1 Installation part.......................................................................................1
1.1 Packing list and installation components.....................................2
1.2 Installation instructions..................................................................3
1.3 Installation methods........................................................................3
1.4 Wiring methods................................................................................5
1.5 Safety precautions..........................................................................6
1.6 System wiring instruction...............................................................7
2 Operation part.........................................................................................8
2.1 Function instructions......................................................................9
2.2 Operation conditions.......................................................................9
2.3 Key words.......................................................................................10
2.3.1 Status indication.....................................................................10
2.3.2 Power on or reset...................................................................10
2.3.3 Emergency stop and forced on.............................................10
2.3.4 Various locking.......................................................................11
2.3.5 ON and OFF ............................................................................12
2.4 Operation instructions.......................... .......................................14
2.4.1 Keys instructions...................................................................15
2.4.2 LCD instructions....................................................................19
2.4.3 Other instructions...................................................................22
2.4.4 Error code table......................................................................24
2.5 Technical index and requirements..............................................25
INSTALLATION PART
1
1.1 Packing list and installation components
1. Please check the packing list of the centralized controller,whether the components are
complete.
1 Centralized controller 1
Wire pipe(jack
4 casing pipe, 2/3 PCS ———— ————
captive nut)
Several For binding cables(as the
5 Tighten strip ————
pieces case maybe)
2
1.2 Installation instructions
Installation instructions
1) Connect 220VAC power to the L、N terminals of the centralized controller directly.
2) Do not lay the signal wire and the power wire of the centralized controller in the same power
wire pipe, there should be 300~500mm distance between two pipes.
3) The signal wire of centralized controller should not exceed 1200m.
4) No intermediate joint is allowed for the shielded cable. If joints are inevitable, crimp it with the
terminal block.
5) After the centralized controller is connected, do not use megohmmeter to inspect the insulation
of the signal cable.
6) Wiring mode of the centralized controller and the network interface:
The communication port between the centralized controller and the network interface of the air
conditioner is polarity-sensitive.The X,Y and E at both sides should correspond properly. Dot
not cross-connect the signal wires,the same to the RS485-RS232 of the centralized controller.
E Y X
X Y E
E Y X
X Y E
E Y X
X Y E
E Y X
1.3 Installation methods
180
137
92
70 48.5
85 68
122
CCM30/BKE-A CCM30/BKE-B
CE-CCM30/BKE-A CE-CCM30/BKE-B
3
Insert the flathead screwdriver into the
concave on the upper side of the box,
and rotate slightly to open the upper cover(3 places).
Base
Dial code
ON
Front cover
~ 00 ~ 15
Fig. 1.2 Installation diagram
X Y E F1 F2 E FORCED ON EMG.STOP L N
4
1.4 System wiring instruction
Network air conditioner wiring diagram (two types for indoor unit: one is the main control board
with an external network interface module; the other is the network interface module is built in the
main control board).
Matched resistance of
communication Electronic Electronic Electronic
Other centralized control box control box control box
controllers terminal 120 Ω Indoor unit Indoor unit Indoor unit
POWER
Electronic Electronic
control box control box
Indoor unit Indoor unit
Matched resistance of
communication Reliably ground the shielding terminal
terminal 120 Ω
Centralized
controller
POWER
Electronic Electronic
control box control box
Indoor unit Indoor unit
Matched resistance of
Electronic Electronic Electronic
communication
control box control box control box
terminal 120 Ω Indoor unit Indoor unit Indoor unit
POWER
T N F1 F2 E X Y E Electronic Electronic
control box control box
Indoor unit Indoor unit
5
Note
The RS485-to-RS232 module and the wires in the wiring diagram are used when the network
system needs to connect with the computer only. One computer can connect with 16 centralized
controllers at most, Namely the maximum of indoor units is 16X64=1024 ,that a network system
can connect. The centralized controllers can be distinguished by address code,which setting range
is 0 to 15. No duplicate addresses is allowed in a same network.
1.5 Safety precautions
Safety precautions
! Read the safety precautions carefully before installing the unit.
! Stated below are important safety issues that must be obeyed.
! The meanings of all parts are as follows:
Warning Means improper handling may lead to personal injury or property loss.
Note Means improper handling may lead to personal death or severe injury.
! Upon completion of the installation, check whether the trial run is normal, and deliver the
user's manual to the user.
Warning
Please entrust the distributor or professionals to install the equipment. Installation by unauthorized
persons may lead to imperfect installation which may result in electric shock or fire.
Adhere to this installation manual. Improper installation may lead to electric shock or fire.
Note
Do not install the equipment in a place vulnerable to leakage of flammable gases. Once
flammable gases are leaked and left around the centralized controller,fire may occur.
The wiring shall adapt to the current of the centralized controller . Otherwise electric leakage or
heating may occur and result in fire.
6
1.6 System wiring instruction.
1) Wiring diagram of building net work airconditioning system.
(a) (b)
2) System wiring diagram of centralized controller and indoor unit of air conditioner.
Both of the following wiring modes of centralized controller and indoor unit are applicable:
(The number of indoor units connected with each centralized controller is not beyond 64)
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Centralized controller
Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit
Centralized controller
Fig.1.5 Wiring diagram of centralized controller and indoor unit of air conditioner
7
OPERATION PART
8
2.1 Function instructions
1. Centralized controller is used for controlling and data querying of air conditioners in the network.
Each centralized controller can be connected to maximum 64 indoor units, through 485
communication can to form an air conditioner LAN and realize the centralized controlling
network in the air conditioner.
2. Centralized controller can connect with computer or gateway, to realize the LAN connection
between computer and all the air conditioners , then can use computer to remote control
(the computer software must support it). Each local computer or gateway maximally connect
16 centralized controllers.
3. Between centralized controller and air conditioner, computer and centralized controller are
applied to the master-slave responding communication method. In the LAN of centralized
controller and air conditioner, centralized controller will be the master unit, and the air
conditioner will be the slave unit. In the LAN of computer and centralized controller, the
computer or gateway will be the master unit, and the centralized controller will be the slave unit.
Air conditioner
Network Local computer
interface Centralized controller
Network interface
may be gathered on
the indoor unit main
control board
……
……
……
……
……
Internet
Maximally 64
indoor units
Maximally 16
centralized controllers
9
2.3 Key words
2. Backlight
The backlight will be on by pressing any key except” ”,when the backlight is off.
The backlight will be on,when centralized controller is operating,
The backlight will be off, if no key is pressed over 30s.
3. Buzzer
When the backlight is on and the centralized controller keys are un-lock, any key (except for
the ) is pressed ,the centralized controller will carry on relative function, the buzzer will buzz
once . If this key has long press function, the centralized controller will carry on the relative
functin, but the buzzer will buzz once only.
When the backlight is off, any key (except for key) is pressed, only the backlight is lighted
on, the centralized controller will not operate the key, and the buzzer will not buzz.
10
of the centralized controller is connected, all air conditioners in the nerwork of the centralized
controller will start up compulsorily. By default, they will run in the cooling mood. The startup
and shutdown operations of the centralized controller and computer and all functional
modules will be disabled (only the command of startup is sent to the air conditioner,without
affecting operation of the remote controller after startup) until the forced on switch is break.
If the foregoing two switches are connected concurrently,the emergent stop switch
shall have preference.
11
2) Operation
Can set the heating mode locking or cooling mode locking.
Under mode locking state, if set the new mode locking, it must be unlocking first, then can
operate the new mode locking.
① Can lock or unlock through the computer.
② Can operate by centralized controller.
In the centralized controller setting interface, choose all the air conditioners of the
centralized controller network as the object, press “ ” and hold on, then press “ ” to
do the mode locking or unlocking.
If the current state is mode locking, press the key to unlock.
If there’s no mode locking, press the key to lock.
12
1) One or more air conditioners under ON state (include timing process of timing ON
and OFF)
“ ” key only has short press function.
Only send the OFF order to the air conditioners with ON state, not for OFF state units.
The memory function is activated, the current state of all air conditioners is memo-
rized.
2) All the air conditioners in the centralized controller network are OFF states
① “ ” key short press
The centralized controller reads the memory contents, and sends relative order to all
air conditioners.
② “ ” key long press
a) If current page is setting parameters, and the setting mode is not OFF, the central-
ized controller will send orders to all air conditioners according to parameters, such as setting
mode, fan speed, setting temperature, etc.
b) If the current is under setting interface but the setting mode is OFF state or under
other interfaces, the centralized controller will send the default ON order to all air
conditioners. The default ON order is : cooling mode, high fan speed, setting temperature
is 24℃ or76℉, operate the swinging function.
13
14
In the setting page, press the “OK” key to send the setting
In the setting page, set the operation
information except the locking signal to the air conditioner.
mode of the air conditioner.
is enabled or disabled
1. “Up” and “Down” keys: For
selecting rows.
2. “Left’ and ”Right” keys: For 1、In the setting page, set the
selecting columns. temperature,increase or decrease
the time of timing on/off.
2、In the query page ,scroll page of
the parameters being queried.
2. Set key “ ”
In other display mode,press the key “ ” to enter the setting mode.
By default, it is single setting, and the first in-service air conditioner is displayed.
In setting operation mode, press the key “ ” again, and the operation will be
performed for all air conditioners in the network. Press the key repeatedly to shift between
single setting and global setting.
→ Single → Global →
3. Mode key “ ”
In setting operation mode,Press this key to set the operation.
→cooling → heating → Fan only → off →
4. Fan key “ ”
In setting operation mode, press this key to set the fan of the indoor unit of the air
conditioner to run in the automatic, high, medium or low level of air.
→ auto → low → medium → high →
5. Time on key “ ”
In setting operation mode, press this key “ ” to set the timing startup of air
conditioner;
Press the key “ ” again to exit the timing setting, and restore the normal
temperature regulation operation mode.
6. Time off key “ ”
In setting operation mode, press this key “ ” to set the timing shutdown of air
conditioner,
Press the key “ ” again to exit the timing setting, and restore the normal
temperature regulation operation mode.
7. Swing key “ ”
In setting operation mode, press this key “ ” to enable or disable the swing function.
If all currently selected air conditioners have no swing function, no effect will result after
pressing the key.
8. Leftward key “ ”
In the query mode, if this key is pressed, the operation status data of the previous
air conditioner will be displayed. If it is currently on the first machine, the data of the last
machine will be displayed,when the key is pressed . If you hold down this key, the address
will decrease one by one.
In the setting mode, if it is in single operation mode, the air conditioner of the previous
in-service address number will be selected,when this key is pressed, If it is in the global
operation mode, no effect will result when this key is pressed.
In the main page , press the key to enter the query mode. By default, it is the first
in-service air conditioner.
Installation & Owner‘s Manual
15
9. Rightward key “ ”
In the query mode, when the key is pressed, the next in-service air conditioner is
selected,and its operation status data will be displayed.If it is currently on the last air
conditioner, the first one is selected and its data displays, when the key is pressed. If this key
is hold down long, the address will increase one by one.
In the setting mode, if it is in the single operation mode, when the key is pressed, the
next in-service air conditioner will be selected. If it is in the global operation mode, no effect
will result when the key is pressed.
In the main page, press the key to enter the query mode. By default, it is the first
in-service air conditioner.
0 .0 0 .5 1 .0 1 .5 2 .0 2 .5 3 .0 3 .5 4 .0 4 .5 5 .0 5 .5
13 12 11 10 9 .5 9 .0 8 .5 8 .0 7 .5 7 .0 6 .5 6 .0
14 15 16 17 18 19 20 21 22 23 24
16
13. Reduce key “ ”
1) Query mode
Press this “ ” key, display the data of the previous page.
If it is now in the first page, press the key “ ” again and the last page will be
displayed.
2) Setting operation mode
① Temperature adjusting method
Press this key “ ”, the setting temperature will decrease one degree.
If you hold down the key “ ”, the setting temperature will decrease one by one.
When reached the lowest allowed set temperature, it can not decrease.
② Timing on or timing off setting method
Press this key “ ”, it will select the next setting time.
If you hold down the key “ ”, the next data will be selected one by one.
When reached the min allowed setting time, it can not decrease.
The timing seting change mode is as follow:
24 23 22 21 20 19 18 17 16 15 14 13
5 .5 6 .0 6 .5 7 .0 7 .5 8 .0 8 .5 9 .0 9 .5 10 11 12
5 .0 4 .5 4 .0 3 .5 3 .0 2 .5 2 .0 1 .5 1 .0 0 .5 0 .0
17
18
Full display of LCD
Telephone module Swing function
SMS modeule communication
mommunication
Display operation
Dehumidifying Electric auxiliary
Function module status:Query, setting,
heating function
communication grouping, operation.
19
a. The array of the liquid crystal display is composed of 4X16 grids, and each grid is
composed of two blocks of different sizes (as shown in the above figure). The
status indication table is as follows:
Status
Constantly on Slow blink Fast blink Not bright
Object
Big black Out of
In-service Selected
block service
Fault of
Small black indoor/ Power
Power on
block outdoor off
unit
b. The array includes horizontal coordinates 00-15 on the up side and vertical
coordinates 00+, 16+, 32+ and 48+ on the left side, which indicate the address of
the indoor unit. The sum the horizontal coordinate and the vertical coordinate
composes the grid the address of the grid. Each grid corresponds to an indoor unit
of this address.
①The LCD displays the main page, 60 air conditioners are in service, which 28 are
powered on and 32 off.
②The address of the air conditioners is sum of the coordinates. For example, the
address of (48+,09) is 48+09=57.
③In the array, the big dots from (16+,00) to (32+,15) are luminous, and the small dots
are not luminous. It indicates the 32 air conditioners with the addresses from 16 to 47 are
powered off.
④In the array, the big and small dots from (48+,09) to (48+,12) are not luminous. It
indicates the four air conditioners with the addresses from 57 to 60 are outside.
⑤All other big and small dots in the array are luminous. It indicates all other air
conditioners are in the net powered on.
⑥The centralized controller communicates with the computer normally,when the
keypad of the centralized controller is locked.
20
2) Description of the query page
①The LCD display shows the query page, and the air conditioner with the address of
01 is being queried.
②Mode of the air conditioner with the address 01 is: Cooling, strong air, swing on,
indoor temperature 22°C,set temperature 20°C, cooling mode “lock”.
③In the array, only the big and small black dots at (00+,00) and (00+,01) are luminous .
It indicates the in-service and power-on status of the air conditioners with the addresses of
00 and 01.
④The centralized controller communicates with the computer normally.
①The LCD display shows the setting page, and queries the air conditioner with the
address of 01 .
②THe mode of the air conditioner with the address 01 is: Cooling, strong air, swing on,
set temperature 22°C, cooling.
③In the array,only the big black dots at (00+,01) to (00+,15) are luminous. It indicates
the air conditioners with the addresses 01 and 15 are in service.
④The centralized controller communicates with the computer normally.
21
4) Fault page display description
①Query the air conditioner with the address of 08 in the query page.
②The air conditioner with the address of 08 is faulty, and fault code is 08. The big black
dot below (00+,08) blinks.
③In the array,only the big and small black dots at (00+,00) and (16+,15) illuminate.
It indicates the in-service status of the air conditioner power on, with the addresses 00
and 31.
④The centralized controller communicates with the computer normally.
22
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
00+
16+
32+
48+
Fig 2.9 Filter net in addition to the dust function involves of show a contents
2) Function setting
① Dial the dial code 3 to “ON”, select the “Has optional function”referring to table 2.1 to , and
then power on the centralized controller, in 1 minute press “ ” key and hold on then press “ ”
key, enter to optional function setting. Dual eight represented function selection (Fig.2.9 a) will be
flashed with 1Hz frequency (default display 00), display the optional function code (see table 2.2).
Press “ ” and “ ” keys to select function, and then press “ ” key to enter parameter
selection.
②After enter parameter selection, dual eight represented function selection will be lighted
on, dual eight represented parameter selection (Fig.2.9 b) will be flashed with 1Hz frequency,
display optional parameter code. Through pressing “ ” and “ ” keys to select the detailed
parameter.
③Press “ ” to confirm parameter selection(details parameter codes’ corresponding time
refer to table 2.3).
④After setting successfully, Dual eight represented function selection and dual eight
represented function selection will be lighted on, the screen will display “Setting successfully”
(Fig. 2.9 d). After 3 seconds will auto exit optional function setting. The screen will back to normal
display.
After enter optional function setting, no operations in 5 seconds will auto exit function
selection, the setting parameter will not change. Only press “ ” key to confirm the parameter
then the setting parameter will save.
23
2.4.4 Fault and protection code table
Protection
Protection content Description
code
PF Other protection
PE Reserved
PD Reserved
PC Reserved
PB Reserved
PA Reserved
P9 Reserved
P8 Over-current of compressor
P7 Power supply over-voltage and undervoltage protection
P6 Discharge low pressure protection
P5 Discharge high pressure protection
P4 Discharge pipe temperature protection
P3 Compressor temperature protection
P2 Condenser high-temperature protection
P1 Anti cool air or defrost protection
P0 Evaporator temperature protection
24
2.5 Technical indices and requirements
25
Take-back of electrical waste
Information for Users to Disposal of electrical and electronic equipment
(private households)
Icon on the product or in the accompanying documentation means that used electric or electronic products
must not be disposed together with domestic waste. For the correct disposal of the product hand it over
to a place for take-back, where it is collected free of charge. By correct disposal of the product you can help
to preserve valuable natural resources and help in preventing potential negative impacts to environment and
human health, which could be consequence of incorrect disposal of waste. Ask for more details from local
authorities, nearest collection point, in Waste Acts of respective country, in the Czech Republic in Act no.
185/2001 Coll., in the wording of later regulations. In case of incorrect disposal of this waste, a fine can be
imposed according to national regulations.
Manufacturer: