Motor Protection Circuit Breakers

About us

Larsen & Toubro infuses engineering with imagination. The Company offers a wide range of advanced solutions in the field of Engineering, Construction, Electrical & Automation, Machinery and Information Technology. L&T Switchgear, a part of the Electrical & Automation business, is India's largest manufacturer of low voltage switchgear, with the scale, sophistication and range to meet global benchmarks. With over five decades of experience in this field, the Company today enjoys a leadership position in the Indian market with a growing international presence. It offers a complete range of products including powergear, controlgear, industrial automation, building electricals & automation, reactive power management, energy meters, and protective relays. These products conform to Indian and International Standards.

Switchgear Factory, Mumbai

Switchgear Factory, Ahmednagar

Product Range
L&T introduces complete range of Supernova products covering Motor Protection Circuit Breakers, Contactors / Thermal Overload Relays & Motors.

Motor Protection Circuit Breakers


The new range of MPCBs is meant for protection against short circuit & overload.

MO Contactors & RTO Thermal Overload Relays

Motors

The latest range of Contactors & Thermal Overload Relays, rated from 9A to 110A.

L&T offers higher efficiency 3 phase LT motors, synonymous with ruggedness and reliability, suitable for all industrial applications upto 400 kW.

Motor Protection Circuit Breakers

Functions
Moulded Case Circuit Breaker and Thermal Overload Relay functions integrated into a highly compact unit known as Motor Protection Circuit Breaker.

Circuit Breaker Functions


Short circuit protection Overcurrent protection l protection Line
l l

Thermal Overload Relay Functions


Overload protection l Phase loss protection l Rated current adjustment Ambient temperature compensation l
l

}
/

MPCB - Advantages
Compactness l Breaking Capacity High l circuit protective coordination Short l Reduction in wiring work l Ecological design standards
l

Selecting the Appropriate Model


Procedure for selecting the appropriate model:
Confirm the motor's full load current

Three-phase load

Single-phase load
For applications in a single-phase circuit, connect the 3-pole in series

Select the rated current of MPCB

Select the branch circuit cable & confirm the control panel specifications

Confirm the short-circuit current of the circuit

Select the operating characteristics


Same characteristics as desired for a standard thermal overload relay Long-time operating type or quick operating type thermal overload relay desired

Adjustable thermal magnetic trip type MPCB

Instantaneous trip type MPCB


3

Typical Problem in the Conventional System and their Solution by using MPCB
Short-Circuit Breaking Capacity
When numerous small and medium motor loads exist in a circuit requiring high breaking capacity, there is no high breaking capacity circuit breaker with a small rated current for a short circuit protection. The MPCB can be used in 100kA short circuit current circuits for three-phase, 240V motors with rated capacity upto 15kW, and in 50kA short circuit current circuits for three phase, 415V motors with rated capacity up to 30kW.

Back-up breaking system


When back-up MCCB is installed upstream to solve the problem described in Shortcircuit breaking protection above, a short in one of the load circuits also trips the upstream breaker and stops the other operating circuits. Despite their compact size, the MPCB provides high-performance short-circuit current breaking. They eliminate the need for an upstream circuit breaker for back-up use.

Overload Protection
Motor Protection breakers cannot be adjusted to match the rated current of the motor being protected. Equipped with a wide range current adjustment dial (with maximum/minimum ratio of 1.4 to 1.6), the MPCB easily adjusts to match the rated current of the motor, for optimum protection.

Control Panel Size


Considerable space is required to install a back-up circuit breaker or a combination starter consisting of a circuit breaker and a thermal overload relay. As a result, the panel size has to be increased. The compact size of the MPCB, including overload relay functions, enables a smaller installation area with less wiring space, for a reduction in panel size.

Technical Specifications

Type Standards Handle type Number of poles Frame size available (up to A) Rated insulation voltage (Ui) Rated operational voltage (Ue) Rated impulse withstand voltage (Uimp) Rated frequency Class of protection Utilization Category (IEC947 - 4 - 1 / 947 - 2) Maximum motor capacity AC3 AC3 Electrical/Mechanical endurance Tripping device Ambient temperature compensation Overload, Phase loss protection Trip Indicator Test Trip Function Instantaneous release Terminal type Wire size Product weight (Kg) Dimensions (mm) W x H x D Relative humidity Standard service condition Operation altitude Solid/Stranded Without/With end sleeve

MOG - S1 IEC60947 -1, -2, -4 -1 Rocker 3 13A AC690V AC200 - 690V 6KV AC50 / 60Hz 10 AC - 3 / Cat. A 7.5 kW (at 200 - 240V), 15 kW (at 380 - 440V) 100000 (32A:70000) / 100000 (32A:70000), (25cycles / hour) Thermal - Magnetic -20C ~ + 60C yes (according to IEC60947 - 4 - 1) Yes Yes 13 X Ie max. Screw terminal, M4 slotted 1 - 10mm2 x 1 / 18 - 8 AWG x 1 1 - 6mm2 x 2 / 18 - 10 AWG x 2 0.35 45 x 90 x 66 45 ~ 85%Rh Up to 2000m No dew formation or freezing due to rapid temperature change allowed

MOG - H1 IEC60947 -1, -2, -4 -1 Rotary 3 32A AC690V AC200 - 690V 6KV AC50 / 60Hz 10 AC - 3 / Cat. A 7.5 kW (at 200 - 240V), 15 kW (at 380 - 440V) 100000 (32A:70000) / 100000 (32A:70000), (25cycles / hour) Thermal - Magnetic -20C ~ + 60C yes (according to IEC60947 - 4 - 1) Yes Yes 13 x Ie max. Screw terminal, M4 slotted 1 - 10mm2 x 1 / 18 - 8 AWG x 1 1 - 6mm2 x 2 / 18 - 10 AWG x 2 0.35 45 x 90 x 66 45 ~ 85% Rh Up to 2000m No dew formation or freezing due to rapid temperature change allowed

MOG - H2 IEC60947 -1, -2, -4 -1 Rotary 3 63A AC1000V AC200 - 690V 8KV AC50 / 60Hz 10 AC - 3 / Cat. A 15 kW (at 200 - 240V), 30 kW (at 380 - 440V) 25000 / 50000, (25cycles / hour) Thermal - Magnetic -20C ~ + 60C yes (according to IEC60947 - 4 - 1) Yes Yes 13 x Ie max. Box terminal, M6 slotted 1 - 25mm2 x 1 / 18 - 4 AWG x 1 1 - 16mm2 x 2 / 18 - 4 AWG x 2 0.78 55 x 110 x 96 45 ~ 85% Rh Up to 2000m No dew formation or freezing due to rapid temperature change allowed

MOG - H1M IEC60947 -1, -2, -4 -1 Rotary 3 32A AC690V AC200 - 690V 6KV AC50 / 60Hz 10 AC - 3 / Cat. A 7.5 kW (at 200 - 240V), 15 kW (at 380 - 440V) 100000 (32A:70000) / 100000 (32A:70000), (25cycles / hour) Magnetic -20C ~ + 60C None Yes Yes 13 x Ie max. Screw terminal, M4 slotted 1 - 10mm2 x 1 / 18 - 8 AWG x 1 1 - 6mm2 x 2 / 18 - 10 AWG x 2 0.37 45 x 90 x 79 45 ~ 85% Rh Up to 2000m No dew formation or freezing due to rapid temperature change allowed

MOG - H2M IEC60947-1, -2, -4 -1 Rotary 3 63A AC1000V AC200 - 690V 8KV AC50 / 60Hz 10 AC - 3 / Cat. A 15 kW (at 200 - 240V), 30 kW (at 380 - 440V) 25000 / 50000, (25cycles / hour) Magnetic -20C ~ + 60C None Yes Yes 13 x Ie max. Box terminal, M6 slotted 1 - 25mm2 x 1 / 18 - 4 AWG x 1 1 - 16mm2 x 2 / 18 - 4 AWG x 2 0.78 55 x 110 x 96 45 ~ 85% Rh Up to 2000m No dew formation or freezing due to rapid temperature change allowed

Atmosphere having no excess Vapour, Steam, Dust, Atmosphere Corrosive gas, Salt, Flammable gas

Atmosphere having no excess Vapour, Steam, Dust, Corrosive gas, Salt, Flammable gas

Atmosphere having no excess Vapour, Steam, Dust, Corrosive gas, Salt, Flammable gas

Atmosphere having no excess Vapour, Steam, Dust, Corrosive gas, Salt, Flammable gas

Atmosphere having no excess Vapour, Steam, Dust, Corrosive gas, Salt, Flammable gas

Breaking Capacity at Different Voltages


MOG - S1
AC240V AC415V AC460V Rating Ie (A) AC230V AC400V AC440V Icu (A) 0016 0025 0040 0063 0100 0160 0250 0400 0630 1000 1300 0.1 - 0.16 0.16 - 0.25 0.25 - 0.4 0.4 - 0.63 0.63 - 1 1 - 1.6 1.6 - 2.5 2.5 - 4 4 - 6.3 6.3 - 10 9 - 13 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 50 100 100 100 100 100 100 100 100 50 15 10 100 100 100 100 100 100 100 100 50 10 6 100 100 100 100 100 100 3 3 3 3 3 AC500V AC690V AC600V

MOG - H1
AC240V AC415V AC460V Rating Ie (A) AC230V AC400V AC440V Icu (A) 0016 0025 0040 0063 0100 0160 0250 0400 0630 1000 1300 1600 2000 2500 3200 0.1 - 0.16 0.16 - 0.25 0.25 - 0.4 0.4 - 0.63 0.63 - 1 1 - 1.6 1.6 - 2.5 2.5 - 4 4 - 6.3 6.3 - 10 9 - 13 11 - 16 14 - 20 19 - 25 24 - 32 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 50 50 50 50 100 100 100 100 100 100 100 100 100 50 50 35 35 35 35 100 100 100 100 100 100 100 100 100 50 42 10 10 10 10 100 100 100 100 100 100 8 8 6 6 6 4 4 4 4 AC500V AC690V AC600V

MOG - H1M
AC240V AC415V AC460V Rating In (A) AC230V AC400V AC440V Icu (A) 0016 0025 0040 0063 0100 0160 0250 0400 0630 1000 1300 1600 2000 2500 3200 0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 10 13 16 20 25 32 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 50 50 50 50 100 100 100 100 100 100 100 100 100 50 50 35 35 35 35 100 100 100 100 100 100 100 100 100 50 42 10 10 10 10 100 100 100 100 100 100 8 8 6 6 6 4 4 4 4 AC500V AC690V AC600V

MOG - H2
AC240V AC415V AC460V Rating Ie (A) AC230V AC400V AC440V Icu (A) 3200 4000 5000 6300 24 - 32 28 - 40 35 - 50 45 - 63 100 100 100 100 50 50 50 50 35 35 35 35 10 10 10 10 5 5 5 5 AC500V AC690V AC600V

MOG - H2M
AC240V AC415V AC460V Rating In (A) AC230V AC400V AC440V Icu (A) 3200 4000 5000 6300 32 40 50 63 100 100 100 100 50 50 50 50 35 35 35 35 10 10 10 10 5 5 5 5 AC500V AC690V AC600V

Ordering Information
Thermal & Magnetic Trip - Rocker Type
Frame size (mm) Rating (A) 0.16A 0.25A 0.4A 0.63A 1.0A 1.6A 2.5A 4.A 6.3A 10.0A 13.0A Motor Rating at 415V, 50Hz (kW) 0.09 0.12 0.25 0.55 0.75 1.50 2.20 4.00 5.40 Type Designation Thermal Release Range (A) 0.1 - 0.16A 0.16 - 0.25A 0.25 - 0.4A 0.4 - 0.63A 0.63 -1.0A 1.0 - 1.6A 1.6 - 2.5A 2.5 - 4A 4.0 - 6.3A 6.3 - 10.0A 9.0 - 13.0A Cat. Nos. ST41889OOOO ST41890OOOO ST41891OOOO ST41892OOOO ST41893OOOO ST41894OOOO ST41895OOOO ST41896OOOO ST41897OOOO ST41898OOOO ST41899OOOO Breaking Capacity

45mm

MOG - S1

100kA

50kA

Thermal & Magnetic Trip - Rotary Type


Frame size (mm) Rating (A) 0.16A 0.25A 0.4A 0.63A 1.0A 1.6A 2.5A 4.0A 6.3A 10.0A 13.0A 16.0A 20.0A 25.0A 32.0A 32.0A 40.0A 50.0A 63.0A Motor Rating at 415V, 50Hz (kW) 0.09 0.12 0.25 0.55 0.75 1.50 2.20 4.00 5.40 7.50 9.00 12.50 15.00 15.00 20.00 25.00 34.00 Type Designation Thermal Release Range (A) 0.1 - 0.16A 0.16 - 0.25A 0.25 - 0.4A 0.4 - 0.63A 0.63 - 1.0A 1.0 - 1.6A 1.6 - 2.5A 2.5 - 4.0A 4.0 - 6.3A 6.3 - 10.0A 9.0 - 13.0A 11.0 - 16.0A 14.0 - 20.0A 19.0 - 25.0A 24.0 - 32.0A 24.0 - 32.0A 28.0 - 40.0A 35.0 - 50.0A 45.0 - 63.0A Cat. Nos. ST41904OOOO ST41905OOOO ST41906OOOO ST41907OOOO ST41908OOOO ST41909OOOO ST41910OOOO ST41911OOOO ST41912OOOO ST41913OOOO ST41914OOOO ST41915OOOO ST41916OOOO ST41917OOOO ST41918OOOO ST41919OOOO ST41920OOOO ST41921OOOO ST41922OOOO Breaking Capacity

100kA

45mm

MOG - H1

50kA

55mm

MOG - H2

Instantaneous Trip - Rotary Type


Frame size (mm) Rating (A) 0.16 0.25A 0.4A 0.63A 1.0A 1.6A 2.5A 4.0A 6.3A 10.0A 13.0A 16.0A 20.0A 25.0A 32.0A 32.0A 40.0A 50.0A 63.0A Motor Rating at 415V, 50Hz (kW) 0.09 0.12 0.25 0.55 0.75 1.50 2.20 4.00 5.40 7.50 9.00 12.50 15.00 15.00 20.00 25.00 34.00 Type Designation Instantaneous Trip Current 2.1 3.3 5.2 8.2 13 20.8 32.5 52 81.9 130 169 208 260 328 416 416 520 650 819 Cat. Nos. ST41923OOOO ST41924OOOO ST41925OOOO ST41926OOOO ST41927OOOO ST41928OOOO ST41929OOOO ST41930OOOO ST41931OOOO ST41932OOOO ST41933OOOO ST41934OOOO ST41935OOOO ST41936OOOO ST41937OOOO ST41938OOOO ST41939OOOO ST41940OOOO ST41941OOOO Breaking Capacity

100kA

45mm

MOG - H1M

50kA

55mm

MOG - H2M

Accessories
Features
l

All accessories can be used with MOG S1 (45mm wide), MOG H1 (45mm wide) and MOG H2 (55mm wide) frames l Shunt trip and undervoltage trip devices are available in a wide range of operating voltages l terminal cover prevents accidental contact to electrically charged parts IP20

Auxiliary contact blocks : MOG-AXF, MOG-AXL


These blocks are linked to the ON/OFF operation of the MPCB. Up to two contact blocks can be mounted to the right/left front and up to two contact blocks can be mounted to the left side.

Alarm contact blocks : MOG-TAF


This block operates when the MPCB trips due to overload, phase-loss, or short-circuit. It is not linked to the ON/OFF operation of the MPCB. Note : Operation can be checked with the test trip function.

Auxiliary and alarm contact blocks : MOG-ATL


This contact block combines auxiliary contact and alarm contact that operate in the event of an overload, phase loss, or short-circuit. Alarm contact is not linked to the ON/OFF operation of the MPCB l An alarm is displayed in the contact blocks indicator when the alarm contact operates
l

Note : Operation can be checked with the test trip function.

Short-circuit alarm contact block : MOG-SAL


The contacts operate only when the MPCB has tripped due to a short-circuit When these contacts operate, the blue reset button extends out, and a trip indication is displayed l power to the MPCB can be turned ON after pressing the reset button The
l l

Note : Operation can not be checked with the test trip function. Be sure to press the reset button before mounting to the MPCB.

Shunt trip devices : MOG-ST


This device is used to remotely trip the MPCB. Notes: l device cannot be used together with an undervoltage trip device This l When the MPCB trips with the shunt trip device, press the reset button before turning ON the power

Accessories
Undervoltage trip devices : MOG-UV
This device automatically trips the MPCB when the control circuit voltage drops below the specified value. Notes:
l l

This device cannot be used together with a shunt trip device When the MPCB has been tripped with the undervoltage trip device, press the reset button before turning ON the power

External operating handles : MOG-EH


To operate the MPCB without opening the panel door l Equipped with an interlock mechanism that prevents someone from opening the panel door when the MPCB is in the ON state l shaft can be cut to match the distance between the MPCB and the panel door The l interlock function Door l lock function OFF Note: Padlocks not included. l Release screw allows the door to be opened with the handle in the ON position l enclosure IP54
l

Ratings of accessories
Accessory type Part number Standard 48V.AC AC-15 125V AC 230V AC 400V AC Rated operational 500V AC current (A) 690V AC 48V DC DC-13 110V DC 220V DC Min. voltage and current Auxiliary contact block/front MOG-AXF 5 3 1.5 1.38 0.55 0.27 Auxiliary contact block/side MOG-AXL 6 4 4 2.2 1.5 0.6 5 1.3 0.5 Alarm contact block MOG-TAF IEC 60947-5-1 5 3 1.5 1.38 0.55 0.27 17V, 5mA Aux. and alarm contact block MOG-ATL 6 4 4 2.2 1.5 0.6 5 1.3 0.5 Short-circuit alarm contact block MOG-SAL 6 4 4 2.2 1.5 0.6 5 1.3 0.5

Accessory type Standard Rated insulation voltage (V AC) No. of ON-OFF operations Operating time (ms) Power consumption Voltage range Time rating of coil (s)
Note: Ue: Rated Voltage

Shunt trip device MOG-ST IEC 60947-1 690 5000 20 21/12 8/1.2 0.7 to 1.1Ue AC: Continuous DC: 5

Undervoltage device MOG-UV

Inrush (VA/W) Sealed (VA/W) Tripping voltage (V) Closing voltage (V)

0.35 to 0.7Ue 0.85 to 1.1Ue AC: Continuous

10

Selection Chart
Fuseless Protection for DOL Starter Feeders with MPCB MOG-H1M/H2M, MO Contactor and RTO1 Overload Relay Type '2' Co-ordination, Iq=50 kA at 415V, 3, 50 Hz as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec. 1), EN 60947-4-1
The selection is valid only for complete L&T combinations i.e. MPCB + Relay + Contactor In any case if this combination is changed to accommodate another brand / rating of MPCB etc. it shall be the responsibility of the person making such a change to assure type 2 performance Selection is for normal starting conditions with starting time l
l l

According to Type 2 Co-ordination, Iq=50kA at 415V, 3, 50Hz


Motor Rating: 3, 415V, 50Hz Sr. No. hp 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 0.125 0.16 0.2 0.25 0.33 0.5 0.75 1 1.5 1.75 2 2.5 3 4 5 5.5 6 7.5 10 12.5 15 17.5 20 25 30 35 kW 0.09 0.12 0.15 0.19 0.25 0.37 0.55 0.75 1.1 1.3 1.5 1.8 2.25 3 3.7 4 4.5 5.5 7.5 9.3 11 13 15 18.6 22.5 26 FLC, In (A 0.4 0.45 0.57 0.75 0.88 1.2 1.6 2.1 2.7 3 3.5 4.8 5 6.4 7.9 8.5 9 11.2 14.8 19 22 24 29 35 40 47 Contactor Type MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 12 MO 12 MO 18 MO 25 MO 25 MO 32 MO 32 MO 40 MO 40 MO 50 Overload Relay Type RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 RTO1 MN 5 Range (A) 0.3 - 0.45 0.3 - 0.45 0.45 - 0.67 0.67 - 1.0 0.67 - 1.0 1.0 - 1.5 1.2 - 2.1 1.8 - 2.7 2.4 - 3.6 2.4 - 3.6 3.5 - 5.0 3.5 - 5.0 4.0 - 6.0 6.3 - 9.0 6.3 - 9.0 6.3 - 9.0 8.5 - 12.5 8.5 - 12.5 12.5 - 18 17 - 24 17 - 24 22- 32 22 - 32 30 - 40 35 - 45 30 - 50 Type MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H2M MOG-H2M MOG-H2M MOG-H2M MPCB Rating 0.63 0.63 1 1 1.6 1.6 2.5 2.5 4 4 6.3 6.3 6.3 10 10 10 13 16 20 25 32 32 40 50 50 63

11

Selection Chart
Fuseless Protection for DOL Starter Feeders with MPCB MOG-S1/H1/H2 and MO Contactor Type '2' Co-ordination, Iq=50 kA at 415V, 3, 50 Hz as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec. 1), EN 60947-4-1
Motor Rating: 3, 415V, 50Hz Sr. No. hp 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 0.125 0.16 0.2 0.25 0.33 0.5 0.75 1 1.5 1.75 2 2.5 3 4 5 5.5 6 7.5 10 12.5 15 17.5 20 25 30 35 kW 0.09 0.12 0.15 0.19 0.25 0.37 0.55 0.75 1.10 1.30 1.50 1.80 2.25 3.00 3.70 4.00 4.50 5.50 7.50 9.30 11.00 13.00 15.00 18.60 22.50 26.00 FLC, In (A 0.40 0.45 0.57 0.75 0.90 1.20 1.60 2.10 2.70 3.00 3.50 4.80 5.00 6.40 7.90 8.50 9.00 11.20 14.80 19.00 22.00 24.00 29.00 35.00 40.00 47.00 Contactor Type MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 9 MO 12 MO 12 MO 18 MO 25 MO 25 MO 32 MO 32 MO 40 MO 40 MO 50 Overload Relay Type Range (A) Type MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-H1 MOG-H1 MOG-H1 MOG-H1 MOG-H1 MOG-H2 MOG-H2 MOG-H2 MOG-H2 MPCB Rating 0.4 - 0.63 0.4 - 0.63 0.63 - 1 0.63 - 1 1 - 1.6 1 - 1.6 1.6 - 2.5 1.6 - 2.5 2.5 - 4 2.5 - 4 4 - 6.3 4 - 6.3 4 - 6.3 6.3 - 10 6.3 - 10 6.3 - 10 9 - 13 11 - 16 14 - 20 19 - 25 24 - 32 24 - 32 28 - 40 35 - 50 35 - 50 45 - 63

12

Selection Chart
Fuseless Protection for DOL Starter Feeders with MPCB MOG-S1/H1/H2 and MNX Contactor Type '2' Co-ordination, Iq=50 kA at 415V, 3, 50 Hz as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec. 1), EN 60947-4-1
Motor Rating: 3, 415V, 50Hz Sr. No. hp 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 0.125 0.16 0.2 0.25 0.33 0.5 0.75 1 1.5 1.75 2 2.5 3 4 5 6 7.5 10 12.5 15 17.5 20 25 30 35 45 kW 0.09 0.12 0.15 0.19 0.25 0.37 0.55 0.75 1.1 1.3 1.5 1.8 2.25 3 3.7 4.5 5.5 7.5 9.3 11 13 15 18.6 22.5 26 33.5 FLC, In (A 0.4 0.45 0.57 0.75 0.88 1.2 1.6 2.1 2.7 3 3.5 4.8 5 6.4 7.9 9 11.2 14.8 19 22 24 29 35 40 47 60 Contactor Type MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX12 MNX 12 MNX 12 MNX 12 MNX 12 MNX 12 MNX 12 MNX 12 MNX 12 MNX 12 MNX 18 MNX 25 MNX 25 MNX 32 MNX40 MNX 40 MNX 45 MNX70 MNX 80 Overload Relay Type Range (A) Type MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-S1/MOG-H1 MOG-H1 MOG-H1 MOG-H1 MOG-H1 MOG-H1 MOG-H2 MOG-H2 MOG-H2 MOG-H2 MPCB Rating 0.25 - 0.4 0.4 - 0.63 0.4 - 0.63 0.63 - 1 0.63 - 1 1 - 1.6 1 - 1.6 1.6 - 2.5 2.5 - 4 2.5 - 4 2.5 - 4 4 - 6.3 4 - 6.3 6.3 - 10 6.3 - 10 6.3 - 10 9 - 13 11 - 16 14 - 20 19 - 25 19 - 25 24 - 32 28 - 40 28 - 40 35 - 50 45 - 63

13

Selection Chart
Fuseless Protection for DOL Starter Feeders with MPCB MOG-H1M/H2M , MNX Contactor and MN 2 Overload Relay Type '2' Co-ordination, Iq=50 kA at 415V, 3, 50 Hz as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec. 1), EN 60947-4-1
Motor Rating: 3, 415V, 50Hz Sr. No. hp 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 0.125 0.16 0.2 0.25 0.33 0.5 0.75 1 1.5 1.75 2 2.5 3 6 7.5 10 12.5 15 17.5 20 25 30 35 40 45 kW 0.09 0.12 0.15 0.19 0.25 0.37 0.55 0.75 1.1 1.3 1.5 1.8 2.25 4.5 5.5 7.5 9.3 11 13 15 18.6 22.5 26 30 33.5 FLC, In (A 0.4 0.45 0.57 0.75 0.88 1.2 1.6 2.1 2.7 3 3.5 4.8 5 9 11.2 14.8 19 22 24 29 35 40 47 55 60 Contactor Type MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 12 MNX 12 MNX 12 MNX 25 MNX 25 MNX 25 MNX 25 MNX 25 MNX 32 MNX 32 MNX 32 MNX 40 MNX 45 MNX 45 MNX 70 MNX 70 MNX 70 Overload Relay Type MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 2 MN 5 MN 5 MN 5 MN 5 MN 5 Range (A) 0.3 - 0.5 0.3 - 0.5 0.45 - 0.75 0.6 - 1 0.6 - 1 0.9 - 1.5 1.4 - 2.3 1.4 - 2.3 2 - 3.3 2 - 3.3 3-5 3-5 4.5 - 7.5 9 - 15 9 - 15 9 - 15 14 - 23 14 - 23 20 - 33 20 - 33 30 - 50 30 - 50 30 - 50 45 - 75 45 - 75 Type MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H2M MOG-H2M MOG-H2M MOG-H2M MOG-H2M MPCB Rating 0.4 0.63 0.63 1 1 1.6 1.6 2.5 4 4 4 6.3 6.3 10 13 16 25 25 25 32 40 40 50 63 63

14

Selection Chart
Fuseless Protection for DOL Starter Feeders with MPCB MOG-H1M/H2M and MNX Contactor Type '2' Co-ordination, Iq=50 kA at 415V, 3, 50 Hz as per Standards : IEC 60947-4-1, IS 13947 (Part 4/Sec. 1), EN 60947-4-1
Motor Rating: 3, 415V, 50Hz Sr. No. hp 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 0.125 0.16 0.2 0.25 0.33 0.5 0.75 1 1.5 1.75 2 2.5 3 4 5 5.5 6 7.5 10 12.5 15 17.5 20 25 30 kW 0.09 0.12 0.15 0.19 0.25 0.37 0.55 0.75 1.1 1.3 1.5 1.8 2.25 3 3.7 4 4.5 5.5 7.5 9.3 11 13 15 18.6 22.5 FLC, In (A 0.4 0.45 0.57 0.75 0.88 1.2 1.6 2.1 2.7 3 3.5 4.8 5 6.4 7.9 8.5 9 11.2 14.8 19 22 24 29 35 40 Contactor Type MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 9 MNX 12 MNX 12 MNX 18 MNX 25 MO 25 MNX 25 MNX 32 MNX 45 MNX 45 Overload Relay Type RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 RTX 1 Range (A) 0.3 - 0.45 0.3 - 0.45 0.45 - 0.67 0.67 - 1.0 0.67 - 1.0 1.0 - 1.5 1.2 - 2.1 1.8 - 2.7 2.4 - 3.6 2.4 - 3.6 3.5 - 5.0 3.5 - 5.0 4.0 - 6.0 6.3 - 9.0 6.3 - 9.0 6.3 - 9.0 8.5 - 12.5 8.5 - 12.5 12.5 - 18 17 - 24 17 - 24 22- 32 22 - 32 30 - 40 35 - 45 Type MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H1M MOG-H2M MOG-H2M MOG-H2M MPCB Rating 0.63 0.63 1 1 1.6 1.6 2.5 2.5 4 4 6.3 6.3 6.3 10 10 10 13 16 20 25 32 32 40 50 50

15

I-t Characteristics
Type MOG - S1 (0.16A - 13A)
10000 10000

Type MOG - H1 (0.16A - 32A)

1000
3-poles from cold state

1000
3-poles from cold state

Average Tripping Time (s)

2-poles from cold state

Average Tripping Time (s)

100

100
2-poles from cold state

10
Instantaneous tripping characteristic is set at 1300% of the maximum current setting

10
Instantaneous tripping characteristic is set at 1300% of the maximum current setting

3-poles from hot state

3-poles from hot state

0.1

0.1

0.01

0.01

0.001 1 10 100

0.001 1 10 100

Multiples of current setting x Ie[A]

Multiples of current setting x Ie[A]

Type MOG - H2 (32A - 63A)


10000

1000

Average Tripping Time (s)

3-poles from cold state

100
2-poles from cold state

10
Instantaneous tripping characteristic is set at 1300% of the maximum current setting

3-poles from hot state

0.1

0.01

0.001 1

10

100

Multiples of current setting x Ie[A]

16

I-t Characteristics
Type MOG - H1M (0.16A - 32A)
10000

1000

100

Tripping Time (s)

10
Instantaneous tripping characteristic is set at 1100 ~ 1560% of the rated current

0.1

0.01

0.001

10

100

Multiples of rated current x In[A]

Type MOG - H2M (32A - 63A)


10000

1000

100

Tripping Time (s)

10
Instantaneous tripping characteristic is set at 1100 ~ 1560% of the rated current

0.1

0.01

0.001 1

10

100

Multiples of rated current x In[A]

17

Overall Dimensions
Type MOG - S1 (0.16A - 13A)
45 14.3 14.3

2-

.6 4

71

2-M4

1 1-

L1

3 1-

L2 3 2-

L3 2-

6-M4

27 13 13.5
24 32 28

27 6

105 116

5.5
2 T1 4 T2 6 T3

27

10 14.3 62.3

45 3.7 14.3

Type MOG - H1 & MOG - H1M (0.16A - 32A)


45 14.3 14.3

2-

.6 4

91

2-M4

1 1-

L1 3 1-

L2 5 2-

L3 2-

6-M4

27 3.3
24 32 28

105

5.5
2 T1 4 T2 6 T3

27

45 10 14.3 75.3 3.7 14.3

Type MOG - H2 & MOG - H2M (32A - 63A)


55 16.5 16.5 107.8 92.3 88.3 4.5

1 L1

3 L2

5 L3

6 - M6

1-

1- 2-

2-

33.8 5.5
45 63 55

120

45

16.3 19

105 33.8 5 4.2 42 110

110

84

2 T1

4 T2

6 T3

42

18

66

116

90

75

45

95

105

90

75

45

95

Overall Dimensions
Trip Alarm Contact Front 1NO
9 M 3.5

21.5

10.5

MOG-TAF 1NO
27

16.7

5.8 38.8

28

I> MOG-TAF 1NC


25

1.5

3.5 18.9 1 8.5

26

I>

S / C Alarm Left 1NO + 1NC


66 48.7 35.7 9 2.3 2.8 18.7 Trip indication (reset by hand)

M3.5

5.2 1

MOG-SAL 1CO
87 85 70.4 53.6 14.8 11.8 47.2 45 90

86

I>

88

6 3.4

19

Overall Dimensions
External Operating Handle (Applicable for Frame 1 & 2)
66 MMS A 66~216

ET RIP ES T

ON

4-3.5 3.3

OFF

MMS

66

MMS (16) 3.7 45 5.5 OFF (4~8) 3 Handle 1.5~5 X 2 4.2 1 52.60.2

68

Type
75

X min

X max +289 +306

Frame 1 +139 Frame 2 +156

Note: Recommended rod link should not exceed 150mm for frame 1 and 170mm for frame 2
B

Aux. Contact Front 1NO


9 M3.5

21.5

10.5

MOG-AXF 1NO
13(23)

16.7

5.8 38.8

14(24)

I>

MOG-AXF 1NC
11(21)

18.9

8.5

12(22)

I>

20

52.60.2

28

Overall Dimensions
Aux. Alarm Left 2NO
66 48.7 9 2.8 2.3 M3.5 35.7 18.7

Indication window

5.2

1 70.4 53.6 14.8 11.8 47.2

MOG-ATL 2NO
73 90 77

45

I
3.4

78 74

Aux. Contact Left 2NO


66 9 2.8 2.3 M3.5 48.7 35.7 18.7

Left side

Right side

70.4 53.6 45

1 5.2 3.4

MOG-AXL 2NO
33(133) 43(143)

MOG-AXL 1CO
31(131) 43(143)

MOG-AXL 2NC
31(131) 41(141)

14.8 47.2 90 42(142)

44(144) 34(134)

44(144)

11.8

32(132)

32(132)

21

Overall Dimensions
Shunt trip and under voltage release MOG - ST & MOG - UV
66 18 2.8 M3.5 2.3 18.7 5.2 48.7

70.4

47.2

45

Accessories for MPCB


Cat. Nos. ST41942OOOO ST41943OOOO ST41944OOOO ST41945OOOO ST41946OOOO ST41947OOOO ST41948OOOO ST41949OOOO Description Auxiliary Contact Front mtg. 1NO Auxiliary Contact Front mtg. 1NC Auxiliary Contact Left side mtg. 2NO Auxiliary Contact Left side mtg. 1NO + 1NC Auxiliary Contact Left side mtg. 2NC Trip Alarm Contact Front mtg. 1NO Trip Alarm Contact Front mtg. 1NC Auxiliary + Alarm Left side mtg. 2NO Model Numbers MOG-AXF 1NO MOG-AXF 1NC MOG-AXL 2NO MOG-AXL 1CO MOG-AXL 2NC MOG-TAF 1NO MOG-TAF 1NC MOG-ATL 2NO Terminal Marking NC NO F (Slot1 / Slot 2) 13, 14 (23, 24) 11, 12 (21, 22) F (Slot1 / Slot 2) "33, 34 (133, 134) L 43, 44 (143, 144)" 43, 44 (143, 144) 31, 32 (131, 132) L "31, 32 (131, 132) L 41, 42 (141, 142)" 27, 28 F (Slot 2 only) 25, 26 F (Slot 2 only) "73, 74 L 77, 78" 85, 86 87, 88 L Position C1, C2

ST41950OOOO Short circuit alarm Left side mtg. 1NO + 1NC MOG-SAL 1CO Shunt trip 24V DC MOG-ST ST41951OOOO MOG-ST ST41952OOOO Shunt trip 110V, 50Hz MOG-ST ST42952OOOO Shunt trip 230V, 50Hz R (one at a time) MOG-UV ST41953OOOO Under Voltage release, 110V, 50Hz MOG-UV ST41954OOOO Under Voltage release, 415V, 50Hz F - Front Mounting L - LHS Mounting R - RHS Mounting Note: 1) On LHS any 2 accessories can be fitted (Alarm contact followed by Auxiliary contact) l MOG-ATL 2NO + MOG-AXL 1CO l MOG-SAL 1CO + MOG-AXL 1CO 2) On RHS only 1 accessory can be fitted (Shunt trip release or Undervoltage release) 3) Any 2 Front mounted accessories are possible at a time. l Front mounted TAF to be fitted only in slot 2 l Front mounted auxiliary contact can be fitted in slot1 / slot 2

D1, D2

22

90

Notes:

Notes:

Electrical Standard Products (ESP) Branch Offices:


REGISTERED OFFICE AND HEAD OFFICE L&T House, Ballard Estate P. O. Box 278 Mumbai 400 001 Tel: 022-67525656 Fax: 022-67525858 Website: www.Larsentoubro.com ELECTRICAL STANDARD PRODUCTS (ESP) 501, Sakar Complex I Opp. Gandhigram Rly. Station Ashram Road Ahmedabad 380 009 Tel: 079-66304006-11 Fax: 079-66304025 e-mail: [email protected] 38, Cubbon Road, P. O. Box 5098 Bangalore 560 001 Tel: 080-25020100/25020324 Fax: 080-25580525 e-mail: [email protected] 131/1, Zone II Maharana Pratap Nagar Bhopal 462 011 Tel: 0755-4098721/7/ 8 / 9 Fax: 0755-2769264 e-mail: [email protected] Plot No. 559, Annapurna Complex Lewis Road Bhubaneswar 751 014 Tel: 0674-6451342, 2436696 Fax: 0674-2537309 e-mail: [email protected] SCO 32, Sector 26-D Madhya Marg, P. O. Box 14 Chandigarh 160 026 Tel: 0172-4646840, 4646853 Fax: 0172-4646802 e-mail: [email protected] 10, Club House Road, Annasalai Chennai 600 002 Tel: 044-28462072 / 4 / 5 / 2109 Fax: 044-28462102 / 3 e-mail: [email protected] 67, Appuswamy Road Post Bag 7156 Opp. Nirmala College Coimbatore 641 045 Tel: 0422-2588120 / 1 / 5 Fax: 0422-2588148 e-mail: [email protected] L&T House, Group MIG-5 Padmanabhpur Durg 491 001 Tel: 0788-2213833 / 14 / 21 / 29 Fax: 0788-2213820 e-mail: [email protected] Khairasol, Degaul Avenue Durgapur 713 212 Tel: 2559848, 2559849, 2559844 Fax: 0343-2553614 e-mail: [email protected] Milanpur Road, Bamuni Maidan Guwahati 781 021 Tel: 0361-2550562 / 65 Fax: 0361-2551308 e-mail: [email protected] II Floor, Vasantha Chambers 5-10-173, Fateh Maidan Road Hyderabad 500004 Tel: 040-66720250 Fax: 040-23296468 e-mail: [email protected] D-24, Prithvi Raj Road, C-Scheme Jaipur 302 001 Tel: 0141-2385915 / 16 / 17 / 18 Fax: 0141-2373280 e-mail: [email protected] Akashdeep Plaza, 2nd Floor P. O. Golmuri Jamshedpur 831 003 Jharkhand Tel: 0657-2312205 / 38 Fax: 0657-2341250 e-mail: [email protected] Skybright Bldg; M. G. Road Ravipuram Junction, Ernakulam Kochi 682 016 Tel: 0484-4409420 / 4 / 5 / 7 Fax: 0484-4409426 e-mail: [email protected] 3-B, Shakespeare Sarani Kolkata 700 071 Tel: 033-44002572 / 3 / 4 Fax: 033-22821025/7587 e-mail: [email protected] A28, Indira Nagar, Faizabad Road Lucknow 226 016 Tel: 0522-2312904 / 5 / 6 Fax: 0522-2311671 e-mail: [email protected] No: 73, Karpaga Nagar, 8th Street K. Pudur Madurai 625007 Tel: 0452-2537404, 2521068 Fax: 0452-2537552 e-mail: [email protected] EBG North Wing Office-Level 2 Gate 7, Powai Campus Mumbai 400 072 Tel: 022-67052874 / 2737 / 1156 Fax: 022-67051112 e-mail: [email protected] 12, Shivaji Nagar North Ambazari Road Nagpur 440 010 Tel: 0712-2260012/3 Fax: 0712-2260020/30 e-mail: [email protected] 32, Shivaji Marg P. O. Box 6223 New Delhi 110 015 Tel: 011-41419514 / 5 / 6 Fax: 011-41419600 e-mail: [email protected] L&T House P. O. Box 119 191/1, Dhole Patil Road Pune 411 001 Tel: 020-26135048/26164048 Fax: 020-26124910, 26135048 e-mail: [email protected] 3rd Floor Vishwakarma Chambers Majura Gate, Ring Road Surat 395 002 Tel: 0261-2473726 Fax: 0261-2477078 e-mail: [email protected] Radhadaya Complex Old Padra Road Near Charotar Society Vadodara 390 075 Tel: 0265-6613610 / 1 / 2 Fax: 0265-2336184 e-mail: [email protected] 48-8-16, Dwarakanagar Visakhapatnam 530 016 Tel: 0891-6620411-2 / 3 Fax: 0891-6620416 e-mail: [email protected]

Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.

Electrical Standard Products Larsen & Toubro Limited Powai Campus, Mumbai 400 072 Customer Interaction Center (CIC) BSNL / MTNL (toll free) : 1800 233 5858 Reliance (toll free) : 1800 200 5858 Tel : 022 6774 5858 Fax : 022 6774 5859 E-mail : [email protected] Website : www.LNTEBG.com

SP 50455 R1

070112

You might also like