Module 3 - Basic Components of AFSS2
Module 3 - Basic Components of AFSS2
AFSS BRIEF
With Fire Sprinkler System, the combustion Per NFPA research, Sprinkler
of products is controlled if extinguished at controls 70% of all fires with five
incipient stage of fire. or fewer sprinklers activated.
2012 PME Code: Automatic Fire Sprinkler System is an
integrated system of underground and overhead piping
designed in accordance with the fire protection engineering
standards
Automatic sprinklers
are connected in a
systematic pattern.
Pipes are always filled with water. Heat from fire opens a sprinkler head.
Usually only one or two heads open.
Water flows until it is manually shut off.
The open sprinkler head(s) is replaced and the system is reset.
A check valve prevents water from re-entering the water supply.
Gauges on both sides of the main valve, register pressure on the supply
and system sides.
A retard chamber prevents sudden pressure surges which could cause a
false alarm.
An alarm check valve detects water flow and activates the alarm system.
There is a main drain valve which drains the system during maintenance.
An Inspectors Test Valve, usually at the end of the system, used to simulate
flow from a single head and to measure the system response.
Wet Pipe Sprinkler
A one-way clapper prevents water
from re-entering the water supply,
Major drawback:
1. Cannot be used
in areas where
temperatures
drop below
freezing
Fire suppression
agent may be water
or foam.
A deluge valve is
activated by a fire
detection system
installed in the same
area as the sprinklers.
Pipes in protected area are empty, it is not filled with water (or gas).
A detector signal triggers the system, allowing water/foam to enter pipes and
flow from all sprinkler heads (which are already open).
If a pipe breaks in one of your fire sprinkler systems, water does not flow
into the system. In this situation a trouble alarm will be triggered due to
the loss of air pressure in the pipe and compressed air will be released
from the pipe, not water.
4. Automatic Sprinkler
2. Fire Pump System
System
Branch lines - the pipe in which the sprinklers are placed, either directly or through risers.
Sprinkler System Component
A. Riser - The main supply pipes in a sprinkler system
CPVC
Nonmetallic piping specification for special listed
chlorinated polyvinyl chloride (CPVC) pipe ASTM F 442
1. Wet Pipe Sprinkler System
– Fittings
Fittings used in
sprinkler
systems shall
meet or exceed
the standards in
Table 6.4.1.
Listing SprinklerSystem Component –
General Requirements
6.1.1.2 Unless the requirements of 6.1.1.3, 6.1.1.4, or
6.1.1.5 are met, all materials and devices essential to
successful system operation shall be listed.
6.8.1 General
Water flow alarm apparatus shall be listed for the service and so
constructed and installed that any flow of water from a sprinkler system
equal to or greater than that from a single automatic sprinkler of the
smallest orifice size installed on the system will result in an audible
alarm on the premises within 5 minutes after such flow begins and until
such flow stops.
Retard Chamber
Brand : Tyco
Model : AV-1-300 Alarm Check Valve
Working Water Pressure Range: 20 to 300 psi (1.4 to 20.7 bar)
Size and connection : 150 mm, ANSI B16.5, Class150
Restriction Assy Main Drain Valve Supply Pressure Gauge
• 8.2.4.3 The floor control valve, check valve, main drain valve, and
flow switch required by 8.2.4.1 shall not be required where the total
area of all floors combined does not exceed the system protection
area limitations of 8.2.1.
Floor Control Valve
Zone Or Floor Control Valve Assembly
It must be installed for multi-level building so that each floor or zone can be shut off
if necessary and the rest of the system will remain operational.
Pressure gauges shall be installed on the inlet and outlet sides of each
pressure-reducing valve.
1. Sprinkler heads.
Maximum Sprinkler
Celing Temperature Sprinkler
Sprinkler Glass Bulb
Temperature Rating Frame Color
Classification Color Code
Code
F C F C
Uncolored or Orange or
100 38 135-170 57-77 Ordinary
Black Red
Yellow or
150 66 175-225 79-107 Intermediate White
Green
225 107 250-300 121-149 High Blue Blue
300 149 325-375 163-191 Extra High Red Purple
Very Extra
375 190 400-475 204-246 Green Black
High
475 246 500-575 250-302 Ultra High Orange Black
625 329 650 343 Ultra High Orange Black
Automatic fire sprinklers can be classified and described
based on 5 characteristics:
1. Orifice size
2. Installation
orientation
and deflector
3. Temperature
rating
4. Thermal
sensitivity
5. Special service
conditions
Upright Sprinkler – it is to be installed in such a way that the
water spray is directed upwards against the deflector.
Pendent Sprinkler - designed to be installed in such a way
that the water stream is directed downward against the
deflector.
Brand : Potter
Model : PS10-1
Type : Pressure type, water flow indicator
Pressure Connection: 1/2" NPT
Maximum System Pressure: 300 PSI (20,68 BAR)
Switch Contacts: One SPDT , 2.0 Amps at 30VDC
Flow switches are fitted with a mechanical delay (up to six minutes)
preventing small or minor water flow fluctuations from signalling an
alarm.
Tamper/Supervisory Switch is used to monitor the open position of an OS&Y
type gate valve.
Brand: Cla-Val
Model:3410-AR116.3
Maximum Pressure
Rating: 300 psi
Size: 25 mm
OS&Y Gate
Valve
Wye Strainer
Relief Valve Line to Storm Drain Expansion Coupling and Pipe Support
Pump Flow Test Line
Minimum supply –
to highest sprinkler
at 15psi
Flow depends on –
hazard, occupancy,
building contents
Jockey Pump, also called Pressure Maintenance Pump, keeps the system
pressure to the design high level pressure to prevent the main fire pump from
operating. Leakage or operation of a single fire sprinkler causing pressure
drop will cause an automatic start of the pump.
Standpipe Systems
Class I Standpipes
a. Concealed Sprinkler is a
recessed sprinkler with cover plates.
These are decorative sprinklers
featuring a flat cover plate designed
to conceal the sprinkler. It is the best
choice for architecturally sensitive
areas such as hotel lobbies, office
buildings, churches & restaurants. Brand : Tyco
Model : TY 3551
K -factor : 5.6
Bulb Temp. : 68 C / 155 F
Cover Temp: 59 C / 139 F
Class : Standard
Concealed Pendent
Listing : UL FM LPCB
b. Flush Sprinkler is a sprinkler in
which all or part of the body,
including the shank thread, is
mounted above the lower plane of
the ceiling
c. Pendent Sprinkler is a sprinkler
designed to be installed in such a way that
the water stream is directed downward
against the deflector.