Ls s100 Userman 21
Ls s100 Userman 21
devices.
* LSLV-S100 is the official name for S100.
Safety Information
Safety Information
Read and follow all safety instructions in this manual precisely to avoid unsafe operating
conditions, property damage, personal injury, or death.
Indicates an imminently hazardous situation which, if not avoided, will result in severe injury or
death.
Indicates a potentially hazardous situation which, if not avoided, could result in injury or death.
Indicates a potentially hazardous situation that, if not avoided, could result in minor injury or
property damage.
Safety information
• Do not open the cover of the equipment while it is on or operating. Likewise, do not operate
the inverter while the cover is open. Exposure of high voltage terminals or charging area
to the external environment may result in an electric shock. Do not remove any covers
or touch the internal circuit boards (PCBs) or electrical contacts on the product when
the power is on or during operation. Doing so may result in serious injury, death, or
serious property damage.
• Do not open the cover of the equipment even when the power supply to the inverter
has been turned off unless it is necessary for maintenance or regular inspection.
Opening the cover may result in an electric shock even when the power supply is off.
• The equipment may hold charge long after the power supply has been turned off. Use a
multi-meter to make sure that there is no voltage before working on the inverter, motor or
motor cable.
ii
Safety Information
The following connection terminals and devices are the Protective Class 0. It means that
the circuit protection level depends on the basic insulation. If there is no basic insulation is
failed, it may cause electric shock accident. When installing or wiring the connection
terminals and devices, take the same protective action as with the power wire.
iii
Safety Information
• Do not modify the interior workings of the inverter. Doing so will void the warranty.
• The inverter is designed for 3-phase motor operation. Do not use the inverter to operate a
single phase motor.
• Do not place heavy objects on top of electric cables. Doing so may damage the cable
and result in an electric shock.
Note
Maximum allowed prospective short-circuit current at the input power connection is defined in
IEC 60439-1 as 100 kA. Depending on the selected MCCB, the LSLV-S100 Series is suitable
for use in circuits capable of delivering a maximum of 100 kA RMS symmetrical amperes at the
drive's maximum rated voltage. The following table shows the recommended MCCB for RMS
symmetrical amperes.
Remarque
Le courant maximum de court-circuit présumé autorisé au connecteur d’alimentation électrique
est défini dans la norme IEC 60439-1 comme égal à 100 kA. Selon le MCCB sélectionné, la
série LSLV-S100 peut être utilisée sur des circuits pouvant fournir un courant RMS symétrique
de 100 kA maximum en ampères à la tension nominale maximale du variateur. Le tableau
suivant indique le MCCB recommandé selon le courant RMS symétrique en ampères.
iv
Table of Contens
Table of Contents
1 Preparing the Installation.................................................................................. 1
1.1 Product Identification ................................................................................. 1
1.2 Part Names ................................................................................................ 3
0.4-22kW Models .......................................................................... 3
30-75kW Models ........................................................................... 5
IP66 Models .................................................................................. 6
1.3 Installation Considerations........................................................................ 8
1.4 Selecting and Preparing a Site for Installation......................................... 9
1.5 Cable Selection ....................................................................................... 13
2 Installing the Inverter ....................................................................................... 15
2.1 Mounting the Inverter .............................................................................. 17
2.2 Cable Wiring ............................................................................................ 21
2.3 Post-Installation Checklist ....................................................................... 54
2.4 Test Run ................................................................................................... 56
3 Learning to Perform Basic Operations ........................................................ 59
3.1 About the Keypad .................................................................................... 59
0.4-22kW Models ........................................................................ 59
30-75kW Models ......................................................................... 60
About the Display........................................................................ 61
Operation Keys ........................................................................... 65
Control Menu............................................................................... 67
3.2 Learning to Use the Keypad ................................................................... 71
Display Mode Selection (30-75kW models only) ...................... 71
Group and Code Selection......................................................... 74
Navigating Directly to Different Codes....................................... 79
Setting Parameter Values .......................................................... 81
Configuring the [ESC] Key (0.4-22kW models only) ................ 84
3.3 Actual Application Examples .................................................................. 85
Acceleration Time Configuration (0.4-22kW models only)....... 85
Frequency Reference Configuration (0.4-22kW models only) 86
Jog Frequency Configuration (0.4-22kW models only)............ 87
v
Table of Contents
vi
Table of Contens
vii
Table of Contents
viii
Preparing the Installation
Note
Check the product name, open the packaging, and then confirm that the product is free from
defects. Contact your supplier if you have any issues or questions about your product.
1
Preparing the Installation
2
Preparing the Installation
0.4-22kW Models
0.4-2.2kW (Single Phase) and 0.4-4.0kW (3–Phase)
3
Preparing the Installation
5.5–22kW(3–Phase)
4
Preparing the Installation
30-75kW Models
Note
The grounding terminal cover of EMC is not existed in the 55-75kW inverters.
5
Preparing the Installation
IP66 Models
The installation location for cooling fan varies according to product capacity.
Inside the product: 0.4-4.0kW; bottom of the product: 5.5-7.5kW; inside and top of the
product: 11-22kW.
6
Preparing the Installation
7
Preparing the Installation
Items Description
Ambient Temperature* Heavy Duty: 14–104F (-10–50℃) Normal Duty: 14–122F (-10– 40℃)
Ambient Humidity 90% relative humidity (no condensation)
Storage Temperature - 4–149F (-20–65℃)
An environment free from corrosive or flammable gases,
Environmental Factors
oil residue or dust
Maximum 1000m above sea level for standard operation. From 1000
Altitude
to 4000m, the rated input voltage and rated output current of the drive
/ Vibration
must be derated by 1% for every 100m. / less than 1G (9.8m/sec2)
Air Pressure 70 –106kPa
* The ambient temperature is the temperature measured at a point 2” (5 cm) from the
surface of the inverter.
* IP66 models only support heavy load operation, and an ambient temperature of between
-10℃ – +40℃.
Do not allow the ambient temperature to exceed the allowable range while operating the
inverter.
8
Preparing the Installation
• The location must be free from vibration, and the inverter must be installed on a wall
that can support the inverter’s weight.
• The inverter can become very hot during operation. Install the inverter on a surface that
is fire-resistant or flame-retardant and with sufficient clearance around the inverter to
allow air to circulate. The illustrations below detail the required installation clearances.
9
Preparing the Installation
• Ensure sufficient air circulation is provided around the inverter when it is installed. If the
inverter is to be installed inside a panel, enclosure, or cabinet rack, carefully consider
the position of the inverter’s cooling fan and the ventilation louver. The cooling fan must
be positioned to efficiently transfer the heat generated by the operation of the inverter.
10
Preparing the Installation
• If you are installing multiple inverters in one location, arrange them side-by-side and
remove the top covers. The top covers MUST be removed for side-by-side installations.
Use a flat head screwdriver to remove the top covers.
• Side-by-side operation only supports 0.4-22kW, IP20 models.
11
Preparing the Installation
• If you are installing multiple inverters, of different ratings, provide sufficient clearance to
meet the clearance specifications of the larger inverter.
12
Preparing the Installation
• Wherever possible use cables with the largest cross-sectional area for mains power
wiring, to ensure that voltage drop does not exceed 2%.
• Use copper cables rated for 600V, 75℃ for power terminal wiring.
• Use copper cables rated for 300V, 75℃ for control terminal wiring.
13
Preparing the Installation
Signal Cable
Without Crimp Terminal
With Crimp Terminal Connectors
Terminals Connectors
(Bootlace Ferrule)
(Bare wire)
mm2 AWG mm2 AWG
P1~P7*/CM/VR/V1/I2
/AO1,AO2/Q1/EG/24/TI/
0.75 18 0.5 20
TO* /SA,SB,SC/S+,
S-,SG
A1/B1/C1/A2/C2 1.0 17 1.5 15
* Standard I/O doesn’t support P6/P7/TI/TO terminal. Refer to Step 4 Control Terminal
Wiring on page 39.
14
Installing the Inverter
Installation Flowchart
The flowchart lists the sequence to be followed during installation. The steps cover
equipment installation and testing of the product. More information on each step is
referenced in the steps.
Testing (p.56)
15
Installing the Inverter
The reference diagram below shows a typical system configuration showing the inverter
and peripheral devices.
Prior to installing the inverter, ensure that the product is suitable for the application (power
rating, capacity, etc). Ensure that all of the required peripherals and optional devices
(resistor brakes, contactors, noise filters, etc.) are available. For more details on peripheral
devices, refer to 7.4 Peripheral Devices on page 228.
• Figures in this manual are shown with covers or circuit breakers removed to show a more
detailed view of the installation arrangements. Install covers and circuit breakers before
operating the inverter. Operate the product according to the instructions in this manual.
• Do not start or stop the inverter using a magnetic contactor, installed on the input power
supply.
• If the inverter is damaged and loses control, the machine may cause a dangerous
situation. Install an additional safety device such as an emergency brake to prevent these
situations.
• High levels of current draw during power-on can affect the system. Ensure that
correctly rated circuit breakers are installed to operate safely during power-on
situations.
• Reactors can be installed to improve the power factor. Note that reactors may be
installed within 30 ft (9.14 m) from the power source if the input power exceeds 10
times 0f inverter capacity. Refer to 7.5 Fuse and Reactor Specifications on page 229
and carefully select a reactor that meets the requirements.
• 30-75kW models have a built-in DC Reactor.
16
Installing the Inverter
Select a wall or panel suitable to support the installation. Refer to 7.3 External Dimensions
on page 213 and check the inverter’s mounting bracket dimensions.
1 Use a level to draw a horizontal line on the mounting surface, and then carefully mark
the fixing points.
2 Drill the two upper mounting bolt holes, and then install the mounting bolts. Do not fully
tighten the bolts at this time. Fully tighten the mounting bolts after the inverter has been
mounted.
17
Installing the Inverter
3 Mount the inverter on the wall or inside a panel using the two upper bolts, and then fully
tighten the mounting bolts. Ensure that the inverter is placed flat on the mounting
surface, and that the installation surface can securely support the weight of the inverter.
18
Installing the Inverter
Note
The quantity and dimensions of the mounting brackets vary based on frame size. Refer to 7.3
External Dimensions on page 213 for detailed information about your model.
0.4kW (Single Phase) and 0.4-0.8kW (3-phase) inverters have only two mounting brackets.
19
Installing the Inverter
• Do not transport the inverter by lifting with the inverter’s covers or plastic surfaces. The
inverter may tip over if covers break, causing injuries or damage to the product. Always
support the inverter using the metal frames when moving it.
• High-capacity inverters are very heavy and bulky. Use an appropriate transport method
that is suitable for the weight.
• Do not install the inverter on the floor or mount it sideways against a wall. The inverter
MUST be installed vertically, on a wall or inside a panel, with its rear flat on the mounting
surface.
20
Installing the Inverter
Read the following information carefully before carrying out wiring connections to the
inverter. All warning instructions must be followed.
21
Installing the Inverter
The front cover, control terminal cover and cable guide must be removed to install cables.
Refer to the following procedures to remove the covers and cable guide. The steps to
remove these parts may vary depending on the inverter model.
1 Loosen the bolt that secures the front cover (right side). Push and hold the latch on the
right side of the cover. Then remove the cover by lifting it from the bottom and moving it
away from the front of the inverter.
22
Installing the Inverter
2 Remove the bolt that secures the front cover (left side) (❶). Push and hold the latch on
the left side of the cover. Then remove the cover by lifting it from the bottom and
moving it away from the front of the inverter (❷).
3 Connect the cables to the power terminals and the control terminals. For cable
specifications, refer to 1.5 Cable Selection on page 13.
23
Installing the Inverter
5.5–22kW (3-phase)
1 Loosen the bolt that secures the front cover. Then remove the cover by lifting it from the
bottom and away from the front.
2 Push and hold the levers on both sides of the cable guide (❶) and then remove the
cable guide by pulling it directly away from the front of the inverter (❷). In some models
where the cable guide is secured by a bolt, remove the bolt first.
24
Installing the Inverter
3 Push and hold the tab on the right side of the control terminal cover. Then remove the
cover by lifting it from the bottom and moving it away from the front of the inverter.
4 Connect the cables to the power terminals and the control terminals. For cable
specifications, refer to 1.5 Cable Selection on page 13.
Note
To connect an LCD loader, remove the plastic knock-out from the bottom of the front cover
(right side). Connect the signal cable of the LCD loader to the RJ-45 port on the control board.
(0.4-22kW models only)
25
Installing the Inverter
30-75kW(3-phase 4type)
1 Loosen the bolt that secures the terminal cover (). Push and hold the latch on the
right side of the cover (). Then remove the cover by lifting it from the bottom and
moving it away from the front of the inverter.
2 Connect the cables to the power terminals and the control terminals. For cable
specifications, refer to 1.5 Cable Selection on page 13.
26
Installing the Inverter
IP66
1 Loosen the bolt that secures the front cover. Then remove the cover by lifting it from the
bottom and moving it away from the front of the inverter.
27
Installing the Inverter
2 Set the bushing to every wiring hole before installing to power and I/O board terminals.
Use the bushing that is NEMA 4X (IP66) or more.
3 Connect the cables to the power terminals and the control terminals. For cable
specifications, refer to 1.5 Cable Selection on page 13.
Note
To connect an LCD loader, remove the plastic knock-out from the bottom of the front cover
(right side). Connect the signal cable of the LCD loader to the RJ-45 port on the control board.
(0.4-22kW models only)
28
Installing the Inverter
Remove the front cover(s), cable guide, and the control terminal cover. Then follow the
instructions below to install the ground connection for the inverter.
Note
• 200 V products require Class 3 grounding. Resistance to ground must be < 100Ω.
• 400 V products require Special Class 3 grounding. Resistance to ground must be < 10Ω.
Install ground connections for the inverter and the motor by following the correct specifications
to ensure safe and accurate operation. Using the inverter and the motor without the specified
grounding connections may result in electric shock.
0.4-22kW
1 Locate the ground terminal and connect an appropriately rated ground cable to the
terminals. Refer to 1.5 Cable Selection on page 13 to find the appropriate cable
specification for your installation.
2 Connect the other ends of the ground cables to the supply earth (ground) terminal.
29
Installing the Inverter
30-75kW
1 Locate the ground terminal and connect an appropriately rated ground cable to the
terminals. Refer to 1.5 Cable Selection on page 13 to find the appropriate cable
specification for your installation.
2 Connect the other ends of the ground cables to the supply earth (ground) terminal.
30
Installing the Inverter
IP66
1 Locate the ground terminal and connect an appropriately rated ground cable to the
terminals. Refer to 1.5 Cable Selection on page 13 to find the appropriate cable
specification for your installation.
2 Connect the other ends of the ground cables to the supply earth (ground) terminal.
31
Installing the Inverter
The following illustration shows the terminal layout on the power terminal block. Refer to the
detailed descriptions to understand the function and location of each terminal before making
wiring connections. Ensure that the cables selected meet or exceed the specifications in 1.5
Cable Selection on page 13 before installing them.
• Apply rated torques to the terminal screws. Loose screws may cause short circuits and • Tighte
malfunctions. Tightening the screw too much may damage the terminals and cause short cables
circuits and malfunctions. termin
• Use copper wires only with 600V, 75℃ rating for the power terminal wiring, and 300V, • Use c
75℃rating for the control terminal wiring. • Use c
• Do not connect two wires to one terminal when wiring the power. • Powe
power
• Power supply wirings must be connected to the R, S, and T terminals. Connecting them to Conne
the U, V, W terminals causes internal damages to the inverter. Motor should be connected neces
to the U, V, and W Terminals. Arrangement of the phase sequence is not necessary.
• Appliquer des couples de marche aux vis des bornes. Des vis desserrées peuvent
provoquer des courts-circuits et des dysfonctionnements. Ne pas trop serrer la vis, car cela
risqué d’endommager les bornes et de provoquer des courts-circuits et des
dysfonctionnements. Utiliser uniquement des fils de cuivre avec une valeur nominale de
600 V, 75 ℃ pour le câblage de la borne d’alimentation, et une valeur nominale de 300 V,
75 ℃ pour le câblage de la borne de commande.
• Ne jamais connecter deux câbles à une borne lors du câblage de l'alimentation.
• Les câblages de l’alimentation électrique doivent être connectés aux bornes R, S et T.
Leur connexion aux bornes U, V et W provoque des dommages internes à l’onduleur.
Le moteur doit être raccordé aux bornes U, V et W. L’arrangement de l’ordre de phase
n’est pas nécessaire.
32
Installing the Inverter
0.4-22kW
33
Installing the Inverter
5.5–22kW (3-phase)
34
Installing the Inverter
30-75kW (3-phase)
35
Installing the Inverter
IP66
0.4-0.8kW (3-phase)
1.5-2.2kW (3-phase)
36
Installing the Inverter
3.7-4.0kW (3-phase)
5.5–22kW (3-phase)
37
Installing the Inverter
Note
• Do not use 3 core cables to connect a remotely located motor with the inverter.
• When you operating Brake resistor, the motor may vibrate under the Flux braking
operation. In this case, please turn off the Flux braking(Pr.50).
• Make sure that the total cable length does not exceed 665ft (202m). For inverters < =
4.0kW capacity, ensure that the total cable length does not exceed 165ft (50m).
• Long cable runs can cause reduced motor torque in low frequency applications due to
voltage drop. Long cable runs also increase a circuit’s susceptibility to stray capacitance
and may trigger over-current protection devices or result in malfunction of equipment
connected to the inverter.
• Voltage drop is calculated by using the following formula:
Voltage Drop (V) = [√3 X cable resistance (mΩ/m) X cable length (m) X current(A)] /
1000
• Use cables with the largest possible cross-sectional area to ensure that voltage drop is
minimized over long cable runs. Lowering the carrier frequency and installing a micro
surge filter may also help to reduce voltage drop.
Distance < 165ft (50m) < 330ft (100m) > 330ft (100m)
< 15 kHz
Allowed Carrier Frequency < 5 kHz < 2.5 kHz
(30-75kW: < 5 kHz)
Do not connect power to the inverter until installation has been fully completed and the inverter
is ready to be operated. Doing so may result in electric shock.
• Power supply cables must be connected to the R, S, and T terminals. Connecting power
cables to other terminals will damage the inverter.
• Use insulated ring lugs when connecting cables to R/S/T and U/V/W terminals.
• The inverter’s power terminal connections can cause harmonics that may interfere with
other communication devices located near to the inverter. To reduce interference the
installation of noise filters or line filters may be required.
• To avoid circuit interruption or damaging connected equipment, do not install phase-
advanced condensers, surge protection, or electronic noise filters on the output side of the
inverter.
• To avoid circuit interruption or damaging connected equipment, do not install magnetic
contactors on the output side of the inverter.
38
Installing the Inverter
The illustrations below show the detailed layout of control wiring terminals, and control
board switches. Refer to the detailed information provided below and 1.5 Cable Selection
on page 13 before installing control terminal wiring and ensure that the cables used meet
the required specifications.
0.4-22kW
<Standard I/O>
<Multiple I/O>
39
Installing the Inverter
30-75kW
<30-75kW I/O>
Switch Description
SW1 NPN/PNP mode selection switch
SW2 analog voltage/current input terminal selection switch
SW3 analog voltage/current output terminal selection switch
SW4 Terminating Resistor selection switch
Name Description
Connector Connect to iS7 Loader or Smart Copier
40
Installing the Inverter
0.4-22kW
<Standard I/O>
<Multiple I/O>
41
Installing the Inverter
30-75kW
42
Installing the Inverter
43
Installing the Inverter
44
Installing the Inverter
Use preinsulated crimp terminal connectors to increase reliability of the control terminal
wiring. Refer to the specifications below to determine the crimp terminals to fit various cable
sizes.
45
Installing the Inverter
To connect cables to the control terminals without using crimp terminals, refer to the
following illustration detailing the correct length of exposed conductor at the end of the
control cable.
Note
• While making wiring connections at the control terminals, ensure that the total cable length
does not exceed 165ft (50m).
• Ensure that the length of any safety related wiring does not exceed 100ft (30m).
• Ensure that the cable length between an LCD keypad and the inverter does not exceed
10ft (3.04m). Cable connections longer than 10ft (3.04m) may cause signal errors.
• Use ferrite material to protect signal cables from electro-magnetic interference.
• Take care when supporting cables using cable ties, to apply the cable ties no closer than
6 inches from the inverter. This provides sufficient access to fully close the front cover.
• When making control terminal cable connections, use a small flat-tip screw driver (0.1in
wide (2.5mm) and 0.015in thick (0.4mm) at the tip).
SA,SB, SC, they are shorted, have 24V voltage. Do not connect power to the inverter until
installation has been fully completed and the inverter is ready to be operated. Doing so may
result in electric shock.
46
Installing the Inverter
The S100 inverter supports both PNP (Source) and NPN (Sink) modes for sequence inputs
at the terminal. Select an appropriate mode to suit requirements using the PNP/NPN
selection switch (SW1) on the control board. Refer to the following information for detailed
applications.
Select PNP using the PNP/NPN selection switch (SW1). Note that the factory default
setting is NPN mode. CM is the common ground terminal for all analog inputs at the
terminal, and P24 is 24V internal source. If you are using an external 24V source, build a
circuit that connects the external source (-) and the CM terminal.
47
Installing the Inverter
Select NPN using the PNP/NPN selection switch (SW1). Note that the factory default
setting is NPN mode. CM is the common ground terminal for all analog inputs at the
terminal, and P24 is 24V internal source.
48
Installing the Inverter
Step 6 Disabling the EMC Filter for Power Sources with Asymmetrical
Grounding
S100 built-in EMC filter prevents electromagnetic interference by reducing radio emissions
from the inverter. EMC filter is activated as a factory default design. If an inverter uses a
power source with an asymmetrical grounding connection or non-grounding, the EMC filter
MUST be turned off. EMC filter use is not always recommended, as it increases leakage
current. Refer to Product Identification on page 1 to check if inverters have built-in EMC
filters.
Note
One Intermediate
phase of a grounding
delta point on one
connectio phase of a
n is delta
grounded connection
• Do not activate the EMC filter if the inverter uses a power source with an asymmetrical
grounding structure, for example a grounded delta connection. Personal injury or death by
electric shock may result.
• Wait at least 10 minutes before opening the covers and exposing the terminal connections.
Before starting work on the inverter, test the connections to ensure all DC voltage has
been fully discharged. Personal injury or death by electric shock may result.
49
Installing the Inverter
0.4-22kW
Before using the inverter, confirm the power supply’s grounding system. Disable the EMC
filter if the power source has an asymmetrical grounding connection. Refer to the figures
below to locate the EMC filter on/off terminal and replace the metal bolt with the plastic bolt.
If the EMC filter is required in the future, reverse the steps and replace the plastic bolt with
the metal bolt to reconnect the EMC filter.
50
Installing the Inverter
30-75kW
1 Remove the EMC ground cover located at the bottom of the inverter.
2 Remove the EMC ground cable from the right terminal (EMC filter-ON / factory default),
and connect it to the left terminal (EMC filter-OFF / for power sources with
asymmetrical grounding).
51
Installing the Inverter
Note
The terminal on the right is used to ENABLE the EMC filter (factory default). The terminal on the
left is used to DISABLE the EMC filter (for power sources with asymmetrical grounding).
52
Installing the Inverter
30-37kW SV037DBH-4
Non UL type
(A type) 45-55kW
SV075DBH-4, SV075DB-4
75kW
LSLV0370DBU-4LN
Non UL type 30-37kW
(B type) LSLV0370DBU-4HN
45-75kW LSLV0750DBU-4LN
30-37kW SV370DBU-4U
UL type 45-55kW SV550DBU-4U
75kW SV750DBU-4U
53
Installing the Inverter
54
Installing the Inverter
Note
STP (Shielded Twisted Pair) cable has a highly conductive, shielded screen around twisted
cable pairs. STP cables protect conductors from electromagnetic interference.
55
Installing the Inverter
1 Turn on the power supply to the inverter. Ensure that the keypad display light is on.
2 Select the command source.
3 Set a frequency reference, and then check the following:
• If V1 is selected as the frequency reference source, does the reference change
according to the input voltage at VR?
• If V2 is selected as the frequency reference source, is the voltage/current selector
switch (SW2) set to voltage, and does the reference change according to the input
voltage?
• If I2 is selected as the frequency reference source, is the voltage/current selector
switch (SW2) set to current, and does the reference change according to the input
current?
4 Set the acceleration and deceleration time.
5 Start the motor and check the following:
• Ensure that the motor rotates in the correct direction (refer to the note below).
• Ensure that the motor accelerates and decelerates according to the set times, and
that the motor speed reaches the frequency reference.
56
Installing the Inverter
Note
If the forward command (Fx) is on, the motor should rotate counterclockwise when viewed
from the load side of the motor. If the motor rotates in the reverse direction, switch the
cables at the U and V terminals.
Remarque
Si la commande avant (Fx) est activée, le moteur doit tourner dans le sens anti-horaire si
on le regarde côté charge du moteur. Si le moteur tourne dans le sens inverse, inverser les
câbles aux bornes U et V.
If the motor rotates in the reverse direction, two of the U/V/W terminals need to be switched.
• Check the parameter settings before running the inverter. Parameter settings may have to
be adjusted depending on the load.
• To avoid damaging the inverter, do not supply the inverter with an input voltage that
exceeds the rated voltage for the equipment.
• Before running the motor at maximum speed, confirm the motor’s rated capacity. As
inverters can be used to easily increase motor speed, use caution to ensure that motor
speeds do not accidently exceed the motor’s rated capacity.
57
Installing the Inverter
58
Learning to Perform Basic Operations
0.4-22kW Models
59
Learning to Perform Basic Operations
30-75kW Models
60
Learning to Perform Basic Operations
The table below lists the way that the keypad displays characters (letters and numbers).
0 0 a A k K u U
1 1 b B l L v V
2 2 c C m M w W
3 3 d D n N x X
4 4 e E o O y Y
5 5 f F p P z Z
6 6 g G q Q - -
7 7 h H r R - -
8 8 i I s S - -
9 9 j J t T - -
61
Learning to Perform Basic Operations
62
Learning to Perform Basic Operations
Display details
No. Name Display Description
MON Monitor Mode
PAR Parameter Mode
1 Mode
TRP Trip Mode
CNF Config Mode
K Keypad operation command
Field Bus communication option operation
O
command
Operation
commands A Application option operation command
R Internal 485 operation command
T Terminal operation command
K Keypad frequency command
2 V V1 input frequency command
P Pulse input frequency command
Frequency command for UP operation (Up - Down
Frequency U
operation)
commands
Frequency command for DOWN operation (Up -
D
Down operation)
Frequency command for STOP operation (Up -
S
Down operation)
O FBus Option frequency command
63
Learning to Perform Basic Operations
64
Learning to Perform Basic Operations
Operation Keys
Install a separate emergency stop switch in the circuit. The [STOP/RESET] key on the keypad
works only when the inverter has been configured to accept an input from the keypad.
The following table lists the names and functions of the keypad’s operation keys.
65
Learning to Perform Basic Operations
[PROG / Ent]
Used to select, confirm, or save a parameter value.
Key
[UP] key Switch between codes or increase or decrease parameter
[DOWN] key values.
[LEFT] key Switch between groups or move the cursor during parameter
[RIGHT] key setup or modification.
Used to perform special functions, such as user code
[MULTI] Key
registration.
Used to cancel an input during parameter setup.
• Pressing the [ESC] key before pressing the [PROG / ENT]
key reverts the parameter value to the previously set value.
• Pressing the [ESC] key while editing the codes in any
[ESC] Key
function group makes the keypad display the first code of
the function group.
• Pressing the [ESC] key while moving through the modes
makes the keypad display Monitor mode.
[FWD] Key Used to operate the motor in the forward direction.
66
Learning to Perform Basic Operations
Control Menu
67
Learning to Perform Basic Operations
68
Learning to Perform Basic Operations
69
Learning to Perform Basic Operations
The following table lists the 5 display modes used to control the inverter functions.
70
Learning to Perform Basic Operations
Confirm the correct values (or the correct range of the values), and then follow the
examples below to configure the inverter with the keypad.
User mode and Trip mode are not displayed when all the inverter settings are set to the
factory default (User mode must be configured before it is displayed on the keypad, and
Trip mode is displayed only when the inverter is at fault, or has previous trip fault history).
71
Learning to Perform Basic Operations
• Parameter mode
• Press the [MODE] key.
72
Learning to Perform Basic Operations
Trip mode is accessible only when the inverter has trip fault history. Refer to 3 Learning to
Perform Basic Operations on page 59 for information about monitoring faults.
• Parameter mode
• Press the [MODE] key.
• Trip mode
• Press the [MODE] key.
• CNF mode
• Press the [MODE] key.
73
Learning to Perform Basic Operations
74
Learning to Perform Basic Operations
Note
For some settings, pressing the [▲] or [▼] key will not increase or decrease the code number
by 1. Code numbers may be skipped and not be displayed. This is because certain code
numbers have been intentionally left blank (or reserved) for new functions to be added in the
future. Also some features may have been hidden (disabled) because a certain code has been
set to disable the functions for relevant codes.
As an example, if Ad.24 (Frequency Limit) is set to 0 (No), the next codes, Ad.25 (Freq Limit Lo)
and Ad.26 (Freq Limit Hi), will not be displayed. If you set code Ad.24 to 1 (Yes) and enable the
frequency limit feature, codes Ad.25 and 26 will appear to allow the maximum and minimum
frequency limitations to be set up.
75
Learning to Perform Basic Operations
After entering Parameter mode from Monitor mode, press the [▶] key to change the display
as shown below. Press the [▶] key to return to the previous mode.
• Parameter mode
• Drive group is displayed.
• Press the [▶] key.
76
Learning to Perform Basic Operations
In monitor mode, press the [▲], [▼] key to display frequency, the output current, or voltage
according to the cursor position.
77
Learning to Perform Basic Operations
The following examples show you how to move through codes in different function groups
(Drive group and Basic group) in Parameter mode. In parameter mode, press the [▲] or [▼]
key to move to the desired functions.
78
Learning to Perform Basic Operations
1
Ensure that you are currently at the first code of the Drive dr.0
group (dr.0).
Press the [ENT] key.
2
Number ‘9’ will flash.
(
Press the [▼] key to display ‘5,’ the first 1s’ place of the group
3 %
destination, ’95.’
Press the [◀] key to move to the 10s’ place.
4 The cursor will move to the left and ‘05’ will be displayed. This )5
time, the number ‘0’ will be flashing.
Press the [▲] key to increase the number from ‘0’ to ‘9,’ the
5 95
10s place digit of the destination, ’95.’
Press the [ENT] key.
6
Code dr.95 is displayed.
dr.95
79
Learning to Perform Basic Operations
The following example shows how to navigate directly to code DRV- 09 from the initial code
(DRV-00 Jump Code) in the Drive group.
80
Learning to Perform Basic Operations
Note
• A flashing number on the display indicates that the keypad is waiting for an input from the
user. Changes will be saved when the [ENT] key is pressed while the number is flashing.
The setting change will be canceled if you press any other key.
• Each code’s parameter values have default features and ranges specified. Refer to 4 Table
of Functions on page 103 for information about the features and ranges before setting or
modifying parameter values.
81
Learning to Perform Basic Operations
The S100 inverter allows basic parameters to be modified in Monitor mode. The following
example shows how to set the frequency.
82
Learning to Perform Basic Operations
The following example shows how to change the frequency in the Drive group. This
example can also be applied to other modes and groups.
• Press the [▲] key to enter 10 Hz, and then press the
[PROG/ENT] key.
83
Learning to Perform Basic Operations
Note
• If the code dr. 90 (ESC key configuration) is set to 1 (JOG Key) or 2 (Local/Remote), the
SET indicator will flash when the [ESC] key is pressed.
• The factory default setting for code dr. 90 is 0 (move to the initial position). You can
navigate back to the initial position (code 0.00 of the Operation group) immediately, by
pressing the [ESC] key while configuring any codes in any groups.
84
Learning to Perform Basic Operations
85
Learning to Perform Basic Operations
Note
• A flashing number on the display indicates that the keypad is waiting for an input from the
user. Changes are saved when the [ENT] key is pressed while the value is flashing.
Changes will be canceled if any other key is pressed.
• The S100 inverter keypad display can display up to 4 digits. However, 5-digit figures can
be used and are accessed by pressing the [◀] or [▶] key, to allow keypad input.
86
Learning to Perform Basic Operations
87
Learning to Perform Basic Operations
Note
Following parameter initialization, all parameters are reset to factory default values. Ensure that
parameters are reconfigured before running the inverter again after an initialization.
88
Learning to Perform Basic Operations
89
Learning to Perform Basic Operations
90
Learning to Perform Basic Operations
Note
The instructions in the table are based on the factory default parameter settings. The inverter
may not work correctly if the default parameter settings are changed after the inverter is
purchased. In such cases, initialize all parameters to reset the values to factory default
parameter settings before following the instructions in the table.
91
Learning to Perform Basic Operations
Note
The instructions in the table are based on the factory default parameter settings. The inverter
may not work correctly if the default parameter settings are changed after the inverter is
purchased. In such cases, initialize all parameters to reset the factory default parameter
settings before following the instructions in the table.
92
Learning to Perform Basic Operations
Note
The instructions in the table are based on the factory default parameter settings. The inverter
may not work correctly if the default parameter settings are changed after the inverter is
purchased. In such cases, initialize all parameters to reset the factory default parameter
settings before following the instructions in the table.
93
Learning to Perform Basic Operations
0.4-22kW Models
Note
You can use the dCL (DC link voltage monitor) and vOL (output voltage monitor) codes in the
Operation group in exactly the same way as shown in the example above, to monitor each
function’s relevant values.
94
Learning to Perform Basic Operations
95
Learning to Perform Basic Operations
Note
• If multiple fault trips occur at the same time, a maximum of 3 fault trip records can be
retrieved as shown in the following example.
• If a warning condition occurs while running at a specified frequency, the current frequency
and the warn signal will be displayed alternately, at 1 second intervals.
96
Learning to Perform Basic Operations
30-75kW Models
How to use Monitor mode
There are 3 types of items that may be monitored in Monitor mode. Some items, including
frequency, may be modified. Users can select the items to be displayed in Config mode
(CNF).
• Monitor mode
• Frequency, current, and voltage are set as the default
monitored items.
• The target frequency is displayed when the inverter is
stopped. The operation frequency is displayed while
operating.
• Configure the items to be displayed in Config mode
(CNF) 21~23.
• Press the [▼] key to go to 23.
97
Learning to Perform Basic Operations
98
Learning to Perform Basic Operations
On the top-right corner of the display, there is a display item. This item is displayed as long
as the inverter is on, regardless of the mode the inverter is operating in.
• Monitor mode
• In the top-right corner of the display, the frequency
reference is displayed (factory default).
99
Learning to Perform Basic Operations
The following example shows how to monitor faults that occurred during inverter operation.
100
Learning to Perform Basic Operations
The following example shows how to monitor multiple faults that occur at the same time.
When fault trips occur, the trip mode saves the content. Up to five fault trips are saved in the
history. Trip mode saves when the inverter is reset, and when a Low Voltage fault trip
occurs due to power outages. If a trip occurs more than five times, the information for the
five previous trips are automatically deleted.
101
Learning to Perform Basic Operations
102
Table of Functions
4 Table of Functions
This chapter lists all the function settings for S100 series inverter. Set the parameters
required according to the following references. If a set value input is out of range, the
following messages will be displayed on the keyboard. In these cases, the inverter will not
operate with the [ENT] key.
1
Table of options are provided separately in the option manual.
103
Table of Functions
104
Table of Functions
2
Displayed when an LCD keypad is in use.
105
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address value
12 Pulse
0 V/F
2 Slip Compen
Control Control
09 0h1109 IM 0: V/F X/A O I/P
mode Mode 4
Sensorless
6 PM S/L
Torque Torque 0 No
10 0h110A 0: No X/A X I
Control Control 1 Yes
0.00, Start
Jog Jog frequency-
11 0h110B 10.00 O/A O I/P
frequency Frequency Maximum
frequency(Hz)
Jog run
Jog Acc
12 0h110C acceleration 0.0-600.0(s) 20.0 O/A O I/P
Time
time
Jog run
Jog Dec
13 0h110D deceleration 0.0-600.0(s) 30.0 O/A O I/P
Time
time
0: 0.2kW,
1: 0.4kW
2: 0.75kW,
3: 1.1kW
4: 1.5kW,
5: 2.2kW
6: 3.0kW,
7: 3.7kW
8: 4.0kW,
9: 5.5kW Varies by
Motor Motor
14 0h110E 10: 7.5kW, Motor X/A O I/P
capacity Capacity
11: 11.0kW capacity
12: 15.0kW,
13: 18.5kW
14: 22.0kW,
15: 30.0kW
16: 37kW
17: 45.0kW
18: 55.0kW
19: 75kW
20: 90kW
Torque boost Torque 0 Manual 0:
15 0h110F X/A O X
options Boost 1 Auto1 Manual
106
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address value
2 Auto2
3 Forward
16 0h1110 Fwd Boost 0.0-15.0(%) 2.0 X/A O X
Torque boost
3 Reverse
17 0h1111 Rev Boost 0.0-15.0(%) 2.0 X/A O X
Torque boost
30.00~400.00(Hz)
[V/F, Slip Compen]
Base 40.00~120.00(Hz)
18 0h1112 Base Freq 60.00 X/A O I/P
frequency [IM Sensorless]
30.00~180.00(Hz)
[PM Sensorless]
Start
19 0h1113 Start Freq 0.01-10.00(Hz) 0.50 X/A O I/P
frequency
40.00~400.00(Hz)
[V/F, Slip Compen]
Maximum 40.00~120.00(Hz)
20 0h1114 Max Freq 60.00 X/A O I/P
frequency [IM Sensorless]
40.00~180.00(Hz)
[PM Sensorless]
Select speed 0 Hz Display 0:Hz
21 0h1115 Hz/Rpm Sel O/L O I/P
unit 1 Rpm Display Display
4 (+)Torque
22 0h1116 (+)Trq Gain 50.0 ~ 150.0[%] 100.0 O/A X I
gain
4 (-)Torque
23 0h1117 (-)Trq Gain 50.0 ~ 150.0[%] 100.0 O/A X I
gain
4 (-)Torque
24 0h1118 (-)Trq Gain0 50.0 ~ 150.0[%] 80.0 O/A X I
gain 0
4 (-)Torque
25 0h1119 (-)Trq Offset 0.0 ~ 100.0[%] 40.0 O/A X I
offset
Select ranges
inverter displays at
power input
Select Run
0 frequency 0: run
5
80 0h1150 ranges at - O/7 O I/P
Acceleration frequency
power input 1 time
Deceleration
2 time
3 Command
3
Displayed when dr.15 is set to 0 (Manual) or 2(Auto2)
4
Displayed when dr.10 is set to 1 (YES)
5
Will not be displayed when an LCD keypad is in use
107
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address value
source
Frequency
4 reference
source
Multi-step
5 speed
frequency1
Multi-step
6 speed
frequency2
Multi-step
7 speed
frequency3
Output
8
current
9 Motor RPM
Inverter DC
10
voltage
User select
11
signal (dr.81)
Currently out
12
of order
Select run
13
direction
output
14
current2
15 Motor RPM2
Inverter DC
16
voltage2
User select
17 signal2
(dr.81)
Monitors user
selected code
Output
0 0:
Select voltage(V)
815 0h1151 - Output output O/7 O I/P
monitor code
1 electric voltage
power(kW)
Torque(kgf
2
m)
85
6 0h1155 Parameter - 0 No X/7 O I/P
0:No
Read 1 Yes
866 0h1156 Parameter - 0 No 0:No X/7 O I/P
6
Displayed when a Remote is in use.
108
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address value
Write 1 Yes
Display 0 View All
0:
895 0h03E3 changed - View O/7 O I/P
1 View All
parameter Changed
Move to initial
0
[ESC] key position 0:
905 0h115A - JOG Key X/7 O I/P
functions 1 None
2 Local/Remote
0 None
SmartDownlo
91 0h115B Smart copy SmartCopy 1 0:None X/A O I/P
ad
3 SmartUpLoad
Parameter 0 No
926 0h115C - 0:No X/7 O I/P
Save 1 Yes
0 No
1 All Grp
2 dr Grp
3 bA Grp
4 Ad Grp
5 Cn Grp
6 In Grp
Parameter
935 0h115D - 7 OU Grp 0:No X/7 O I/P
initialization
8 CM Grp
9 AP Grp
12 Pr Grp
13 M2 Grp
14 US Grp
15 UF Grp
16 run Grp
Password
945 0h115E 0-9999 O/7 O I/P
registration
Parameter
955 0h115F 0-9999 O/7 O I/P
lock settings
Software
975 0h1161 - -/7 O I/P
version
Display I/O
98 0h1162 board IO S/W Ver -/A O I/P
version
0 Multiple IO
Display I/O
1 Standard IO Standard
99 0h1163 board H/W IO H/W Ver -/A O I/P
Standard IO IO
version 2
(M)
109
Table of Functions
7
Displayed if bA.01 is not set to 0 (None).
110
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
0 Keypad-1
1 Keypad-2
2 V1
2nd Torque 4 V2
0:
06 0h1206 command Trq 2nd Src 5 I2 O X I
Keypad-1
source 6 Int 485
8 FieldBus
9 UserSeqLink
12 Pulse
0 Linear
V/F pattern 1 Square 0:
07 0h1207 V/F Pattern X/A O X
options 2 User V/F Linear
3 Square 2
Acc/dec Ramp T 0 Max Freq 0:
08 0h1208 standard X/A O I/P
frequency Mode 1 Delta Freq Max Freq
0 0.01 sec
Time scale
09 0h1209 settings Time Scale 1 0.1 sec 1:0.1 sec X/A O I/P
2 1 sec
Input power 0 60Hz
10 0h120A frequency 60/50 Hz Sel 0:60Hz X/A O I/P
1 50Hz
Number of
11 0h120B motor poles Pole Number 2-48 X/A O I/P
Rated slip Dependent X/A
12 0h120C speed Rated Slip 0-3000(Rpm) O I
on motor
Motor rated
13 0h120D current Rated Curr 1.0-1000.0(A) setting X/A O I/P
Motor noload
14 0h120E current Noload Curr 0.0-1000.0(A) X/A O I
Motor rated
15 0h120F voltage Rated Volt 170-480(V) 0 X/A O I/P
Dependent
Motor
16 0h1210 efficiency Efficiency 64-100(%) on motor X/A O I/P
setting
Load inertia
17 0h1211 rate Inertia Rate 0-8 X/A O I/P
Trim power Trim
18 0h1212 display 70-130(%) O/A O I/P
Power %
Input power
19 0h1213 voltage AC Input Volt 170-480V 220/380V O/A O I/P
0 None
All (Rotation
1
type)
Auto
20 - Auto Tuning ALL (Static 0:None X/A X I/P
Tuning 2
type)
Rs+Lsigma
3
(Rotation
111
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
type)
Tr (Static
6
type)
7 All PM
Stator
21 - Rs X/A X I/P
resistance
Dependent
Leakage Dependent on
22 - Lsigma on motor X/A X I
inductance motor setting
setting
Stator
23 - Ls X/A X I
inductance
8 Rotor time
24 - Tr 25-5000(ms) - X/A X I
constant
Stator
8
25 - inductance Ls Scale 50 ~ 150[%] 100 X/A X I
scale
Rotor time
8
26 - constant Tr Scale 50 ~ 150[%] 100 X/A X I
scale
289 D-axis
- Ld (PM) 0 X/A X P
inductance Settings vary
299 Q-axis depending on
Lq (PM) 0 X/A X P
inductance the motor
Flux
309 PM Flux Ref specifications. 0.147 X/A X P
reference
Regeneratio
8 Ls Regen
31 n inductance 70 ~ 100[%] 80 X/A X I
Scale
scale
Q-axis
329 Lq(PM)
- inductance 50–150[%] 100 X/A X P
Scale
scale
349 PM auto Ld,Lq Tune
- 20.0–50.0[%] 33.3 X/A X P
tuning level Lev
PM auto
359 Ld,Lq Tune
- tuning 80.0–150.0[%] 100.0 X/A X P
Hz
frequency
10 User 0.00-Maximum
41 0h1229 User Freq 1 15.00 X/A O X
frequency1 frequency(Hz)
10 User
42 0h122A User Volt 1 0-100(%) 25 X/A O X
voltage1
8
Displayed when dr.09 is set to 4(IM Sensorless)
9
Displayed when dr.09 (Control Mode) is set to 6 (PM Sensorless).
10
Displayed if either bA.07 or M2.25 is set to 2 (User V/F).
112
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
0.00-0.00-
10 User
43 0h122B User Freq 2 Maximum 30.00 X/A O X
frequency2
frequency(Hz)
10 User
44 0h122C User Volt 2 0-100(%) 50 X/A O X
voltage2
10 User 0.00-Maximum
45 0h122D User Freq 3 45.00 X/A O X
frequency3 frequency(Hz)
10 User
46 0h122E User Volt 3 0-100(%) 75 X/A O X
voltage3
10 User 0.00-Maximum Maximum
47 0h122F User Freq 4 X/A O X
frequency4 frequency(Hz) frequency
10 User
48 0h1230 User Volt 4 0-100(%) 100 X/A O X
voltage4
Multi-step
11 0.00-Maximum
50 0h1232 speed Step Freq-1 10.00 O/L O I/P
frequency(Hz)
frequency1
Multi-step
11 0.00-Maximum
51 0h1233 speed Step Freq-2 20.00 O/L O I/P
frequency(Hz)
frequency2
Multi-step
11 0.00-Maximum
52 0h1234 speed Step Freq-3 30.00 O/L O I/P
frequency(Hz)
frequency3
Multi-step
12 0.00-Maximum
53 0h1235 speed Step Freq-4 40.00 O/A O I/P
frequency(Hz)
frequency4
Multi-step
12 0.00-Maximum
54 0h1236 speed Step Freq-5 50.00 O/A O I/P
frequency(Hz)
frequency5
Multi-step
12 0.00-Maximum Maximum
55 0h1237 speed Step Freq-6 O/A O I/P
frequency(Hz) frequency
frequency6
Multi-step
12 0.00-Maximum Maximum
56 0h1238 speed Step Freq-7 O/A O I/P
frequency(Hz) frequency
frequency7
Multi-step
70 0h1246 acceleration Acc Time-1 0.0-600.0(s) 20.0 O/A O I/P
time1
Multi-step
71 0h1247 deceleration Dec Time-1 0.0-600.0(s) 20.0 O/A O I/P
time1
13
72 0h1248 Multi-step Acc Time-2 0.0-600.0(s) 30.0 O/A O I/P
11
Displayed when an LCD keypad is in use.
12
Displayed if one of In.65-71 is set to Speed–L/M/H.
113
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
acceleration
time2
Multi-step
13
73 0h1249 deceleration Dec Time-2 0.0-600.0(s) 30.0 O/A O I/P
time2
Multi-step
13
74 0h124A acceleration Acc Time-3 0.0-600.0(s) 40.0 O/A O I/P
time3
Multi-step
13
75 0h124B deceleration Dec Time-3 0.0-600.0(s) 40.0 O/A O I/P
time3
Multi-step
13
76 0h124C acceleration Acc Time-4 0.0-600.0(s) 50.0 O/A O I/P
time4
Multi-step
13
77 0h124D deceleration Dec Time-4 0.0-600.0(s) 50.0 O/A O I/P
time4
Multi-step
13
78 0h124E acceleration Acc Time-5 0.0-600.0(s) 40.0 O/A O I/P
time5
Multi-step
13
79 0h124F deceleration Dec Time-5 0.0-600.0(s) 40.0 O/A O I/P
time5
Multi-step
13
80 0h1250 acceleration Acc Time-6 0.0-600.0(s) 30.0 O/A O I/P
time6
Multi-step
13
81 0h1251 deceleration Dec Time-6 0.0-600.0(s) 30.0 O/A O I/P
time6
Multi-step
13
82 0h1252 acceleration Acc Time-7 0.0-600.0(s) 20.0 O/A O I/P
time7
Multi-step
13
83 0h1253 deceleration Dec Time-7 0.0-600.0(s) 20.0 O/A O I/P
time7
13
Displayed one of In.65-71 is set to Xcel–L/M/H.
114
Table of Functions
14
Displayed when Ad. 01 is set to 1 (S-curve).
15
Displayed when Ad. 02 is set to 1 (S-curve).
16
DC braking and power braking (Ad.08, stop mode options 1 and 4) are not available
when dr.09 (Control Mode) is set to 6 (PM Sensorless).
115
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
direction Reverse
2
Prev
Starting with Power-on 0 No
10 0h130A 0:No O/A O I/P
power on Run 1 Yes
DC braking
17 DC-Start
12 0h130C time at 0.00-60.00(s) 0.00 X/A O I/P
Time
startup
Amount of
13 0h130D DC Inj Level 0-200(%) 50 X/A O I/P
applied DC
Output
18 blocking time DC-Block
14 0h130E 0.00- 60.00(s) 0.10 X/A O I/P
before DC Time
braking
18 DC braking DC-Brake
15 0h130F 0.00- 60.00(s) 1.00 X/A O I/P
time Time
18 DC braking DC-Brake
16 0h1310 0-200(%) 50 X/A O I/P
rate Level
18 DC braking DC-Brake Start frequency-
17 0h1311 5.00 X/A O I/P
frequency Freq 60Hz
Dwell Start frequency-
Acc Dwell
20 0h1314 frequency on Maximum 5.00 X/A O I/P
Freq
acceleration frequency(Hz)
Dwell
operation Acc Dwell
21 0h1315 0.0-60.0(s) 0.0 X/A O I/P
time on Time
acceleration
Dwell Start frequency-
Dec Dwell
22 0h1316 frequency on Maximum 5.00 X/A O I/P
Freq
deceleration frequency(Hz)
Dwell
operation Dec Dwell
23 0h1317 0.0-60.0(s) 0.0 X/A O I/P
time on Time
deceleration
Frequency 0 No
24 0h1318 Freq Limit 0:No X/A O I/P
limit 1 Yes
Frequency
19 Freq Limit 0.00-Upper limit
25 0h1319 lower limit 0.50 O/A O I/P
Lo frequency(Hz)
value
19
26 0h131A Frequency Freq Limit Hi Lower limit maximum X/A O I/P
17
Displayed when Ad. 07 is set to 1 (DC-Start).
18
Displayed when Ad. 08 is set to 1 (DC-Brake).
19
Displayed when Ad. 24 is set to 1 (Yes).
116
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
upper limit frequency- frequency
value Maximum
frequency(Hz)
Frequency 0 No
27 0h131B Jump Freq 0:No X/A O I/P
jump 1 Yes
Jump 0.00-Jump
20
28 0h131C frequency Jump Lo 1 frequency upper 10.00 O/A O I/P
lower limit1 limit1(Hz)
Jump Jump frequency
20 lower limit1-
29 0h131D frequency Jump Hi 1 15.00 O/A O I/P
Maximum
upper limit1
frequency(Hz)
Jump 0.00-Jump
20
30 0h131E frequency Jump Lo 2 frequency upper 20.00 O/A O I/P
lower limit2 limit2(Hz)
Jump Jump frequency
20
frequency lower limit2-
31 0h131F Jump Hi 2 Maximum 25.00 O/A O I/P
upper limit2 frequency(Hz)
Jump 0.00-Jump
20
32 0h1320 frequency Jump Lo 3 frequency upper 30.00 O/A O I/P
lower limit3 limit3(Hz)
Jump Jump frequency
20
frequency lower limit3-
33 0h1321 Jump Hi 3 Maximum 35.00 O/A O I/P
upper limit3 frequency(Hz)
Brake
21
41 0h1329 release BR Rls Curr 0.0-180.0(%) 50.0 O/A O I/P
current
Brake
21
42 0h132A release delay BR Rls Dly 0.00-10.00(s) 1.00 X/A O I/P
time
Brake
21 release BR Rls Fwd 0.00-Maximum
44 0h132C Forward 1.00 X/A O I/P
Fr frequency(Hz)
frequency
Brake
21 release BR Rls Rev 0.00-Maximum
45 0h132D Reverse 1.00 X/A O I/P
Fr frequency(Hz)
frequency
21 Brake
46 0h132E BR Eng Dly 0.00-10.00(s) 1.00 X/A O I/P
engage delay
20
Displayed when Ad. 27 is set to 1 (Yes).
21
Displayed if either OU.31~33 is set to 35 (BR Control).
117
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
time
Brake
21 0.00-Maximum
47 0h132F engage BR Eng Fr 2.00 X/A O I/P
frequency(Hz)
frequency
Energy 0 None
E-Save
50 0h1332 saving 1 Manual 0:None X /A O X
Mode
operation 2 Auto
22 Energy Energy
51 0h1333 0-30(%) 0 O/A O X
saving level Save
Acc/Dec time
Xcel 0.00-Maximum
60 0h133C transition 0.00 X/A O I/P
Change Fr frequency(Hz)
frequency
Rotation
Load Spd
61 0h133D count speed 0.1~6000.0[%] 100.0 O/A O I/P
Gain
gain
0 x1
Rotation 1 x 0.1
Load Spd
62 0h133E count speed 2 x 0.01 0: x 1 O/A O I/P
Scale
scale 3 x 0.001
4 x 0.0001
Rotation 0 Rpm
Load Spd
63 0h133F count speed 0: rpm O/A O I/P
Unit 1 mpm
unit
0 During Run
Cooling fan 1 Always ON 0:During
64 0h1340 FAN Control O/A O I/P
control Temp Run
2
Control
Up/down 0 No
operation U/D Save
65 0h1341 0:No O/A O I/P
frequency Mode 1 Yes
save
Output 0 None
contact 1 V1
On/Off Ctrl
66 0h1342 On/Off 3 V2 0:None X/A O I/P
Src
control 4 I2
options 6 Pulse
Output Output contact
On-Ctrl
67 0h1343 contact On off level- 90.00 X/A O I/P
Level
level 100.00%
Output -100.00-output
Off-Ctrl
68 0h1344 contact Off contact on level 10.00 X/A O I/P
Level
level (%)
Safe Run En Always
70 0h1346 0 0:Always X/A O I/P
operation Mode Enable
22
Displayed if Ad.50 is not set to 0 (None).
118
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
selection DI Enable
1
Dependent
0 Free-Run
Safe
23 Run Dis 1 Q-Stop 0:Free-
71 0h1347 operation X/A O I/P
Stop Q-Stop Run
stop options 2
Resume
Safe
23 operation
72 0h1348 Q-Stop Time 0.0-600.0(s) 5.0 O/A O I/P
deceleration
time
Selection of 0 No
regeneration RegenAvd
24
74 0h134A evasion 0:No X/A O I
function for Sel 1 Yes
press
Voltage level 200V : 300-400V 350
of
24 regeneration RegenAvd
75 0h134B evasion X/A O I
Level 400V : 600-800V 700
motion for
press
Compensation
frequency limit
25 of CompFreq
76 0h134C 0.00- 10.00Hz 1.00 X/A O I
regeneration Limit
evasion for
press
Regeneration
25 RegenAvd
77 0h134D evasion for 0.0- 100.0% 50.0 O/A O I
Pgain
press P gain
Regeneration
25 RegenAvd
78 0h134E evasion for 20-30000(ms) 500 O/A O I
Igain
press I gain
200V:
DB Unit turn 26 390[V]
DB Turn On Min ~400[V]
79 0h134F on voltage X/A O I/P
Lev 400V:
level 26 780[V]
Min ~800[V]
0 None
Fire mode Fire Mode
80 0h1350 1 Fire Mode 0:None X/A O I/P
selection Sel
2 Fire Mode
23
Displayed when Ad.70 is set to 1 (DI Dependent).
24
Displayed when dr.09 (Control Mode) is not set to 6 (PM Sensorless).
25
Displayed when Ad.74 is set to 1 (Yes).
26
DC voltage value (convert bA.19 AC Input voltage) + 20V (200V type) or + 40V (400V type)
119
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
Test
27 Fire mode Fire Mode
81 0h1351 0.00~60.00(Hz] 60.00 X/A O I/P
frequency Freq
27 Fire mode Fire Mode 0 Forward 0:
82 0h1352 X/A O I/P
direction Dir 1 Reverse Forward
27 Fire Mode Fire Mode Cannot be
83
Count Cnt modified
0 U/D Normal
Up-down
27 U/D Mode 1 U/D Step 0: U/D
85 0h1355 mode X/A O I/P
Sel U/D Step+ Normal
selection 2
Norm
Up-down
27 U/D Step
86 0h1356 step 0-maxFreq 0 O/A O I/P
Freq
frequency
Overmodulati 0 No
27 OVM Mode
87 0h1357 on mode 0: No X/A O X
Sel 1 Yes
selection
27
Displayed when Ad.80 is set to 1 (Yes).
120
Table of Functions
28
The setting range is for 5.5-22kW models. For more information on the entire capacities,
refer to 7.8 Continuous Rated Current Derating.
29
PM synchronous motor sensorless vector control mode does not support normal duty
operation [when dr.09 (Control Mode) is set to 6 (PM Sensorless)].
30
Refer to the Footnote 28.
31
Displayed when dr.09 (Control Mode) is not set to 6 (PM Sensorless).
121
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
Continued
11 0h140B operation Hold Time 0.00-60.00(s) 0.00 X/A X I
duration
PM S/L
speed
32 ASR P Gain
12 0h140D controller 0~5000 100 X/A X P
1
proportional
gain1
PM S/L
speed
32 ASR P Gain
13 0h140F controller 0~5000 150 X/A X P
1
integral
gain1
PM S/L
speed
32 ASR P Gain
15 0h1410 controller 0~5000 100 X/A X P
1
proportional
gain2
PM S/L
speed
32 ASR P Gain
16 0h1410 controller 0~9999 150 X/A x P
1
integral
gain2
Sensorless 0 No
31 2nd SL2 G View
20 0h1414 0:No O/A X I
gain display Sel 1 Yes
setting
Sensorless
speed
31 ASR-SL
21 0h1415 controller 0-5000(%) O/A X I
P Gain1
proportional
gain1
Dependent
Sensorless
on motor
speed
31 ASR-SL I setting
22 0h1416 controller 10-9999(ms) O/A X I
Gain1
integral
gain1
33 Sensorless ASR-SL P
23 0h1417 1.0-1000.0(%) O/A X I
speed Gain2
32
Displayed when dr.09 (Control Mode) is set to 6 (PM Sensorless).
33
Displayed when dr.09 is set to 4 (IM Sensorless) and Cn.20 is set to 1 (YES).
122
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
controller
proportional
gain2
Sensorless
speed
33 ASR-SL I
24 0h1418 controller 1.0-1000.0(%) O/A X I
Gain2
integral
gain2
Sensorless
speed
33 ASR-SL I
25 0h1419 controller 10~9999(ms) O/A X I
Gain0
integral gain
0
Flux
33 estimator
26 0h141A Flux P Gain 10-200(%) O/A X I
proportional
gain
Flux
33
27 0h141B estimator Flux I Gain 10-200(%) O/A X I
integral gain
Speed
33 estimator S-Est P
28 0h141C 0-32767 O/A X I
proportional Gain1
gain
Speed
33 estimator S-Est I
29 0h141D 100-1000 O/A X I
integral Gain1
gain1
Speed
33 estimator S-Est I
30 0h141E 100-10000 O/A X I
integral Gain2
gain2
Sensorless
current
33 ACR SL
31 0h141F controller 10-1000 O/A X I
P Gain
proportional
gain
Sensorless
33 current ACR SL I
32 0h1420 10 -1000 O/A X I
controller Gain
integral gain
34 PM D-axis PM EdGain
33 0h1421 0~300.0[%] 100.0 X/A X P
back-EMF Perc
34
Displayed when dr.09 (Control Mode) is set to 6 (PM Sensorless).
123
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
estimation
gain [%]
PM Q-axis
34 back-EMF PM EqGain
34 0h1422 0~300.0[%] 100.0 X/A X P
estimation Perc
gain [%]
Initial pole
34 position PD Repeat
35 0h1423 0~10 2 X/A X P
detection Num
retry number
Initial pole
34 position
36 0h1424 Pulse Interval 1~100 20 X/A X P
detection
pulse interval
Initial pole
position
34
37 0h1425 detection Pulse Curr % 10~100 15 X/A X P
current level
[%]
Initial pole
position
34
38 0h1426 detection Pulse Volt % 100~4000 500 X/A X P
voltage level
[%]
PM dead
34 PMdeadBand
39 0h1427 time range 50.0~100.0 100.0 X/A X P
Per
[%]
PM dead
34 PMdeadVolt
40 0h1428 time voltage 50.0~100.0 100.0 X/A X P
Per
[%]
Speed
34 PM SpdEst
41 0h1429 estimator P 0~32000 100 X/A X P
Kp
gain1
Speed
34 PM SpdEst
42 0h142A estimator I 0~32000 10 X/A X P
Ki
gain1
Speed
34 PM SpdEst
43 0h142B estimator P 0~32000 300 X/A X P
Kp 2
gain2
Speed
34 PM SpdEst
44 0h142C estimator I 0~32000 30 X/A X P
Ki 2
gain2
Speed
34 estimator PM Flux
45 0h142D 0~100[%] 30.0 X/A X P
feed forward FF %
high speed
124
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
rate [%]
Initial pole 0 None
34 position 1 Angle
46 0h142E Init Angle Sel 1 X/A P
detection
options
2 Align
Current
34
48 - controller P ACR P Gain 0-10000 1200 O/A X I/P
gain
Current
34
49 - controller I ACR I Gain 0-10000 120 O/A X I/P
gain
Voltage
34
50 0h1432 controller V Con HR 0~100.0[%] 10.0 X/A X P
limit
Voltage
34
51 0h1433 controller I V Con Ki 0~1000.0[%] 10.0 X/A X P
gain
Torque
Torque Out
52 0h1434 controller 0-2000(ms) 0 X/A X I/P
LPF
output filter
0 Keypad-1
1 Keypad-2
2 V1
Torque limit 4 V2
Torque Lmt 0:
53 0h1435 setting 5 I2 X/A X I/P
Src Keypad-1
options 6 Int 485
8 FieldBus
9 UserSeqLink
12 Pulse
Positive-
35 direction FWD
54 0h1436 0.0-200.0(%) 180 O/A X I/P
reverse +Trq Lmt
torque limit
Positive-
35 direction FWD
55 0h1437 0.0-200.0(%) 180 O/A X I/P
regeneration –Trq Lmt
torque limit
Negative-
35 direction REV +Trq
56 0h1438 0.0-200.0(%) 180 O/A X I/P
regeneration Lmt
torque limit
35
Displayed when dr.09 is set to 4 (IM Sensorless). This will change the initial value of the
parameter at Ad.74 (Torque limit) to 150%.
125
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
Negative-
35 direction REV –Trq
57 0h1439 0.0-200.0(%) 180 O/A X I/P
reverse Lmt
torque limit
0 Keypad-1
1 Keypad-2
2 V1
35 Speed limit Speed Lmt 4 V2 0:
62 0h143E X/A X I/P
Setting Src 5 I2 Keypad-1
6 Int 485
7 FieldBus
8 UserSeqLink
Positive-
35 FWD Speed 0.00~ Maximum
63 0h143F direction 60.00 O/A X I/P
Lmt frequency (Hz)
speed limit
Negative-
35 REV Speed 0.00~ Maximum
64 0h1440 direction 60.00 O/A X I/P
Lmt frequency (Hz)
speed limit
Speed limit
35 Speed Lmt
65 0h1441 operation 100~5000[%] 500 O/A X I/P
Gain
gain
PM speed
36 SS Pulse
69 search Curr
15 10~100 O/A X P
current
Flying
0 37
Speed Start-1
0:
search Flying
70 0h 1446 SS Mode 1 Flying X/A O I/P
mode Start-2
selection Start-1
Flying
2 36
Start-3
0000-
bit
1111
Selection of
Speed search
Speed speed 38
71 0h1447 operation 0001 0000 X/A O I/P
Search search on
selection
acceleration
When
0010
starting on
36
Displayed when dr.09 (Control Mode) is set to 6 (PM Sensorless).
37
Will not be displayed if dr.09 is set to 4 (IM Sensorless).
38
The initial value 0000 will be displayed on the keypad as .
126
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
initialization
after fault
trip
When
restarting
after
0100
instantaneo
us power
interruption
When
1000 starting with
power on
Speed
39 search SS Sup-
72 0h1448 80-200(%) 150 O/A O I/P
reference Current
current
Flying
Speed Start-1
40 search : 100
73 0h1449 SS P-Gain 0-9999 Flying O/A O I
proportional
gain Start-2
41
: 600
Flying
Start-1
Speed
40 : 200
74 0h144A search SS I-Gain 0-9999 O/A O I
Flying
integral gain
Start-2
: 1000
Output
blocking
40 SS Block
75 0h144B time before 0.0-60.0(s) 1.0 X/A O I/P
Time
speed
search
Speed
40 search Spd Est
76 0h144C 50-150(%) 100 O/A O I
Estimator Gain
gain
Energy 0 No
77 0h144D KEB Select 0:No X/A O I/P
buffering 1 KEB-1
39
Displayed when any of the Cn.71 code bits are set to 1 and Cn70 is set to 0 (Flying
Start-1).
40
Displayed when any of the Cn.71 code bits are set to 1.
41
The initial value is 1200 when the motor-rated capacity is less than 7.5 kW
127
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
selection 2 KEB-2
Energy
42 KEB Start
78 0h144E buffering 110.0-200.0(%) 130.0 X/A O I/P
Lev
start level
Energy
42 KEB Stop
79 0h144F buffering Cn78~210.0(%) 135.0 X/A O I/P
Lev
stop level
Energy
42
80 0h1450 buffering P KEB P Gain 0-20000 1500 O/A O I/P
gain
Energy
42
81 0h1451 buffering KEB I Gain 1~20000 500 O/A O I/P
I gain
Energy
42 KEB Slip
82 0h1452 buffering 0~2000.0% 30.0 O/A O I
Gain
Slip gain
Energy
42 buffering KEB Acc
83 0h1453 0.0~600.0(s) 10.0 O/A O I/P
acceleration Time
time
Flux
43 estimator Flux P
85 0h1455 100-700 370 O/A X I
proportional Gain1
gain1
Flux
43 estimator Flux P
86 0h1456 0-100 0 O/A X I
proportional Gain2
gain2
Flux
43 estimator Flux P
87 0h1457 proportional 0-500 100 O/A X I
Gain3
gain3
Flux
43 estimator
88 0h1458 integral Flux I Gain1 0-200 50 O/A X I
gain1
Flux
43 estimator
89 0h1459 integral Flux I Gain2 0-200 50 O/A X I
gain2
Flux
43
90 0h145A estimator Flux I Gain3 0-200 50 O/A X I
integral
42
Displayed when Cn.77 is not set to 0 (No).
43
Displayed when Cn.20 is set to 1 (Yes).
128
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
gain3
Sensorless
43 voltage SL Volt
91 0h145B compensati 0-60 O/A X I
Comp1
on1
Sensorless Depende
43 voltage SL Volt nt on
92 0h145C 0-60 O/A X I
compensati Comp2 motor
on2 setting
Sensorless
43 voltage SL Volt
93 0h145D 0-60 O/A X I
compensati Comp3
on3
Sensorless
field
43
94 0h145E weakening SL FW Freq 80.0-110.0(%) 100.0 X/A X I
start
frequency
Sensorless
43 gain
95 0h145F SL Fc Freq 0.00-8.00(Hz) 2.00 X/A X I
switching
frequency
129
Table of Functions
44
Displayed when In.06 is set to 1 (Bipolar).
130
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
Maximum
input voltage
V1 output at V1 –Perc
44
15 0h150F Maximum -100.00-0.00(%) -100.00 O/A O I/P
voltage (%) y2’
V1 rotation 0 No
16 0h1510 direction V1 Inverting 0: No O/A O I/P
1 Yes
change
V1 45
V1 0.00 , 0.04-
17 0h1511 quantization 0.04 X/A O I/P
Quantizing 10.00(%)
level
V2 input
46 V2
35 0h1523 voltage 0.00-12.00(V) 0.00 -/A O I/P
Monitor(V)
display
V2 input
46
37 0h1525 filter time V2 Filter 0-10000(ms) 10 O/A O I/P
constant
46 V2 Minimum
38 0h1526 V2 Volt x1 0.00-10.00(V) 0.00 O/A X I/P
input voltage
V2 output at
46
39 0h1527 Minimum V2 Perc y1 0.00-100.00(%) 0.00 O/A O I/P
voltage (%)
V2
46
40 0h1528 Maximum V2 Volt x2 0.00-10.00(V) 10 O/A X I/P
input voltage
V2 output at
46
41 0h1529 Maximum V2 Perc y2 0.00-100.00(%) 100.00 O/A O I/P
voltage (%)
V2 rotation 0 No
46
46 0h152E direction V2 Inverting 0:No O/A O I/P
change 1 Yes
V2 45
46 V2 0.00 , 0.04-
47 0h152F quantization 0.04 O/A O I/P
Quantizing 10.00(%)
level
I2 input
47 I2 Monitor
50 0h1532 current 0-24(mA) 0.00 -/A O I/P
display (mA)
47 I2 input filter
52 0h1534 I2 Filter 0-10000(ms) 10 O/A O I/P
time
45
Quantizing is not used when set to 0.
46
Displayed when V is selected on the analog current/voltage input circuit selection switch
(SW2).
47
Displayed when I is selected on the analog current/voltage input circuit selection switch
(SW2).
131
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
constant
47 I2 minimum
53 0h1535 I2 Curr x1 0.00-20.00(mA) 4.00 O/A O I/P
input current
I2 output at
47
54 0h1536 Minimum I2 Perc y1 0.00-100.00(%) 0.00 O/A O I/P
current (%)
47 I2 maximum
55 0h1537 I2 Curr x2 0.00-24.00(mA) 20.00 O/A O I/P
input current
I2 output at
47
56 0h1538 Maximum I2 Perc y2 0.00-100.00(%) 100.00 O/A O I/P
current (%)
Changing 0 No
47 rotation
61 0h153D I2 Inverting 0:No O/A O I/P
direction of 1 Yes
I2
I2 45
47 I2 0.00 ,0.04-
62 0h153E quantization 0.04 O/A O I/P
level Quantizing 10.00(%)
0 None
P1 terminal
65 0h1541 function P1 Define 1:Fx X/A O I/P
setting 1 Fx
P2 terminal
66 0h1542 function P2 Define 2 Rx 2:Rx X/A O I/P
setting
P3 terminal
67 0h1543 function P3 Define 3 RST 5:BX X/A O I/P
setting
P4 terminal
External
68 0h1544 function P4 Define 4 3:RST X/A O I/P
setting Trip
P5 terminal
69 0h1545 function P5 Define 5 BX 7:Sp-L X/A O I/P
setting
P6 terminal
70 0h1546 function P6 Define 6 JOG 8:Sp-M X/A O I/P
setting
P7 terminal
71 0h1547 function P7 Define 7 Speed-L 9:Sp-H X/A O I/P
setting
8 Speed-M
9 Speed-H
11 XCEL-L
12 XCEL-M
13 RUN
132
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
Enable
14 3-Wire
2nd
15
Source
16 Exchange
17 Up
18 Down
20 U/D Clear
Analog
21
Hold
I-Term
22
Clear
PID
23
Openloop
24 P Gain2
XCEL
25
Stop
26 2nd Motor
34 Pre Excite
38 Timer In
dis Aux
40
Ref
46 FWD JOG
47 REV JOG
49 XCEL-H
50 User Seq
51 Fire Mode
KEB-1
52
Select
48
54 TI
Multi- P7 ~ P1
function Disable
input 0
84 0h1554 Dl Delay Sel (Off) 1 1111
49
O/A O I/P
terminal On
filter Enable
1
selection (On)
Multi-
function
85 0h1555 input DI On Delay 0-10000(ms) 10 O/A O I/P
terminal On
filter
48
Displayed only when the P5 terminal function is selected in Standard I/O.
49
The initial value 11111 will be displayed on the keypad as
133
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
Multi-
function
86 0h1556 input DI Off Delay 0-10000(ms) 3 O/A O I/P
terminal Off
filter
Multi- P7 – P1
function A contact
DI NC/NO 0 50
87 0h1557 input (NO) 0 0000 X/A O I/P
Sel
contact B contact
1
selection (NC)
Multi-step
InCheck
89 0h1559 command 1-5000(ms) 1 X/A O I/P
Time
delay time
Multi- P7 – P1
function 0 release(Off)
50
90 0h155A input DI Status 0 0000 -/A O I/P
terminal Connection
1
status (On)
Pulse input Pulse
91 0h155B amount Monitor 0.00-50.00(kHz) 0.00 -/A O I/P
display (kHz)
TI input filter
92 0h155C time TI Filter 0-9999(ms) 10 O/A O I/P
constant
TI Minimum
93 0h155D TI Pls x1 0.00-32.00(kHz) 0.00 O/A O I/P
input pulse
TI output at
94 0h155E Minimum TI Perc y1 0.00-100.00(%) 0.00 O/A O I/P
pulse (%)
TI Maximum
95 0h155F TI Pls x2 0.00-32.00(kHz) 32.00 O/A O I/P
input pulse
TI Output at
96 0h1560 Maximum TI Perc y2 0-100(%) 100.00 O/A O I/P
pulse (%)
TI rotation 0 No
97 0h1561 direction TI Inverting 0:No O/A O I/P
change 1 Yes
TI 45
TI 0.00 , 0.04-
98 0h1562 quantization 0.04 O/A O I/P
Quantizing 10.00(%)
level
SW1(NPN/P Bit 00~11
99 0h1563 NP) IO SW State 00 V2, NPN 00 -/A O I/P
SW2(V1/V2 01 V2, PNP
50
The initial value 0000 will be displayed on the keypad as .
134
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
[I2]) 10 I2, NPN
status 11 I2, PNP
135
Table of Functions
136
Table of Functions
51
The initial value 0010 will be displayed on the keypad as .
137
Table of Functions
138
Table of Functions
52
The initial value 0000 will be displayed on the keypad as .
139
Table of Functions
140
Table of Functions
Built-in ModBus 0:
53 Int485 0
02 0h1702 communication RTU ModBus O/A O I/P
protocol Proto
2 LS Inv 485 RTU
0 1200 bps
1 2400 bps
2 4800 bps
Built-in 3 9600 bps 3:
53 Int485
03 0h1703 communication 4 19200 bps 9600 O/A O I/P
BaudR
speed 5 38400 bps bps
6 56 Kbps
54
7 115 Kbps
0 D8/PN/S1
Built-in
53 Int485 1 D8/PN/S2 0:
04 0h1704 communication O/A O I/P
Mode 2 D8/PE/S1 D8/PN/S1
frame setting
3 D8/PO/S1
Transmission
53 Resp
05 0h1705 delay 0-1000(ms) 5ms O/A O I/P
Delay
after reception
Communication
55 FBus S/W
06 0h1706 option - 0.00 O/A O I/P
Ver
S/W version
Communication
55
07 0h1707 option FBus ID 0-255 1 O/A O I/P
inverter ID
53
Will not be displayed when P2P and MultiKPD is set.
54
115,200bps
55
Displayed only when a communication option card is installed.
141
Table of Functions
56
Only the range of addresses set at COM-30 is displayed.
57
Only the range of addresses set at COM-50 is displayed.
142
Table of Functions
143
Table of Functions
58
Displayed only when the P5 terminal function is selected in Standard I/O.
144
Table of Functions
59
Displayed only when a communication option card is installed.
60
Displayed when AP.01 is set to 2 (Proc PID).
145
Table of Functions
61
Displayed when AP.01 is set to 2 (Proc PID).
146
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
integral time
PID controller
61
24 0h1818 differentiation PID D-Time 0-1000(ms) 0 O/A O I/P
time
PID controller
61 feed-forward
25 0h1819 PID F-Gain 0.0-1000.0(%) 0.0 O/A O I/P
compensation
gain
61 Proportional
26 0h181A P Gain Scale 0.0-100.0(%) 100.0 X/A O I/P
gain scale
61 PID output
27 0h181B PID Out LPF 0-10000(ms) 0 O/A O I/P
filter
Process
0
61 PID
28 0h181C PID Mode PID Mode 0 X/A O I/P
Normal
1
PID
PID lower limit
61 PID upper limit
29 0h181D PID Limit Hi frequency- 60.00 O/A O I/P
frequency
300.00(Hz)
-300.00 -PID
61 PID lower limit
30 0h181E PID Limit Lo upper limit -60.00 O/A O I/P
frequency
frequency(Hz)
61 PID output 0 No
31 0h181F PID Out Inv 0:No X/A O I/P
inverse 1 Yes
61 PID output PID Out
32 0h1820 0.1-1000.0(%) 100.0 X/A O I/P
scale Scale
PID controller 0.00-
61
34 0h1822 motion Pre-PID Freq Maximum 0.00 X/A O I/P
frequency frequency(Hz)
61 PID controller
35 0h1823 motion level Pre-PID Exit 0.0-100.0(%) 0.0 X/A O I/P
PID controller
61 Pre-PID
36 0h1824 motion delay Delay
0-9999(s) 600 O/A O I/P
time
PID sleep
61
37 0h1825 mode PID Sleep DT 0.0-999.9(s) 60.0 O/A O I/P
delay time
PID sleep 0.00-
61 PID Sleep
38 0h1826 mode Freq
Maximum 0.00 O/A O I/P
frequency frequency(Hz)
61 PID wake-up PIDWakeUp
39 0h1827 0-100(%) 35 O/A O I/P
level Lev
Below
0
61 PID wake-up PID WakeUp Level 0:Below
40 0h1828 O/A O I/P
mode setting Mod Above Level
1
Level
147
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
Beyond
2
Level
0 %
1 Bar
2 mBar
3 Pa
4 kPa
5 Hz
6 rpm
7 V
61 PID controller 8 I
42 0h182A PID Unit Sel 0:% O/A O I/P
unit selection 9 kW
10 HP
11 ℃
12 ℉
13 CUST
14 PSI
15 inWC
16 gl/m
61 0.00-
43 0h182B PID unit gain PID Unit Gain 100.00 O/A O I/P
300.00(%)
0 x100
1 x10
61 PID Unit
44 0h182C PID unit scale 2 x1 2:x 1 O/A O I/P
Scale
3 x 0.1
4 x 0.01
PID 2nd
61
45 0h182D proportional PID P2-Gain 0.0-1000.0(%) 100.0 X/A O I/P
gain
148
Table of Functions
Input voltage
06 0h1B06 range during IPO V Band 1-100(V) 15 X/A O I/P
open-phase
Deceleration
Trip Dec
07 0h1B07 time at fault 0.0-600.0(s) 3.0 O/A O I/P
Time
trip
Selection of 0 No
08 0h1B08 startup on trip RST Restart 0:No O/A O I/P
reset 1 Yes
Number of
Retry
09 0h1B09 automatic 0-10 0 O/A O I/P
Number
restarts
62
IP66 models do not support normal duty setting.
63
The initial value 0000 will be displayed on the keypad as .
149
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
Automatic
64
10 0h1B0A restart Retry Delay 0.0-60.0(s) 1.0 O/A O I/P
delay time
0 None
Motion 1 Free-Run
at speed Lost Cmd 2 Dec
12 0h1B0C 0:None O/A O I/P
command Mode 3 Hold Input
loss 4 Hold Output
5 Lost Preset
Time to
decide
65 Lost Cmd
13 0h1B0D speed 0.1-120(s) 1.0 O/A O I/P
Time
command
loss
Operation
Start
frequency
65 Lost Preset frequency-
14 0h1B0E at speed 0.00 O/A O I/P
F Maximum
command
frequency(Hz)
loss
64
Displayed when Pr.09 is set higher than 0.
65
Displayed when Pr.12 is not set to 0 (NONE).
150
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
warning
1 Yes
selection
Underload UL Warn
26 0h1B1A 0.0-600.0(s) 10.0 O/A O I/P
warning time Time
0 None
Underload
27 0h1B1B UL Trip Sel 1 Free-Run 0:None O/A O I/P
fault selection
2 Dec
Underload
28 0h1B1C UL Trip Time 0.0-600.0(s) 30.0 O/A O I/P
fault time
Underload
29 0h1B1D lower limit UL LF Level 10-30(%) 30 O/A O I/P
level
Underload
30 0h1B1E upper limit UL BF Level 30-100(%) 30 O/A O I/P
level
No motor 0 None
No Motor
31 0h1B1F motion at 0:None O/A O I/P
Trip 1 Free-Run
detection
No motor
No Motor
32 0h1B20 detection 1-100(%) 5 O/A O I
Level
current level
No motor
No Motor
33 0h1B21 detection 0.1-10.0(s) 3.0 O/A O I
Time
delay
Electronic 0 None
ETH Trip
40 0h1B28 thermal fault 1 Free-Run 0:None O/A O I/P
Sel
selection 2 Dec
0 Self-cool
Motor cooling Motor 0:Self-
41 0h1B29 Forced- O/A O I/P
fan type Cooling 1 cool
cool
Electronic
42 0h1B2A thermal 1 ETH 1min 120-200(%) 150 O/A O I/P
minute rating
Electronic
thermal
43 0h1B2B ETH Cont 50-150(%) 120 O/A O I/P
continuous
rating
0 Free-Run
45 0h1B2D BX trip mode BX Mode 0 X/A O I/P
1 Dec
Stall 00000-
50 0h1B32 Stall Prevent bit 0 0000 X/A O X
prevention 11111
151
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
motion and Accelerating
flux braking 00001
(Mode 1)
Accelerating
10001
(Mode 2)
At constant
00010 speed
(Mode 1)
At constant
10010 speed
(Mode 2)
At
#0100
deceleration
#1000 FluxBraking
Start
Stall frequency-
51 0h1B33 Stall Freq 1 60.00 O/A O X
frequency1 Stall
frequency2(Hz)
52 0h1B34 Stall level1 Stall Level 1 30-250(%) 180 X/A O X
Stall
Stall frequency1-
53 0h1B35 Stall Freq 2 60.00 O/A O X
frequency2 Stall
frequency3(Hz)
54 0h1B36 Stall level2 Stall Level 2 30-250(%) 180 X/A O X
Stall
Stall frequency2-
55 0h1B37 Stall Freq 3 60.00 O/A O X
frequency3 Stall
frequency4(Hz)
56 0h1B38 Stall level3 Stall Level 3 30-250(%) 180 X/A O X
Stall
Stall frequency3-
57 0h1B39 Stall Freq 4 60.00 O/A O X
frequency4 Maximum
frequency(Hz)
58 0h1B3A Stall level4 Stall Level 4 30-250(%) 180 X/A O X
Flux braking Flux Brake
59 0h1B3B Kp 0 ~ 150[%] 0 O/A O I
gain
DB resistor DB
66 0h1B42 0-30(%) 0 O/A O I/P
warning level Warn %ED
Speed Speed Dev 0 No
73 0h1B22 0:No O/A O I/P
deviation trip Trip 1 Yes
66 Speed Speed Dev
74 0h1B23 1 ~ 20 5 O/A O I/P
deviation Band
66
Displayed when Pr.73 is set to 1(YES)
152
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
band
66 Warning
90 0h1B5A - - - -/7 O I/P
information
66
91 0h1B5B Fault history 1 - - - -/7 O I/P
66
92 0h1B5C Fault history 2 - - - -/7 O I/P
66
93 0h1B5D Fault history 3 - - - -/7 O O
66
94 0h1B5E Fault history 4 - - - -/7 O O
66
95 0h1B5F Fault history 5 - - - -/7 O O
66 Fault history 0 No
96 0h1B60 - 0:No -/7 O O
deletion 1 Yes
153
Table of Functions
154
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
Number of M2-Pole
10 0h1C0A 2-48 X/A O I
motor poles Num
Rated slip M2-Rated
11 0h1C0B 0-3000(rpm) X/A O I
speed Slip
Motor rated M2-Rated
12 0h1C0C 1.0-1000.0(A) X/A O I
current Curr
Motor no-load M2-Noload
13 0h1C0D 0.5-1000.0(A) X/A O I
current Curr
Motor rated M2-Rated
14 0h1C0E 170-480(V) X/A O I
voltage Volt Dependent
Motor M2- on motor X/A
15 0h1C0F 64-100(%) O I
efficiency Efficiency settings
Load inertia M2-Inertia
16 0h1C10 0-8 X/A O I
rate Rt
Stator
17 - M2-Rs X/A O I
resistance
Leakage Dependent on
18 - M2-Lsigma X/A O I
inductance motor settings
Stator
19 - M2-Ls X/A O I
inductance
67 Rotor time
20 - M2-Tr 25-5000(ms) X/A O I
constant
0 Linear
2 User V/F
Forward M2-Fwd
26 0h1C1A 0.0-15.0(%) X/A O I
Torque boost Boost
2.0
Reverse M2-Rev
27 0h1C1B 0.0-15.0(%) X/A O I
Torque boost Boost
Stall
M2-Stall
28 0h1C1C prevention 30-150(%) 150 X/A O I
Lev
level
Electronic
M2-ETH
29 0h1C1D thermal 1 100-200(%) 150 X/A O I
1min
minute rating
Electronic
thermal M2-ETH
30 0h1C1E 50-150(%) 100 X/A O I
continuous Cont
rating
40 0h1C28 Rotation count Load Spd 0~6000.0[%] 100.0 O/A O I
67
Displayed when M2.08 is set to 4(IM Sensorless)
155
Table of Functions
Comm. Initial
Code Name LCD Display Setting Range Property* V/F SL
Address Value
speed gain Gain
0 x1
1 x 0.1
Rotation count Load Spd
41 0h1C29 2 x 0.01 0: x 1 O/A O I
speed scale Scale
3 x 0.001
4 x 0.0001
Rotation count Load Spd 0 Rpm
42 0h1C2A 0: rpm O/A O I
speed unit Unit 1 mpm
156
Table of Functions
157
Table of Functions
158
Table of Functions
159
Table of Functions
160
Table of Functions
161
Table of Functions
162
Table of Functions
163
Table of Functions
164
Table of Functions
165
Table of Functions
166
Table of Functions
167
Table of Functions
168
Table of Functions
169
Table of Functions
170
Table of Functions
171
Table of Functions
172
Table of Functions
173
Table of Functions
174
Table of Functions
175
Table of Functions
176
Table of Functions
177
Table of Functions
178
Table of Functions
179
Table of Functions
180
Table of Functions
181
Table of Functions
68
Supported only Extension I/O(Option)
182
Table of Functions
0 No
Reset of accumulated
75 Fan Time Rst 0:No
cooling fan operation time 1 Yes
183
Table of Functions
184
Troubleshooting
5 Troubleshooting
This chapter explains how to troubleshoot a problem when inverter protective functions,
fault trips, warning signals, or a fault occurs. If the inverter does not work normally after
following the suggested troubleshooting steps, please contact the LS ELECTRIC customer
service center.
• Level: When the fault is corrected, the trip or warning signal disappears and the fault is
not saved in the fault history.
• Latch: When the fault is corrected and a reset input signal is provided, the trip or warning
signal disappears.
• Fatal: When the fault is corrected, the fault trip or warning signal disappears only after
the user turns off the inverter, waits until the charge indicator light goes off, and turns the
inverter on again. If the inverter is still in a fault condition after powering it on again,
please contact the supplier or the LS ELECTRIC customer service center.
185
Troubleshooting
Fault Trips
Protection Functions for Output Current and Input Voltage
Keypad LCD
Type Description
Display Display
Displayed when the motor overload trip is activated and
olt Over Load Latch the actual load level exceeds the set level. Operates
when Pr.20 is set to a value other than 0.
Displayed when the motor underload trip is activated
Under
ult Load
Latch and the actual load level is less than the set level.
Operates when Pr.27 is set to a value other than 0.
Over Displayed when inverter output current exceeds 200%
oct Current1 Latch
of the rated current.
Over Displayed when internal DC circuit voltage exceeds the
ovt Voltage Latch
specified value.
Low Displayed when internal DC circuit voltage is less than
lut Voltage Level
the specified value.
Low Displayed when internal DC circuit voltage is less than
lv2 Voltage2 Latch
the specified value during inverter operation.
Displayed when a ground fault trip occurs on the output
Ground side of the inverter and causes the current to exceed
gft Trip*
Latch
the specified value. The specified value varies
depending on inverter capacity.
Displayed based on inverse time-limit thermal
eth E-Thermal Latch characteristics to prevent motor overheating. Operates
when Pr.40 is set to a value other than 0.
Displayed when a 3-phase inverter output has one or
pot OutOpen Phase
Latch more phases in an open circuit condition. Operates
when bit 1 of Pr.05 is set to 1.
Displayed when a 3-phase inverter input has one or
In Phase
ipo Open
Latch more phases in an open circuit condition. Operates
only when bit 2 of Pr.05 is set to 1.
Displayed when the inverter has been protected from
overload and resultant overheating, based on inverse
Inverter time-limit thermal characteristics. Allowable overload
iol OLT
Latch
rates for the inverter are 150% for 1 min and 200% for
4 sec. Protection is based on inverter rated capacity,
and may vary depending on the device’s capacity.
No Motor Displayed when the motor is not connected during
nmh Trip
Latch
inverter operation. Operates when Pr.31 is set to 1.
* S100 inverters rated for 4.0kW or less do not support the ground fault trip (GFT) feature.
Therefore, an over current trip (OCT) or over voltage trip (OVT) may occur when there is a
low-resistance ground fault.
* For products with built-in filters, CPU Reset or OCT or OC2 Trip can occur in an anomaly
in which the Surge input (such as Lightning Surge) is received.
186
Troubleshooting
Keypad
LCD Display Type Description
Display
Displayed when the temperature of the inverter heat
oht Over Heat Latch
sink exceeds the specified value.
Over Displayed when the DC circuit in the inverter detects a
oc2 Current2
Latch
specified level of excessive, short circuit current.
Displayed when an external fault signal is provided by
the multi-function terminal. Set one of the multi-function
ext External Trip Latch
input terminals at In.65-71 to 4 (External Trip) to enable
external trip.
Displayed when the inverter output is blocked by a
signal provided from the multi-function terminal. Set
bx BX Level
one of the multi-function input terminals at In.65-71 to 5
(BX) to enable input block function.
Displayed when an error is detected in the memory
(EEPRom), analog-digital converter output (ADC Off
Set), or CPU watchdog (Watch Dog-1, Watch Dog-2).
187
Troubleshooting
Keypad
LCD Display Type Description
Display
Displayed when a frequency or operation command
error is detected during inverter operation by controllers
Lost
lcr Command
Level other than the keypad (e.g., using a terminal block and
a communication mode). Activate by setting Pr.12 to
any value other than 0.
Displayed when the I/O board or external
iot communication card is not connected to the inverter or
there is a bad connection.
hold
IO Board
Latch
Trip Displayed when the hold error code continues for
errc more than 5 sec.
(‘Errc’ -> ’-rrc’ -> E-rc’ -> ’Er-c’ -> ‘Err-‘ -> ’- -rc’ -> ‘Er- -
‘ -> ’- - - -‘-> ’Errc’ -> …)
Displayed when communication fails during parameter
ParaWrite
par Trip
Latch writing. Occurs when using an LCD keypad due to a
control cable fault or a bad connection.
Displayed when a communication error is detected
Option Trip- between the inverter and the communication board.
opt 1
Latch
Occurs when the communication option card is
installed.
188
Troubleshooting
Warning Messages
Keypad
LCD Display Description
Display
Displayed when the motor is overloaded. Operates when Pr.17 is
set to 1. To operate, select 5. Set the digital output terminal or
olw Over Load relay (OU.31 or OU.33) to 5 (Over Load) to receive overload
warning output signals.
189
Troubleshooting
190
Troubleshooting
191
Troubleshooting
192
Troubleshooting
193
Troubleshooting
194
Troubleshooting
195
Troubleshooting
196
Maintenance
6 Maintenance
This chapter explains how to replace the cooling fan, the regular inspections to complete,
and how to store and dispose of the product. An inverter is vulnerable to environmental
conditions and faults also occur due to component wear and tear. To prevent breakdowns,
please follow the maintenance recommendations in this section.
• Before you inspect the product, read all safety instructions contained in this manual.
• Before you clean the product, ensure that the power is off.
• Clean the inverter with a dry cloth. Cleaning with wet cloths, water, solvents, or
detergents may result in electric shock or damage to the product.
Daily Inspections
Inspection Inspection Inspection Judgment Inspection
Inspection details
area item method standard equipment
No icing
Is the ambient (ambient
temperature and temperature: -
Refer to 1.3
humidity within 10 - +40) and Thermometer,
Ambient Installation
the design range, no hygrometer,
environment Considerations
and is there any condensation recorder
on page 8.
dust or foreign (ambient
objects present? humidity below
50%)
All
Is there any
Visual No
Inverter abnormal
inspection abnormality
vibration or noise?
Measure
Refer to 7.1
voltages
Are the input and Input and Digital
Power between R/ S/
output voltages Output multimeter
voltage T-phases in.
normal? Specification tester
the inverter
on page 203.
terminal block.
Is there any
Input/Output Smoothing Visual No
leakage from the -
circuit capacitor inspection abnormality
inside?
197
Maintenance
Annual Inspections
Inspection Inspection Inspection Inspection Judgment Inspection
area item details method standard equipment
Disconnect
inverter and
short
Megger test R/S/T/U/V/W
(between terminals, and
Must be
input/output then measure
above 5 MΩ
terminals and from each
earth terminal) terminal to the
DC 500 V
ground
All Megger
Input/Output terminal using
circuit a Megger.
Is there
Tighten up all
anything loose
screws.
in the device?
No
Is there any
abnormality
evidence of Visual
parts inspection
overheating?
Cable Are there any Visual No
-
connections corroded inspection abnormality
198
Maintenance
199
Maintenance
Bi-annual Inspections
Inspection Inspection Inspection Inspection Judgment Inspection
area item details method standard equipment
Megger test Disconnect
(between the the cables for
Insulation Must be
Motor input, output terminals U/V/ DC 500 V Megger
resistance above 5 MΩ
and earth W and test the
terminals). wiring.
Do not run an insulation resistance test (Megger) on the control circuit as it may result in
damage to the product.
200
Maintenance
Note
The life times of major components are based on the operating rated load consecutively. The
lifetime may be different according to conditions and environment.
Storage
If you are not using the product for an extended period, store it in the following way:
• Store the product in the same environmental conditions as specified for operation (refer
to 1.3 Installation Considerations on page 8).
• When storing the product for a period longer than 3 months, store it between 10˚C and
30˚C, to prevent depletion of the electrolytic capacitor.
• Do not expose the inverter to snow, rain, fog, or dust.
• Package the inverter in a way that prevents contact with moisture. Keep the moisture
level below 70% in the package by including a desiccant, such as silica gel.
201
Maintenance
Disposal
When disposing of the product, categorize it as general industrial waste. Recyclable
materials are included in the product, so recycle them whenever possible. The packing
materials and all metal parts can be recycled. Although plastic can also be recycled, it can
be incinerated under controlled conditions in some regions.
If the inverter has not been operated for a long time, capacitors lose their charging
characteristics and are depleted. To prevent degradation, turn on the product once a year and
allow the device to operate for 30-60 min. Run the device under no-load conditions.
202
Technical Specification
7 Technical Specification
0.4-22kW Models
Single Phase 200V (0.4-2.2 kW)
203
Technical Specification
204
Technical Specification
205
Technical Specification
206
Technical Specification
207
Technical Specification
Note
Precautions for 1–phase input to 3-phase drive
• Please connect single-phase input to R(L1) and T(L3).
• AC or DC reactor is necessary to reduce DC ripple. Please select built-in reactor type
for 30-75kW. For 0.4-22kW, external AC or DC reactor should be installed.
• Same peripheral devices (including a fuse and reactor) as 3-phase can be used for 1-
phase as well.
• If phase open trip occurs, please turn off the input phase open protection(PR-05).
• Protection for output current like OCT or IOLT is based on 3-phase input ratings which
is larger than single-phase input. User should set the parameters that are relative to
motor information(bA-11~16), overload trip(Pr-17~22) and E-thermal functions(Pr-
40~43)
• Performance of sensorless control could be unstable depending on DC ripple.
• The minimum input voltage must be larger than 228Vac for 240Vac supply and 456Vac for
480Vac supply to ensure motor voltage production of 207Vac and 415Vac, respectively.
• To minimize the effect of voltage deprivation, please choose 208Vac motor for 240Vac
supply and 400Vac motor for 480Vac supply.
208
Technical Specification
30-75kW Models
3-Phase 400 V (30–75 kW)
209
Technical Specification
210
Technical Specification
Items Description
open
collector
terminal
Multi
Less than (N.O., N.C.) AC250V
function
1A,
relay
Less than DC 30V, 1A
terminal
Analog
output, 0-12Vdc (0-24mA): Select frequency, output current, output
Analog voltage, DC terminal voltage and others
output 1
Analog 0-12Vdc: Select frequency, output current, output voltage,
output 2 DC terminal voltage and others
Pulse trainMaximum 32 kHz, 10-12V
• Over voltage trip
• Over current trip • Temperature sensor
• External signal trip trip
• ARM short circuit current trip • Inverter over heat
• Over heat trip • Option trip
• Input imaging trip • Output imaging trip
• Ground trip • Inverter overload trip
• Motor over heat trip • Fan trip
Trip • I/O board link trip • Pre-PID operation
• No motor trip failure
• Parameter writing trip • External brake trip
• Emergency stop trip • Low voltage trip during
Protection • Command loss trip operation
function • External memory error • Low voltage trip
• CPU watchdog trip • Safety A(B) trip
• Motor normal load trip • Analog input error
• Motor overload trip
Command loss trip alarm, overload alarm, normal load
alarm, inverter overload alarm, fan operation alarm,
Alarm
resistance braking rate alarm, number of corrections on
rotor tuning error
Heavy load less than 15 ms (normal load less than 8 ms):
continue operation (must be within the rated input voltage
Instantaneous
and rated output range)
blackout
Heavy load more than 15 ms (normal load more than 8
ms ): auto restart operation
Structure/ Cooling type Forced fan cooling structure (excluding some models)
working • IP 20 , UL Open Type
environment Protection structure (UL Enclosed Type 1 is satisfied by conduit installation
211
Technical Specification
Items Description
option.)
• IP66(NEMA 4X Indoor Only)
• 0.4-22kW: Keypad (LCD loader: Installation available
Input Mode but sold separately.)
• 30-75kW: LCD loader
Heavy load: -10-50℃ (14–122F), normal load: -10-40℃
(14–104F)
Ambient
temperature No ice or frost should be present.
Working under normal load at 50℃ (122F), it is
recommended that less than 80% load is applied.
Relative humidity less than 90% RH (to avoid condensation
Ambient humidity
forming)
Storage
-20C-65C (-4–149F)
temperature.
Prevent contact with corrosive gases, inflammable gases,
Surrounding
oil stains, dust, and other pollutants (Pollution Degree 3
environment
Environment).
Maximum 1000m above sea level for standard operation.
Operation altitude From 1000 to 4000m, the rated input voltage and rated
/ Vibration output current of the drive must be derated by 1% for every
100m. / less than 1G (9.8m/sec2)
Pressure 70-106 kPa
* , ** IP66 models do not support normal load operation.
212
Technical Specification
0.4-22kW Models
0.4 kW (Single Phase), 0.4-0.8 kW (3-Phase)
213
Technical Specification
Items W1 W2 H1 H2 H3 D1 A B Φ
0004S100-1, 61.1 128 119 5 128 3.5 4 4
68
0008S100-2,
(2.68) (2.41) (5.04) (4.69) (0.20) (5.04) (0.14) (0.16) (0.16)
0008S100-4
0004S100-2, 68 61.1 128 119 5 123 3.5 4 4.2
0004S100-4 (2.68) (2.41) (5.04) (4.69) (0.20) (4.84) (0.14) (0.16) (0.17)
004S100-1,
004S100-4, 68 63.5 180 170.5 5 130 4.5 4.5 4.2
008S100-4 (2.68) (2.50) (7.09) (6.71) (0.20) (5.12) (0.18) (0.18) (0.17)
EMC Type
Units: mm (inches)
214
Technical Specification
215
Technical Specification
Items W1 W2 H1 H2 H3 D1 A B Φ
0008S100-1,
100 91 128 120 4.5 130 4.5 4.5 4.5
0015S100-2,
(3.94) (3.58) (5.04) (4.72) (0.18) (5.12) (0.18) (0.18) (0.18)
0015S100-4
0015S100-1,
100 91 128 120 4.5 145 4.5 4.5 4.5
0022S100-2,
(3.94) (3.58) (5.04) (4.72) (0.18) (5.71) (0.18) (0.18) (0.18)
0022S100-4
0008S100-1,
0015S100-1,
100 91 180 170 5 140 4.5 4.5 4.2
0015S100-4,
(3.94) (3.58) (7.09) (6.69) (0.20) (5.51) (0.18) (0.18) (0.17)
0022S100-4
EMC Type
Units: mm (inches)
216
Technical Specification
Items W1 W2 H1 H2 H3 D1 A B Φ
0022S100-1
0037S100-2
140 132.2 128 120.7 3.7 145 3.9 4.4 4.5
0040S100-2
(5.51) (5.20) (5.04) (4.75) (0.15) (5.71) (0.15) (0.17) (0.18)
0037S100-4
0040S100-4
0022S100-1,
0037S100-4, 140 132 180 170 5 140 4 4 4.2
0040S100-4 (5.51) (5.20) (7.09) (6.69) (0.20) (5.51) (0.16) (0.16) (0.17)
EMC Type
Units: mm (inches)
217
Technical Specification
5.5-22 kW (3-Phase)
Items W1 W2 H1 H2 H3 D1 A B Φ
0055S100-2 160 137 232 216.5 10.5 140 5 5
-
0075S100-2 (6.30) (5.39) (9.13) (8.52) (0.41) (5.51) (0.20) (0.20)
3-
phase 0110S100-2 180 157 290 273.7 11.3 163 5 5
-
200V (7.09) (6.18) (11.4) (10.8) (0.44) (6.42) (0.20) (0.20)
220 193.8 350 331 13 187 6 6
0150S100-2 -
(8.66) (7.63) (13.8) (13.0) (0.51) (7.36) (0.24) (0.24)
0055S100-4 160 137 232 216.5 10.5 140 5 5
-
0075S100-4 (6.30) (5.39) (9.13) (8.52) (0.41) (5.51) (0.20) (0.20)
3-
0110S100-4 180 157 290 273.7 11.3 163 5 5
phase -
0150S100-4 (7.09) (6.18) (11.4) (10.8) (0.44) (6.42) (0.20) (0.20)
400V
0185S100-4 220 193.8 350 331 13 187 6 6
-
0220S100-4 (8.66) (7.63) (13.8) (13.0) (0.51) (7.36) (0.24) (0.24)
Units: mm (inches)
218
Technical Specification
30-75kW Models
30 kW (3-Phase)
37–45 kW (3-Phase)
219
Technical Specification
55–75 kW (3-Phase)
Items W1 W2 H1 H2 H3 D1 A B
275 450
0300S100-4 232 428.5 14
(10.8) (17.7) 284 7 7
0370S100-4 510 (11.2) (0.28) (0.28)
282 486.5
0450S100-4 325 (20.1)
16
0550S100-4 (12.8) 550 309
275 524.5 9 9
0750S100-4 (21.7) (12.2)
Units: mm (inches)
220
Technical Specification
IP66 Models
0.4-4.0kW – NP (Non PDS) type
221
Technical Specification
222
Technical Specification
Items W1 W2 H1 H2 H3 D1 D2 A Φ T1 T2
0004S100-1
0004S100-2 Non-PDS :
180 170 256.6 245 8.2 174.1 177.1 (6.97) 4.5 4.5 22.3
0008S100-2 -
(7.09) (6.69) (1010) (9.65) (0.32) (6.85) PDS : (0.18) (0.18) (0.88)
0004S100-4 188.2 (7.41)
0008S100-4
0008S100-1
0015S100-1
0022S100-1
0015S100-2
0022S100-2 Non-PDS :
220 204 258.8 241 11.8 201 204 (8.03) 5.5 5.5 22.3 28.6
0037S100-2
(8.66) (8.03) (10.19) (9.49) (0.46) (7.91) PDS : (0.22) (0.22) (0.88) (1.13)
0040S100-2 215 (8.46)
0015S100-4
0022S100-4
0037S100-4
0040S100-4
Units: mm (inches)
223
Technical Specification
224
Technical Specification
Items W1 W2 H1 H2 H3 D1 D2 A Φ T1 T2
0055S100-2 Non-PDS :
0075S100-2 230.1
250 232 328 308 11 227.2 (9.06) 6 6 22.3 28.6
0055S100-4
(9.84) (9.13) (12.91) (12.13) (0.43) (8.94) PDS: (0.24) (0.24) (0.88) (1.13)
241.2
0075S100-4
(9.50)
Units: mm (inches)
225
Technical Specification
226
Technical Specification
Items W1 W2 H1 H2 H3 D1 D2 A T1 T2
0110S100-2 Non-PDS :
0150S100-2 260 229.2 399.6 377 14.6 245.4 248.5 (9.78) 6.5 22.3 34.9
0110S100-4 (10.24) (9.02) (15.73) (14.84) (0.57) (9.66) PDS : (0.26) (0.88) (1.37)
0150S100-4 259.6 (10.22)
Non-PDS :
0185S100-4 300 270.8 460 436.5 15.5 250 253.1 (9.96) 7 22.3 44.5
(11.81) (10.66) (18.11) (17.19) (0.61) (9.84) PDS : (0.28) (0.88) (1.75)
0220S100-4 264 (10.39)
Units: mm (inches)
227
Technical Specification
0.4-22kW Models
Compatible Circuit Breaker, Leakage Breaker and Magnetic Contactor Models
(manufactured by LS ELECTRIC)
1.5 MC-9a, 9
15 MC-9b
10 10
3- 2.2 MC-12a, 12
ABS33c EBS33c MC-12b
phase UTE100
400V 3.7 15 15 MC-18a,
18
4 20 20 20 MC-18b
5.5 MC-22b 22
30 30 30
7.5 MC-32a 32
11 ABS53c 50 50 EBS53c 50 MC-50a 50
228
Technical Specification
30-75kW Models
Compatible Circuit Breaker, Leakage Breaker and Magnetic Contactor Models
(manufactured by LS ELECTRIC)
Magnetic
Circuit Breaker Leakage Breaker
Contactor
Product(kW)
Current Current Current Current
Model Model Model Model
(A) (A) (A) (A)
EBS MC-
30 kW-4 ABS103c 125 125 125 105
103c 100a
UTS150
MC-
37 kW-4 150 150 150 130
130a
MC-
45 kW-4 ABS203c 175 175 EBS203c 175 150
150a
UTS250
MC-
55 kW-4 225 225 225 185
185a
EBS MC-
75 kW-4 ABS403c 300 UTS400 300 300 225
403c 225a
0.4-22kW Models
AC Input Fuse AC Reactor DC Reactor
Product (kW) Voltage Inductance Inductance Current
Current (A) Current(A)
(V) (mH) (mH) (A)
0.4
10 1.20 10 4 8.67
Single phase 0.75
600
200V 1.5 15 0.88 14 3 13.05
2.2 20 0.56 20 1.3 18.45
229
Technical Specification
30-75kW Models
Product AC Input Fuse AC Reactor
(kW) Current (A) Voltage (V) Inductance(mH) Current(A)
30 kW-4 0.29 69
125 A
37 kW-4 0.24 85
45 kW-4 160 A 600 0.20 100
55 kW-4 0.15 134
200 A
75 kW-4 0.13 160
230
Technical Specification
Only use Class H or RK5, UL listed input fuses and UL listed circuit breakers. See the table
above for the voltage and current ratings for fuses and circuit breakers.
231
Technical Specification
232
Technical Specification
Apply the rated torque when tightening terminal screws. Loose screws may cause short circuits
and malfunctions. Overtightening terminal screws may damage the terminals and cause short
circuits and malfunctions. Use copper conductors only, rated at 600V, 75℃ for power terminal
wiring, and rated at 300V, 75℃ for control terminal wiring.
Appliquer des couples de marche aux vis des bornes. Des vis desserrées peuvent provoquer
des courts-circuits et des dysfonctionnements. Ne pas trop serrer la vis, car cela risque
d’endommager les bornes et de provoquer des courts-circuits et des dysfonctionnements.
Utiliser uniquement des fils de cuivre avec une valeur nominale de 600 V, 75 ℃ pour le câblage
de la borne d’alimentation, et une valeur nominale de 300 V, 75 ℃ pour le câblage de la borne
de commande.
233
Technical Specification
234
Technical Specification
Note
• It is not necessary to use option type dynamic braking unit for S100 below 22kW capacity
because basically the dynamic braking unit is built in.
• You must refer to dynamic braking unit manual for usage recommended dynamic braking
unit in the table above due to changeable table.
Terminal arrangement
Group 1: P N G B1 B2
Group 2:
G N B2 P/B1
Terminals Functions
G Ground Terminal
B2 Terminal for connection with B2 of DBU
B1 Terminal for connection with B1 of DBU
N Terminal for connection with N of Inverter
P Terminal for connection with P1 of Inverter
235
Technical Specification
Group 3:
Terminals Functions
G Ground Terminal
B2 Terminal for connection with B2 of DBU
B1 Terminal for connection with B1 of DBU
N Terminal for connection with N of Inverter
P Terminal for connection with P1 of Inverter
Group 4,5:
Terminals Functions
P(+) Terminal for connection with P of Inverter
N(-) Terminal for connection with N of Inverter
B1 Terminal for connection with B1 of DBU
B2 Terminal for connection with B2 of DBU
N.C Unused
E Ground Terminal
Note
• You must refer to dynamic braking unit manual for choice the braking resistor to use the
dynamic braking unit.
• For detailed information on DBU wiring, refer to 2.2 Cable Wiring, Step 7 Selecting the
brake unit (30-75kW models only) on page 53.
236
Technical Specification
RESE
POWE
RUN
231
24
25
OHT
R U
WIRING
B2
OCT
S V IM B1
T (P2) W
P N
B2
B1
G
N
P
166.
1
2
5
2
5. 15
80
123 27
130
Group 3 Group 5
WIRING
R U R1
S V IM R2
(P2)
T W
P N
G
B2
N
B1
WIRING P
R U R1
S V IM R2
T (P2) W
P N
G
B2
N
B1
P
적
용
제 237
품
Technical Specification
Hole position
Capacity of Dimension (mm) for installation Hole size for
Voltage Weight
applied (mm) installation
(V) (kg)
motor(kW) ()
W H H2 D W1 H1
30~37 1.56
440 140 227.4 192 76.4 125 215.4 M4
45~75 1.85
Group 4
Hole position
Capacity Dimension (mm) for installation Weig Hole size for
Voltage
of applied %ED (mm) ht installation
(V)
motor(kW) (kg) ()
W H H2 D W1 H1
440 30~37 50 140 227.4 192 76.4 125 215.4 1.56 M4
238
Technical Specification
Display Functions
DB Resistors connect with B1, B2 of DB Unit. DBU has 3 LEDs. Red LED which is located
in middle displays supplying main power, one Green LED which is right side displays under
braking and another green LED which is left side displays Over Heat Trip(OHT).
Note
• The resistance/rated capacity/braking torque/%ED of DB Resistor are valid only for the DB
unit of type A and the values of DB Resistor for type B and C refer to the manual of DB
Unit..
• Rating Watt of DBU has to be doubled when %ED is doubled.
239
Technical Specification
Refer to the following graphs for carrier frequency ranges and default values by product
capacity.
The continuous rated current of the inverter is limited based on the carrier frequency. Refer
to the following graph.
Carrier frequency
(kHz)
240
Technical Specification
Carrier frequency
(kHz)
Continuous Rated Current Graph (0.4-75kW Normal Duty)
Continuous rated current
Carrier frequency
(kHz)
Capacity (kW) DR (%) Capacity (kW) DR (%) Capacity (kW) DR (%)
0.4kW-2 85% 15kW-2 90% 11kW-4 85%
0.8kW-2 88% 0.4kW-4 74% 15kW-4 84%
1.5kW-2 88% 0.8kW-4 85% 18.5kW-4 92%
2.2kW-2 94% 1.5kW-4 84% 22kW-4 83%
3.7kW-2 92% 2.2kW-4 85% 30kW-4 86%
4.0kW-2 96% 3.7kW-4 85% 37kW-4 87%
5.5kW-2 85% 4.0kW-4 93% 45kW-4 89%
7.5kW-2 85% 5.5kW-4 81% 55kW-4 83%
11kW-2 87% 7.5kW-4 77% 75kW-4 92%
* DR (%) includes maximum carrier frequency values by product capacity.
241
Technical Specification
The continuous rated current of the inverter is limited based on the input voltage. Refer to
the following graph.
Continuous rated current
Input Voltage
The constant-rated current of the inverter is limited based on the ambient temperature and
installation type. Refer to the following graph. A side-by-side operation is only available with
0.4-22kW IP20.
242
Technical Specification
Single
Phase
3-Phase
Heat emission data is based on operations with default carrier frequency settings, under
normal operating conditions.
243
Technical Specification
Scale : mm
Installation.
5 Take off the top cover of the I/O board kit and remove the hole cover to connect remote
cable on the side.
6 Connect the other side of the remote cable to the remote keypad as shown below.
244
Applying Drives to Single-Phase Input Application
8.1 Introduction
LSLV-S100 is a three-phase standard variable frequency drive(VFD). When applying
single-phase power to a three-phase VFD, there are several constraints that need to be
considered. Standard Pulse-Width-Modulated (PWM) VFDs use a 6-pulse diode rectifier.
The 6-pulse rectification results in 360 Hz DC bus ripple when used with a three-phase 60
Hz supply.
However, under single-phase use, the DC bus ripple becomes 120 Hz and the VFDs DC
bus circuit is subject to higher stress in order to deliver equivalent power.
Additionally, input currents and harmonics increase beyond those encountered with three-
phase input.
Input current distortion of 90% THD and greater can be expected under single-phase input,
compared to approximately 40% with three-phase input as indicated in Figure 2.
Therefore, single-phase use requires the three-phase VFD power rating be reduced
(derated) to avoid over stressing the rectifier and DC link components.
245
Applying Drives to Single-Phase Input Application
246
Applying Drives to Single-Phase Input Application
247
Product Warranty
Warranty Information
Fill in this warranty information form and keep this page for future reference or when
warranty service may be required.
LS ELECTRIC
Product Name Date of Installation
Standard Inverter
Model Name LSLV-S100 Warranty Period
Name
(or company)
Contact Info.
Name
Contact info.
Warranty Period
The product warranty covers product malfunctions, under normal operating conditions, for 12
months from the date of installation. If the date of installation is unknown, the product
warranty is valid for 18 months from the date of manufacturing. Please note that the product
warranty terms may vary depending on purchase or installation contracts.
248
Non-Warranty Service
A service fee will be incurred for malfunctions in the following cases:
• intentional abuse or negligence
• power supply problems or from other appliances being connected to the product
• acts of nature (fire, flood, earthquake, gas accidents etc.)
• modifications or repair by unauthorized persons
• missing authentic LS ELECTRIC rating plates
• expired warranty period
249
250
UL mark
The UL mark applies to products in the United States and Canada. This mark indicates that
UL has tested and evaluated the products and determined that the products satisfy the UL
standards for product safety. If a product received UL certification, this means that all
components inside the product had been certified for UL standards as well.
CE mark
The CE mark indicates that the products carrying this mark comply with European safety
and environmental regulations. European standards include the Machinery Directive for
machine manufacturers, the Low Voltage Directive for electronics manufacturers and the
EMC guidelines for safe noise control.
EMC Directive
The Directive defines the requirements for immunity and emissions of electrical equipment
used within the European Union. The EMC product standard (EN 61800-3) covers
requirements stated for drives.
EAC mark
The EAC (EurAsian Conformity) mark is applied to the products before they are placed on
the market of the Eurasian Customs Union member states.
It indicates the compliance of the products with the following technical regulations and
requirements of the Eurasian Customs Union:
Technical Regulations of the Customs Union 004/2011 “On safety of low voltage equipment”
Technical Regulations of the Customs Union 020/2011 “On electromagnetic compatibility of
technical products”
251
252
Footprint Filters EN 55011 CLASS B IEC/EN 61800-3 C2
Leakage
Current Voltage Current[mA] Dimension Mounting Weight Output
Inverter Power Code Fig.
[A] [Vac] [L,W,H] [Y,X] [Kg] Choke
Nom. Max.
Leakage
Current Voltage Current[mA] Dimension Mounting Weight Output
Inverter Power Code Fig.
[A] [Vac] [L,W,H] [Y,X] [Kg] Choke
Nom. Max.
LSLV0055S100-2 5.5kW FLD 3042 42A 220-480 0.5 27 335x60x150 35x320 2.8 C FS-2
LSLV0075S100-2 7.5kW FLD 3055 55A 220-480 0.5 27 335x60x150 35x320 3.1 C FS-2
LSLV0110S100-2 11kW FLD 3075 75A 220-480 0.5 27 335x60x150 35x320 4 C FS-2
LSLV0150S100-2 15kW FLD 3100 100A 220-480 0.5 27 330x80x220 55x314 5.5 C FS-3
Leakage
Current Voltage Current[mA] Dimension Mounting Weight Output
Inverter Power Code Fig.
[A] [Vac] [L,W,H] [Y,X] [Kg] Choke
Nom. Max.
Leakage
Current Voltage Current[mA] Dimension Mounting Weight Output
Inverter Power Code Fig.
[A] [Vac] [L,W,H] [Y,X] [Kg] Choke
Nom. Max.
253
254
Manual Revision History
Revision History
255
Index
Index
[ advanced features group .........................................68
Advanced function group ..Refer to ADV (advanced)
[DOWN] key ............................................................. 66 function group
[ESC] key .................................................................. 66 analog input..................................................42, 67, 68
[HAND] key ............................................................... 66 analog input selection switch(SW2)........................40
[LEFT] key ................................................................ 66 analog output ............................................................44
[MODE] key .............................................................. 66 AO terminal ..........................................................44
[MULTI] key............................................................... 66 analog output selection switch(SW3) .....................40
[OFF] key .................................................................. 66 AO terminal ...............................................................44
[PROG / Ent] key ..................................................... 66 analog output selection switch(SW3) ................40
[RIGHT] key .............................................................. 66 AP(Application Function group) ........................... 146
[STOP/RESET] key ................................................. 66 asymmetric ground power .......................................49
[UP] key..................................................................... 66 asymmetric ground structure
EMC filter..............................................................49
2 Auto Tuning ............................................................. 111
24 terminal ..........................................................44, 47 B
2nd Motor Function group ... Refer to M2 (2nd Motor
Function group ) group bA(Basic function group) .......................................110
basic configuration diagram.....................................16
3 Basic group ......Refer to BAS (Basic function group)
basic operation..........................................................59
3-phase 200V (0.4~4k W)..................................... 204 Bootlace Ferrule .......................................................45
3-phase 200V (5.5~15 kW)................................... 205 brake resistor ...............................................34, 35, 37
3-phase 400V (0.4~4 kW)..................................... 206 braking resistance
3-phase 400V (5.5~22 kW).......................... 207, 209 braking torque ................................................... 234
braking resistors........................................................16
BX ........................................................................... 187
4
4-pole standard motor ..........................203, 206, 207 C
cable ................ 13, 23, 25, 26, 28, 29, 30, 31, 32, 39
7 selection ..... 13, 23, 25, 26, 28, 29, 30, 31, 32, 39
shielded twisted pair ............................................55
7-segment display.................................................... 61 signal(control) cable specifications ....................14
letters.................................................................... 61 Cable
numbers ............................................................... 61 Ground Specifications .........................................13
Power I/O Cable Specifications .........................13
A cable tie .....................................................................46
carrier frequency .......................................................38
A1/C1/B1 terminal .................................................... 45 charge indicator ...................................... 21, 185, 192
AC power input terminal ..... Refer to R/S/T terminal, charge lamp ..............................................................21
cleaning .................................................................. 197
Refer to R/S/T terminal, Refer to R/S/T terminal
CM terminal ........................................................ 42, 47
Ad (Expanded function group).............................. 115 CM(communication function group) .................... 141
256
Cn (Control Function group) ................................. 121 0.4kW(Single Phase), 0.4~0.8kW(3 Phase) . 221
CNF (configuration mode)....................................... 70 External Trip ........................................................... 187
common terminal .................... Refer to EG terminal
Communication function group........... Refer to COM F
(communication function group)
Considerations for the installation factory default..................................................... 92, 93
Air Pressure ........................................................... 8 Fan Trip................................................................... 187
Altitude/Vibration ................................................... 8 Fan Warning........................................................... 189
Ambient Humidity.................................................. 8 fatal.......................................................................... 185
Environmental Factors ......................................... 8 fault
Considerations for the installation fatal .................................................................... 185
Ambient Temperature ........................................... 8 latch.................................................................... 185
Control groupRefer to CON (Control Function group) level .................................................................... 185
control terminal board wiring ................................... 39 fault monitoring
cursor keys ............................................................... 66 multiple fault trips .......................................... 101
[DOWN] key ........................................................ 66 fault signal output terminal ......... Refer to A1/C1/B1
[LEFT] key ........................................................... 66
terminal
[RIGHT] key......................................................... 66
[UP] key ............................................................... 66 fault trip mode ...........................................................70
ferrite ..........................................................................46
frequency setting
D variable resistor....................................................91
frequency setting (Pulse train) terminal .... Refer to TI
delta wiring ....................................................... 49, 208
disposal .......................................................... 197, 202 terminal
dr(Drive group) ....................................................... 105 frequency setting(voltage) terminal......... Refer to V1
Drive group ..................... Refer to DRV (Drive group) terminal
fuse ......................................................................... 230
E Fuse and Reactor Specifications ......................... 229
257
Index
[OFF] key..............................................................66
I [PROG / Ent] key .................................................66
I2 42 [STOP/RESET] key.............................................66
analog input selection switch(SW2) .................. 43 configuration mode..............................................70
frequency setting(current/voltage) terminal ...... 42 cursor keys ...........................................................66
In Phase Open ....................................................... 186 display...................................................................59
In(Input Terminal Block Function group) .............. 130 monitor mode .......................................................70
input and output specification navigating between groups ................................69
applied motor..................................................... 203 operation keys .....................................................59
rated input .......................................................... 203 parameter mode ..................................................70
rated output........................................................ 203 trip mode...............................................................70
input terminal ............................................................ 42 keypad display ..........................................................61
CM terminal ......................................................... 42 keypad key ................................................................65
I2 terminal ............................................................ 42 [▲]/[▼]/[◀]/[▶] key ............................................65
P1–P7 terminal.................................................... 42 [ESC] key .............................................................65
[RUN] key .............................................................65
SA terminal .......................................................... 43
[STOP/RESET] key.............................................65
SB terminal .......................................................... 43
SC terminal .......................................................... 43
TI terminal ............................................................ 43 L
V1 terminal........................................................... 42
VR terminal .......................................................... 42 latch......................................................................... 185
Input terminal function group ......... Refer to IN (Input LCD keypad ....................................................... 25, 28
terminal function group) wiring length .........................................................46
inspection leakage breaker ..................................................... 228
annual inspection .............................................. 198 level ......................................................................... 185
bi-annual inspection)......................................... 200 locating the installation site ........................................9
installation ................................................................. 15 location ...................................................................9
basic configuration diagram ............................... 16 Lost Command ..............................................188, 189
Installation flowchart ........................................... 15 Low Voltage............................................................ 186
wiring .................................................................... 21
Installation
Mounting the Inverter.......................................... 17
M
installation considerations ......................................... 8 M2(2nd Motor Function group) ............................ 154
IP 20 ........................................................................ 211 magnetic contactor ...................................................38
Magnetic contactor ................................................ 228
J maintenance .......................................................... 197
megger test ............................................................ 198
Jog Operation micro surge filter .......................................................38
[ESC] key configuration ...................................... 84 monitor .......................................................................94
monitoring
monitor mode .......................................................70
K monitor mode display ..........................................62
motor rotational direction..........................................57
keypad....................................................................... 59
mounting bolt.............................................................17
[ESC] key ............................................................. 66
mounting bracket ......................................................19
[HAND] key.......................................................... 66
multi function input terminal
[MODE] key ......................................................... 66
In.65~71 ............................................................ 132
[MULTI] key ......................................................... 66
258
Px terminal function setting .............................. 132 Over Voltage .......................................................... 186
multi function input terminal
Px Define ........................................................... 132
Multi-function (open collector) output terminal
P
Multi-function output item1(Q1 Define) ........... 138 P1+ terminals(+ DC link terminals) ............34, 35, 37
Multi-function relay 1 item(Relay 1)................. 137 parameter ..................................................................81
multi-function input terminal .................................... 42 parameter setting.................................................81
factory default ...................................................... 42 parameter settings...............................................82
P1–P7................................................................... Refer parameter mode .......................................................70
multi-function key ..................................................... 61 part names ..................................................................3
Multi Key Sel...................................................... 182 parts illustrated ............................................................3
multi-function key options................................. 182 Peripheral devices ................................................. 228
multi-function(open collector) output terminal .. Refer phase-to-phase voltage ........................................ 193
to Q1 terminal PID control
PID feedback .................................................... 187
PNP mode(Source) ..................................................47
N PNP/NPN mode selection switch(SW1) ................40
NPN mode(Sink) .................................................48
N- terminal(- DC link terminal) ..........................34, 37
PNP mode(Source) .............................................47
No Motor Trip .......................................................... 186
post-installation checklist .........................................54
noise .......................................................................... 49
power terminal ..........................................................37
Normal Duty................................................................ 8
N- terminal ..................................................... 34, 37
normal load ............................................................. 203
P2+/B terminal ........................................34, 35, 37
NPN mode(Sink) ...................................................... 48
U/V/W terminal........................................34, 35, 37
power terminal board wiring ....................................32
O power terminals
R/S/T terminals .......................................34, 35, 37
oOut Phase Open .................................................. 186 Pr(Protection Function group) .............................. 149
operation group ...................................................... 103 Preinsulated Crimp Terminal ...................................45
OU(Output Terminal Block Function group) ........ 136 Pulse output terminal............... Refer to TO terminal
output terminal.......Refer to R/S/T terminal, Refer to
R/S/T terminal, Refer to R/S/T terminal
Q
Output terminal function group ............ Refer to OUT
(Output terminal function group) Q1 terminal ................................................................44
output/communication terminal .............................. 44
24 terminal ........................................................... 44
A1/C1/B1 terminal............................................... 45 R
AO terminal.......................................................... 44
R/S/T terminal ...........................................................38
EG terminal.......................................................... 44
R/S/T terminals ................................... 34, 35, 37, 192
Q1 terminal .......................................................... 44
rated ........................................................................ 204
S+/S-/SG terminal ............................................... 45
braking resistance rated capacity ................... 234
TO terminal .......................................................... 44
dynamic raking capacity .................................. 239
Over Current1......................................................... 186
rated input ......................................................... 204
Over Current2......................................................... 187
rated output ....................................................... 204
Over Heat ............................................................... 187
reactor............................................................... 16, 230
Over Load ............................................................... 186
RS-485
overload warning............................................... 189
signal terminal ......................................................45
259
Index
260
cover disassembly .............................................. 22 wiring length .................................................. 38, 46
ferrite .................................................................... 46
ground .................................................................. 29
power terminal board wiring............................... 32
ㅈ
re-assembling the covers ................................... 53
중량(kg) .................................................................. 203
signal wiring ......................................................... 45
torque ................................................................... 21
261