WEG Molded Case Circuit Breakers UBW225
WEG Molded Case Circuit Breakers UBW225
WEG Molded Case Circuit Breakers UBW225
User’s Manual
www.weg.net
WARNING
Do not attempt to install or perform maintenance on equipment while it is
The user is cautioned to observe all recommendations, warnings and cautions relating
to the safety of personnel and equipment, as well as all general and local health and
safety laws, codes and procedures.
The recommendations and information contained herein are based on WEG
experience and judgment, but should not be considered to be all-inclusive or
covering every application or circumstance which may arise. If any questions arise,
contact WEG for further information or instructions.
1. INTRODUCTION
The UBW225 circuit breakers (Figure 1) are rated from 15 A to 225 A continuous
current thermal-magnetic circuit breakers. Circuit breakers are listed in accordance
with Underwriters Laboratories, Inc. Standard UL 489, and satisfy the (P1)
requirements of the International Electrotechnical Commission Recommendation
No. IEC 157-1.
2. INSTALLATION
The installation procedure consists of inspecting and mounting the circuit breaker,
connecting and torquing the line and load terminations, and attaching terminal
shields or barriers, when supplied. To install the circuit breaker perform the
following steps:
Note: the UBW225 circuit breakers are factory sealed. UL 489 requires that internal accessories be installed at the
factory. Where local codes and standards permit and UL listing is not required, internal accessories can be field
installed. Accessory installation should be done before the circuit breaker is mounted and connected.
WARNING
Before mounting the circuit breaker in an electrical system, make sure
Note: before mounting the circuit breaker, check if the termination devices should be installed first. See terminations
instructions.
CAUTION
Do not exceed connector/bus capacity in WEG power line.
1.375
(34.93)
.164-32 tap holes
(M4 x 0.7)
2.313
(58.75)
2.906
(73.81)
Circuit Breaker
Handle
1.325
.250 R (33.66)
Load
(6.35)
End
.188 (4.78 mm) Dia. Hole for
access to push-to-trip
4. If an optional terminal end cover is to be installed with the circuit breaker (usually
line end only), it must be positioned before cable is connected to terminals.
CAUTION
When aluminum conductors are used, the application of a suitable joint
5. After mounting the circuit breaker, line and load terminals and accessory leads
should be connected (see accessory schematic diagram on side of circuit
breaker.)
Note: if terminal shield or interphase barriers are to be installed on the circuit breaker, install them after the terminals
are connected.
6. If required, install terminal shield on circuit breaker cover with mounting screws
provided.
7. If required, install an interphase barrier by sliding barrier into dovetail grooves
between terminals.
8. After the circuit breaker is installed, check all mounting hardware and terminal
connecting hardware for correct torque loading. Torque values for line/load
terminals are given in Tables 1, 2, and 3 and on the circuit breaker nameplate.
Terminal Terminal
Screw AWG wire Metric wire Wire Torque value,
catalog body
head type range range type Lb. in.(N.m)
number material
3/16 socket
LT3 UBW2251) Aluminum #4-4/0 25-95 Cu/Al 120 (13.6)
hex
5/32 socket
WT3 UBW225 Aluminum #14-2 25-95 Cu/Al 70 (7.9)
hex
3/32 socket
WT6 UBW225 Aluminum #14-6 2.5-10 Cu/Al 25 (2.8)
hex
Metric wire range Torque value N.m AWG wire range Torque value, Lb.-In.
10 4.52 #8 40
3. MANUAL OPERATION
Manual operation of the circuit breaker is controlled by the circuit breaker handle
and the PUSH-TO-TRIP button. The circuit breaker handle has three indicated
positions, two of which are shown on the cover with raised lettering to indicate
ON and OFF. On the sliding handle barrier, ON, OFF, and trip are also shown by
a color-coded strip for each circuit breaker handle position: red for ON, white for
tripped, and green for OFF. On the sliding handle barrier, ON/OFF is also shown
with the international symbols I/0 (see Figure 4.)
International symbol
(OFF)
ON
Handle position
Indicator color:
Red - ON
Trip White - Trip
Green - OFF
Reset
OFF
Reset
Handle
Push-to-trip Push-to-trip
button
Note: in the event of a thermal trip, the circuit breaker cannot be reset until the thermal element cools.
4.1. INSPECTION
Circuit breakers in service should be inspected periodically. The inspection should
include the following checks 1 thru 7.
WARNING
Before inspecting the circuit breaker in an electrical system, make sure
the circuit breaker is switched to the off position and there is no voltage
present where work is to be performed. Special attention should be paid
to reverse feed applications to ensure no voltage is present. The voltages
in energized equipment can cause injury or death.
CAUTION
Make sure that cleaning agents or solvents used to clean the circuit
breaker are suitable for the job. Some commercial cleaning agents will
damage the name plates or molded parts.
1. Remove dust, dirt, soot, grease, or moisture from the surface of the circuit
breaker using a lint-free dry cloth, brush, or vacuum cleaner. Do not blow debris
into circuit breaker. If contamination is found, look for the source and eliminate
the problem.
2. Switch circuit breaker to ON and OFF several times to be sure that the mechanical
linkages are free and do not bind. If mechanical linkages are not free, replace
circuit breaker.
3. Press the PUSH-TO-TRIP button to mechanically trip the circuit breaker. Trip,
reset, and switch circuit breaker ON several times. If mechanism does not reset
each time the circuit breaker is tripped, replace the circuit.
4. Check base, cover, and operating handle for cracks, chipping, and discoloration.
Circuit breakers should be replaced if cracks or severe discoloration is found.
5. Check terminals and connectors for looseness or signs of over-heating.
Overheating will show as discoloration, melting, or blister- ing of conductor
insulation, or as pitting or melting of conductor sur- faces due to arcing. If
there is no evidence of overheating or loose- ness, do not disturb or tighten
the connections. If there is evidence of overheating, terminations should be
cleaned or replaced. Before re-energizing the circuit breaker, all terminations
and cable should be refurbished to the condition when originally installed.
6. Check circuit breaker mounting hardware. Tighten if necessary.
7. Check area where circuit breaker is installed for any safety hazards, including
personal safety and fire hazards. Exposure to certain types of chemicals can
cause deterioration of electrical connections.
5. HFDDC
The instructions for installation, testing, maintenance, or repairherein are provided
for the use of the product in general commercial applications and may not be
appropriate for use in nuclear applica- tions. Additional instructions may be available
upon specific request to replace, amend, or supplement these instructions to
qualify them for use with the product in safety-related applications in a nuclear
facility.
The information, recommendations, descriptions, and safety nota- tions in this
document are based on WEG’s experience and judg- ment with respect to
Retrofitting of Power Breakers. This instruction- al literature is published solely
for information purposes and should not be considered all-inclusive. If further
information is required, you should consult an authorized WEG sales representative.
The sale of the product shown in this literature is subject to the terms and conditions
outlined in appropriate WEG selling policies or other contractual agreement
between the parties. This literature is not intended to and does not enlarge or add
to any such contract. The sole source governing the rights and remedies of any
purchaser of this equipment is the contract between the purchaser and WEG.
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES
OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR
WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE,
ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS, AND
DESCRIPTIONS CONTAINED HEREIN. In no event will WEG be responsible to
the purchaser or user in contract, in tort (including negligence), strict liability or
otherwise for any special, indirect, incidental or conse- quential damage or loss
whatsoever, including but not limited to damage or loss of use of equipment, plant
or power system, cost of capital, loss of power, additional expenses in the use of
existing power facilities, or claims against the purchaser or user by its customers
resulting from the use of the information, recommendations and description
contained herein.
NOTES
NOTES
NOTES
Changzhou – Jiangsu
Phone: +86 519 88067692
[email protected]
The values shown are subject to change without prior notice.
For those countries where there is not a WEG own operation, find our local distributor at www.weg.net.
Rev: 00 | Date (m/y): 03/2017