Fire Sprinkler System Fundamental of Design & Installation
Fire Sprinkler System Fundamental of Design & Installation
Fire Sprinkler System Fundamental of Design & Installation
SYSTEM FUNDAMENTALS
Sprinkler heads activate for no reason. Sprinkler heads undergo numerous tests by third-party
testing and certification organizations to ensure that they
maintain stability when standing ready to operate. It is rare
that a sprinkler head accidentally activates unless it has
suffered mechanical damage, exposure to freezing
conditions, or excessive heat not related to a fire.
HOW TO DO IT
WHAT TO DO
REFERENCE
PRODUCT
STANDARDS AND
TEST PROTOCOL
The ceiling jet is approximately 10 percent of the distance from the base of the fire
to the ceiling
• Pressure gauges are a small but important component of the fire sprinkler system. Some systems
only have water gauges, but others also have air gauges. Gauges help fire fighters, sprinkler
system contractors, and building maintenance workers to determine the available water or air
pressure at the gauge location.
• In addition, a gauge can help to determine whether there is a problem with the system if the gauge
reading is outside the normal or expected pressure readings.
• Water gauges are typically installed on the supply and system sides of the various fire sprinkler
system valves and fire pumps, at the tops of standpipes, at the main drain, at each floor level when
feeding a sprinkler system from a standpipe, and on each side of pressure-regulating devices. Air
gauges are installed on the system side of certain fire sprinkler valves, on system air sources, on air
supply lines, and on quick-opening devices.
• Gauges should not be subject to freezing temperatures, should have a shut-off valve, and should be
capable of draining.
• All automatic fire sprinkler system control valves must be indicating-type valves so that a person
can look at the valve and determine if the valve is open, partially open, or shut. In addition, these
valves require identification with a permanent metal or rigid plastic weatherproof sign, which must
identify the area of the building served by that valve (National Fire Protection Association 2019,
NFPA 13, Section 16.9.12.1).
• All indicating valves must be able to handle 175 psi or carry an appropriate rating for an anticipated
pressure above 175 psi. Fully open indicating valves shall not close in less than 5 seconds when
operated at maximum possible speed (National Fire Protection Association 2019, NFPA 13, Section
7.6.1). Indicating valves in fire sprinkler systems are usually 2 in. or larger and include the outside
screw and yoke (OS&Y) valve, butterfly indicator valve, wall post indicator valve (WPIV), and post
indicator valve (PIV)
Supervised control
Monitored
❑ Hydraulic or Electrical;
▪ Standard heads are marked with SSU (standard sprinkler upright) or SSP (standard sprinkler pendent)
on the deflector,
▪ Upright
▪ Pendant
▪ Sidewall
▪ Recessed heads
Sprinklers
Conventional
Fast Response Spray Sprinklers Large Drop
Sprinklers
Residential QR ESFR
Extended Extended
FF Design- Mehboob
Coverage LHShaikh(B.Eng,CFPS, CFI, AMIE) Coverage OH
EDUFIRE.IR Telegram: EDUFIRE.IR
Sprinklers Temperature Rating
The size of the bubble and the expansion rate of the liquid
establish the operating temperature of the sprinkler.
❑ Storage Cabinet;
▪ Extra heads
▪ Sprinkler wrench
NFPA 13 defines “fast-response” and “standard-response” sprinklers based on these RTI values (3.3.205.4):
•Fast response sprinklers have RTIs of 50 or less.
•Standard response sprinklers have RTIs of 80 or less.
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Standard vs QR vs Residential
Q=K√P
• Each size orifice has a K-factor value that applies when performing hydraulic
calculations. For example, a ½-in. orifice has an applied nominal K-factor of 5.6,
a ¾-in. orifice has a nominal K-factor of 14.0, and a 1-in. orifice has a nominal K-
factor of 25.2
Sprinkler head orifices with K-factors of 25.2, 14.0, and 5.6 (from left to right).
❑ Pipes are always filled with water. Heat from fire opens a sprinkler head,
❑ Gauges on both sides of the main valve, register pressure on the supply and system
sides,
❑ A retard chamber prevents sudden pressure surges which could cause a false
alarm,
❑ An alarm check valve detects water flow and activates the alarm system,
❑ There is a main drain valve which drains the system for service,
❑ And an Inspectors TestValve, usually at the end of the system, used to simulate flow
from a single head and to measure the system response.
Clapper Valve
▪ Some occupancies have required systems for life safety, i.e., public assembly, hotels
and high-rises,
▪ Or at least, shut off the closest control valve and leave the rest of the system
operational,
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Wet Pipe Sprinkler
▪ after the fire is completely under control, the closest sectional water control
valve should be closed,
▪ the main control valve should not be closed unless there are no sectional valves,
▪ the sprinkler head(s) are replaced with an identical one from the spares in the
sprinkler control room,
▪ open the Inspectors Test Valve to ensure water is flowing to the topmost sprinkler.
❑ Dry pipe systems are more difficult to design than wet pipe systems and are harder
to restore,
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Dry Pipe Sprinkler
❑ Pipes are not filled with water (but with pressurized gas or air)
❑ Air pressure drops in the piping and opens a water valve (the dry-pipe valve)
❑Water fills the pipes and exits through an open sprinkler head(s),
❑ System is reset,
❑ The clapper valve has a locking mechanism to keep the clapper open until it is reset,
by draining the system, opening the dry pipe valve cover and resetting the lock,
❑ Dry pipe systems are a little slower to activate than wet pipe systems, so most
have either an Exhauster or Accelerator to speed up the system operation,
When dry pipe sprinkler systems are ‘trip tested’ for acceptance, the
following events occur after the inspectors test valve is opened.
1. Air pressure begins to drop in the system as a result of the open
inspectors test valve. The loss of air pressure in the system causes the
dry pipe valve to trip at its designed air/water ratio, or when an
optional accelerator trips the valve on loss of air pressure.
2. When the valve trips, water begins to fill the system by compressing
trapped air and forcing air from the inspector’s test connection.
3. Water reaches the test connection and a steady water discharge is
established.
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
The dry pipe valve trip pressure
• Different models of dry pipe valves trip at different water to air
pressure ratios.
• A typical Water to Air Pressure Ratio = 5.5 : 1
1128.6 gallon (4272 liter) capacity (20 lines by 20 lines sprinklers) 410.8 gallon (1555 liter) capacity (10 lines by 10 lines sprinklers)
• All of the trapped air in the system has to be vented from the
sprinkler prior to water arrival.
• In the smaller system, there are no pockets of air to compress, or
non-flowing volumes for the water front to push the air except out of
the open sprinkler.
• The single open sprinkler cannot exhaust air as fast as the 6"(150mm)
riser can fill the system causing back pressure of air and slowing the
fill rate of water.
• Cl. 7.2.3.1.1 - For dry pipe systems protecting dwelling unit portion of
any occupancy, system size shall be such that initial water is
discharged from the system test connection in not more than 15
seconds, starting at the normal air pressure on the system and at the
time of fully opened inspection test connection
• Cl. 7.2.3.2 System size shall be such that initial water is discharged
from the system test connection in not more than 60 seconds,
starting at the normal air pressure on the system and at the time of
fully opened inspection test connection
Cl. 7.2.3.3 A system size of not more than 500 gal (1893 L) shall be
permitted without a quick-opening device and shall not be required to
meet any specific water delivery requirement to the inspection test
connection.
Cl. 7.2.3.4 A system size of not more than 750 gal (2839 L) shall be
permitted with a quick-opening device and shall not be required to
meet any specific water delivery requirement to the inspection test
connection.
▪ the system has to be drained and the dry pipe valve has to
be reset, this is a complex procedure,
❑ All sprinkler heads are of the standard type (they are closed),
DESIGN FUNDAMENTALS
1 ft 1 ft
15 ft
5 ft
P = 0.433 x 200 ft
200 ft
P = 90.93psi
P=?
P 91 psi
6 ft
Q = A x V = constant flow
X gpm
5.7 ? 3-inch
6-inch
ft/s
• If water is flowing at 5.7 ft/sec in 6-inch pipe, how fast is it flowing when
the pipe size is reduced to 3-inch?
Q = 29.83 di Pv CD
2
• Where:
• Q is the flow (gpm)
• di is the diameter of opening (inches)
• Pv is the measured velocity pressure (psi)
• CD is the discharge coefficient of the device
Q =k P
Q = 5.6 20 psi
Q = 25.0 gpm
• 65 gpm
k=
Q 30 psi
k=
P 65
k= = 11.86
5.48
• Hazen-Williams formula
• Fire sprinkler systems
• Water-spray systems
• Darcy-Weisbach formula
• Anti-freeze systems
• Water mist systems
• Foam-water systems
• Fanning formula
32 ft
1.85 1.85
4.52Q 4.52(110gpm)
PL = 1.85 4.87 = 1.85 4.87
C di (120) (2.067in)
• PL = 0.112 psi/ft
• Friction Loss = 0.112 psi/ft x 32 ft = 3.6 psi
• Gage Pressure = 40 psi – 3.6 psi 36 psi
Fittings & Valves Fittings & Valves Expressed in Equivalent Feet of Pipe
1¼
¾ in 1 in 1 ½ in 2 in 2 ½ in 3 in 3 ½ in 4 in 5 in 6 in 8 in 10 in 12 in
in
45° Elbow 1 1 1 2 2 3 3 3 4 5 7 9 11 12
90° Standard
2 2 3 4 5 6 7 8 10 12 14 18 22 27
Elbow
• What is the equivalent pipe length of Type K copper tube which used
for a 3-inch standard turn 90-degree elbow?
• NFPA 13 Table 23.4.3.1.1 :
• 3-inch 90-degree elbow = 7 ft of pipe
• Adjustments are needed for:
• Type K Copper
• Interior diameter
• What is the equivalent pipe length of Type K copper tube which used
for a 3-inch standard turn 90-degree elbow?
• Adjustment for material (C-factor)
• Copper has a C-Factor of 150
• Per Table 22.4.3.2.1: Multiplier = 1.51
• Adjustment for inside diameter
• 3-inch copper has an inside diameter of 2.907-inch
4.87
4.87
Actual i.d. 2.907
Factor = = = 0.77
Schedule 40 Steel Pipe i.d. 3.068
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Equivalent Length Exercise Solution
(continued)
• What is the equivalent pipe length of Type K copper tube which used
for a 3-inch standard turn 90-degree elbow?
• Apply the factors:
• Equivalent pipe length per Table 22.4.3.1.1 = 7 ft
• Adjustment for C-factor = 1.51
• Adjustment for diameter = 0.77
• The equivalent length for a 3-inch Type K Copper standard turn elbow
is:
7 ft x 1.51 x 0.77 = 8.14 ft
Cross Main
Riser
Branch lines and sprinklers are
fed from only one direction
2
1.2 1500ft
= 4.65 5 sprinkler/line
10ft
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Density/Area Example 2 (continued)
Which sprinklers on the 3rd line should be added?
E 10 5
D 9 4
C 8 3
B 7 2
A 6 1
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Area Adjustments
• Dry-Pipe Systems
• Increase area 30% (Section 11.2.3.2.5)
• Double Interlock Pre-action Systems
• Increase Area 30% (Section 11.2.3.2.5)
• Extra Hazard Occupancy with High Temperature Sprinklers
• Decrease Area 25%, but minimum of 2000 ft2 (Section 11.2.3.2.6)
• Sloped Ceilings
• Area of operation is increased by 30% if pitch exceeds 2 in 12 (rise in run). This is
an angle of 9.46°
rise
run
EDUFIRE.IR FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE) Telegram: EDUFIRE.IR
Multiple Adjustments Example 1
• Compound adjustments based on original area of operation selected
from Figure 11.2.3.1.1.
• Dry-pipe system installed under slope of 4 in 12
• 30% increase for dry system
• 30% increase for slope
• Using 1500 ft2 as the selected operation area
• 1500 ft2 x 1.3 x 1.3 = 2535 ft2 design area
• There is no change in the density.
The logic of examining only the set number of heads at the most
remote portion of the building is as follows:
Keeping pipe diameters and minimum water flow requirements the same
throughout the building, because of physics and hydraulics, if the minimum
required water pressure and gpm are met at the most remote section of the
building, as you move closer to the riser, water pressure and gpm will
automatically be greater
38 ft
80 ft
12.5 ft
5.5 ft
5 ft
5 ft
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Example (continued)
38 ft
80 ft
12.5 ft
5.5 ft
5 ft
5 ft
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Determine the Starting Pressure
• Most remote sprinkler needs 25 gpm
• Sprinkler k = 5.6
2 2
Q 25
P= = = 19.9psi
k 5.6
• Starting information for the first sprinkler:
• 25 gpm at 19.9 psi
• Next work back to the water supply adding pressure
losses and flows throughout the system
38 ft
BL1 BL2
TOR
4 8
12.5 ft
3 7
5.5 ft
2 6
5 ft
1 5 5 ft
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Full System Hydraulic Calculation
• An electronics factory is being built.
• Water supply tests were done near the site and produced the
following information:
• Static pressure = 90 psi
• Residual pressure = 60 psi
• Flow at 60 psi = 1000 gpm
Water Supply
120
Flow Test
110 Summary Sheet
90 psi static
100
pressure
90
80
60 psi residual
70 pressure at 1000 gpm
Pressure (psi)
60
50
40
30
20
10
0
100 200 300 400 500 600 700 800 900 1000 1100
Flow (gpm)
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
The Layout Process
1. Define the Hazard
2. Analyze the Structure
3. Analyze the Water Supply
4. Select the Type of System
5. Select the Sprinkler Type(s) and Locate Them
6. Arrange the Piping
7. Arrange Hangers and Bracing (where needed)
8. Include System Attachments
9. Hydraulic Calculations
10. Notes and Details for Plans
11. As-Built Drawings
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
System Details
• Type of System:
• Wet pipe system
• Type of Sprinkler: TY3121
• Standard spray quick response upright sprinkler with a K-factor of 5.6
• Typical Sprinkler Spacing:
• Sprinklers are 10 ft apart on the branch lines, and 12.5 ft between branch
lines
10 ft 12.5
ft
53 ft
Mains are
Schedule 10
100 ft
200 ft
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Electronics Factory Elevation View
15 ft
18 ft
5 ft
4-inch PVC
(ID – 4.240 inches)
7 ft
Long Turn
Elbow 42 ft
1-inch
1 ¼-inch
1 ¼-inch
1 ½-inch
1 ½-inch 1 ft riser nipple
1 ½-inch
15 ft
N
Underground
4-inch PVC
2
1.2 1080 ft
= 3.94 4 sprinklers
10 ft
• Continue to add branch lines until 9 sprinklers are
included
53 ft
4 8 9 Mains are
Schedule 10
100 ft
ft Schedule 40
200 ft
FF Design- Mehboob Shaikh(B.Eng,CFPS, CFI, AMIE)
EDUFIRE.IR Telegram: EDUFIRE.IR
Information Needed for Calculations
completed
1. Select initial pipe sizes
2. Locate nodes on all places where:
a) Flow (Q) takes place,
b) Type of pipe or system changes (C), and
c) Diameter (di) changes.
3. Layout calculation paths starting with primary path then
attachment paths
4. Fill in hydraulic calculation sheets
1-inch 15
1 ¼-inch 26
1 ¼-inch 37
1 ½-inch 4 89
1 ½-inch 1 ft riser nipple
1 ½-inch
TOR
main and riser
3-inch
15 ft
N
FF
Underground
4-inch PVC
D A
The “Four Times Rule” is really just an extension of the “three times rule” however
it covers extended coverage sprinklers and the maximum clearance is 36 inches
(0.9144 m).
For obstructions wider than 4 feet (1.2192 m), sprinkler protection is required
below the obstruction with deflectors to be located less than 12 inches (0.3048 m)
from the bottom of the obstruction.
For obstructions less than 4 feet (1.2192 m) in width sprinklers may not be required
underneath the obstruction
Ceiling
Ceiling
Horizontal Distance
Sprinkler Deflector.
Ceiling Object Located Below
Maximum Vertical Distance of
Obstruction are not permitted to
cross from shaded area into this
area
35 Inch
1 inch.
Sprinkler Deflector.
Ceiling Object Located Below
Maximum Vertical Distance of
Obstruction are not permitted to
cross from shaded area into this
area
14 Inch.
Deflector.
Object Located Below Sprinkler
Maximum Vertical Distance of Ceiling
Obstruction are not permitted to
cross from shaded area into this
area
21 Inch
1 inch.
Sprinkler Deflector.
Ceiling Object Located Below
Maximum Vertical Distance of
Obstruction are not permitted to
cross from shaded area into this
area
14 Inch.
Deflector.
Object Located Below Sprinkler
Maximum Vertical Distance of Ceiling
Obstruction are not permitted to
cross from shaded area into this
area
14 Inch
1 inch.
Sprinkler Deflector.
Ceiling Object Located Below
Maximum Vertical Distance of
Obstruction are not permitted to
cross from shaded area into this
area
14 Inch.
Deflector.
Object Located Below Sprinkler
Maximum Vertical Distance of Ceiling
Obstruction are not permitted to
cross from shaded area into this
area
31 Inch
Deflector.
Object Located Below Sprinkler
Maximum Vertical Distance of Ceiling
Obstruction are not permitted to
cross from shaded area into this
area
31 Inch
226
EDUFIRE.IR Telegram: EDUFIRE.IR
Thank You