Trip Time (s)

0.1 100ms 0.1 100ms 0.1

Inst

0.01 0.01 0.01


1 1.5 8 10 0.1 0.2 0.5 1 0.1 0.5 11.5 10
Current multiples (xIr) Current multiples (xIr) Current multiples (xIr)

For MTX3.0 only For MTX3.0 only *: IDMT disable in case of MTX3.0

* Only Short Circuit setting available in MTX1.0


• Under Short Circuit fault conditions, MCCBs will clear the fault in less then 10 msec
Wiring Diagrams
n
Motorised Circuit Breakers Control 60
through AuXC - 2000
n
Earth Fault Modules 61
n
MTX2.0 with Current Metering Module 62
n
MTX3.0 with Communication 63
through Modbus
60 Wiring Diagrams

Control of Motorised Moulded Case Circuit Breakers


(Without Undervoltage Relay)
SOURCE 1 SOURCE 2

K2 K1

K1 K2

K1
K2
K1
K2

OUT 1

OUT 2
OUT1 - OUT7
B300 / 250V~ 8A AC1 / 1A 30V= PILOT DUTY
OUT 3

OUT 4

OUT 5

OUT 6

OUT 7
INP 1

INP 2

INP 3

INP 4

INP 5

INP 6

COM

OUT 3

OUT 4

OUT 5

OUT 6

OUT 7
INP 1

INP 2

INP 3

INP 4

INP 5

INP 6

COM

1 2 3 4 5 AUX TAC 1 2 3 4 5 AUX TAC

MCCB 1 MCCB 2
CONTROL CONNECTIONS CONTROL CONNECTIONS

Programming Connection Parameter Setting (Description)


Terminal code
Others - P05.07 Breaker pulse or breaker continuous
15(INP1) P10.01.01 Line 1 breaker closed (Feedback 1)
16(INP2) P10.02.01 Line 2 breaker closed (Feedback 2)
Inputs
17(INP3) P10.03.01 Line 1 circuit breaker protection (Trip 1)
18(INP4) P10.04.01 Line 2 circuit breaker protection (Trip 2)
25(OUT4) P11.04.01 Open line 1 contactor/circuit breaker
27(OUT5) P11.05.01 Close line 1 contactor/circuit breaker
Outputs
28(OUT6) P11.06.01 Open line 2 contactor/circuit breaker
30(OUT7) P11.07.01 Close line 2 contactor/circuit breaker
Wiring Diagrams 61

Earth Fault Modules

GF1 & GF2

FROM MCCB 240 Vac


R Y B N
SENSING
1
CIRCUIT MCCB
RELAY SHUNT
2 RELEASE

RECTIFIER
L
3
AUX.
SUPPLY
N
4 240 Vac
TO LOAD

GF11

FROM MCCB
240 Vac
R Y B N RELAY 1
MCCB
2 SHUNT
S1 RELEASE
SENSING
CIRCUIT
S2 5
S1
CT Sec.
S2 RECTIFIER L
3
S1 AUX
SUPPLY
S2
4 240 Vac
N
S1

S2

TO LOAD
62 Wiring Diagrams

MTX2.0 with Current Metering Module

Display Module

Metering
Module

MTX2.0 Release

Inst
to other
MTX2.0

24 Vdc 24 Vdc
+ - + -

Auxiliary
Power Supply
Module

L 240 Vac
50 Hz
N
Wiring Diagrams 63

MTX3.0 with Communication through Modbus


Display Module

Laptop / SCADA
System
D+ Convertor
D-
RS485 RS232
+Vs
Gnd

Communication
Module Voltage Module

MTX3.0 Release

Inst

3 Phase
415 Vac Supply

+ - + -
24 Vdc 24 Vdc

Auxiliary
Power Supply
Module

L 240 Vac
50 Hz
N
Dimensions
Dimensions of MCCB
n 66
DN0
}
DN1
}
DN2
}
DN3B
}
DN3
}
DN4
}

Dimensions of Accessory
n 72
Rotary Operating Mechanism
}
Stored Energy Electrically
}
Operated Mechanism
Panel Mounted Key Lock
}
Mechanical Interlock Kit
}
External Neutral CTs
}
MTX Modules
}
Auto Source Transfer Switch: AuXC-2000
}
Earth Fault Modules
}
Size I Enclosure for DN0 MCCB
}
Size II Enclosure for DN1 MCCB
}
66 Dimensions of MCCB

DN0-125 MCCB
86
64
60
20 2
75 (3P) MCCB MOUNTING HOLES
M3 SCREW 6 Nos.

32
25 25 25 12.5
10
25 25

50.5 50.5

61.5
25.5

58

48.5
13.5

52
75
2.25 27.25
116.4

17
112

130

112
46
39
N N CUT OUT 1

45
38
CUT OUT 2
29.5
76
101
25 25 25
32.2

100 (4P) Mounting &


Door Cut-out Details
2
20

DIN rail kit

DN0-125 with Spreader Links 86


64
60
Ø8.5 13 13 13 20 2
13 13
Ø9
11

11

32
28

28

10

61.5
58
13.5

75
17
172.2
194.2

172.2
194.2

N
45
38
30.2

32.2

2
22 22 20
35 35 35 35 35
92 127.2
DIN rail kit

Recommended cat. nos.


for DN0 spreaders
Current 3P 4P
upto 100A CM97785OOOO CM97921OOOO
125A CM90687OOLO CM90688OOLO
Note: • Spreaders are available as spare
• It is recommended to use spreader links for enhancing termination capacity
• Frame size is same for DN0 / DN0-SD / DN0-M
All dimensions are in mm
Dimensions of MCCB 67

DN1-250 MCCB

MCCB MOUNTING
HOLES 6 Nos.
105 (3P) 93.7
141
35 35 35 17.5 64.5
60
35 35
17.5 17.5

58.6
78.65
95.7

126
145
165
126

46
N
N

45
88 53

70.5 70.5

35 35 35 Mounting &
140 (4P) Door Cut-out Details

DN1-250 with Spreader Links 93.7


64.5
19 19 19 60
4
Ø10.2 18
Ø10.2 19.5 19.5
18
18

46
47.5
38

78.65
95.7
221
147

257
221
257

N
45

250A
47.5

46

35 4
54.5 54.5 35 18
144 54 54 54
197

Recommended cat. nos.


for DN1 spreaders
3P 4P
ST98053OOOO CM92007OOOO

Note: • Spreaders are available as spare


• It is recommended to use spreader links for enhancing termination capacity
• Frame size is same for DN1 / DN1-M All dimensions are in mm
68 Dimensions of MCCB

DN2-250 MCCB

105 (3P) MCCB


119.57 MOUNTING HOLES
35 35 35 17.5 M4 SCREW 6 Nos.
96.5
8 35 35

25.5 60.5

89.27
72.7

61
CUT OUT

157
163
157

179

46.5
N

45
86

35 35 35
140 (4P) Mounting &
Door Cut-out Details

DN2-250 with Spreader Links 119.57


96.5
19 19 19 28.65
19.5 19.5 4
Ø10.2 Ø10.2
18
18

48
38
38

89.27
72.7
239
275
239
275

N
45
41

48

35 35 4
54 54 54 A
54.5 54.5
144 197

Rating Dimension (A)


Recommended cat. nos. 125-250A TM 26
for DN2 spreaders
63-100A TM 25.5
3P 4P 32-50A TM 26.25
ST98053OOOO CM92007OOOO MTX breakers 28

Note: • Spreaders are available as spare


• It is recommended to use spreader links for enhancing termination capacity
• Frame size is same for DN2 / DN2-SD / DN2-M All dimensions are in mm
Dimensions of MCCB 69

DN3B-400 MCCB

MCCB
MOUNTING HOLES
M5 SCREW 6 Nos.
44.50 44.50
140
139.5 (3P) 115

52.50
44.5 44.5 44.5 25.25 110
38.25 82.75

CUT OUT

68
98

176
79
182
205
176

77
121

44.5 44.5 47.5


184 (4P)
Mounting &
Door Cut-out Details

DN3B-400 with Spreader Links


140
115
110
26.5
23.5 23.5 23 21.5 23 5
23

Ø10.5
23

Ø10.5
56.5
45
45

68
98
272

318
272
318

N
77
56.5

40 40 5
63.5 63.5 63 61.5 63 26.5
167 227.5

Recommended cat nos.


for DN3B spreaders
3P 4P
ST98065OOOO ST98066OOOO

Note: • Spreaders are available as spare


• It is recommended to use spreader links for enhancing termination capacity
• Frame size is same for DN3B / DN3B-SD All dimensions are in mm
70 Dimensions of MCCB

DN3-400/630 MCCB
180
143 MCCB MOUNTING HOLES
140 (3P) 120 M5 SCREW 6 Nos.
43,5 43,5 43,5 26,5 103 43,5 43,5

104

38.75

82.25
CUT OUT

82,7
224
234
266
224

77

78
N

121

43,5 43,5
Mounting &
183.5 (4P) Door Cut-out Details

DN3-400/630 with Spreader Links 180


143
120
103
22,5 22,5 22 20,5 22 A
23

23

Ø10.5 5
Ø10.5

F
C

104
D

D
E

77
N

F
40 40
62,5 62,5 62 60,5 62 B
165 224,5
Type DN3-400 DN3-630
Recommended cat nos. A 39 43
for DN3 spreaders B 37* 39#
Rating 3P 4P C 45 55
D 324 344
400A ST98065OOOO ST98066OOOO
E 370 390
630A ST98054OOOO CM92004OOOO
F 52 62

* 38 for MTX
# 38 for 500A TM

Note: • Spreaders are available as spare


• It is recommended to use spreader links for enhancing termination capacity All dimensions are in mm
• Frame size is same for DN3 / DN3-SD / DN3-M
Dimensions of MCCB 71

DN4-800/1000/1250 MCCB
MCCB
210 (3P)
197 MOUNTING HOLES
68 68 68 143 M5 SCREW 6 Nos.
68 68

132.5

109.5
57 125

198.5
105

107
330
370
326

326
N
CUT OUT
182

24
71 68 68 71
Mounting &
180
Door Cut-out Details
278 (4P)

DN4-800/1000/1250 with Spreader Links

Ø12.5 A A Ø12.5 143


A A A
Y
15
D D
C

85

132.5
105
370
510

N
85
15

60 24 60 24 46
B B 198

3P Frame 4P Frame
3/4P Frame
Type A B C D Type A B C D
Type Y
800A 98 256 6 38 800A 88 324 6 28
N version 46
1000A 98 256 12 38 1000A 88 324 12 28
S version 42
1250A 86 232 20 26 1250A 80 300 20 20

Recommended cat nos. for DN4 spreaders


Rating 3P 4P
800A CM91161OOUO ST90362OOOO
1000A CM91161OOVO CM90064OOVO
1250A CM91161OOAO ST98058OOOO

Note: • Spreaders are available as spare


• It is recommended to use spreader links for enhancing termination capacity All dimensions are in mm
• Frame size is same for DN4 / DN4-SD
72 Dimensions of Accessories

Rotary Operating Mechanism (ROM)


Direct ROM Door Cut-out Detail

L5

L4
L3
N

L2

L1 68
Mounting &
Door Cut-out Details

L1 = Mounting Depth Type L1 L2 L3 L4 L5


L2/L3 = Panel Cut-out DN0 96.5 58 52 43.5 37
L4/L5 = Breaker Mounting Refer DN1 96.5 73 52 56.5 54
DN2 122 96 63 53 66
DN3 146 121 87 78 82
DN3B 146 121 87 49 82.5

Extended ROM Door Cut-out Detail

L2 Ø51
450 Ø76
L3

N Ø4

L1=Minimum Panel Depth suggested 68


Mounting & Door Cut-out Details

Type L1 L L2 L3
DN0 169 L1 - 119 7.5 69.5
L
DN1 169 L1 - 119 24.5 81.7
DN2 202 L1 - 152 27 84
L = Length of Shaft Required DN3 233 L1 - 183 39 122
for Panel Depth L1 DN3B 233 L1 - 183 39 92
Total Length of Shaft =275mm DN4 302 L1 - 252 69 170

All dimensions are in mm


Dimensions of Accessories 73

MCCB with Stored Energy Electrically


Operated Mechanism (SE-EOM)
DN2
245.5
35 Door
237.5

18.7
= =

Door
Cut-out

94
157

N ON TRIP

T
156

= =
94

DN3 264
Mounting 43.5
holes for MCCB 256
= =

Door
62.1

45 49
94

Door
Cut-out
224

94

N ON TRIP

Panel Mounted Key Lock


Type 1 / 2 / 3 / 12 / 23
72 48.5
2 Holes, Ø4.2
Ø76
Ø50
Ø50
450

Cut-out for
136

Handle Assembly
68
68

12

Cut-out for
Panel Mounted Key Lock Ø29
2.2

58 52
Mounting &
Door Cut-out Details
Note: Panel Mounted key lock can be used only with extended ROM All dimensions are in mm
74 Dimensions of Accessories

Mechanical Interlocking Kit

DN2

372
Ø10 Mounting Holes
41.5 141 141
35
10

149

209
239

177
141 141 Holes for Breaker Mounting

Mounting Details

DN3

Ø10 Mounting Holes 180


436
161 161 56

152
21
55
316

266
346

446

161 161 Holes for Breaker Mounting

All dimensions are in mm


Dimensions of Accessories 75

External Neutral CTs

DN2/DN3
K
L

B
C
D

G
H
J

Bottom Bottom
Side Side

ØF

Frame A B C D E F
DN2 250A 93 59 47 81 35 10.2
Adaptor Terminal
DN3 400A 93.5 58 46 81.5 40 13
DN3 630A 93.5 58 46 81.5 40 10.5

ON
TRIP
Frame G H J K L M OFF
DN2 250A 77 153 189 26 4 55 Bottom
Side
DN3 400A 63.5 153.5 199.5 39 5 60
DN3 630A 63.5 173.5 219.5 39 5 60

Note: • Adaptor Terminals shown are not available with product >M
• Kindly refer accessories data for ordering separately
• Circuit Breaker shown for reference only All dimensions are in mm
76 Dimensions of Accessories

External Neutral CTs

DN4
M P
H

G
K
D
A

Bottom Bottom
Side Side

ØF
E

DN4 A B C D E F G
800A 132 88.5 73.5 117 60 12.5 92
1000A 132 88.5 73.5 117 60 12.5 92
1250A 132 88.5 73.5 117 60 12.5 92

DN4 H J K L M P

800A 24 302 272 80 47 6


Bottom
Side
1000A 24 302 272 80 47 12
1250A 24 302 272 80 47 20

Note: • Adaptor Terminals shown are not available with product


• Kindly refer accessories data for ordering separately
• Circuit Breaker shown for reference only
>L
Special Note: • Adaptor Terminals for DN4 range of product are not symmetrical.
• Kindly ensure proper orientation in assembly as shown in figure. All dimensions are in mm
Dimensions of Accessories 77

MTX Modules
Display Module
36

44.5
51
10
96

44.5

91.5

91.5

Door Cut-out Details

Voltage/Communication/Metering Module
3

73.3

73.3
81

87
3

23
14.3 60
Door Cut-out
23 65
Details

All dimensions are in mm


78 Dimensions of Accessories

Auto Source Transfer Switch:


AuXC-1000 and AuXC-2000
144 43.30 10 138

144

138
35

Earth Fault Modules - GF1, GF2, GF11


Terminal Block

8.5 274.5 60

24 110
108

105.5
Cable / Busbar entry

71.5

71.5
Cable / Busbar entry (165 mm x 61.5 mm)
32

(110 mm x 32 mm)

5
20

175 15 54
158 50
USE M6 SCREW 30
195

74
96
30

Terminal
Block 90 90
= =
175
USE M4 SCREW
Terminal Block
GF2
GF1
108

158 50

195
Terminals for external CT
secondary connection
30

175
USE M4 SCREW

GF11 All dimensions are in mm


Dimensions of Accessories 79

Size I Enclosure for DN0 MCCB


73.7 26.4
198
58

186.5
197.5
222.6

543
179.5
178.3
58

91
110
97

Size II Enclosure for DN1 MCCB

118.1 67.9
337
84

289.2
301.8
348.8

830
322.2
295.8
84

150 106.2
111.2
All dimensions are in mm
80 Notes
Notes 81
82 Notes
Aimed at maximizing productivity, conserving energy, minimizing costs and enhancing safety, our
Electrical & Automation training programmes have benefitted over 1.35 Lakh professionals in the
last 28 years. These training programmes are highly beneficial as they provide right exposure and
impart knowledge on selection, installation, maintenance and testing of Electrical & Automation
Products.

So gain the advantage and go the extra mile with:


— 22 courses on contemporary topics
— Courses applicable to all switchgear brands
— Training Centers in Pune, Lucknow, Coonoor, Vadodara, Delhi & Kolkata
— Blend of theory and practical experience

The typical training programmes cover:


— Low Voltage & Medium Voltage Switchgear
— Switchboard Electrical Design
— AC Drives & Building Management Solutions
— Protective Relays, Earthing, Reactive Power Management & Harmonics
— Energy Conservation & Management

Please contact any of the training centres for participation and detailed training programme schedule.

Pune Lucknow Coonoor


Larsen & Toubro Limited Larsen & Toubro Limited Larsen & Toubro Limited
Switchgear Training Centre, Switchgear Training Centre, Switchgear Training Centre,
T-156/157, MIDC C - 6 & 7, UPSIDC Ooty-Coonoor Main Road
Bhosari, Pune - 411 026 P. O. Sarojininagar, Yellanahalli P.O.,
Tel: 020 2712 0037 / 2712 0653 Lucknow - 226 008 The Nilgiris - 643 243
Fax: 020 2712 2933 Tel: 0522 247 6015 / 97944 54455 Tel. : 0423 251 7107
E-mail: [email protected] Fax: 0522 247 6015 Fax : 0423 251 7158
E-mail: [email protected] E-mail: [email protected]

Vadodara Delhi Kolkata


Larsen & Toubro Limited Larsen & Toubro Ltd Larsen & Toubro Limited
Switchgear Training Centre Switchgear Training Centre Switchgear Training Centre
Behind L&T Knowledge City, 32, Shivaji Marg, 4th Floor, 3B, Shakespeare Sarani,
Near Village Ankhol, Near Motinagar Metro Station, Kolkata - 700071
Vadodara - 390019 New Delhi - 110015 Tel: 033 42005975 / 42005978
Tel: 0265 2457805 Tel: 011 41419515 / 41419695 / 41419500 E-mail: [email protected]
E-mail: [email protected] Fax: 011 41419600
E-mail: [email protected]
SP 50584 R9