We wish to save you time and money! We can assure you that a thorough reading of this manual will guarantee correct installation and safe use of the product described.
IMPORTANT BEFORE INSTALLING OR OPERATING ON THE DEVICE, CAREFULLY READ THE INSTRUCTIONS IN THIS MANUAL.
This instrument has been designed to operate without risks only if: installation, operation and maintenance are performed according to the instructions of this manual; environmental conditions and supply voltage fall within the values indicated here below. Any different use or changes which have not been previously authorised by the manufacturer, are considered improper. Responsibility for injures or damage caused by improper use will fall exclusively on the user. Warning: voltage is present in some electrical components of this instrument, thus all the service or maintenance operations must be performed by expert and skilled personnel only, aware of the necessary precautions to be taken. Before accessing the internal parts, disconnect the power supply. Disposing of the parts of the controller The controller is made from metal parts and plastic parts. All these parts should be disposed of according to local standards on waste disposal. Cleaning the controller Only use neutral detergents and water.
User manual
Contents
Introduction 1. 1.1 1.2 1.3 1.4 2. 3. 3.1 3.2 3.3 3.4 3.5 3.6 4. 4.1 4.2 4.3 4.3.1 4.3.2 4.4 4.4.1 4.5 5. 6. 6.1 6.2 6.2.1 6.2.2 6.3 6.4 Installation and connections General warnings installation and connection environments Panel installation Wall-mounted installation Electrical connections Function and description of the buttons Operation Display Set Point (required temperature value) Manual defrost Silencing the buzzer Light ON/OFF Continuous cycle Parameters First level - frequent parameters Second level - configuration parameters Modifying and saving the parameters Modifying Saving Configuring the digital inputs Duty setting selection (parameters c4 and A6) Table of the parameters Alarms, signals and troubleshooting Technical specifications General characteristics Electrical specifications Inputs Outputs Mechanical characteristics Dimensions 23 23 23 24 25 26 27 28 28 28 28 28 28 28 29 29 29 29 29 29 30 30 31 33 34 34 34 34 34 35 35
Introduction
MasterCella is a control for static or ventilated refrigerated units. It manages all devices: compressors, fans, defrost, alarms and lights. The enclosure is IP65 and cable connection is extremely easy thanks to an easly removable front cover. MasterCella belongs to a range of controls able to meet customer requests. Thanks to the chosen case, the MasterCell can be both panel-mounted and wall-mounted.
prg
SET
MasterCella
a b
Fig. 1.2.1
120
m n
i
parte inferiore lower part
100
Fig. 1.3.1
Compressore Compressor
non connesso not connected
mod. MTCA*
Sonda ambiente Room probe
D+ GND D-
1 2 3 4 5 6 7 8 9
10 11
15 16
17 18 19
20 21
FUSE 50mA T 250 Vac
0T50
ID1
ID2
RS-485
N F
Allarme Alarm
N F
230 Vac +10% -15%
mod. MTCD*
Sonda ambiente Room probe
D+ GND D-
1 2 3 4 5 6 7 8 9
10 11
12 13 14
15 16
17 18 19
20 21
FUSE 50mA T 250 Vac
0T50
ID1
ID2
RS-485
N F
Allarme Alarm
N F
230 Vac +10% -15%
Fig. 1.4.1
1
1 Silences the buzzer, while the alarm code remains as long as the alarm condition remains: - if pressed when turning On the instrument: allows to restore the default parameters (see section Alarms, signalling and troubleshooting); - if pressed for more than 5 seconds: allows access to the frequent parameters selection menu (F); - if pressed for more than 5 seconds together with the SET button: allows access to the configuration menu through password 22 (see section Second level: configuration parameters);
prg
SET
Fig. 2.1
if pressed for more than 5 seconds: activates/deactivates a continuous cycle, that is the forced activation of the compressor for a period to be selected (see parameter cc); allows the switching On/Off of the refrigerating unit. Warning: when the controller is OFF, all outputs, with the exception of the light output and the light button, will be deactivated whereas the On/Off led will be flashing. It is necessary to select the c2 parameter to ensure that, between one switching Off and the following switching On, the minimum time the compressor is Off is maintained. The ON/OFF button can be deactivated: it is sufficient to select one digital input as remote ON/OFF (see Configuring the digital inputs). selects the Set Point (see Set Point); displays the value of the selected parameter (see Modifying and saving the parameters); - if pressed for more than 5 seconds together with the prg button: allows access to the configuration menu through password 22 (see Second level: configuration parameters); decreases the data value on the display during selection of Set Point and/or parameters; - if pressed for more than 5 seconds: it forces a manual defrosting cycle; activates/deactivates the lights of the cold room (or any other aux. output connected to the 4th relay); increases the displayed value during selection of Set Point and/or parameters.
LED indicators
cooling on defrosting in progress continuous cycle functioning fan evaporator activated lights ON unit deactivated (OFF unit)
3. Operation
3.1 Display
During normal functioning the display shows the value read by the ambient probe. In case of alarm the temperature values will flash alternately with the connected alarm code. When the controller is deactivated (OFF unit) the On/Off led flashes while the display shows the temperature read by the probe.
and
4. Parameters
The parameters have been organised into two levels.
and
SET
4. confirm by pressing button; 5. the display shows the code of the first parameter to be modified. To modify the parameters see the following section, Modifying and saving the parameters.
button to visualise the value associated to the parameter; and/or buttons until the desired value is displayed;
button to temporarily confirm the newly set value and to go back to the param. code display; and/or to modify other parameters values.
e. repeat all operations from the point press Per memorizzare passare a Saving. 4.3.2 Saving To store the new set values of the parameters:
1. Press the button to store definitively all the new set values and exit the procedure. 2. It is possible to exit without modifying parameters: do not press any button for at least 60 seconds (TIME OUT exit).
prg
3. If the button is not pressed after modifying operations, all the effected variations will be lost, and the starting values will be restored.
prg
Remote On-Off
Curtain switch
Open Contact = alarm active Open contact = alarm active. Delay: see parameter A7 Open contact = defrost not enabled Defrost is activated when the contact closes. Open contact = door open. When the door is opened the compressor, the evaporator fans and the display start to flash; the light is activated and the temperature alarms are deactivated. After an interval of time that can be selected (d8), the buzzer begins to sound and the controller start the normal operation (fan on and compressor on at the occurance) Closed contact = On. This causes the deactivation of the button on the frontal part of the instrument. When the control is off, the temperature is displayed, the protections of the compressor are kept, the LIGHT button keeps working. Contact close = curtain down. With r4=3.0 (value (pre-programmed) the Set Point is increased of 3 degrees with respect to the used value with open curtain. If the auxiliary output is used for lights management, the curtain down switches automatically off the lights while the curtain up switches it on.
4.4.1 Duty setting selection (parameters c4 and A6) If the control probe alarm (E0 flashing) is activated, the parameter c4 allows the compressor to function: c4=value between 1 and 99: sets the compressor On-time (expressed in minutes), followed by a fixed Off-time equal to 15 min; c4=0: compressor always Off; c4=100: compressor always On. If an external alarm (IA or dA flashing) is activated on the digital input (A4=1; A4=2), the parameter A6 allows the compressor to function: A6= value between 1 and 99: sets the compressor On-time (expressed in minutes), followed by a fixed Off-time equal to 15 min; A6=0: compressor always Off; A6=100: compressor always On.
A AH
Ad A4 A5 A6
A7 F F0
ALARM PARAMETERS High temperature alarm (indicates the max. allowed deviation from the Set Point). AH=0 disabled high temperature alarm Temperature alarm delay Digital input n.1 configuration Digital input n.2 configuration Cut-out of compressor by external alarm: 0=OFF,100=ON. Enabled if either A4 or A5 is 1 or 2. See Duty setting and digital input Delay in registration of the input delayed alarm (A4 or A5=2)
+199
C/F
C C C C
0 0 0 0
199 7 7 100
min min
120 0 0 0
199
min
F1
F2 F3 Fd H H0 H1
FAN PARAMETERS Management of fans: 0=always activated except on C specific phases (see parameters F2, F3, and Fd) 1=controlled by a thermostat according to the difference between ambient temp. and evaporator temperature 2=controlled by a thermostat according to the evaporator temperature Fans ON Set-Point: F0=1 fans activated if evap. T. < F (ambient T - F1-A0) and OFF if evap. T. > (ambient T. - F1) F0=2 fans ON if evap. T. < (F1-A0); and OFF with evap. T. > F1 Stop fans when compressor is Off (0=no,1=yes). Active if F0=0 C Stop fans during defrost (0=no,1=yes). Active for any value of F0 Stop after dripping. Active for any value of F0 OTHER SETTINGS Address within network Selection of relay 4 functioning: 0=auxiliary output 1=alarm: normally de-energised relay 2=alarm: normally energised relay 0=buttons inhibited; 2=buttons & IR inhibited; 3=IR inhibited Code to enable remote programming 1=disabled buzzer C F C C
flag
-50
199
C/F
0 0 0 0 0
1 1 15 15 1
1 1 1 1 0
H2 H3 H4
C C C
0 00 0
3 199 1
flag flag
1 00 0
Warning: 1. for parameters indicated with a grey-shaded background, it is recommended to check before installing if the default values are suitable for the required use. 2. for the set times to become operative, the instrument must be swtiched OFF and ON again. 3. on MTCA models the following values have to be assigned to the next parameters: - r3: must be 0 - d0: 2 or 3 (default: d0= 2) - dt: irrilevant - dI: 0. For a more detailed information on parameters, please refer to the IR32 refrigeration manual (+030220170).
Door switch broken or door open Door open for a period of time longer than d8 parameter Control probe error
Flashing E1
Alarm from digital input Delayed alarm from digital input Low temperature alarm (temp. lower than SET - AL - A0) High temperature alarm (temp higher than SET + AH + A0) Data acquisition error. RESET procedure (for mod. MTCA* see point 3 of the Warning chapter 4.5)
Probe not compatible with the equipment; probe cable interrupted or short circuit. Faulty sensor: disconnect the probe from the instrument and measure the resistance (NTC: 0C=27K). Probe not compatible with the equipment; probe cable interrupted or short circuit. Faulty sensor: disconnect the probe from the instrument and measure the resistance (NTC: 0C=27K). Check Multi-function inputs and parameters A4 and A5. Check Multi-function inputs and parameters A4, A5 and A7. Check param.s AL, Ad and A0. The alarm will cease as soon as the temp. returns within the limits selected. Check param.s AH, Ad and A0. The alarm will cease as soon as the temp. returns within the limits selected. In order to restore normal working conditions, reset the default value of the param.s, using this procedure: turn off the control; pressing the button and, keeping it pressed, turn on the controller; the display shows -c-; release the PRG button; after a few seconds, the instrument enters the RESET procedure and allows the modification of parameters;
prg
Flashing Ed
Flashing dF
Defrosting in progress
should EE persist, press the button until the the message disappears. If the error persists, it is necessary to replace the instrument. Any modification made before the reset procedure will be lost Check parameters dt, dP and d4. Check if the defrost was done. if neces. inhibit the Ed alarm through the r3 par. This is not an alarm signal, but it indic. that the instr. is carrying out a defrost. Appears only if par. d6=0.
6. Technical specifications
6.1 General characteristics
operating conditions storage conditions environmental pollution period of stress across the insulating parts PTI of the insulating materials Class of insulation immunity against voltage surges index of protection parameter modification software class and structure display category of resistance to fire and heat number of automatic operating cycles type of action-disconnection signal lights 050C, 2080% r.H. -3070C, 2080% r.H. normal long 250V Class II Category 1 IP65 from keypad, from remote control Class A 2 and a half digits category D 100.000 1B ON, compressor, continuous cycle, defrost, fan, light
2 free, not optically-isolated digital contacts (configurable) cold room temperature probe (Carel NTC 10k at 25C) defrost temperature probe (Carel NTC 10k at 25C) -50T50 (-5050C, -58+122F) 1C 0.1C (0.1F) between -19.9 and 19.9 1C (1 F) in the rest of the field
6.2.2 Outputs If the outputs supply loads other than those described in the table, contact the manufacturer Carel. model relay outputs compressor defrost fans light/aux output alarm output MTCA000100 MTCD000100 MTCD200100 all with 1B type action, according to ECC EN 60730-1 SPST relay, 8(2)A / 250Vac SPST relay, 10(10)A / 250Vac not available SPST relay, 10(4)A / 250Vac not available SPST relay, 4(2)A / 250Vac SPST relay, 4(4)A / 250Vac SPDT relay, 2(2)A / 250Vac
MasterCella compact
PRG
prg
SET SEL
MasterCella
Fig. 6.4.1
Fig. 6.4.2
Carel reserves the right to modify the features of its products without prior notice.