Neutral current transformer (NCT) is required for ground fault setting. This is an example, how to select convenient NCT rating based on burden value of each equipment.

Uploaded by

witpur2014
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
2K views1 page

NCT Calculation

Neutral current transformer (NCT) is required for ground fault setting. This is an example, how to select convenient NCT rating based on burden value of each equipment.

Uploaded by

witpur2014
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PROYEK PEMBANGUNAN PABRIK NPK FUSION II

KAPASITAS 2 X 100,000 MTPY


PT. PUPUK SRIWIDJAJA PALEMBANG

I. DATA OF TRANSFORMER
kVA = 2000 kVA Capacity
kV p = 13.8 kV Primary Voltage
kV s = 0.4 kV Secondary Voltage
Ip = 83.67 A Primary Current
Is = 2886.75 A Secondary Current

II. NEUTRAL CT SELECTION


Ground Fault Setting for Neutral Transformer
Setting = 0.50 x IFL
I sett = 1443.38 Ampere
Ration CT Selection
Primary = 1500 A
Secondary = 1A ( Due to for use in remote situation, Length between transformer with MV Switchgear + 80m )
CT Selection = 1500/1 A

Lead Cable
Type Cable = 2C - 2.5mm2 @ NYFGbY
Length = 160 meter @ 2x80m
Resistance = 8.866 Ohm/km ( Based on cable catalog)
RW = 1.42 Ohm

. .
> + + −
.

c = 1.4 (Safety Factor)


Ik = 10 x IN Maximum through fault short circuit current ( Assumption)
k ALF = 20 Accuracy limit factor
I NTRa = 2886.75 Ampere Rated current of the transformer
I NCT = 1500 Ampere Rated primer current of the CT
I NCT sec = 1 Ampere Nominal secondary current of CT
R CT = 0.20 Ohm Winding Resistance of CT (Assumption)
RW = 1.42 Ohm Wiring Resistance
RL = 0.69 Ohm Resistance of the protection relay input (Assumption)
SN = 2.91 VA Nominal burden of CT
Selection of Burden CT = 10VA

III. CONCLUSION
Based on calculation above, the current transformer selected is 1500/1A, 10VA 5P10