CONTENTS
CONTENTS...........................................................................................................................1
Safety Precautions ................................................................................................................3
1. INTRODUCTION ............................................................................................................4
1.1 Technology Features .............................................................................................4
1.2 Description of Name Plate ..................................................................................5
1.3 Selection Guide .....................................................................................................6
1.4 Parts Description ...................................................................................................8
1.5 Description of Extension Card ..............................................................................9
1.6 External Dimensions ........................................................................................... 11
2. UNPACKING INSPECTION .........................................................................................13
3. DISASSEMBLE AND INSTALLATION.........................................................................14
3.1 Environmental Requirement ...............................................................................14
3.2 Installation Space ................................................................................................16
3.3 Dimensions of External Keypad..........................................................................17
3.4 Disassembly ........................................................................................................17
4. WIRING.........................................................................................................................19
4.1 Connections of Peripheral Devices ....................................................................20
4.2 Terminal Configuration ........................................................................................21
4.3 Typical Wiring Diagram .......................................................................................22
4.4 Specifications of Breaker, Cable, Contactor and Reactor..................................23
4.5 Wiring the Main Circuits ......................................................................................28
4.6 Wiring Control Circuit Terminals .........................................................................31
4.7 Installation Guidline to EMC Compliance ...........................................................33
5. OPERATION.................................................................................................................37
5.1 Operating Keypad Description ............................................................................37
5.2 Operation Process...............................................................................................39
5.3 Running State ......................................................................................................42
5.4 Quick Start ...........................................................................................................44
6. DETAILED FUNCTION DESCRIPTION ......................................................................45
6.1 P0 Group--Basic Function...................................................................................45
6.2 P1 Group--Start and Stop Control.......................................................................54
6.3 P2 Group--Motor Parameters .............................................................................59
6.4 P3 Group--Vector Control ...................................................................................60
.1.
CHV100 Series Close Loop Vector Control Inverter
.2.
CHV100 Series Close Loop Vector Control Inverter
1. INTRODUCTION
1.1 Technology Features
● Input & Output
u Input Voltage Range: 1140/690/380/220V±15%
u Input Frequency Range: 47~63Hz
u Output Voltage Range: 0~ input voltage rating
u Output Frequency Range: 0~400Hz
● I/O Features
u Programmable Digital Input: Provide 5 terminals which can accept ON-OFF
inputs, and 1 terminal which can accept high speed pulse input (HDI1). 4 inputs
can be extended by I/O extension card.
u Programmable Analog Input: AI1 can accept input of 0 ~10V, AI2 can accept input
of 0~10V or 0~20mA. AI3 (-10V~10V) and AI4 (0~10V or 0~20mA) can be
extended by I/O extension card.
u Programmable Open Collector Output: Provide 1 output terminal. 1 output (open
collector output or high speed pulse output) can be extended by I/O extension
card.
u Relay Output: Provide 2 output terminals. 1 output can be extended by I/O
extension card.
u Analog Output: Provide 1 output terminal, whose output scope can be 0/4~20 mA
or 0~10 V, as chosen. 1 AO (0/4~20mA or 0/2~10V) can be extended by I/O card.
● Main Control Function
u Control Mode: Sensorless vector control (SVC), Vector control with PG (VC), V/F
control.
u Overload Capacity: 60s with 150% of rated current, 10s with 180% of rated
current.
u Starting Torque: 150% of rated torque at 0.5Hz (SVC); 180% of rated torque at
0Hz (VC).
u Speed Adjusting Range: 1:100 (SVC); 1:1000 (VC)
u Speed Accuracy: ± 0.5% of maximum speed (SVC); ± 0.1% of maximum speed
(VC)
u Carrier Frequency: 1.0 kHz~16.0 kHz.
u Frequency reference source: keypad, analog input, HDI, serial communication,
.4.
Company name SHENZHEN INVT ELECTRIC CO.
,LTD
Power POWER:45kW
.7.
CHV100 Series Close Loop Vector Control Inverter
.8.
CHV100 Series Close Loop Vector Control Inverter
.9.
CHV100 Series Close Loop Vector Control Inverter
.10.
CHV100 Series Close Loop Vector Control Inverter
.12.
CHV100 Series Close Loop Vector Control Inverter
.18.
CHV100 Series Close Loop Vector Control Inverter
P1 (+) (-)
R S T U V W
P1 (+) (-)
Terminal of ground
.21.
CHV100 Series Close Loop Vector Control Inverter
.23.
CHV100 Series Close Loop Vector Control Inverter
.25.
CHV100 Series Close Loop Vector Control Inverter
Braking resistor
Braking unit
Model No. (100% braking torque)
Order No. Quantity Specification Quantity
3AC 380V ±15%
CHV100-1R5G-4 400Ω/260W 1
CHV100-2R2G-4
150Ω/390W 1
CHV100-004G-4
CHV100-5R5G-4 Build- in 1 100Ω/520W 1
CHV100-7R5G-4
50Ω/1040W 1
CHV100-011G-4
CHV100-015G-4 40Ω/1560W 1
CHV100-018G-4
CHV100-022G-4 20Ω/6000W 1
CHV100-030G-4
DBU-055-4 1
CHV100-037G-4
CHV100-045G-4 13.6Ω/9600W 1
CHV100-055G-4
CHV100-075G-4
CHV100-090G-4 DBU-055-4 2 13.6Ω/9600W 2
CHV100-110G-4
CHV100-132G-4
DBU-160-4 1 4Ω/30000W 1
CHV100-160G-4
CHV100-185G-4
CHV100-200G-4 DBU-220-4 1 3Ω/40000W 1
CHV100-220G-4
CHV100-250G-4
CHV100-280G-4 DBU-315-4 1 3Ω/40000W 2
CHV100-315G-4
Notice:
1. Above selection is based on following condition: 700V DC braking voltage
threshold, 100% braking torque and 10% usage rate.
2. Parallel connection of braking unit is helpful to improve braking capability.
3. Wire between inverter and braking unit should be less than 5m.
4. Wire between braking unit and braking resistor should be less than 10m.
.26.
CHV100 Series Close Loop Vector Control Inverter
5. Braking unit can be used for braking continuously for 5 minutes. When
braking unit is working, temperature of cabinet will be high, user is not
allowed to touch to prevent from injury.
For more details, please refer to DBU and RBU user manual.
4.4.4 Specification of input filter and output filter
Model No. Input Filter Output Filter
CHV100-1R5G-4 NFI-005 NFO-005
CHV100-2R2G-4 NFI-010 NFO-010
CHV100-004G-4 NFI-010 NFO-010
CHV100-5R5G-4 NFI-020 NFO-020
CHV100-7R5G-4 NFI-020 NFO-020
CHV100-011G-4 NFI-036 NFO-036
CHV100-015G-4 NFI-036 NFO-036
CHV100-018G-4 NFI-050 NFO-050
CHV100-022G-4 NFI-050 NFO-050
CHV100-030G-4 NFI-065 NFO-065
CHV100-037G-4 NFI-080 NFO-080
CHV100-045G-4 NFI-100 NFO-100
CHV100-055G-4 NFI-150 NFO-150
CHV100-075G-4 NFI-150 NFO-150
CHV100-090G-4 NFI-200 NFO-200
CHV100-110G-4 NFI-250 NFO-250
CHV100-132G-4 NFI-250 NFO-250
CHV100-160G-4 NFI-300 NFO-300
CHV100-185G-4 NFI-400 NFO-400
CHV100-200G-4 NFI-400 NFO-400
CHV100-220G-4 NFI-600 NFO-600
CHV100-250G-4 NFI-600 NFO-600
CHV100-280G-4 NFI-900 NFO-900
CHV100-315G-4 NFI-900 NFO-900
CHV100-350G-4 NFI-1200 NFO-1200
CHV100-400G-4 NFI-1200 NFO-1200
.27.
CHV100 Series Close Loop Vector Control Inverter
.28.
CHV100 Series Close Loop Vector Control Inverter
• Inverters of 15KW and below have built-in braking unit. In order to dissipate the
regenerative energy generated by dynamic braking, the braking resistor should be
installed at (+) and PB terminals. The wire length of braking resistor should be less than
5m.
• Inverter of 18.5KW and above need connect external braking unit which should be
installed at (+) and (-) terminals. The cable between inverter and braking unit should be
less than 5m. The cable between braking unit and braking resistor should be less than
10m.
• The temperature of braking resistor will increase because the regenerative energy will
be transformed into heat. Safety protection and good ventilation is recommended.
Notice: Be sure that the electric polarity of (+) (-) terminals is right; it is not allowed
to connect (+) with (-) terminals directly, Otherwise damage or fire could occur.
4.5.3 Wiring at motor side of main circuit
l Output Reactor
When the distance between inverter and motor is more than 50m, inverter may be
tripped by over-current protection frequently because of the large leakage current
resulted from the parasitic capacitance with ground. And the same time to avoid the
damage of motor insulation, the output reactor should be installed.
l Output EMC filter
EMC filter should be installed to minimize the leakage current caused by the cable and
minimize the radio noise caused by the cables between the inverter and cable. Just see
the following figure.
.29.
CHV100 Series Close Loop Vector Control Inverter
.30.
CHV100 Series Close Loop Vector Control Inverter
Terminal Description
Input impedance: 3.3kΩ
High speed pulse or ON-OFF signal input, optical coupling with PW
and COM.
HDI1(HDI2) Pulse input frequency range: 0~50kHz
Input voltage range: 9~30V
Input impedance: 1.1kΩ
External power supply. +24V terminal is connected to PW terminal
as default setting. If user need external power supply, disconnect
PW
+24V terminal with PW terminal and connect PW terminal with
external power supply.
Provide output power supply of +24V.
+24V
Maximum output current: 150mA
Analog input, 0~10V
AI1(AI3,AI4)
Input impedance: 10kΩ
Analog input, 0~10V/ 0~20mA, switched by J18.
AI2
Input impedance:10kΩ (voltage input) / 250Ω (current input)
Common ground terminal of analog signal and +10V.
GND
GND must isolated from COM.
Open collector output terminal, the corresponding common ground
terminal is CME.
Y1(Y2) External voltage range: 0~24V
Output current range: 0~50mA
The range of 24V pull-up resistor: 2k~10kΩ
CME Common terminal of open collector output
Common ground terminal for digital signal and +24V (or external
COM
power supply).
+10V Supply +10V for inverter.
High speed pulse output terminal. The corresponding common
HDO ground terminal is COM.
Output frequency range: 0~50 kHz
Provide voltage or current output which can be switched by J19.
AO1(AO2)
Output range: 0~10V/ 0~20mA
PE Ground Terminal.
RO1A、RO1B、 RO1 relay output: RO1A—common; RO1B—NC; RO1C—NO.
.32.
CHV100 Series Close Loop Vector Control Inverter
Terminal Description
RO1C Contact capacity: AC 250V/3A, DC 30V/1A.
RO2A、RO2B、 RO2 relay output: RO2A—common; RO2B—NC; RO2C—NO.
RO2C Contact capacity: AC 250V/3A, DC 30V/1A.
RO3A、RO3B、 RO3 relay output: RO3A—common; RO3B—NC; RO3C—NO.
RO3C Contact capacity: AC 250V/3A, DC 30V/1A.
4.6.3 Jumper on control board
Jumper Description
J2, J4, J5, It is prohibited to be connected together, otherwise it will cause
J13, J14 inverter malfunction.
Switch between (0~10V) voltage input and (0~20mA) current input.
J18 V connect to GND means voltage input;
I connected with GND means current input.
Switch between (0~10V) voltage output and (0~20mA) current
output.
J19
V connected with OUT means voltage output;
I connected with OUT means current output..
.33.
CHV100 Series Close Loop Vector Control Inverter
.34.
CHV100 Series Close Loop Vector Control Inverter
.35.
CHV100 Series Close Loop Vector Control Inverter
wire, can not only flow into inverter system but also other devices. It also can make
leakage current circuit breaker, relay or other devices malfunction. The value of
line-to-line leakage current, which means the leakage current passing through
distributed capacitors of input output wire, depends on the carrier frequency of inverter,
the length and section areas of motor cables. The higher carrier frequency of inverter,
the longer of the motor cable and/or the bigger cable section area, the larger leakage
current will occur.
Countermeasure:
Decreasing the carrier frequency can effectively decrease the leakage current. In the
case of motor cable is relatively long (longer than 50m), it is necessary to install AC
reactor or sinusoidal wave filter at the output side, and when it is even longer, it is
necessary to install one reactor at every certain distance.
4.7.3.5 EMC Filter
EMC filter has a great effect of electromagnetic decoupling, so it is preferred for
customer to install it.
For inverter, noise filter has following categories:
l Noise filter installed at the input side of inverter;
l Install noise isolation for other equipment by means of isolation transformer or
power filter.
4.7.4 If user install inverter and EMI filter according to the installation guideline, we
believe inverter system comply with following compliance.
l EN61000-6-4
l EN61000-6-3
l EN61800-3
.36.
CHV100 Series Close Loop Vector Control Inverter
5. OPERATION
5.1 Operating Keypad Description
5.1.1 Keypad schematic diagram
UP Increment
Progressively increase data or function codes.
Key
DOWN
Decrement Progressive decrease data or function codes.
Key
In parameter setting mode, press this button to select
Shift Key the bit to be modified. In other modes, cyclically
displays parameters by right shift
.37.
CHV100 Series Close Loop Vector Control Inverter
.38.
CHV100 Series Close Loop Vector Control Inverter
.39.
CHV100 Series Close Loop Vector Control Inverter
UP/DOWN to select different shortcut parameter, and then press DATA/ENT to enter the
shortcut second-level menu. The method to modify parameter at the shortcut
second-level menu is the same as that at the general third-level menu. If want to return
to last display, press QUICK/JOG.
The operation example is as following:
.41.
CHV100 Series Close Loop Vector Control Inverter
.42.
CHV100 Series Close Loop Vector Control Inverter
collector output status, PID setting, PID feedback, AI1 voltage, AI2 voltage, AI3
voltage/current, AI4 voltage, HDI1 frequency, HDI2 frequency, step number of simple
PLC or multi-step speed, length value. Whether or not to display can be determined by
setting the corresponding binary bit of P7.07. Press the 》/SHIFT to scroll through the
parameters in right order . Press DATA/ENT + QUICK/JOG to scroll through the
parameters in left order.
5.3.3 Operation
In running status, there are twenty one running parameters which can be chosen to
display or not. They are: running frequency, reference frequency, DC bus voltage, output
voltage, output current, rotating speed, output power, output torque, PID setting, PID
feedback, ON-OFF input status, open collector output status, length value, count value,
step number of PLC or multi-step speed, AI1 voltage, AI2 voltage, AI3 voltage/current,
AI4 voltage, HDI1 frequency, HDI2 frequency. Whether or not to display can be
determined by setting the corresponding binary bit of P7.06. Press the 》/SHIFT to scroll
through the parameters in right order . Press DATA/ENT + QUICK/JOG to scroll through
the parameters in left order.
5.3.4 Fault
In fault status, inverter will display parameters of STOP status besides parameters of
fault status. Press the 》/SHIFT to scroll through the parameters in right order . Press
DATA/ENT + QUICK/JOG to to scroll through the parameters in left order.
.43.
Start
Operation is OK
End
CHV100 Series Close Loop Vector Control Inverter
.45.
CHV100 Series Close Loop Vector Control Inverter
The control commands of inverter include: start, stop, forward run, reverse run, jog, fault
reset and so on.
0: Keypad (LED extinguished);
Both RUN and STOP/RST key are used for running command control. If Multifunction
key QUICK/JOG is set as FWD/REV switching function (P7.03 is set to be 1), it will be
used to change the rotating orientation. In running status, pressing RUN and
STOP/RST in the same time will cause the inverter coast to stop.
1: Terminal (LED flickering)
The operation, including forward run, reverse run, forward jog, reverse jog etc. can be
controlled by multifunctional input terminals.
2: Communication (LED lights on)
The operation of inverter can be controlled by host through communication.
Function Setting Factory
Name Description
Code Range Setting
0: Valid, save UP/DOWN
value when power off
1: Valid, do not save
UP/DOWN UP/DOWN value when
P0.02 0~2 0
setting power off
2: Invalid
3: Valid during running,
clear when power off
0: Valid, save UP/DOWN value when power off.
User can adjust the reference frequency by UP/DOWN. The value of UP/DOWN can be
saved when power off.
1: Valid, do not save UP/DOWN value when power off.
User can adjust the reference frequency by UP/DOWN, but the value of UP/DOWN will
not be saved when power off.
2: Invalid.
User can not adjust the reference frequency by UP/DOWN. The value of UP/DOWN will
be cleared if P0.02 is set to 2.
3: Valid during running, clear when power off
User can adjust the reference frequency by UP/DOWN when inverter is running. When
inverter power off, the value of UP/DOWN will be cleared
Notice:
.46.
CHV100 Series Close Loop Vector Control Inverter
.47.
CHV100 Series Close Loop Vector Control Inverter
.48.
CHV100 Series Close Loop Vector Control Inverter
2. HDI2
The principle is the same as AI1.
Function Setting Factory
Name Description
Code Range Setting
0: A
Frequency
1: B
P0.06 command 0~3 0
2: A+B
selection
3: Max(A, B)
This parameter can be used to select the reference frequency command.
0: Only frequency command source A is active.
1: Only Frequency command source B is active.
2: Both Frequency command source A and B are active.
Reference frequency = reference frequency A + reference frequency B.
3: Either Frequency command source A or B is active.
Reference frequency = Max (reference frequency A, reference frequency B).
Notice: The frequency command source can be selected not only P0.06 but also
by multifunctional terminals. Please refer to description of P5 Group.
.49.
CHV100 Series Close Loop Vector Control Inverter
.52.
CHV100 Series Close Loop Vector Control Inverter
.53.
CHV100 Series Close Loop Vector Control Inverter
and finally LED displays the same as stop status. When “-TUN-” is flickering,
autotune can be quited by pressing PRG/ESC.
During autotune, pressing STOP/RST can stop the autotune.
Notice: Only keypad can control the autotuning. P0.17 will restore to 0
automatically when the autotuning is finished or cancelled.
2: Static autotuning:
l If it is difficult to disconnect the load, static autotuning is recommended.
l The operation process is the same as rotation autotuning except step c.
Notice: The Mutual inductance and current without load will not be detected by
static autotuning, if needed user should input suitable value according to
experience.
Function Setting Factory
Name Description
Code Range Setting
0: No action
1: Restore factory setting
Restore
P0.18 2: Clear fault records 0~3 0
parameters
3:Restore parameters for
injection molding machine
0: No action
1: Inverter restores all parameters to factory setting except P2 group.
2: Inverter clear all fault records.
3: Inverter restores special parameters for injection molding machine.
This function code will restore to 0 automatically when complete the function operation.
.54.
CHV100 Series Close Loop Vector Control Inverter
then start running to its reference frequency based on current speed. This can realize
smooth start of rotating motor with big inertia load when instantaneous power off.
Notice: It only applies on the inverter of 7.5kW and above.
Function Setting Factory
Name Description
Code Range Setting
P1.01 Starting frequency 0.00~10.0Hz 0.00~10.00 0/1.5Hz
Hold time of
P1.02 0.0~50.0s 0.0~50.0 0.0s
starting frequency
The inverter runs from the Starting frequency. After hold time of starting frequency, the
inverter will accelerate to the setting frequency according to the setting acceleration time.
If the setting frequency is smaller than starting frequency, the inverter stands by. Starting
frequency is not limited by lower frequency limit
Notice: When sensorless vector control or V/F control is active, factory setting of
P1.01 is 1.5HZ, while factory setting is 0 HZ on condition of vector control.
.56.
CHV100 Series Close Loop Vector Control Inverter
.57.
CHV100 Series Close Loop Vector Control Inverter
.58.
CHV100 Series Close Loop Vector Control Inverter
1: Stop: This parameter is used to prevent motor running at low speed for a long time.
2: Stand-by: Inverter will stand-by when the running frequency is less than P0.09. When
the reference frequency is higher than or equal to P0.09 again, the inverter will start to
run automatically.
Function Setting Factory
Name Description
Code Range Setting
Restart after 0: Disabled
P1.15 0~1 0
power off 1: Enabled
Delay time for
P1.16 0.0~3600.0s 0.0~3600.0 0.0s
restart
0: Disabled: Inverter will not automatically restart when power on again until run
command takes effect.
1: Enabled: When inverter is running, after power off and power on again, if run
command source is keypad control (P0.01=0) or communication control (P0.01=2),
inverter will automatically restart after delay time determined by P1.16; if run command
source is terminal control (P0.01=1), inverter will automatically restart after delay time
determined by P1.16 only if FWD or REV is active.
Notice:
l If P1.15 is set to be 1, it is recommended that start mode should be set as
speed tracing mode (P1.00=2).
l This function may cause the inverter restart automatically, please be
cautious.
.59.
CHV100 Series Close Loop Vector Control Inverter
.61.
CHV100 Series Close Loop Vector Control Inverter
The system's dynamic response can be faster if the proportion gain K p is increased;
However, if Kp is too large, the system tends to oscillate.
The system dynamic response can be faster if the integral time Ki is decreased;
However, if Ki is too small, the system becomes overshoot and tends to oscillate.
P3.00 and P3.01 are corresponding to Kp and Ki at low frequency, while P3.03 and P3.04
are corresponding to K p and Ki at high frequency. Please adjust these parameters
according to actual situation. The adjustment procedure is as follow:
l Increase the proportional gain (Kp) as far as possible without creating oscillation.
l Reduce the integral time (Ki) as far as possible without creating oscillation.
For more details about fine adjustment, please refer to description of P9 group.
Function Setting Factory
Name Description
Code Range Setting
ACR proportional
P3.06 0~65535 0~65535 500
gain P
P3.07 ACR integral gain I 0~65535 0~65535 500
The bigger the proportional gain P, the faster the response, but oscillation may easily
occur. If only proportional gain P is applied in regulation, the bias cannot be eliminated.
In order to eliminate the bias, apply the integral gain I to achieve PI regulator.
Function Setting Factory
Name Description
Code Range Setting
Speed detection
P3.08 0.00~5.00s 0.00~5.00 0.00s
filter time
The noise along with speed detection signals can be filtered by setting the time constant
of filter (P3.08). The bigger the time constant, the better the immunity capability, but the
response becomes slow, vice versa.
Function Setting Factory
Name Description
Code Range Setting
Slip compensation
P3.09 50.0~200.0% 50~100 100%
rate of VC
The parameter is used to adjust the slip frequency of vector control and improve the
precision of speed control. Properly adjusting this parameter can effectively restrain the
static speed bias.
Function Setting Factory
Name Description
Code Range Setting
P3.10 PG parameter 1~65535 1~65535 1000
.62.
CHV100 Series Close Loop Vector Control Inverter
.63.
CHV100 Series Close Loop Vector Control Inverter
.64.
CHV100 Series Close Loop Vector Control Inverter
.66.
CHV100 Series Close Loop Vector Control Inverter
load change can be reduced. The value of compensated slip is dependent on the motor’s
P 4.09 = fb − n * P / 60 .
rated slip which can be calculated as: Where fb is
motor rated frequency (P2.01), n is motor rated speed (P2.02), and P is pole pairs of
motor.
Function Setting Factory
Name Description
Code Range Setting
0: Disabled
1: Enabled all the time
P4.10 AVR function 0~2 1
2: Disabled during
deceleration
AVR ( Auto Voltage Regulation) function ensure the output voltage of inverter stable no
matter how the DC bus voltage changes. During deceleration, if AVR function is disabled,
the deceleration time will be short but the current will be big. If AVR function is enabled
all the time, the deceleration time will be long but the current will be small.
Function Setting Factory
Name Description
Code Range Setting
Auto energy 0: Disabled
P4.11 0~1 0
saving selection 1: Enabled
When P4.11 is set to be 1, while there is a light load, it will reduce the inverter output
voltage and saves energy.
Function Setting Factory
Name Description
Code Range Setting
FWD/REV enable
0: Disabled
P4.12 option when 0~1 0
1: Enabled
power on
Notice:
l This function only takes effect if run command source is terminal control.
l If P4.12 is set to be 0, when power on, inverter will not start even if FWD/REV
terminal is active, until FWD/REV terminal disabled and enabled again.
l If P4.12 is set to be 1, when power on and FWD/REV terminal is active,
inverter will start automatically.
l This function may cause the inverter restart automatically, please be
cautious.
.67.
CHV100 Series Close Loop Vector Control Inverter
.69.
CHV100 Series Close Loop Vector Control Inverter
Setting
Function Description
value
DOWN
11
command
Clear
12
UP/DOWN
Use this terminal to clear UP/DOWN setting. Please refer
to description of P0.02.
Switch between
13 P0.06
A and B A B A+B
Terminal action
Switch between
14 13 valid B A
A and A+B
14 valid A+B A
Switch between
15 15 valid A+B B
B and A+B
Multi-step 16 steps speed control can be realized by the combination
16 speed of these four terminals. For details, please refer to following
reference1 multi-step speed reference terminal status and according
Multi-step speed step value table:
17
reference 2 Such as:
Multi-step 0000: select the multi-speed 0; 1111: multi-speed 15.
18 speed Notice: multi-speed 1 is low bit, and multi-speed 4 is high
reference 3 bit.
.70.
CHV100 Series Close Loop Vector Control Inverter
Setting
Function Description
value
4 groups of ACC/DEC time can be selected by the
combination of these two terminals.
ACC/DEC time ACC/DEC time ACC/DEC time
21 ACC/DEC time
selection1 selection 2 selection1
ACC/DEC time 0
OFF OFF
(P0.11、P0.12)
ACC/DEC time 1
OFF ON
(P8.00、P8.01)
ACC/DEC time ACC/DEC time 2
22 ON OFF
selection 2 (P8.02、P8.03)
ACC/DEC time 3
ON ON
(P8.04、P8.05)
When simple PLC stops, the status of PLC such as running
Reset simple
23 step, running time and running frequency will be cleared
PLC when stop
when this terminal is enabled.
Inverter runs at zero frequency and PLC pauses the timing
Pause simple when this terminal is enabled. If this terminal is disabled,
24
PLC inverter will start and continue the PLC operation from the
status before pause.
PID adjustment will be paused and inverter keeps output
25 Pause PID
frequency unchanged.
Inverter keeps output frequency unchanged. If this terminal
Pause traverse
26 is disabled, inverter will continue traverse operation from
operation
current frequency.
Reset traverse Reference frequency of inverter will be forced as center
27
operation frequency of traverse operation.
28 Reset counter Clear the value of counter.
29 Reset length Clear the value of actual length (P8.20).
Pauses acceleration or deceleration and maintains output
ACC/DEC
30 frequency. When this terminal is disabled,
ramp hold
acceleration/deceleration is restarted.
Disable torque Torque control is disabled. Inverter will work in speed
31
control control mode.
.71.
CHV100 Series Close Loop Vector Control Inverter
Setting
Function Description
value
32~52 Reserved Reserved for water supply control.
Combine with FWD/REV operation to be 3-wire jog control.
3-wire jog
53
control
K1 K2 K3 Command
ON OFF Forward running
OFF
OFF ON Reverse running
ON OFF Forward jogging
ON
OFF ON Reverse jogging
54~55 Reserved Reserved
K1 K2 Run command
.72.
CHV100 Series Close Loop Vector Control Inverter
.74.
CHV100 Series Close Loop Vector Control Inverter
lower limit and upper limit, it will be regarded as the upper limit or lower limit.
The analog input AI1 can only provide voltage input, and the range is 0V~10V.
For different applications, the corresponding value of 100.0% analog setting is different.
For details, please refer to description of each application.
Notice: AI1 lower limit must be less or equal to AI1 upper limit.
.75.
CHV100 Series Close Loop Vector Control Inverter
.78.
CHV100 Series Close Loop Vector Control Inverter
Setting
Function Description
Value
Upper frequency
14 ON: Running frequency reaches the value of P0.08.
limit reached
Lower frequency
15 ON: Running frequency reaches the value of P0.09.
limit reached
16 Ready ON: Inverter is ready (no fault, power is ON).
Auxiliary motor 1 In the case of simple water supply system with one
17
started inverter driving three pumps, it is used to control
Auxiliary motor 2 auxiliary pumps. For details, please refer to
18
started descriptions of P8.29, P8.30 and P8.31.
19 Motor running ON: Inverter has output signal
Output pulse signal for 2s when running frequency
20 Stop pulse output
is lower than 0.1Hz
21~31 Reserved Reserved
.79.
CHV100 Series Close Loop Vector Control Inverter
Setting
Function Range
Value
7 AI1 voltage 0~10V
8 AI2 voltage/current 0~10V/0~20mA
9 AI3 voltage -10V~10V
10 AI4 voltage 0~10V
11 HDI1 frequency 0.1~50.0kHz
12 HDI2 frequency 0.1~50.0kHz
13 Length value 0~preset length (P8.19)
14 Count value 0~preset count value (P8.22)
.81.
CHV100 Series Close Loop Vector Control Inverter
P7.00 is set to be 00000, user’s password set before will be cleared and the password
protection function will be disabled.
After the password has been set and becomes valid, the user can not access menu if the
user’s password is not correct. Only when a correct user’s password is input, the user
can see and modify the parameters. Please keep user’s password in mind.
Function Setting Factory
Name Description
Code Range Setting
LCD language 0: Chinese
P7.01 0~1 0
selection 1: English
0: Invalid
1: Upload parameters to
P7.02 Parameter copy LCD 0~2 0
2: Download parameters
from LCD
P7.02 will take effect when LCD keypad is used.
1: All value of parameters will be uploaded from inverter to LCD.
2: All value of parameters will be downloaded from LCD to inverter.
Notice: When upload or download operation completes, P7.02 will be set to 0
automatically.
Function Setting Factory
Name Description
Code Range Setting
0: Quick debugging mode
QUICK/JOG 1: FDW/REV switching
P7.03 0~3 0
function selection 2: Jog
3: Clear UP/DOWN setting
QUICK/JOG is a multifunctional key, whose function can be defined by the value of
P7.03.
0: Quick debugging mode: Please refer to description of Chapter 5.
1: FWD/REV switching: Press QUICK/JOG, the running direction of inverter will reverse.
It is only valid if P0.01 is set to be 0.
2: Jog: Press QUICK/JOG , the inverter will jog.
3: Clear UP/DOWN setting: Press QUICK/JOG, the UP/DOWN setting will be cleared.
.82.
CHV100 Series Close Loop Vector Control Inverter
.83.
CHV100 Series Close Loop Vector Control Inverter
following figure.
.88.
CHV100 Series Close Loop Vector Control Inverter
Rise time of traverse: Indicates the time rising from the lowest traverse frequency to the
highest traverse frequency.
Fall time of traverse: Indicates the time falling from the highest traverse frequency to the
lowest traverse frequency.
Notice:
l P8.12 determines the output frequency range which is as below:
(1-P8.12%) * reference frequency ≤ output frequency ≤ (1+P8.12%) *
reference frequency
l The output frequency of traverse is limited by upper frequency limit (P0.08)
and lower frequency limit (P0.09).
Function Setting Factory
Name Description
Code Range Setting
P8.16 Auto reset times 0~3 0~3 0
0: Disabled
P8.17 Fault relay action 0~1 0
1: Enabled
P8.18 Reset interval 0.1~100.0s 0.1~100.0 1.0s
Auto reset function can reset the fault in preset times and interval. When P8.16 is set to
be 0, it means “auto reset” is disabled and the protective device will be activated in case
of fault.
P8.17 defines if fault relay active or not during auto reset. If continuous production
without interruption is needed, please set P8.17=0.
Notice:
l The fault such as OUT 1, OUT 2, OUT 3, OH1 and OH2 cannot be reset
automatically.
l If fault has not occurred for ten minutes after the fault is reset, inverter will
automatically clear the previous times of auto reset.
Function Setting Factory
Name Description
Code Range Setting
P8.19 Preset length 1~65535 1~65535 1000
P8.20 Actual length 0~65535 0~65535 0
Number of pulse
P8.21 0.1~6553.5 0.1~6553.5 100.0
per cycle
These parameters are mainly used for fixed-length control.
The length is calculated by input pulse signal. If input pulse frequency is high, it is
required to use HDI1 or HDI2 input (P5.35 or P5.36 = 2)
.89.
CHV100 Series Close Loop Vector Control Inverter
Actual length (P8.20) = Accumulated input pulse number / Number of pulse per cycle
(P8.21).
When the value of P8.20 exceeds the value of P8.19, if multifunctional output terminal is
set to be 11 (Length reached), ON signal will be output.
Function Setting Factory
Name Description
Code Range Setting
P8.22 Preset count value 1~65535 1~65535 1000
Specified count
P8.23 1~65535 1~65535 1000
value
The count pulse input channel can be S1~S5 (≤200Hz) and HDI.
If function of output terminal is set as preset count reached, when the count value
reaches preset count value (P8.22), it will output an ON-OFF signal. Inverter will clear
the counter and restart counting.
If function of output terminal is set as specified count reached, when the count value
reaches specified count value (P8.23), it will output an ON-OFF signal until the count
value reaches preset count value (P8.22). Inverter will clear the counter and restart
counting.
Notice:
l Specified count value (P8.23) should not be greater than preset count value
(P8.22).
l Output terminal can be RO1, RO2 or HDO.
This function is shown as following figure.
Figure 6.22 Timing chart for preset and specified count reached.
Function Setting Factory
Name Description
Code Range Setting
Preset running
P8.24 0~65535h 0~65535 65535 h
time
If function of output terminal is set as running time reached, when the accumulated
.90.
CHV100 Series Close Loop Vector Control Inverter
running time reaches the preset running time, it will output an ON-OFF signal.
Function Setting Factory
Name Description
Code Range Setting
P8.25 FDT level 0.00~ P0.07 0.00~ P0.07 50.00Hz
P8.26 FDT lag 0.0~100.0% 0.0~100.0 5.0%
When the output frequency reaches a certain preset frequency (FDT level), output
terminal will output an ON-OFF signal until output frequency drops below a certain
frequency of FDT level (FDT level - FDT lag), as shown in following figure.
.91.
CHV100 Series Close Loop Vector Control Inverter
.92.
CHV100 Series Close Loop Vector Control Inverter
.93.
CHV100 Series Close Loop Vector Control Inverter
.94.
CHV100 Series Close Loop Vector Control Inverter
.95.
CHV100 Series Close Loop Vector Control Inverter
.96.
CHV100 Series Close Loop Vector Control Inverter
.97.
CHV100 Series Close Loop Vector Control Inverter
.98.
CHV100 Series Close Loop Vector Control Inverter
.100.
CHV100 Series Close Loop Vector Control Inverter
.101.
CHV100 Series Close Loop Vector Control Inverter
.102.
CHV100 Series Close Loop Vector Control Inverter
.103.
CHV100 Series Close Loop Vector Control Inverter
.104.
CHV100 Series Close Loop Vector Control Inverter
Low byte BIT 0 BIT 1 BIT 2 BIT 3 BIT 4 BIT 5 BIT 6 BIT 7
PA.34 0 0 1 0 0 1 1 1
PA.35 1 1 1 1 0 1 0 0
High byte BIT 8 BIT 9 BIT 10 BIT 11 BIT 12 BIT 13 BIT 14 BIT 15
PA.34 0 1 1 0 1 1 0 0
PA.35 0 0 0 0 0 1 0 1
So the value of PA.34 should be: 0X36E4, the value of PA.35 should be: 0XA02F.
Function Setting Factory
Name Description
Code Range Setting
0: Second
PA.36 Time unit 0~1 0
1: Hour
This parameter determines the unit of x step running time.
.106.
CHV100 Series Close Loop Vector Control Inverter
too small to achieve voltage compensation effect. So please set PB.08 according
to load inertia and the actual load.
Function Setting Factory
Name Description
Code Range Setting
Over-voltage stall 0: Disabled
PB.09 0~1 0
protection 1: Enabled
Over-voltage stall
PB.10 110~150% 110~150 125%
protection point
During deceleration, the motor’s decelerating rate may be lower than that of inverter’s
output frequency due to the load inertia. At this time, the motor will feed the energy back
to the inverter, resulting in DC bus voltage rise. If no measures taken, the inverter will trip
due to over voltage.
During deceleration, the inverter detects DC bus voltage and compares it with
over-voltage stall protection point. If DC bus voltage exceeds PB.10, the inverter will stop
reducing its output frequency. When DC bus voltage become lower than PB.10, the
deceleration continues, as shown in following figure.
.108.
CHV100 Series Close Loop Vector Control Inverter
output frequency rise rate because of too big load. If no measures to take, inverter will
trip caused by over-current.
The principle of over-current protection is to detect the output current of inverter during
inverter operation and compare it with over-current stall threshold determined by PB.12.
If it exceeds the value of PB.12 during acceleration, inverter will remain output frequency;
if it exceeds the value of PB.12 during constant speed running, inverter will decrease
output frequency. When output current of inverter is lower than the value of PB.12,
inverter will continue to accelerate until output frequency reach frequency reference.
Please refer to following diagram.
.109.
CHV100 Series Close Loop Vector Control Inverter
.110.
CHV100 Series Close Loop Vector Control Inverter
7. TROUBLE SHOOTING
7.1 Fault and trouble shooting
Fault Code Fault Type Reason Solution
1. Acc/Dec time is too
OUT1 IGBT Ph-U fault 1. Increase Acc/Dec
short.
time.
2. IGBT module fault.
2. Ask for support.
OUT2 IGBT Ph-V fault 3. Malfunction caused by
3. Inspect external
interference.
equipment and eliminate
OUT3 IGBT Ph-W fault 4. Grounding is not interference.
properly.
Over-current 1. Inspect whether motor
OC1 when 1.Short-circuit or ground damaged, insulation
acceleration fault occurred at inverter worn or cable damaged.
Over-current output. 2. Increase Acc/Dec time
OC2 when 2.Load is too heavy or or select bigger capacity
deceleration Acc/Dec time is too short. inverter.
Over-current 3.V/F curve is not suitable. 3. Check and adjust V/F
OC3 when constant 4.Sudden change of load. curve.
speed running 4. Check the load.
Over-voltage
OV1 when
acceleration 1. Increase Dec time or
1. Dec time is too short
Over-voltage connect braking resistor
and regenerative energy
OV2 when 2. Decrease input
from the motor is too large.
deceleration voltage within
2. Input voltage is too high.
Over-voltage specification.
OV3 when constant
speed running
1.Open phase occurred
with power supply.
DC bus Inspect the input power
UV 2.Momentary power loss
Under-voltage supply or wiring.
occurred
3.Wiring terminals for
.111.
CHV100 Series Close Loop Vector Control Inverter
.112.
CHV100 Series Close Loop Vector Control Inverter
.113.
CHV100 Series Close Loop Vector Control Inverter
.114.
CHV100 Series Close Loop Vector Control Inverter
voltage or not with multi-meter. If the power supply has problem, inspect and solve
it.
l Inspect whether the three-phase rectify bridge is in good condition or not. If the
rectification bridge is burst out, ask for support.
l Check the CHARGE light. If the light is off, the fault is mainly in the rectify bridge or
the buffer resistor. If the light is on, the fault may be lies in the switching power
supply. Please ask for support.
Power supply air switch trips off when power on:
l Inspect whether the input power supply is grounded or short circuit. Please solve
the problem.
l Inspect whether the rectify bridge has been burnt or not. If it is damaged, ask for
support.
Motor doesn’t move after inverter running:
l Inspect if there is balanced three-phase output among U, V, W. If yes, then motor
could be damaged, or mechanically locked. Please solve it.
l If the output is unbalanced or lost, the inverter drive board or the output module
may be damaged, ask for support..
Inverter displays normally when power on, but switch at the input side trips when
running:
l Inspect whether the output side of inverter is short circuit. If yes, ask for support.
l Inspect whether ground fault exists. If yes, solve it.
l If trip happens occasionally and the distance between motor and inverter is too far,
it is recommended to install output AC reactor.
.115.
CHV100 Series Close Loop Vector Control Inverter
.117.
CHV100 Series Close Loop Vector Control Inverter
When supplying AC power to the drive, use a voltage regulator to raise the input voltage
to rated input voltage gradually. The drive should be powered for 5 hours without load.
7. Before performing insulation tests, all main circuit input/output terminals should be
short-circuited with conductors. Then proceed insulation test to the ground. Insulation
test of single main circuit terminal to ground is forbidden; otherwise the drive might be
damaged. Please use a 500V Mega-Ohm-Meter.
8. Before the insulation test of the motor, disconnect the motor from the drive to avoid
damaging it.
.118.
CHV100 Series Close Loop Vector Control Inverter
.119.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
0: Keypad
1: AI1
2. AI3
Frequency A 3: HDI1 FREQ
P0.03 0 ◎
command source 4:Simple PLC SOURCE A
5. Multi-Step speed
6: PID
7: Communication
0:AI2
Frequency B FREQ
P0.04 1:AI4 0 ◎
command source SOURCE B
2:HDI2
Scale of
0: Maximum frequency FREQ B
P0.05 frequency B 0 ○
1: Frequency A command SCALE
command
0: A
Frequency
1: B FREQ
P0.06 command 0 ○
2: A+B SELECTION
selection
3: Max(A, B)
Maximum
P0.07 10.0~400.00Hz 50.00Hz ◎ MAX FREQ
frequency
Upper frequency UP FREQ
P0.08 P0.09~P0.07 50.00Hz ○
limit LIMIT
Lower frequency LOW FREQ
P0.09 0.00Hz~ P0.08 0.00Hz ○
limit LIMIT
Keypad reference KEYPAD
P0.10 0.00 Hz ~ P0.08 50.00Hz ○
frequency REF FREQ
Acceleration time
P0.11 0.0~3600.0s 20.0s ○ ACC TIME 0
0
Deceleration time
P0.12 0.0~3600.0s 20.0s ○ DEC TIME 0
0
0: Forward
Running direction RUN
P0.13 1: Reverse 0 ◎
selection DIRECTION
2: Forbid reverse
.120.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
Depend CARRIER
P0.14 Carrier frequency 1.0~16.0kHz ○
on model FREQ
0:Fixed
P0.15 PWM mode 0 ○ PWM MODE
1:Random
Carrier frequency 0: Disabled
AUTO
P0.16 adjust based on 1: Enabled 0 ◎
ADJUST
temperature
0: No action
Motor parameters AUTO-
P0.17 1: Rotation autotuning 0 ◎
autotuning TUNING
2: Static autotuning
0: No action
1: Restore factory setting
Restore 2: Clear fault records RESTORE
P0.18 0 ◎
parameters 3:Restore parameters for PARA
injection molding
machine
P1 Group: Start and Stop Control
0: Start directly
1: DC braking and start START
P1.00 Start Mode 0 ◎
2: Speed tracking and MODE
start
Starting START
P1.01 0.00~10.0Hz 1.50Hz ◎
frequency FREQ
Hold time of
P1.02 0.0~50.0s 0.0s ◎ HOLD TIME
starting frequency
DC Braking
START
P1.03 current before 0.0~150.0% 0.0% ◎
BRAK CURR
start
DC Braking time START
P1.04 0.0~50.0s 0.0s ◎
before start BRAK TIME
Acceleration
0:Linear ACC/DEC
P1.05 /Deceleration 0 ◎
1:S curve MODE
mode
.121.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
Start section of S 0.0~40.0% START
P1.06 30.0% ◎
curve (ACC/DEC time) SECTION
End section of S 0.0~40.0% END
P1.07 30.0% ◎
curve (ACC/DEC time) SECTION
0:Deceleration to stop
P1.08 Stop Mode 0 ○ STOP MODE
1:Coast to stop
Starting
STOP BRAK
P1.09 frequency of DC 0.00~P0.07 0.00Hz ○
FREQ
braking
Waiting time
STOP BRAK
P1.10 before DC 0.0~50.0s 0.0s ○
DELAY
braking
DC braking STOP BRAK
P1.11 0.0~150.0% 0.0% ○
current CURR
STOP BRAK
P1.12 DC braking time 0.0~50.0s 0.0s ○
TIME
Dead time of FWD/REV
P1.13 0.0~3600.0s 0.0s ○
FWD/REV DEADTIME
Action when 0: Running at the lower
running frequency frequency limit ACT(FREQ<
P1.14 0 ◎
is less than lower 1: Stop P0.09)
frequency limit 2: Stand-by
Restart after 0: Disabled
P1.15 0 ○ RESTART
power off 1: Enabled
Delay time for
P1.16 0.0~3600.0s 0.0s ○ DELAY TIME
restart
P2 Group: Motor Parameters
0:G model INVERTER
P2.00 Inverter model 0 ◎
1: P model MODEL
Motor rated MOTOR
P2.01 0.01Hz~P0.07 50.00Hz ◎
frequency RATE FREQ
.122.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
MOTOR
Motor rated 1460
P2.02 0~36000rpm ◎ RATE
speed rpm
SPEED
Motor rated Depend MOTOR
P2.03 0~3000V ◎
voltage on model RATE VOLT
Motor rated Depend MOTOR
P2.04 0.1~2000.0A ◎
current on model RATE CURR
Depend MOTOR
Motor rated
P2.05 1.5~900.0kW on model ◎ RATE
power
POWER
Motor stator Depend STATOR
P2.06 0.001~65.535Ω ○
resistance on model RESISTOR
Motor rotor Depend ROTOR
P2.07 0.001~65.535Ω ○
resistance on model RESISTOR
Motor leakage Depend LEAK
P2.08 0.1~6553.5mH ○
inductance on model INDUCTOR
Motor mutual Depend MUTUAL
P2.09 0.1~6553.5mH ○
inductance on model INDUCTOR
Current without Depend NO LOAD
P2.10 0.01~655.35A ○
load on model CURR
P3 Group: Vector Control
ASR proportional
P3.00 0~100 20 ○ ASR Kp1
gain Kp1
ASR integral time
P3.01 0.01~10.00s 0.50s ○ ASR Ki1
Ki1
ASR
ASR switching
P3.02 0.00Hz~P3.05 5.00Hz ○ SWITCHPOI
point 1
NT1
ASR proportional
P3.03 0~100 25 ○ ASR Kp2
gain Kp2
ASR integral time
P3.04 0.01~10.00s 1.00s ○ ASR Ki2
Ki2
.123.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
ASR
ASR switching
P3.05 P3.02~P0.07 10.00Hz ○ SWITCHPOI
point 2
NT2
ACR proportional
P3.06 0~65535 500 ○ ACR P
gain P
ACR integral gain
P3.07 0~65535 500 ○ ACR I
I
Speed detection FEEDBACK
P3.08 0.00~5.00s 0.00s ○
filter time FILTER
Slip
VC SLIP
P3.09 compensation 50.0~200.0% 100% ○
COMP
rate of VC
PG
P3.10 PG parameter 1~65535 1000 ◎
PARAMETER
PG direction 0:Forward PG
P3.11 0 ◎
selection 1:Reverse DIRECTION
0:Disabled
1: Keypad
2:AI1
3:AI2
Torque setting TORQUE
P3.12 4:AI3 0 ○
source SETTING
5:AI4
6:HDI1
7:HDI2
8:Communication
KEYPAD
Keypad torque
P3.13 -100.0%~100.0% 50.0% ○ TORQUE
setting
SET
0.0~200.0%(rated current TORQUE
P3.14 Torque limit 150.0% ○
of inverter) LIMIT
P4 Group: V/F Control
.124.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
0:Linear curve
1: User-defined curve
2: Torque_stepdown
V/F curve curve (1.3 order)
P4.00 0 ◎ V/F CURVE
selection 3: Torque_stepdown
curve (1.7 order)
4: Torque_stepdown
curve (2.0 order)
0.0%: auto TORQUE
P4.01 Torque boost 1.0% ○
0.1%~10.0% BOOST
Torque boost 0.0%~50.0% (motor rated BOOST
P4.02 20.0% ◎
cut-off frequency) CUT-OFF
P4.03 V/F frequency 1 0.00Hz~ P4.05 5.00Hz ◎ V/F FREQ 1
V/F
P4.04 V/F voltage 1 0.0%~100.0% 10.0% ◎
VOLTAGE 1
P4.05 V/F frequency 2 P4.03~ P4.07 30.00Hz ◎ V/F FREQ 2
V/F
P4.06 V/F voltage 2 0.0%~100.0% 60.0% ◎
VOLTAGE 2
P4.07 V/F frequency 3 P4.05~ P2.01 50.00Hz ◎ V/F FREQ 3
V/F
P4.08 V/F voltage 3 0.0%~100.0% 100.0% ◎
VOLTAGE 3
V/F slip V/F SLIP
P4.09 0.00~10.00Hz 0.0Hz ○
compensation COMP
0: Disabled
1: Enabled all the time
P4.10 AVR function 1 ○ AVR
2: Disabled during
deceleration
Auto energy 0: Disabled ENERGY
P4.11 0 ○
saving selection 1: Enabled SAVING
FWD/REV enable
0: Disabled FWD/REV
P4.12 option when 0 ○
1: Enabled ENABLE
power on
.125.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
P5 Group: Input Terminals
0: HDI1 and HDI2 are high
speed pulse input.
1: HDI1 is ON-OFF input,
HDI2 is high speed
pulse input. HDI
P5.00 HDI selection 0 ◎
2: HDI2 is ON-OFF input, SELECTION
HDI1 is high speed
pulse input.
3: HDI1 and HDI2 are
ON-OFF input.
Communication 0: Concrete INPUT
P5.01 0 ◎
Input selection 1: Virtual SELECTION
0:Invalid
S1 Terminal 1:Forward S1
P5.02 1 ◎
function 2:Reverse FUNCTION
3:3-wire control
S2 Terminal 4:Jog forward S2
P5.03 4 ◎
function 5:Jog reverse FUNCTION
.126.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
A+B
16: Multi-step speed
S7 Terminal reference1 S7
P5.10 0 ◎
function 17: Multi-step speed FUNCTION
reference2
18: Multi-step speed
reference3
19: Multi-step speed
reference4
20: Multi-step speed
pause
21: ACC/DEC time
selection 1
22: ACC/DEC time
selection 2
23: Reset simple PLC
when stop
24: Pause simple PLC
S8 Terminal S8
P5.11 25: Pause PID 0 ◎
function 26: Pause traverse FUNCTION
operation
27: Reset traverse
operation
28: Reset counter
29: Reset length
30: ACC/DEC ramp hold
31: Disable torque control
32~52: Water supply
control
53: 3-wire jog control
54~55: reversed
ON-OFF filter Sx FILTER
P5.12 1~10 5 ○
times TIMES
.127.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
0: 2-wire control mode 1
FWD/REV control 1: 2-wire control mode 2 FWD/REV
P5.13 0 ◎
mode 2: 3-wire control mode 1 CONTROL
3: 3-wire control mode 2
UP/DOWN setting UP/DOWN
P5.14 0.01~50.00Hz/s 0.50Hz/s ○
change rate RATE
AI1 LOW
P5.15 AI1 lower limit 0.00V~10.00V 0.00V ○
LIMIT
AI1 lower limit
AI1 LOW
P5.16 corresponding -100.0%~100.0% 0.0% ○
SETTING
setting
P5.17 AI1 upper limit 0.00V~10.00V 10.00V ○ AI1 UP LIMIT
P5.18 AI1 upper limit
AI1 UP
corresponding -100.0%~100.0% 100.0% ○
SETTING
setting
P5.19 AI1 filter time AI1 FILTER
0.00s~10.00s 0.10s ○
constant TIME
AI2 LOW
P5.20 AI2 lower limit 0.00V~10.00V 0.00V ○
LIMIT
AI2 lower limit
AI2 LOW
P5.21 corresponding -100.0%~100.0% 0.0% ○
SETTING
setting
P5.22 AI2 upper limit 0.00V~10.00V 5.00V ○ AI2 UP LIMIT
AI2 upper limit
AI2 UP
P5.23 corresponding -100.0%~100.0% 100.0% ○
SETTING
setting
AI2 filter time AI2 FILTER
P5.24 0.00s~10.00s 0.10s ○
constant TIME
AI3 LOW
P5.25 AI3 lower limit -10.00V ~10.00V 0.00V ○
LIMIT
.128.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
AI3 lower limit
AI3 LOW
P5.26 corresponding -100.0%~100.0% 0.0% ○
SETTING
setting
P5.27 AI3 upper limit -10.00V ~10.00V 10.00V ○ AI3 UP LIMIT
AI3 upper limit
AI3 UP
P5.28 corresponding -100.0%~100.0% 100.0% ○
SETTING
setting
AI3 filter time AI3 FILTER
P5.29 0.00s~10.00s 0.10s ○
constant TIME
AI4 LOW
P5.30 AI4 lower limit 0.00V~10.00V 0.00V ○
LIMIT
AI4 lower limit
AI4 LOW
P5.31 corresponding -100.0%~100.0% 0.0% ○
SETTING
setting
P5.32 AI4 upper limit 0.00V~10.00V 10.00V ○ AI4 UP LIMIT
AI4 upper limit
AI4 UP
P5.33 corresponding -100.0%~100.0% 100.0% ○
SETTING
setting
AI4 filter time AI4 FILTER
P5.34 0.00s~10.00s 0.10s ○
constant TIME
HDI1 function 0: Reference input HDI1
P5.35 0 ◎
selection 1: Counter input FUNCTION
2: Length input
HDI2 function HDI2
P5.36 3: Reserved 0 ◎
selection FUNCTION
4: Reserved
HDI1 LOW
P5.37 HDI1 lower limit 0.0 kHz ~50.0kHz 0.0KHz ○
LIMIT
HDI1 lower limit
HDI1 LOW
P5.38 corresponding -100.0%~100.0% 0.0% ○
SETTING
setting
HDI1 UP
P5.39 HDI1 upper limit 0.0 kHz ~50.0kHz 50.0KHz ○
LIMIT
.129.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
HDI1 upper limit
HDI1 UP
P5.40 corresponding -100.0%~100.0% 100.0% ○
SETTING
setting
HDI1 filter time HDI1 FILTER
P5.41 0.00s~10.00s 0.10s ○
constant TIME
HDI2 LOW
P5.42 HDI2 lower limit 0.0 kHz ~50.0kHz 0.0KHz ○
LIMIT
HDI2 lower limit
HDI1 LOW
P5.43 corresponding -100.0%~100.0% 0.0% ○
SETTING
setting
HDI2 UP
P5.44 HDI2 upper limit 0.0 kHz ~50.0kHz 50.0KHz ○
LIMIT
HDI2 upper limit
HDI2 UP
P5.45 corresponding -100.0%~100.0% 100.0% ○
SETTING
setting
HDI2 filter time HDI2 FILTER
P5.46 0.00s~10.00s 0.10s ○
constant TIME
P6 Group: Output Terminals
0: High-speed pulse
HDO
P6.00 HDO selection output 0 ◎
SELECTION
1: ON-OFF output
Y1 output 0: NO output Y1
P6.01 1 ○
selection 1: Run forward SELECTION
Y2 output 2: Run reverse Y2
P6.02 0 ○
selection 3: Fault output SELECTION
HDO ON-OFF 4: Motor overload HDO
P6.03 0 ○
output selection 5: Inverter overload SELECTION
Relay 1 output 6: FDT reached RO1
P6.04 3 ○
selection 7: Frequency reached SELECTION
Relay 2 output 8: Zero speed running RO2
P6.05 9: Preset count value 0 ○
selection SELECTION
.130.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
reached
10: Specified count value
reached
11: Length reached
12: PLC cycle completed
13: Running time reached
14: Upper frequency limit
reached
Relay 3 output 15: Lower frequency limit RO3
P6.06 0 ○
selection reached SELECTION
16: Ready
17: Auxiliary motor1
started
18: Auxiliary motor2
started
19: Motor running
20: Stop pulse output
21~31: Reserved
0: Running frequency
AO1 function 1: Reference frequency AO1
P6.07 0 ○
selection 2: Motor speed SELECTION
3: Output current
4: Output voltage
AO2 function AO2
P6.08 5: Output power 0 ○
selection SELECTION
6: Output torque
7: AI1 voltage
8: AI2 voltage/current
9: AI3 voltage
10: AI4 voltage
HDO function HDO
P6.09 11: HDI1 frequency 0 ○
selection SELECTION
12: HDI2 frequency
13: Length value
14: Count value
.131.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
AO1 LOW
P6.10 AO1 lower limit 0.0%~100.0% 0.0% ○
LIMIT
AO1 lower limit
AO1 LOW
P6.11 corresponding 0.00V ~10.00V 0.00V ○
OUTPUT
output
AO1 UP
P6.12 AO1 upper limit 0.0%~100.0% 100.0% ○
LIMIT
AO1 upper limit
AO1 UP
P6.13 corresponding 0.00V ~10.00V 10.00V ○
OUTPUT
output
AO2 LOW
P6.14 AO2 lower limit 0.0%~100.0% 0.0% ○
LIMIT
AO2 lower limit
AO2 LOW
P6.15 corresponding 0.00V ~10.00V 0.00V ○
OUTPUT
output
AO1 UP
P6.16 AO2 upper limit 0.0%~100.0% 100.0% ○
LIMIT
AO2 upper limit
AO2 UP
P6.17 corresponding 0.00V ~10.00V 10.00V ○
OUTPUT
output
HDO LOW
P6.18 HDO lower limit 0.0%~100.0% 0.0% ○
LIMIT
HDO lower limit
HDO LOW
P6.19 corresponding 0.0 ~ 50.0kHz 0.0kHz ○
OUTPUT
output
HDO UP
P6.20 HDO upper limit 0.0%~100.0% 100.0% ○
LIMIT
HDO upper limit
HDO UP
P6.21 corresponding 0.0 ~ 50.0kHz 50.0kHz ○
OUTPUT
output
P7 Group: Display Interface
.132.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
USER
P7.00 User password 0~65535 0 ○
PASSWORD
LCD language 0: Chinese LANGUAGE
P7.01 0 ○
selection 1: English SELECT
0: Invalid
1: Upload parameters to
P7.02 Parameter copy LCD 0 ◎ PARA COPY
2: Download parameters
from LCD
0: Quick debugging mode
1: FDW/REV switching
QUICK/JOG QUICK/JOG
P7.03 2: Jog 0 ◎
function selection FUNC
3: Clear UP/DOWN
setting
0: Valid when keypad
control (P0.01=0)
1: Valid when keypad or
terminal control (P0.01=0
STOP/RST STOP/RST
P7.04 or 1) 0 ○
function selection FUNC
2: Valid when keypad or
communication control
(P0.01=0 or 2)
3: Always valid
0: Preferential to external
keypad
1: Both display, only
Keypad display external key valid. KEYPAD
P7.05 0 ○
selection 2: Both display, only local DISPLAY
key valid.
3: Both display and key
valid.
.133.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
1.Output frequency
2.Reference frequency
3.DC bus voltage
4.Output voltage
5.Output current
Other parameters display
is determined by 16 bit
binary digit
BIT0: Rotation speed
BIT1: Output power
BIT2: Output torque
BIT3: PID preset
Running status RUNNING
P7.06 BIT4: PID feedback 0x00FF ○
display selection DISPLAY
BIT5: Input terminal status
BIT6: Output terminal
status
BIT7: AI1
BIT8: AI2
BIT9: AI3
BIT10: AI4
BIT11: HDI1
BIT12: HDI2
BIT13: Step No. of PLC
BIT14: Length value
BIT15: Count value
.134.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
BIT0: Reference
frequency
BIT1: DC bus voltage
BIT2: Input terminal status
BIT3: Output terminal
status
BIT4: PID preset
BIT5: PID feedback
Stop status BIT6: AI1 STOP
P7.07 0x00FF ○
display selection BIT7: AI2 DISPLAY
BIT8: AI3
BIT9: AI4
BIT10: HDI1
BIT11: HDI2
BIT12: Step No. of PLC
BIT13: Length value
BIT14: Reserved
BIT15: Reserved
Rectifier module RECTIFIER
P7.08 0~100.0℃ ●
temperature TEMP
IGBT module
P7.09 0~100.0℃ ● IGBT TEMP
temperature
MCU software MCU
P7.10 Factory setting ●
version VERSION
DSP software DSP
P7.11 Factory setting ●
version VERSION
Accumulated TOTAL RUN
P7.12 0~65535h ●
running time TIME
.135.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
0: Not fault
1: IGBT Ph-U fault(OUT1)
2: IGBT Ph-V fault(OUT2)
3: IGBT Ph-W fault(OUT3)
Third latest fault 3rd LATEST
P7.13 4: Over-current when ●
type FAULT
acceleration(OC1)
5: Over-current when
deceleration(OC2)
6: Over-current when
constant speed running
(OC3)
7: Over-voltage when
acceleration(OV1)
8: Over-voltage whe
deceleration(OV2)
9: Over-voltage when
Second latest 2nd LATEST
P7.14 constant speed ●
fault type FAULT
running(OV3)
10: DC bus
Under-voltage(UV)
11: Motor overload (OL1)
12: Inverter overload
(OL2)
13: Input phase failure
.136.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
(SPI)
14: Output phase failure
(SPO)
15: Rectify overheat
(OH1)
16: IGBT overheat (OH2)
17: External fault (EF)
18: Communication fault
(CE)
19: Current detection fault
(ITE)
20: Autotuning fault (TE)
21: Encoder fault(PCE) CURRENT
P7.15 Latest fault type ●
22: Encoder reverse FAULT
fault(PCDE)
23: System fault(OPSE)
24: : EEPROM fault (EEP)
25: PID feedback fault
(PIDE)
26: Brake unit fault (BCE)
27: Trial time
reached(END)
28: LCD
disconnected(LCD-E)
29: Clock chip fault(TI-E)
30: Reserved
Output frequency FAULT
P7.16 ●
at current fault FREQ
Output current at FAULT
P7.17 ●
current fault CURR
DC bus voltage at FAULT DC
P7.18 ●
current fault VOLT
.137.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
Input terminal
FAULT Sx
P7.19 status at current ●
STATUS
fault
Output terminal
FAULT DO
P7.20 status at current ●
STATUS
fault
P8 Group: Enhanced Function
Acceleration time
P8.00 0.0~3600.0s 20.0s ○ ACC TIME 1
1
Deceleration time
P8.01 0.0~3600.0s 20.0s ○ DEC TIME 1
1
Acceleration time
P8.02 0.0~3600.0s 20.0s ○ ACC TIME 2
2
Deceleration time
P8.03 0.0~3600.0s 20.0s ○ DEC TIME 2
2
Acceleration time
P8.04 0.0~3600.0s 20.0s ○ ACC TIME 3
3
Deceleration time
P8.05 0.0~3600.0s 20.0s ○ DEC TIME 3
3
P8.06 Jog reference 0.00~P0.07 5.00Hz ○ JOG REF
Jog Acceleration JOG ACC
P8.07 0.0~3600.0s 20.0s ○
time TIME
Jog Deceleration JOG DEC
P8.08 0.0~3600.0s 20.0s ○
time TIME
SKIP FREQ
P8.09 Skip frequency 1 0.00~P0.07 0.00Hz ○
1
SKIP FREQ
P8.10 Skip frequency 2 0.00~P0.07 0.00Hz ○
2
Skip frequency SKIP FREQ
P8.11 0.00~P0.07 0.00Hz ○
bandwidth RANGE
Traverse 0.0~100.0% (with TRAV
P8.12 0.0% ○
amplitude reference to P0.10) AMPLITUDE
.138.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
JITTER
P8.13 Jitter frequency 0.0~50.0% 0.0% ○
FREQ
Rise time of TRAV RISE
P8.14 0.1~3600.0s 5.0s ○
traverse TIME
Fall time of TRAV FALL
P8.15 0.1~3600.0s 5.0s ○
traverse TIME
AUTO
P8.16 Auto reset times 0~3 0 ○ RESET
TIMES
0: Disabled FAULT
P8.17 Fault relay action 0 ○
1: Enabled ACTION
RESET
P8.18 Reset interval 0.1~100.0s 1.0s ○
INTERVAL
PRESET
P8.19 Preset length 1~65535 1000 ○
LENGTH
ACTUAL
P8.20 Actual length 0~65535 0 ○
LENGTH
Number of pulse PULSE
P8.21 0.1~6553.5 100.0 ○
per cycle NUMBER
Preset count PRESET
P8.22 1~65535 1000 ○
value COUNT
Specified count SPECIFIED
P8.23 1~65535 1000 ○
value COUNT
Preset running RUNNING
P8.24 0~65535h 65535 h ○
time TIME
P8.25 FDT level 0.00~ P0.07 50.00Hz ○ FDT LEVEL
P8.26 FDT lag 0.0~100.0% 5.0% ○ FDT LAG
Frequency arrive 0.0~100.0% (maximum
P8.27 0.0% ○ FAR RANGE
detecting range frequency)
DROOP
P8.28 Droop control 0.00~10.00Hz 0.00Hz ○
CONTROL
.139.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
0: Invalid
Auxiliary motor 1: Motor 1 valid AUXILIARY
P8.29 0 ◎
selection 2: Motor 2 valid MOTOR
3: Both valid
Auxiliary motor1
MOTOR 1
P8.30 START/STOP 0.0~3600.0s 5.0s ○
DELAY
delay time
Auxiliary motor2
MOTOR 2
P8.31 START/STOP 0.0~3600.0s 5.0s ○
DELAY
delay time
Brake threshold
P8.32 320.0~750.0V 700.0V ○ BRAK VOLT
voltage
Low-frequency
threshold of LO FREQ
P8.33 0~9999 1000 ○
restraining RESTRAIN
oscillation
High-frequency
threshold of HI FREQ
P8.34 0~9999 1000 ○
restraining RESTRAIN
oscillation
P9 Group: PID Control
0: Keypad
1: AI1
2: AI2
3: AI3
PID preset source
P9.00 4: AI4 0 ○ PID PRESET
selection
5: HDI1
6: HDI2
7: Communication
8: Simple PLC
Keypad PID KEYPAD PID
P9.01 0.0%~100.0% 0.0% ○
preset SET
.140.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
0: AI1
1: AI2
2: AI3
3: AI4
PID feedback 4: AI1-AI2 PID
P9.02 0 ○
source selection 5: AI3-AI4 FEEDBACK
6: HDI1
7: HDI2
8: HDI1-HDI2
9: Communication
PID output 0: Positive
P9.03 0 ○ PID OUTPUT
characteristics 1: Negative
Proportional gain PROPORTIO
P9.04 0.00~100.00 0.10 ○
(Kp) N GAIN
INTEGRAL
P9.05 Integral time (Ti) 0.01~10.00s 0.10s ○
TIME
Differential time DIFFERENTI
P9.06 0.00~10.00s 0.00s ○
(Td) A TIME
Sampling cycle SAMPLING
P9.07 0.01~100.00s 0.50s ○
(T) CYCLE
P9.08 Bias limit 0.0~100.0% 0.0% ○ BIAS LIMIT
PID output filter OUTPUT
P9.09 0.00~10.00s 0.00 ○
time FILTER
Feedback lost FEEDBACK
P9.10 0.0~100.0% 0.0% ○
detecting value LOST
Feedback lost FEEDBACK
P9.11 0.0~3600.0s 1.0s ○
detecting time LOST(t)
PA Group: Multi-step Speed Control
0: Stop after one cycle
1: Hold last frequency
PA.00 Simple PLC mode 0 ○ PLC MODE
after one cycle
2: Circular run
.141.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
0: Not saved
Simple PLC
1: Saved STATUS
PA.01 status saving 0 ○
2: Not saved when power SAVING
selection
off, saved when stop
Multi-step speed MULTI-SPEE
PA.02 -100.0~100.0% 0.0% ○
0 D0
th
0 Step running RUNNING
PA.03 0.0~6553.5s(h) 0.0s ○
time TIME 0
Multi-step speed MULTI-SPEE
PA.04 -100.0~100.0% 0.0% ○
1 D1
st
1 Step running RUNNING
PA.05 0.0~6553.5s(h) 0.0s ○
time TIME 1
Multi-step speed MULTI-SPEE
PA.06 -100.0~100.0% 0.0% ○
2 D2
nd
2 Step running RUNNING
PA.07 0.0~6553.5s(h) 0.0s ○
time TIME 2
Multi-step speed MULTI-SPEE
PA.08 -100.0~100.0% 0.0% ○
3 D3
rd
3 Step running RUNNING
PA.09 0.0~6553.5s(h) 0.0s ○
time TIME 3
Multi-step speed MULTI-SPEE
PA.10 -100.0~100.0% 0.0% ○
4 D4
th
4 Step running RUNNING
PA.11 0.0~6553.5s(h) 0.0s ○
time TIME 4
Multi-step speed MULTI-SPEE
PA.12 -100.0~100.0% 0.0% ○
5 D5
th
5 Step running RUNNING
PA.13 0.0~6553.5s(h) 0.0s ○
time TIME 5
Multi-step speed MULTI-SPEE
PA.14 -100.0~100.0% 0.0% ○
6 D6
th
6 Step running RUNNING
PA.15 0.0~6553.5s(h) 0.0s ○
time TIME 6
.142.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
Multi-step speed MULTI-SPEE
PA.16 -100.0~100.0% 0.0% ○
7 D7
th
7 Step running RUNNING
PA.17 0.0~6553.5s(h) 0.0s ○
time TIME 7
Multi-step speed MULTI-SPEE
PA.18 -100.0~100.0% 0.0% ○
8 D8
th
8 Step running RUNNING
PA.19 0.0~6553.5s(h) 0.0s ○
time TIME 8
Multi-step speed MULTI-SPEE
PA.20 -100.0~100.0% 0.0% ○
9 D9
th
9 Step running RUNNING
PA.21 0.0~6553.5s(h) 0.0s ○
time TIME 9
Multi-step speed MULTI-SPEE
PA.22 -100.0~100.0% 0.0% ○
10 D 10
th
10 Step running RUNNING
PA.23 0.0~6553.5s(h) 0.0s ○
time TIME 10
Multi-step speed MULTI-SPEE
PA.24 -100.0~100.0% 0.0% ○
11 D 11
th
11 Step running RUNNING
PA.25 0.0~6553.5s(h) 0.0s ○
time TIME 11
Multi-step speed MULTI-SPEE
PA.26 -100.0~100.0% 0.0% ○
12 D 12
th
12 Step running RUNNING
PA.27 0.0~6553.5s(h) 0.0s ○
time TIME 12
Multi-step speed MULTI-SPEE
PA.28 -100.0~100.0% 0.0% ○
13 D 13
th
13 Step running RUNNING
PA.29 0.0~6553.5s(h) 0.0s ○
time TIME 13
Multi-step speed MULTI-SPEE
PA.30 -100.0~100.0% 0.0% ○
14 D 14
th
14 Step running RUNNING
PA.31 0.0~6553.5s(h) 0.0s ○
time TIME 14
.143.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
Multi-step speed MULTI-SPEE
PA.32 -100.0~100.0% 0.0% ○
15 D 15
th
15 Step running RUNNING
PA.33 0.0~6553.5s(h) 0.0s ○
time TIME 15
ACC/DEC time
0~7 TIME
PA.34 selection for step 0~65535 0 ○
SELECT
0~7
ACC/DEC time
8~15 TIME
PA.35 selection for step 0~65535 0 ○
SELECT
8~15
0: Second
PA.36 Time unit 0 ◎ TIME UNIT
1: Hour
PB Group: Protection Function
Input
0: Disabled IN PHASE
PB.00 phase-failure 1 ○
1: Enabled FAIL
protection
Output
0: Disabled OUT PHASE
PB.01 phase-failure 1 ○
1: Enabled FAIL
protection
0: Disabled
Motor overload 1: Normal motor MOTOR
PB.02 2 ◎
protection 2: Variable frequency OVERLOAD
motor
Motor overload OVERLOAD
PB.03 20.0%~120.0% 100.0% ○
protection current CURR
Overload
OL WARN
PB.04 pre-warning 20.0%~150.0% 130.0% ○
CURR
threshold
.144.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
0: Always detect relative
to motor rated current
1: Detect while constant
speed relative to motor
Overload
rated current OL WARN
PB.05 pre-warning 0 ◎
2: Always detect relative SELECT
selection
to inverter rated current
3: Detect while constant
speed relative to inverter
rated current
Overload
OL WARN
PB.06 pre-warning delay 0.0~30.0s 5.0s ○
DELAY
time
Threshold of TRIPFREE
Pb.07 230.0V~600.0V 450.0V ○
trip-free POINT
Decrease rate of TRIPFREE
PB.08 0.00Hz~P0.07 0.00Hz ○
trip-free DECRATE
Over-voltage stall 0: Disabled OVER VOLT
PB.09 0 ○
protection 1: Enabled STALL
OV
Over-voltage stall
PB.10 110~150% 125% ○ PROTECT
protection point
POINT
Over-current 0: Disabled
PB.11 1 ○ OVER CURR
protection 1: Enabled
OC
Over-current stall
PB.12 50~200% 160% ○ THRESHOL
threshold
D
Frequency FREQ DEC
PB.13 0.00~50.00Hz/s 1.00 Hz/s ○
decrease rate RATE
PC Group: Serial Communication
1~247 LOCAL
PC.00 Local address 1 ○
0: broadcast address ADDRESS
.145.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
0: 1200BPS
1: 2400BPS
Baud rate 2: 4800BPS
PC.01 4 ○ BAUD RATE
selection 3: 9600BPS
4: 19200BPS
5: 38400BPS
.146.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
0: RTU, 1 start bit, 8 data
bits, no parity check, 1
stop bit.
1: RTU, 1 start bit, 8 data
bits, even parity check, 1
stop bit.
2: RTU, 1 start bit, 8 data
bits, odd parity check, 1
stop bit.
3: RTU, 1 start bit, 8 data
bits, no parity check, 2
stop bits.
4: RTU, 1 start bit, 8 data
bits, even parity check, 2
stop bits.
5: RTU, 1 start bit, 8 data
bits, odd parity check, 2
stop bits.
6: ASCII, 1 start bit, 7 data
bits, no parity check, 1
stop bit.
7: ASCII, 1 start bit, 7 data
bits, even parity check, 1
stop bit.
8: ASCII, 1 start bit, 7 data
bits, odd parity check, 1
stop bit. DATA
PC.02 Data format 0 ○
9: ASCII, 1 start bit, 7 data FORMAT
bits, no parity check, 2
stop bits.
10: ASCII, 1 start bit, 7
data bits, even parity
check, 2 stop bits.
11: ASCII, 1 start bit, 7
.147.
data bits, odd parity
check, 2 stop bits.
CHV100 Series Close Loop Vector Control Inverter
Function Factory
Name Description Modify LCD Display
Code Setting
Communication COM DELAY
PC.03 0~200ms 5 ○
delay time TIME
Communication 0.0(invalid) COM
PC.04 0.0s ○
timeout delay 0.1~100.0s TIMEOUT
0: Enabled RESPONSE
PC.05 Response action 0 ○
1: Disabled ACTION
0: Alarm and coast to stop
1: Not alarm and keep
running
Communication 2: Not alarm and stop if FAULT
PC.06 0~3 0
fault action command source is ACTION
communication
3: Not alarm and stop in
any command source
PD Group: Supplementary Function
0: Keypad
1: AI1
2: AI2
Upper frequency 3: AI3 UPPER
PD.00 0 ○
limit selection 4: AI4 FREQ LIMIT
5: HDI 1
6: HDI 2
7: communication
NO/NC input NO/NC
PD.01 0~0x3FF 0x000 ◎
selection SELECT
PE Group: Factory Setting
FACTORY
PE.00 Factory Password 0~65535 ***** ●
PASSWORD
.148.