Chf100a Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 156

CHF100A series high performance universal inverter

TABLE OF CONTENTS

SAFETY PRECAUTIONS........................................................................................ 3
1. INTRODUCTION............................................................................................... 4
1.1 Technology Features .................................................................................. 4
1.2 Description of Name Plate .......................................................................... 5
1.3 Selection Guide .......................................................................................... 5
1.4 Parts Description ........................................................................................ 7
2. UNPACKING INSPECTION................................................................................. 9
3. INSTALLATION .............................................................................................. 10
3.1 Environmental Requirement ..................................................................... 11
4. WIRING........................................................................................................... 12
4.1 Connection of Peripheral Devices ............................................................ 13
4.2 Terminal Configuration.............................................................................. 14
4.3 Wiring Diagram......................................................................................... 16
4.4 Wiring Main Circuits.................................................................................. 18
4.5 Wiring Control Circuit................................................................................ 21
4.6 Installation Guidline to EMC Compliance.................................................. 23
5. OPERATION...................................................................................................... 27
5.1 Keypad Description .................................................................................. 27
5.2 Operation Process.................................................................................... 29
5.3 Running State........................................................................................... 31
5.4 Shortcut Menu .......................................................................................... 32
6. DETAILED FUNCTION DESCRIPTION............................................................. 33
6.1 P0 Group--Basic Function ........................................................................ 33
6.2 P1 Group --Start and Stop Control ............................................................ 41
6.3 P2 Group--Motor Parameters ................................................................... 46
6.4 P3 Group—Vector Control ........................................................................ 47
6.5 P4 Group—V/F Control ............................................................................ 50
6.6 P5 Group--Input Terminals........................................................................ 54
6.7 P6 Group--Output Terminals ..................................................................... 61
6.8 P7 Group—Display Interface .................................................................... 66
6.9 P8 Group--Enhanced Function ................................................................. 72
6.10 P9 Group--PID Control ........................................................................... 78
6.11 PA Group--Simple PLC and Multi-step Speed Control............................. 82
.1.
CHF100A series high performance universal inverter

6.12 PB Group-- Protection Function.............................................................. 88


6.13 PC Group--Serial Communication .......................................................... 93
6.14 PD Group--Supplementary Function....................................................... 95
6.15 PE Group—Factory Setting .................................................................... 96
7. TROUBLE SHOOTING ..................................................................................... 97
7.1 Fault and Trouble shooting ....................................................................... 97
7.2 Common Faults and Solutions................................................................ 100
8. MAINTENANCE .......................................................................................... 102
8.1 Daily Maintenance .................................................................................. 102
8.2 Periodic Maintenance ............................................................................. 103
8.3 Replacement of wearing parts ................................................................ 104
9. COMMUNICATION PROTOCOL ..................................................................... 105
9.1 Interfaces ............................................................................................... 105
9.2 Communication Modes ........................................................................... 105
9.3 Protocol Format ...................................................................................... 105
9.4 Protocol function..................................................................................... 106
9.5 Note:........................................................................................................111
9.6 CRC Check .............................................................................................111
9.7 Example ..................................................................................................111
Appendix A: External Dimension...................................................................... 113
A.1 380V .......................................................................................................113
A.2 220V .......................................................................................................115
A.3 Installation Space ....................................................................................117
A.4 Dimensions of External small Keypad .....................................................117
A.5 Dimensions of External big Keypad.........................................................118
A.6 Disassembly............................................................................................118
Appendix B Specifications of Breaker, Cable, Contactor and Reactor.......... 121
B.1 Specifications of breaker, cable and contactor ....................................... 121
B.2 Specifications of AC input/output reactor and DC reactor ....................... 122
B.3 Specifications of AC input/output filter .................................................... 123
B.4 Specifications of braking unit and braking resistor.................................. 124
Appredix C: LIST OF FUNCTION PARAMETERS ............................................. 128

.2.
CHF100A series high performance universal inverter

1. INTRODUCTION
1.1 Technology Features
● Input & Output
u Input Voltage Range: 380/220V±15%
u Input Frequency Range: 47~63Hz
u Output Voltage Range: 0~rated input voltage
u Output Frequency Range: 0~400Hz
● I/O Features
u Programmable Digital Input: Provide 7 terminals which can support ON-OFF
inputs, 1 terminal which can support high speed pulse input and support PNP,
NPN
u Programmable Analog Input: AI1 can accept input of -10V ~10V, AI2 can accept
input of 0~10V or 0~20mA.
u Programmable Open Collector Output: Provide 1 output terminal (open collector
output)
u Relay Output: Provide 2 output terminals
u Analog Output: Provide 2 output terminal, whose output scope can be 0/4~20 mA
or 0~10 V, as chosen.
● Main Control Function
u Control Mode: V/F control, Sensorless Vector Control (SVC)
u Overload Capacity: 60s with 150% of rated current, 10s with 180% of rated
current.
u Speed Adjusting Range: 1:100 (SVC)
u Carrier Frequency: 1 kHz ~15.0 kHz.
u Frequency reference source: keypad, analog input, HDI, serial communication,
multi-step speed, simple PLC and PID. The combination of multi- modes and the
switch between different modes can be realized.
u PID Control Function
u Simple PLC, Multi-Steps Speed Control Function: 16 steps speed can be set.
u Traverse Control Function
u None-Stop when instantaneous power off.
u Speed Trace Function: Smoothly start the running motor.
u QUICK/JOG Key: User defined shortcut key can be realized.
u Automatic Voltage Regulation Function (AVR):

.4.
CHF100A series high performance universal inverter

u Automatically keep the output voltage stable when input voltage fluctuating
u Up to 25 fault protections:
u Protect from over current, over voltage, under voltage, over temperature, phase
failure, over load etc.

1.2 Description of Name Plate

Figure 1.1 Nameplate of inverter.

1.3 Selection Guide


Rated output Rated input Rated output
Model No. Size
Power (kW) current (A) current (A)
1AC 220V ±15%
CHF100A-1R5G-S2 1.5 14.2 7.0 B
CHF100A-2R2G-S2 2.2 23.0 10 B
3AC 220V ±15%
CHF100A-0R7G-2 0.75 5.0 4.5 B
CHF100A-1R5G-2 1.5 7.7 7 B
CHF100A-2R2G-2 2.2 11.0 10 B
CHF100A-004G-2 4.0 17.0 16 C
CHF100A-5R5G-2 5.5 21.0 20 C
CHF100A-7R5G-2 7.5 31.0 30 D
CHF100A-011G-2 11.0 43.0 42 E
CHF100A-015G-2 15.0 56.0 55 E
CHF100A-018G-2 18.5 71.0 70 E
CHF100A-022G-2 22.0 81.0 80 F
CHF100A-030G-2 30.0 112.0 110 F

.5.
CHF100A series high performance universal inverter

Rated output Rated input Rated output


Model No. Size
Power (kW) current (A) current (A)
CHF100A-037G-2 37.0 132.0 130 F
CHF100A-045G-2 45.0 163.0 160 G
CHF100A-055G-2 55.0 181.0 190.0 G
3AC 380V ±15%
CHF100A-1R5G/2R2P-4 1.5 5.0 3.7 B
CHF100A-2R2G/004P-4 2.2 5.8 5 B
CHF100A-004G/5R5P-4 4.0/5.5 10/15 9/13 C
CHF100A-5R5G/7R5P-4 5.5/7.5 15/20 13/17 C
CHF100A-7R5G/011P-4 7.5/11 20/26 17/25 D
CHF100A-011G/015P-4 11/15 26/35 25/32 D
CHF100A-015G/018P-4 15/ 18.5 35/38 32/37 D
CHF100A-018G/022P-4 18.5/ 22 38/46 37/45 E
CHF100A-022G/030P-4 22/30 46/62 45/60 E
CHF100A-030G/037P-4 30/37 62/76 60/75 E
CHF100A-037G/045P-4 37/45 76/90 75/90 F
CHF100A-045G/055P-4 45/55 90/105 90/110 F
CHF100A-055G/075P-4 55/75 105/ 140 110/ 150 F
CHF100A-075G/090P-4 75/90 140/ 160 150/ 176 G
CHF100A-090G/110P-4 90/110 160/ 210 176/ 210 G
CHF100A-110G/132P-4 110/132 210/ 240 210/ 250 G
CHF100A-132G/160P-4 132/160 240/ 290 250/ 300 H
CHF100A-160G/185P-4 160/185 290/ 330 300/ 340 H
CHF100A-185G/200P-4 185/200 330/ 370 340/ 380 H
CHF100A-200G/220P-4 200/220 370/ 410 380/ 415 I
CHF100A-220G/250P-4 220/250 410/ 460 415/ 470 I
CHF100A-250G/280P-4 250/280 460/ 500 470/ 520 I
CHF100A-280G/315P-4 280/315 500/ 580 520/ 600 I
CHF100A-315G/350P-4 315/350 580/ 620 600/ 640 I
CHF100A-350G-4 350 620 640 2*H
CHF100A-400G-4 400 670 690 2*I
CHF100A-500G-4 500 835 860 2*I
CHF100A-560G-4 560 920 950 2*I

.6.
CHF100A series high performance universal inverter

1.4 Parts Description

Figure 1.2 Parts of inverter (15kw and below).

.7.
CHF100A series high performance universal inverter

Figure 1.3 Parts of inverter (18.5kw and above).

.8.
CHF100A series high performance universal inverter

3.1 Environmental Requirement


3.1.1 Temperature
Environment temperature range: -10°C ~ +40°C. Inverter will be derated at 4%/1°C if
ambient temperature exceeds 40°C up to 50°C. The utmost permited ambient
temperature shoud not exceed 50°C.
3.1.2 Humidity
Less than 90% RH, without dewfall.
3.1.3 Altitude
Inverter can output the rated power when installed with altitude of lower than 1000m. It
will be derated when the altitude is higher than 1000m. For details, please refer to the
following figure:
Iout

100%

80%

60%

40%

20%

1000 2000 3000 4000(m)

Figure 3.1 Relationship between output current and altitude.


3.1.4 Impact and Oscillation
It is not allowed that the inverter falls down or suffers from fierce impact or the inverter is
installed at the place that oscillation frequently.
3.1.5 Electromagnetic Radiation
Keep away from the electromagnetic radiation source.
3.1.6 Water
Do not install the inverter at the wringing or dewfall place.
3.1.7 Air Pollution
Keep away from air pollution such as dusty, corrosive gas.
3.1.8 Storage
Do not store the inverter in the environment with direct sunlight, vapor, oil fog and
vibration.

.11.
CHF100A series high performance universal inverter

4.2 Terminal Configuration


4.2.1 Main Circuit Terminals (380VAC)
R S T U V W
(+) PB
POWER MOTOR
Figure 4.2 Main circuit terminals (1.5~2.2kW).
R S T U V W
(+) PB (-)
POWER MOTOR
Figure 4.3 Main circuit terminals (4~5.5kW).
R S T U V W
(+) PB (-)
POWER MOTOR
Figure 4.4 Main circuit terminals (7.5~15kW).
R S T U V W
P1 (+) (-)
POWER MOTOR
Figure 4.5 Main circuit terminals (18.5~110kW).

R S T U V W
POWER MOTOR

P1 (+) (-)

Figure 4.6 Main circuit terminals (132~315kW).

R S T U V W
POWER MOTOR

P1 (+) (-)

Figure 4.7 Main circuit terminals (350~500kW).


4.2.2 Main Circuit Terminals (220VAC)

Figure 4.8 Main circuit terminals (4~5.5kW).

.14.
CHF100A series high performance universal inverter

Figure 4.9 Main circuit terminals (7.5kW).

Figure 4.10 Main circuit terminals (11~18.5kW).

Figure 4.11 Main circuit terminals (22kW and bigger).


the main circuit terminals’s description are as following. Wire the terminal correctly for
the desired purposes.
Terminal Symbol Function Description
R、S、T Terminals of 3 phase AC input
(+)、(-) Spare terminals of external braking unit
(+)、PB Spare terminals of external braking resistor
P1、(+) Spare terminals of external DC reactor
(-) Terminal of negative DC bus
U、V、W Terminals of 3 phase AC output
Terminal of ground
(+) Terminal of positive DC bus

4.2.3 Control Circuit Terminals

Figure 4.12 Control circuit terminals.

.15.
CHF100A series high performance universal inverter

4.3 Wiring Diagram


4.3.1 Typical Wiring Diagram
DC Reactor P P
Propositional Protection Braking Resistor
Circuit N PB

P1 (+) (-)

3 Phase
380V±15% R U
50/60Hz
S V M
CHF100A Series
T W
Inverter
PE
Multifunctional On-Off Input 1 S1

Multifunctional On-Off Input 2 S2

J15 AO1
Multifunctional On-Off Input 3 S3 Analog Output
V I 0-10V/0-20mA
Multifunctional On-Off Input 4 GND
S4
Multifunctional On-Off Input 5 S5 J17 AO2 Analog Output
Multifunctional On-Off Input 6 0-10V/0-20mA
S6 V I GND
Multifunctional On-Off Input 7 S7
High Speed Pulse Input HDO
HD1
Or Collector Open-circuit Collector Open-circuit Output
Input COM COM
PW
485+ 485+
+24V 485 Communication selection
PE 485- 485-

Power Supply For Frequecy Setting


RO1A

Frequency/PID Setting
AI1 Multifunctional Analog Input RO1B
{ Relay Output 1
AI2 J16 RO1C
0-10V Input V I
0/4-20mA Input GND Jumper of AI2 to select
I or V RO2A

PE RO2B
{ Relay Output 2
RO2C

Figure4.13 Typical Wiring diagram.


Notice:
u Inverters between 18.5kW and 90kW have built-in DC reactor which is used to
improve power factor. For inverters above 110kW, it is recommended to
install DC reactor between P1 and (+).
u The inverters below 18.5kW have build-in braking unit. If need braking, only
need to install braking resistor between PB and (+).
u For inverters above (including) 18.5kW, if need braking, should install
external braking unit between (+) and (-).
u Only the inverters above 4 kW provide Relay output 2.
u +24V connect with PW as default setting. If user need external power supply,

.16.
CHF100A series high performance universal inverter

disconnect +24V with PW and connect PW with external power supply.


u 485+ and 485- are optional for 485 communications.
4.3.2 Outpu and input signal connection
Set the common emitter/common collector mode and out/input power supply by U-short
splicing. The factory setting is the common emitter.

Figure 4.14 U-short splicing.


Common emitter mode:
Please set the U-short splicing according to the type of power supply, when the input
signal is from the NPN transistor.

S1 S1

S2 S2

C OM COM

+24V +24V
COM COM COM COM COM
+24V
C OM
PW PW
PW PW PW
+24V PW +24V
+24V +24V
+24V
+24V

Mode of common emitter(0V is Mode of common emitter(0V is


public point)inner power public point)exterior power

Figure 4.15 Common emitter mode.


Common Collector mode:
Please set the U-short splicing according to the type of power supply, when the input
signal is from the PNP transistor.

.17.
CHF100A series high performance universal inverter

S1 S1

S2 S2

C OM COM

+2 4V + 24V
C OM COM C OM COM
C OM
+24V
PW PW
PW PW
C OM PW
+24 V +2 4V
+2 4V +2 4V

PW +24V

+24V

Mode of common collector( +24V Mode of common collector( +24V is


is public point) inner power public point) exterior power

Figure 4.16 Common collector mode.

4.4 Wiring Main Circuits


4.4.1 Wiring at input side of main circuit
4.4.1.1 Circuit breaker
It is necessary to connect a circuit breaker which is compatible with the capacity of
inverter between 3ph AC power supply and power input terminals (R, S, T ). The
capacity of breaker is 1.5~2 times to the rated current of inverter. For details, see
<Specifications of Breaker, Cable, and Contactor>.
4.4.1.2 Contactor
In order to cut off the input power effectively when something is wrong in the system,
contactor should be installed at the input side to control the ON-OFF of the main circuit
power supply.
4.4.1.3 AC reactor
In order to prevent the rectifier damage result from the large current, AC reactor should
be installed at the input side. It can also prevent rectifier from sudden variation of power
voltage or harmonic generated by phase-control load.
4.4.1.4 Input EMC filter
The surrounding device may be disturbed by the cables when the inverter is working.
EMC filter can minimize the interference. Just like the following figure.

.18.
CHF100A series high performance universal inverter

Figure4.17 Wiring at input side.


4.4.2 Wiring at inverter side of main circuit
4.4.2.1 DC reactor
Inverters from 18.5kW to 90kW have built-in DC reactor which can improve the power
factor,
4.4.2.2 Braking unit and braking resistor
• Inverter of 15KW and below have built-in braking unit. In order to dissipate the
regenerative energy generated by dynamic braking, the braking resistor should be
installed at (+) and PB terminals. The wire length of the braking resistor should be less
than 5m.
• Inverter of 18.5KW and above need connect external braking unit which should be
installed at (+) and (-) terminals. The cable between inverter and braking unit should be
less than 5m. The cable between braking unit and braking resistor should be less than
10m.
• The temperature of braking resistor will increase because the regenerative energy will
be transformed to heat. Safety protection and good ventilation is recommended.
Notice: Be sure that the electric polarity of (+) (-) terminals is right; it is not allowed
to connect (+) with (-) terminals directly, Otherwise damage or fire may occur.
4.4.3 Wiring at motor side of main circuit
4.4.3.1 Output Reactor
Output reator must be installed in the following condition. When the distance between
inverter and motor is more than 50m, inverter may be tripped by over-current protection
frequently because of the large leakage current resulted from the parasitic capacitance
with ground. And the same time to avoid the damage of motor insulation, the output
reactor should be installed.
4.4.3.2 Output EMC filter

.19.
CHF100A series high performance universal inverter

EMC filter should be installed to minimize the leakage current caused by the cable and
minimize the radio noise caused by the cables between the inverter and cable. Just see
the following figure.

Figure 4.18 Wiring at motor side.


4.4.4 Wiring of regenerative unit
Regenerative unit is used for putting the electricity generated by braking of motor to the
grid. Compared with traditional 3 phase inverse parallel bridge type rectifier unit,
regenerative unit uses IGBT so that the total harmonic distortion (THD) is less than 4%.
Regenerative unit is widely used for centrifugal and hoisting equipment.

RST
Grid

Figure 4.19 Wiring of regenerative unit.


4.4.5 Wiring of Common DC bus
Common DC bus method is widely used in the paper industry and chemical fiber industry
which need multi-motor to coordinate. In these applications, some motors are in driving
status while some others are in regenerative braking (generating electricity) status. The
regenerated energy is automatically balanced through the common DC bus, which
means it can supply to motors in driving status. Therefore the power consumption of
whole system will be less compared with the traditional method (one inverter drives one
motor).

.20.
CHF100A series high performance universal inverter

When two motors are running at the same time (i.e. winding application), one is in driving
status and the other is in regenerative status. In this case the DC buses of these two
inverters can be connected in parallel so that the regenerated energy can be supplied to
motors in driving status whenever it needs. Its detailed wiring is shown in the following
figure:

Figure 4.20 Wiring of common DC bus.


Notice: Two inverters must be the same model when connected with Common DC
bus method. Be sure they are powered on at the same time.
4.4.6 Ground Wiring (PE)
In order to ensure safety and prevent electrical shock and fire, terminal PE must be
grounded with ground resistance. The ground wire should be big and short, and it is
2
better to use copper wire (>3.5mm ). When multiple inverters need to be grounded, do
not loop the ground wire.

4.5 Wiring Control Circuit


4.5.1 Precautions
4.5.1.1 Use shielded or twisted-pair cables to connect control terminals.
4.5.1.2 Connect the ground terminal (PE) with shield wire.
4.5.1.3 The cable connected to the control terminal should leave away from the main
circuit and heavy current circuits (including power supply cable, motor cable, relay and
contactor connecting cable) at least 20cm and parallel wiring should be avoided. It is
suggested to apply perpendicular wiring to prevent inverter malfunction caused by
external interference.

.21.
CHF100A series high performance universal inverter

4.5.2 Control circuit terminals


Terminal Description
ON-OFF signal input, optical coupling with PW and COM.
S1~S7 Input voltage range: 9~30V
Input impedance: 3.3kΩ
High speed pulse or ON-OFF signal input, optical coupling with PW
and COM.
HDI Pulse input frequency range: 0~50kHz
Input voltage range: 9~30V
Input impedance: 1.1kΩ
External power supply. +24V terminal is connected to PW terminal
as default setting. If user need external power supply, disconnect
PW
+24V terminal with PW terminal and connect PW terminal with
external power supply.
Provide output power supply of +24V.
+24V
Maximum output current: 150mA
Analog input, -10V~10V
AI1
Input impedance: 20kΩ
Analog input, 0~10V/ 0~20mA, switched by J16.
AI2
Input impedance: 10kΩ (voltage input) / 250Ω (current input)
Common ground terminal of analog signal and +10V.
GND
GND must isolated from COM.
+10V Supply +10V for inverter.
HDO Open collector output
Common ground terminal for digital signal and +24V (or external
COM
power supply).
Provide voltage or current output which can be switched by J15 and
AO1、AO2
J17. Output range: 0~10V/ 0~20mA
RO1A、RO1B、 RO1 relay output: RO1A—common; RO1B—NC; RO1C—NO.
RO1C Contact capacity: AC 250V/3A, DC 30V/1A.
RO2A、RO2B、 RO2 relay output: RO2A—common; RO2B—NC; RO2C—NO.
RO2C Contact capacity: AC 250V/3A, DC 30V/1A.
485+、485- 485 communication port. 485 differenticial signal, +,-.

.22.
CHF100A series high performance universal inverter

4.5.3 Jumper on control board


Jumper Description
It is prohibited to be connected together, otherwise it will cause
J2, J4
inverter malfunction.
Switch between (0~10V) voltage input and (0~20mA) current input.
J16 V connect to GND means voltage input;
I connect to GND means current input.
J15、J17 Switch between (0~10V) voltage output and (0~20mA) current
(4.0kW 以上) output.
J14、J15 V connect to GND means voltage output;
(1.5~2.2kW) I connect to GND means current output.
Switch of terminal resistor for RS485 communication. ON:
SW1 Connect to terminal resistor. OFF: Disconnect to terminal resistor.
(Valid for inverter of 4.0KW or above)
J17 RS485 communication jumper
Switch of terminal resistor for RS485 communication. Jumper
enable: Connect terminal resistor.
J17, J18
Jumper disable: Disconnect terminal resistor. (Valid for inverter of
1.5~2.2kW).

4.6 Installation Guidline to EMC Compliance


4.6.1 General knowledge of EMC
EMC is the abbreviation of electromagnetic compatibility, which means the device or
system has the ability to work normally in the electromagnetic environment and will not
generate any electromagnetic interference to other equipments.
EMC includes two subjects: electromagnetic interference and electromagnetic
anti-jamming.
According to the transmission mode, Electromagnetic interference can be divided into
two categories: conducted interference and radiated interference.
Conducted interference is the interference transmitted by conductor. Therefore, any
conductors (such as wire, transmission line, inductor, capacitor and so on) are the
transmission channels of the interference.
Radiated interference is the interference transmitted in electromagnetic wave, and the
energy is inverse proportional to the square of distance.

.23.
CHF100A series high performance universal inverter

Three necessary conditions or essentials of electromagnetic interference are:


interference source, transmission channel and sensitive receiver. For customers, the
solution of EMC problem is mainly in transmission channel because of the device
attribute of disturbance source and receiver can not be changed.
4.6.2 EMC features of inverter
Like other electric or electronic devices, inverter is not only an electromagnetic
interference source but also an electromagnetic receiver. The operating principle of
inverter determines that it can produce certain electromagnetic interference noise. At the
same time inverter should be designed with certain anti-jamming ability to ensure the
smooth working in certain electromagnetic environment. Following is its EMC features:
4.6.2.1 Input current is non-sine wave. The input current includes large amount of
high-harmonic waves that can cause electromagnetic interference, decrease the grid
power factor and increase the line loss.
4.6.2.2 Output voltage is high frequency PMW wave, which can increase the
temperature rise and shorten the life of motor. And the leakage current will also increase,
which can lead to the leakage protection device malfunction and generate strong
electromagnetic interference to influence the reliability of other electric devices.
4.6.2.3 As the electromagnetic receiver, too strong interference will damage the inverter
and influence the normal using of customers.
4.6.2.4 In the system, EMS and EMI of inverter coexist. Decrease the EMI of inverter can
increase its EMS ability.
4.6.3 EMC Installation Guideline
In order to ensure all electric devices in the same system to work smoothly, this section,
based on EMC features of inverter, introduces EMC installation process in several
aspects of application (noise control, site wiring, grounding, leakage current and power
supply filter). The good effective of EMC will depend on the good effective of all of these
five aspects.
4.6.3.1 Noise control
All the connections to the control terminals must use shielded wire. And the shield layer
of the wire must ground near the wire entrance of inverter. The ground mode is 360
degree annular connection formed by cable clips. It is strictly prohibitive to connect the
twisted shielding layer to the ground of inverter, which greatly decreases or loses the
shielding effect.
Connect inverter and motor with the shielded wire or the separated cable tray. One side
of shield layer of shielded wire or metal cover of separated cable tray should connect to

.24.
CHF100A series high performance universal inverter

ground, and the other side should connect to the motor cover. Installing an EMC filter
can reduce the electromagnetic noise greatly.
4.6.3.2 Site wiring
Power supply wiring: the power should be separated supplied from electrical transformer.
Normally it is 5 core wires, three of which are fire wires, one of which is the neutral wire,
and one of which is the ground wire. It is strictly prohibitive to use the same line to be
both the neutral wire and the ground wire
Device categorization: there are different electric devices contained in one control
cabinet, such as inverter, filter, PLC and instrument etc, which have different ability of
emitting and withstanding electromagnetic noise. Therefore, it needs to categorize these
devices into strong noise device and noise sensitive device. The same kinds of device
should be placed in the same area, and the distance between devices of different
category should be more than 20cm.
Wire Arrangement inside the control cabinet: there are signal wire (light current) and
power cable (strong current) in one cabinet. For the inverter, the power cables are
categorized into input cable and output cable. Signal wires can be easily disturbed by
power cables to make the equipment malfunction. Therefore when wiring, signal cables
and power cables should be arranged in different area. It is strictly prohibitive to arrange
them in parallel or interlacement at a close distance (less than 20cm) or tie them
together. If the signal wires have to cross the power cables, they should be arranged in
90 angles. Power input and output cables should not either be arranged in interlacement
or tied together, especially when installed the EMC filter. Otherwise the distributed
capacitances of its input and output power cable can be coupling each other to make the
EMC filter out of function.
4.6.3.3 Ground
Inverter must be ground safely when in operation. Grounding enjoys priority in all EMC
methods because it does not only ensure the safety of equipment and persons, but also
is the simplest, most effective and lowest cost solution for EMC problems.
Grounding has three categories: special pole grounding, common pole grounding and
series-wound grounding. Different control system should use special pole grounding,
and different devices in the same control system should use common pole grounding,
and different devices connected by same power cable should use series-wound
grounding.
4.6.3.4 Leakage Current
Leakage current includes line-to-line leakage current and over-ground leakage current.

.25.
CHF100A series high performance universal inverter

Its value depends on distributed capacitances and carrier frequency of inverter. The
over-ground leakage current, which is the current passing through the common ground
wire, can not only flow into inverter system but also other devices. It also can make
leakage current circuit breaker, relay or other devices malfunction. The value of
line-to-line leakage current, which means the leakage current passing through
distributed capacitors of input output wire, depends on the carrier frequency of inverter,
the length and section areas of motor cables. The higher carrier frequency of inverter,
the longer of the motor cable and/or the bigger cable section area, the larger leakage
current will occur.
Countermeasure:
Decreasing the carrier frequency can effectively decrease the leakage current. In the
case of motor cable is relatively long (longer than 50m), it is necessary to install AC
reactor or sinusoidal wave filter at the output side, and when it is even longer, it is
necessary to install one reactor at every certain distance.
4.6.3.5 EMC Filter
EMC filter has a great effect of electromagnetic decoupling, so it is preferred for
customer to install it.
For inverter, noise filter has following categories:
l Noise filter installed at the input side of inverter;
l Install noise isolation for other equipment by means of isolation transformer or
power filter.
4.6.4 The installation complies with the following standard:
l EN61000-6-4: Electromagnetic Interference Detection on the industrial condition.
l EN61800-3: Comply with the electromagnetic radiation standard of EN61800-3
(The second environment). Can comply with the electromagnetic radiation
standard of EN61000-6-3(residence) and standard of EN61000-6-4.
4.6.5 Notice
l This type of PDS is not intended to be used on a low-voltage public network
which supplies domestic premise;
l Radio frequency interference is expected if used on such a network.

.26.
CHF100A series high performance universal inverter

5. OPERATION
5.1 Keypad Description
5.1.1 Keypad schematic diagram

Figure 5.1 Keypad schematic diagram.


5.1.2 Function key description
Key Name Function Description
Programming
Entry or escape of first-level menu.
Key

Enter Key Progressively enter menu and confirm parameters.

UP Increment
Progressively increase data or function codes.
Key
DOWN
Progressive decrease data or function codes.
Decrement Key
In parameter setting mode, press this button to
Right shift Key select the bit to be modified. In other modes,
cyclically displays parameters by right shift

Run Key Start to run the inverter in keypad control mode.

.27.
CHF100A series high performance universal inverter

Key Name Function Description


In running status, restricted by P7.04, can be used
STOP/RESET
to stop the inverter. When fault alarm, can be used
Key
to reset the inverter without any restriction.
Determined by Function Code P7.03:
0: Display status switching
1: Jog operation
Shortcut Key
2: Switch between forward and reverse
3: Clear the UP/DOWN settings.
4: Quick debugging mode

Combination Pressing the RUN and STOP/RST at the same



Key time can achieve inverter coast to stop.

5.1.3 Indicator light description


5.1.3.1 Function Indicator Light Description
Function indicator Description
Extinguished: stop status
RUN/TUNE Flickering: parameter autotuning status
Light on: operating status
Extinguished: forward operation
FWD/REV
Light on: reverse operation.
Extinguished: keypad control
LOCAL/REMOT Flickering: terminal control
Light on: communication control
Extinguished: normal operation status
TRIP
Flickering: overload pre-warning status
5.1.3.2 Unit Indicator Light Description
Unit indicator Description
Hz Frequency unit
A Current unit
V Voltage unit
RPM Rotating speed unit
% Percentage
5.1.3.3 Digital Display
.28.
CHF100A series high performance universal inverter

Have 5 digit LED , which can display all kinds of monitoring data and alarm codes such
as reference frequency, output frequency and so on.

5.2 Operation Process


5.2.1 Parameter setting
Three levels of menu are:
l Function code group (first-level);
l Function code (second-level);
l Function code value (third-level).
Remarks:
Press both the PRG/ESC and the DATA/ENT can return to the second-class menu from
the third-class menu. The difference is: pressing DATA/ENT will save the set parameters
into the control panel, and then return to the second-class menu with shifting to the next
function code automatically; while pressing PRG/ESC will directly return to the
second-class menu without saving the parameters, and keep staying at the current
function code.

Figure 5.2 Flow chart of parameter setting.


Under the third-class menu, if the parameter has no flickering bit, it means the function
code cannot be modified. The possible reasons could be:
l This function code is not modifiable parameter, such as actual detected parameter,
operation records and so on;

.29.
CHF100A series high performance universal inverter

l This function code is not modifiable in running status, but modifiable in stop status.
5.2.2 Fault reset
If the inverter has fault, it will prompt the related fault information. User can use
STOP/RST or according terminals determined by P5 Group to reset the fault. After fault
reset, the inverter is at stand-by state. If user does not reset the inverter when it is at fault
state, the inverter will be at operation protection state, and can not run.
5.2.3 Motor parameters autotuning
The procedure of motor parameter autotuning is as follows:
Firstly, choose the keypad command channel as the operation command channel
(P0.01).
And then input following parameters according to the actual motor parameters:
P2.01: motor rated power.
P2.02: motor rated frequency;
P2.03: motor rated speed;
P2.04: motor rated voltage;
P2.05: motor rated current;
Notice: the motor should be uncoupled with its load; otherwise, the motor parameters
obtained by autotuning may be not correct.
Set P0.16 to be 1, and for the detail process of motor parameter autotuning, please refer
to the description of Function Code P0.16. And then press RUN on the keypad panel,
the inverter will automatically calculate following parameter of the motor:
P2.06: motor stator resistance;
P2.07: motor rotor resistance;
P2.08: motor stator and rotor inductance;
P2.09: motor stator and rotor mutual inductance;
P2.10: motor current without load;
Then motor autotuning is finished.
5.2.4 Password setting
CHF100A series inverter offers user’s password protection function. When P7.00 is set
to be nonzero, it will be the user’s password, and after exiting function code edit mode, it
will become effective after 1 minute. If pressing the PRG/ESC again to try to access the
function code edit mode, “------” will be displayed, and the operator must input correct
user’s password, otherwise will be unable to access it.
If it is necessary to cancel the password protection function, just set P7.00 to be zero.

.30.
CHF100A series high performance universal inverter

5.2.5 Shortcut menu setting


Shortcut menu, in which parameters in common use can be programmed, provides a
quick way to view and modify function parameters. In the shortcut menu, a parameter
being displayed as “hP0.11” means the function parameter P0.11. Modifying parameters
in the shortcut menu has the same effect as doing at normal programming status.
Maximum 16 function parameters can be saved into the shortcut menu, and these
parameters can be added or deleted when P7.03 is set to be 0.

5.3 Running State


5.3.1 Power-on initialization
Firstly the system initializes during the inverter power-on, and LED displays “8.8.8.8.8.8”.
After the initialization is completed, the inverter is in stand-by status
5.3.2 Stand-by
At stop or running status, parameters of multi-status can be displayed. Whether or not to
display this parameter can be chosen through Function Code P7.06, P7.07 (Running
status display selection) and P7.08 (Stop status display selection) according to binary
bits, the detailed description of each bit please refer the function code description of
P7.06, P7.07 and P7.08.
In stop status, there are ten parameters which can be chosen to display or not. They are:
reference frequency, DC bus voltage, ON-OFF input status, open collector output status,
PID setting, PID feedback, analog input AI1 voltage, analog input AI2 voltage, HDI
frequency, step number of simple PLC and multi-step speed. Whether or not to display
can be determined by setting the corresponding binary bit of P7.08. Press the 》/SHIFT
to scroll through the parameters in right order. Press DATA/ENT + QUICK/JOG to scroll
through the parameters in left order.
5.3.3 Operation
In running status, there are nineteen running parameters which can be chosen to display
or not. They are: running frequency, reference frequency, DC bus voltage, output voltage,
output current, rotating speed, line speed, output power, output torque, PID setting, PID
feedback, ON-OFF input status, open collector output status, length value, count value,
step number of PLC and multi-step speed, voltage of AI1, voltage of AI2, high speed
pulse input HDI frequency. Whether or not to display can be determined by setting the
corresponding bit of P7.06, P7.07. Press the 》/SHIFT to scroll through the parameters
in right order. Press DATA/ENT + QUICK/JOG to scroll through the parameters in left
order.

.31.
CHF100A series high performance universal inverter

5.3.4 Fault
In fault status, inverter will display parameters of STOP status besides parameters of
fault status. Press the 》/SHIFT to scroll through the parameters in right order . Press
DATA/ENT + QUICK/JOG to to scroll through the parameters in left order.
CHF series inverter offers a variety of fault information. For details, see inverter faults
and their troubleshooting.

5.4 Shortcut Menu


Shortcut menu provides a quick way to view and modify function parameters.
Seting the P7.03 to be 4, the press QUICK/JOG, the inverter will search the parameter
which is different from the factory seting, save these parameters to be ready for checking.
The buffer length of shortcut menu is 32. So when the record data beyonds to 32, can
not display the overlength part. Press QUICK/JOG will be the shortcut debugging mode.
If the UICK/JOG display “NULLP”, It means the parameters is the same with the factory
setting. If want to return to last display, press QUICK/JOG.

.32.
CHF100A series high performance universal inverter

6. DETAILED FUNCTION DESCRIPTION


6.1 P0 Group--Basic Function
Function Setting Factory
Name Description
Code Range Setting
0: V/F control
Control
P0.00 1: Sensorless vector control 0~2 0
model
2: Torque control
0: V/F control: It is suitable for general purpose application such as pumps, fans etc.
1: Sensorless vector control: It is widely used for the application which requires high
torque at low speed, high speed accuracy, and quicker dynamic response, such as
machine tool, injection molding machine, centrifugal machine and wire-drawing machine,
etc.
2. Torque control: It is suitable for the application with low accuracy torque control, such
as wired-drawing.
Notice:
l The autotuning of motor parameters must be accomplished properly If you
use the sensorless vector control mode or Torque control mode. How to
autotuning of motor parameters please refer to page 36
l In order to achieve better control characteristic, the parameters of vector
control (P3 Group) should be adjusted.
Function Setting Factory
Name Description
Code Range Setting
0: Keypad (LED extinguished)
Run
1: Terminal (LED flickering)
P0.01 command 0~2 0
2: Communication (LED lights
source
on)
The control commands of inverter include: start, stop, forward run, reverse run, jog, fault
reset and so on.
0: Keypad (LED extinguished);
Both RUN and STOP/RST key are used for running command control. If Multifunction
key QUICK/JOG is set as FWD/REV switching function (P7.03 is set to be 1), it will be
used to change the rotating orientation. In running status, pressing RUN and
STOP/RST in the same time will cause the inverter coast to stop.

.33.
CHF100A series high performance universal inverter

1: Terminal (LED flickering)


The operation, including forward run, reverse run, forward jog, reverse jog etc. can be
controlled by multifunctional input terminals.
2: Communication (LED lights on)
The operation of inverter can be controlled by host through communication.
Function Setting Factory
Name Description
Code Range Setting
0: Valid, save UP/DOWN value
when power off
1: Valid, do not save
UP/DOWN UP/DOWN value when power
P0.02 0~3 0
setting off
2: Invalid
3: Valid during running, clear
when stop.
0: User can adjust the reference frequency by UP/DOWN. The value of UP/DOWN can
be saved when power off.
1: User can adjust the reference frequency by UP/DOWN, but the value of UP/DOWN
will not be saved when power off.
2: User can not adjust the reference frequency by UP/DOWN. The value of UP/DOWN
will be cleared.
3: User can only adjust the reference frequency by UP/DOWN during the inverter is
running. The value of UP/DOWN will be cleared when the inverter stops.
Notice:
l UP/DOWN function can be achieved by keypad (∧ and ∨) and
multifunctional terminals.
l Reference frequency can be adjusted by UP/DOWN.
l UP/DOWN has highest priority which means UP/DOWN is always active no
matter which frequency command source is.
l When the factory setting is restored (P0.17 is set to be 1), the value of
UP/DOWN will be cleared.
Function Setting Factory
Name Description
Code Range Setting
Maximum
P0.03 10.00~400.00Hz 10.00~400.00 50.00Hz
frequency

.34.
CHF100A series high performance universal inverter

Notice: The frequency reference should not exceed maximum frequency, and it is
the basis of ramping time of ACC/DEC.
Function Setting Factory
Name Description
Code Range Setting
Upper
P0.04 P0.05~P0.03 P0.05~P0.03 50.00Hz
frequency limit
Notice:
l Upper frequency limit should exceed than the maximum frequency
l Output frequency should not exceed upper frequency limit.
Function Setting Factory
Name Description
Code Range Setting
Lower
P0.05 frequency 0.00~P0.04 0.00~P0.04 0.00Hz
limit
Notice:
l Lower frequency limit should exceed than upper frequency limit (P0.04).
l If frequency reference is lower than P0.05, the action of inverter is
determined by P1.12. Please refer to description of P1.12.
Function Setting Factory
Name Description
Code Range Setting
Keypad
P0.06 reference 0.00~P0.03 0.00~P0.03 50.00Hz
frequency
When Frequency A command source is set to be Keypad, this parameter is the initial
value of inverter reference frequency.
Function Setting Factory
Name Description
Code Range Setting
0: Keypad
1: AI1
2. AI2
Frequency
3: HDI
P0.07 A command 0~7 0
4. Simple PLC
source
5: Multi-step speed
6: PID
7: Communication

.35.
CHF100A series high performance universal inverter

0: Keypad: Please refer to description of P0.06


1: AI1
2: AI2
The reference frequency is set by analog input. AI1 is -10V~10V voltage input terminal,
while AI2 is 0~10V/0(4)~20mA, which can be selected by J16. When AI2 is selected to
be 0~20mA, which corresponds with 5V.
3: HDI
The reference frequency is set by high speed pulse input.
Pulse specification: pulse voltage range 15~30V, and pulse frequency range 0.0~50.0
kHz. 100% of the setting inpluse corresponds with maximal frequency, while -100%
corresponds with minus maximal frequency.
4. Simple PLC
User can set reference frequency, hold time, running direction of each step and
acceleration/deceleration time between steps. For details, please refer to description of
PA group.
5. Multi-step speed
The reference frequency is determined by P5 and PA group. The selection of steps is
determined by combination of multi-step speed terminals.
Notice:
l Multi-step speed mode will enjoy priority in setting reference frequency if
P0.03 is not set to be 4 or 5. In this case, only step 1 to step 15 are available.
l If P0.03 is set to be 5, step 0 to step 15 can be realized.
l Jog has highest priority.
6. PID
The reference frequency is the result of PID adjustment. For details, please refer to
description of P9 group.
7. Communication
The reference frequency is set through RS485. For details, please refer to Modbus
protocol in Chapter 9.

Function Setting Factory


Name Description
Code Range Setting
Frequency 0:AI1
P0.08 B command 1:AI2 0~2 0
source 2:HDI

.36.
CHF100A series high performance universal inverter

For details, please refer to P0.07.


Function Setting Factory
Name Description
Code Range Setting
Scale of
0: Maximum frequency
P0.09 frequency B 0~1 0
1: Frequency A command
command
Notice: If set AI2 to be 0~20mA input, the relative voltage of 20mA is 5V. P0.09 is
used when the frequeny B is superimposed.
Function Setting Factory
Name Description
Code Range Setting
0: A
Frequency
1: B
P0.10 command 0~3 0
2: A+B
selection
3: Max(A, B)
This parameter can be used to select the reference frequency command.
0: Only frequency command source A is active.
1: Only Frequency command source B is active.
2: Both Frequency command source A and B are active.
Reference frequency = reference frequency A + reference frequency B.
3: Both Frequency command source A and B are active.
Reference frequency = Max (reference frequency A, reference frequency B).
Notice: Combination (0、1、2)can be switched by Multifunctional terminal S1~S7
Function Setting Factory
Name Description
Code Range Setting
Acceleration Depend
P0.11 0.1~3600.0s 0.1~3600.0
time 0 on model
Deceleration Depend
P0.12 0.1~3600.0s 0.1~3600.0
time 0 on model
Acceleration time is the time of accelerating from 0Hz to maximum frequency (P0.03).
Deceleration time is the time of decelerating from maximum frequency (P0.03) to 0Hz.
Please refer to following figure.

.37.
CHF100A series high performance universal inverter

Figure 6.1 Acceleration and deceleration time.


When the reference frequency is equal to the maximum frequency, the actual
acceleration and deceleration time will be equal to actual setting.
When the reference frequency is less than the maximum frequency, the actual
acceleration and deceleration time will be less than actual setting.
The actual acceleration (deceleration) time = setting ACC/DEC time* referrence
frequency/ maximum frequency.
1st group: P0.11, P0.12
2nd group: P8.00, P8.01
3rd group: P8.02, P8.03
4th group: P8.04, P8.05.
The acceleration and deceleration time can be selected by combination of
multifunctional ON-OFF input terminals.
Function Setting Factory
Name Description
Code Range Setting
Running 0: Forward
P0.13 direction 1: Reverse 0~2 0
selection 2: Forbid reverse
Notice: If the parameters are restored, the running direction will be back to its
original status.
Function Setting Factory
Name Description
Code Range Setting
Carrier Depend
P0.14 1.0~15.0kHz 1.0~15.0
frequency on model

.38.
CHF100A series high performance universal inverter

Figure 6.2 Effect of carrier frequency.


The following table is the relationship between power rating and carrier frequency.

Carrier f Highest Carrier f Lowest Carrier f Factory setting


Model ( kHz ) ( kHz ) ( kHz )
0.4kW~11kW 15 1.0 8
15kW~55kW 8 1.0 4
75kW~630kW 6 1.0 2
Carrier frequency will affect the noise of motor and the EMI of inverter.
If the carrier frequency is increased, it will cause better current wave, less harmonic
current and lower noise of motor.
Notice:
l The factory setting is optimal in most cases. Modification of this parameter
is not recommended.
l If the carrier frequency exceeds the factory setting, the inverter must be
derated because the higher carrier frequency will cause more switching loss,
higher temperature rise of inverter and stronger electromagnetic interference.
l If the carrier frequency is lower than the factory setting, it is possible to
cause less output torque of motor and more harmonic current.
Function Setting Factory
Name Description
Code Range Setting
AVR
P0.15 0~2 0~2 1
function
Notice: AVR function is automatical debugging of output voltage

.39.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
Motor 0: No action
P0.16 parameters 1: Rotation autotuning 0~2 0
autotuning 2: Static autotuning
0: No action: Forbidding autotuning.
1: Rotation autotuning:
u Do not connect any load to the motor when performing autotuning and ensure the
motor is in static status.
u Input the nameplate parameters of motor (P2.01 - P2.05) correctly before
performing autotuning. Otherwise the parameters detected by autotuning will be
incorrect; it may influence the performance of inverter.
u Set the proper acceleration and deceleration time (P0.11 and P0.12) according to
the motor inertia before performing autotuning. Otherwise it may cause
over-current and over-voltage fault during autotuning.
u The operation process is as follow:
a. Set P0.16 to be 1 then press the DATA/ENT, LED will display “-TUN-” and
flickers. During “-TUN-” is flickering, press the PRG/ESC to exit autotuning.
b. Press the RUN to start the autotuning, LED will display “TUN-0”.
c. After a few seconds the motor will start to run. LED will display “TUN-1” and
“RUN/TUNE” light will flicker.
d. After a few minutes, LED will display “-END-”. That means the autotuning is
finished and return to the stop status.
e. During the autotuning, press the STOP/RST will stop the autotuning.
Notice: Only keypad can control the autotuning. P0.12 will restore to 0
automatically when the autotuning is finished or cancelled.
2: Static autotuning:
u If it is difficult to disconnect the load, static autotuning is recommended.
u The operation process is the same as rotation autotuning except step c.
Notice: The Mutual inductance and current without load will not be detected by
static autotuning, if needed user should input suitable value according to
experience.

.40.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
0: No action
Restore
P0.17 1: Restore factory setting 0~2 0
parameters
2: Clear fault records
0: No action
1: Inverter restores all parameters to factory setting except P2 group.
2: Inverter clear all fault records.
This function code will restore to 0 automatically when complete the function operation.

6.2 P1 Group --Start and Stop Control


Function Setting Factory
Name Description
Code Range Setting
0: Start directly
P1.00 Start Mode 1: DC braking and start 0~2 0
2: Speed tracking and start
0: Start directly: Start the motor at the starting frequency determined by P1.01.
1: DC braking and start: Inverter will output DC current firstly and then start the motor at
the starting frequency. Please refer to description of P1.03 and P1.04. It is suitable for
the motor which have small inertia load and may reverse rotation when start.
2: Speed tracking and start: Inverter detects the rotation speed and direction of motor,
then start running to its reference frequency based on current speed. This can realize
smooth start of rotating motor with big inertia load when instantaneous power off.
Notice: It only applies on the inverter of 7.5kW and above.
Function Setting Factory
Name Description
Code Range Setting
Starting
P1.01 0.00~10.00Hz 0.00~10.00 0.00Hz
frequency
Hold time of
P1.02 starting 0.0~50.0s 0.0~50.0 0.0s
frequency
Notice:
l Set proper starting frequency can increase the starting torque.
l If the reference frequency is less than starting frequency, inverter will be at
stand-by status. The indicator of RUN/TUNE lights on, inverter has no output.

.41.
CHF100A series high performance universal inverter

l The starting frequency could be less than the lower frequency limit (P0.05).
l P1.01 and P1.02 take no effect during FWD/REV switching.

Figure 6.3 Starting diagram.


Function Setting Factory
Name Description
Code Range Setting
DC Braking
P1.03 current 0.0~150.0% 0.0~150.0 0.0%
before start
DC Braking
P1.04 time before 0.0~50.0s 0.0~50.0 0.0s
start
When inverter starts, it performs DC braking according to P1.03 firstly, then start to
accelerate after P1.04.
Notice:
l DC braking will take effect only when P1.00 is set to be 1.
l DC braking is invalid when P1.04 is set to be 0.
l The value of P1.03 is the percentage of rated current of inverter. The bigger
the DC braking current, the greater the braking torque.
Function Setting Factory
Name Description
Code Range Setting
Acceleration /
0: Linear
P1.05 Deceleration 0~1 0
1: reserved
mode
0: Linear: Output frequency will increase or decrease with fixed acceleration or
deceleration time.
1: Reserved
Notice: CHF100A inverter offers 4 groups of specific acceleration and deceleration

.42.
CHF100A series high performance universal inverter

time, which can be determined by the multifunctional ON-OFF input terminals (P5
Group).
Function Setting Factory
Name Description
Code Range Setting
0: Deceleration to stop
P1.06 Stop mode 0~1 0
1: Coast to stop
0: Deceleration to stop
When the stop command takes effect, the inverter decreases the output frequency
according to P1.05 and the defined deceleration time till stop.
1: Coast to stop
When the stop command takes effect, the inverter blocks the output immediately. The
motor coasts to stop by its mechanical inertia.
Function Setting Factory
Name Description
Code Range Setting
Starting
P1.07 frequency of 0.00~P0.03 0.00~P0.03 0.00Hz
DC braking
Waiting time
P1.08 before DC 0.0~50.0s 0.0~50.0 0.0s
braking
DC braking
P1.09 0.0~150.0% 0.0~150.0 0.0%
current
DC braking
P1.10 0.0~50.0s 0.0~50.0 0.0s
time
Starting frequency of DC braking: Start the DC braking when running frequency reaches
starting frequency determined by P1.07.
Waiting time before DC braking: Inverter blocks the output before starting the DC braking.
After this waiting time, the DC braking will be started so as to prevent over-current fault
caused by DC braking at high speed.
DC braking current: The value of P1.09 is the percentage of rated current of inverter. The
bigger the DC braking current is, the greater the braking torque is.
DC braking time: The time used to perform DC braking. If the time is 0, the DC braking
will be invalid.

.43.
CHF100A series high performance universal inverter

Figure 6.4 DC braking diagram.


Function Setting Factory
Name Description
Code Range Setting
Dead time of
P1.11 0.0~3600.0s 0.0~3600.0 0.0s
FWD/REV
Set the hold time at zero frequency in the transition between forward and reverse
running.
It is shown as following figure:

Figure 6.5 FWD/REV dead time diagram.


Function Setting Factory
Name Description
Code Range Setting
Action when
running 0: Running at the lower
frequency is frequency limit
P1.12 0~2 0
less than 1: Stop
lower 2: Stand-by
frequency limit

.44.
CHF100A series high performance universal inverter

0: Running at the lower frequency limit (P0.05): The inverter runs at P0.05 when the
running frequency is less than P0.05.
1: Stop: This parameter is used to prevent motor running at low speed for a long time.
2: Stand-by: Inverter will Coast to stop when the running frequency is less than P0.05.
When the reference frequency is higher than or equal to P0.05 again, the inverter will
start to run automatically.
Function Setting Factory
Name Description
Code Range Setting
Delay time
P1.13 0.0~3600.0s 0.0~3600.0 0.0s
for restart
Restart after 0: Disabled
P1.14 0~1 0
power off 1: Enabled
0: Disabled: Inverter will not automatically restart when power on again until run
command takes effect.
1: Enabled: When inverter is running, after power off and power on again, if run
command source is key control (P0.01=0) or communication control (P0.01=2), inverter
will automatically restart after delay time determined by P1.14; if run command source is
terminal control (P0.01=1), inverter will automatically restart after delay time determined
by P1.14 only if FWD or REV is active.
Notice:
l If P1.14 is set to be 1, it is recommended that start mode should be set as
speed tracing mode (P1.00=2).
l This function may cause the inverter restart automatically, please be
cautious.
Function Setting Factory
Name Description
Code Range Setting
Waiting time
P1.15 0.0~3600.0s 0.0~3600.0s 0.0
of restart
Notice: Valid when P1.14=1
Function Setting Factory
Name Description
Code Range Setting
Terminal
function 0: Disabled
P1.16 0~1 0
examined 1: Enabled
when power is

.45.
CHF100A series high performance universal inverter

on

Notice:
l This function only takes effect if run command source is terminal control.
l If P1.15 is set to be 0, when power on, inverter will not start even if FWD/REV
terminal is active, until FWD/REV terminal disabled and enabled again.
l If P1.15 is set to be 1, when power on and FWD/REV terminal is active,
inverter will start automatically.
l This function may cause the inverter restart automatically, please be
cautious.

Function Setting Factory


Name Description
Code Range Setting
P1.17~P1.19 Reversed

6.3 P2 Group--Motor Parameters


Function Setting Factory
Name Description
Code Range Setting
Inverter 0: G model
P2.00 0~1 0
model 1: P model
0: G model: Applicable to constant torque load.
1: P model: Applicalbe to constant power load.
Function Setting Factory
Name Description
Code Range Setting
Motor rated Depend
P2.01 0.4~3000.0kW 0.4~3000.0
power on model
Motor rated
P2.02 10Hz~P0.03 10~P0.03 50.00Hz
frequency
Motor rated Depend
P2.03 0~36000rpm 0~36000
speed on model
Motor rated Depend
P2.04 0~800V 0~800V
voltage on model
Motor rated Depend
P2.05 0.8~6000.0A 0.8~6000.0
current on model
Notice:
l In order to achieve superior performance, please set these parameters

.46.
CHF100A series high performance universal inverter

according to motor nameplate, and then perform autotuning.


l The power rating of inverter should match the motor. If the bias is too big,
the control performances of inverter will be deteriorated distinctly.
l Reset P2.01 can initialize P2.06~P2.10 automatically.
Function Setting Factory
Name Description
Code Range Setting
Motor stator Depend
P2.06 0.001~65.535Ω 0.001~65.535
resistance on model
Motor rotor Depend
P2.07 0.001~65.535Ω 0.001~65.535
resistance on model
Motor
Depend
P2.08 leakage 0.1~6553.5mH 0.1~6553.5
on model l
inductance
Motor mutual Depend
P2.09 0.1~6553.5mH 0.1~6553.5
inductance on model
Current Depend
P2.10 0.01~655.35A 0.01~655.35
without load on model
After autotuning, the value of P2.06~P2.09 will be automatically updated.
Notice: Do not change these parameters, otherwise it may deteriorate the control
performance of inverter.

6.4 P3 Group—Vector Control


Function Setting Factory
Name Description
Code Range Setting
ASR
P3.00 proportional 0~100 0~100 20
gain Kp1
ASR integral
P3.01 0.01~10.00s 0.01~10.00 0.50s
time Ki 1
ASR switching
P3.02 0.00Hz~P3.05 0.00~P3.05 5.00Hz
point 1
ASR
P3.03 proportional 0~100 0~100 25
gain Kp2

.47.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
ASR integral
P3.04 0.01~10.00s 0.01~10.00 1.00s
time Ki 2
ASR switching
P3.05 P3.02~P0.03 P3.02~P0.03 10.00Hz
point 2
P3.00~P3.05 are only valid for vector control and torque control and invalid for V/F
control. Through P3.00~P3.05, user can set the proportional gain K p and integral time Ki
of speed regulator (ASR), so as to change the speed response characteristic. ASR's
structure is shown in following figure.

Figure 6.6 ASR diagram.


P3.00 and P3.01 only take effect when output frequency is less than P3.02. P3.03 and
P3.04 only take effect when output frequency is greater than P3.05. When output
frequency is between P3.02 and P3.05, Kp and KI are proportional to the bias between
P3.02 and P3.05. For details, please refer to following figure.

Figure 6.7 PI parameter diagram.


The system's dynamic response can be faster if the proportion gain K p is increased;
However, if Kp is too large, the system tends to oscillate.
The system dynamic response can be faster if the integral time Ki is decreased;
However, if Ki is too small, the system becomes overshoot and tends to oscillate.
P3.00 and P3.01 are corresponding to Kp and Ki at low frequency, while P3.03 and P3.04
are corresponding to K p and Ki at high frequency. Please adjust these parameters
according to actual situation. The adjustment procedure is as follow:

.48.
CHF100A series high performance universal inverter

u Increase the proportional gain (Kp) as far as possible without creating oscillation.
u Reduce the integral time (Ki) as far as possible without creating oscillation.
For more details about fine adjustment, please refer to description of P9 group.
Function Setting Factory
Name Description
Code Range Setting
Slip
P3.06 compensation 50.0%~200.0% 50~200 100%
rate of VC
The parameter is used to adjust the slip frequency of vector control and improve the
precision of speed control. Properly adjust this parameter can effectively restrain the
static speed bias.
Function Setting Factory
Name Description
Code Range Setting
Torque upper Depend
P3.07 0.0~200.0% 0~200
limit on model
Notice:
l 100% setting corresponding to rated current. G model : 150.0%;P model:
120.0%.
l Under torque control, P3.07 and P3.09 are all related with torque setting.
Function Setting Factory
Name Description
Code Range Setting
0: Keypad (P3.09)
1:AI1
Torque
2:AI2
P3.08 setting 0~5 0
3:HDI
source
4:Multi-step speed
5:Communication
0: Keypad (P3.09)
1:AI1
2:AI2
3:HDI
4:Multi-step speed
5:Communication
1~5: Torque control is valid, which defines the torque setting source. When the torque
setting is minus, the motor will reverse.

.49.
CHF100A series high performance universal inverter

Under speed control model, output torque matches load torque automatically, but limited
by P3.07.
Under torque control model, output torque is limited by upper and lower frequency limit.
Notice:
l speed control and torque control can be switched by using multi-function
input terminals.
l 1~5:100% corresponding to twice of rated current of inverter.
l When inverter decelerate to stop, Torque control model is switched to speed
control mode automatically
Function Factory
Name Description Setting Range
Code Setting
Keypad
P3.09 torque -200.0%~200.0% -200.0%~200.0% 50.0%
setting
0: Keypad (P0.04)
Upper 1: AI1
frequency 2: AI2
P3.10 0~5 0
setting 3: HDI
source 4: Multi-step
5: Communication
Notice: 1~4 100% Corresponding to maximum frequency.

6.5 P4 Group—V/F Control


Function Setting Factory
Name Description
Code Range Setting
0:Linear V/F curve
1: User-defined curve
2: Torque_stepdown curve
V/F curve (1.3 order)
P4.00 0~4 0
selection 3: Torque_stepdown curve
(1.7 order)
4: Torque_stepdown curve
(2.0 order)
0: Linear V/F curve. It is applicable for normal constant torque load.
1: User-defined curve. It can be defined through setting (P4.03~P4.08).

.50.
CHF100A series high performance universal inverter

2~4: Torque_stepdown curve. It is applicable for variable torque load, such as blower,
pump and so on. Please refer to following figure.
Notice:Vb= Motor rated voltage Fb= Motor rated frequency.

Figure 6.8 V/F curve.


Function Setting Factory
Name Description
Code Range Setting
0.0%: (auto)
P4.01 Torque boost 0.0~10.0 0.0%
0.1%~10.0%
Torque boost 0.0%~50.0% (motor rated
P4.02 0.0~50.0 20.0%
cut-off frequency)
Torque boost will take effect when output frequency is less than cut-off frequency of
torque boost (P4.02). Torque boost can improve the torque performance of V/F control at
low speed.
The value of torque boost should be determined by the load. The heavier the load, the
larger the value.
Notice: This value should not be too large, otherwise the motor would be
over-heat or the inverter would be tripped by over-current or over-load.
If P4.01 is set to be 0, the inverter will boost the output torque according to the load
automatically. Please refer to following diagram.

.51.
CHF100A series high performance universal inverter

Figure 6.9 Torque boost by hand.


Function Factory
Name Description Setting Range
Code Setting
V/F
P4.03 0.00Hz~P4.05 0.00~P4.05 0.00Hz
frequency 1

P4.04 V/F voltage 1 0.0%~100.0% 0.0~100.0 0.0%

V/F
P4.05 P4.03~P4.07 P4.03~ P4.07 0.00Hz
frequency 2

P4.06 V/F voltage 2 0.0%~100.0% 0.0~100.0 0.0%

V/F
P4.07 P4.05~P2.02 P4.05~ P2.02 0.00Hz
frequency 3

P4.08 V/F voltage 3 0.0%~100.0% 0.0~100.0 0.0%

This function is only active when P4.00 is set to be 1. P4.03~P4.08 are used to set the
user-defined V/F curve. The value should be set according to the load characteristic of
motor.
Notice:
l 0<V1<V2<V3<rated voltage.
l 0<f1<f2<f3<rated frequency.
l The voltage corresponding to low frequency should not be set too high,
otherwise it may cause motor overheat or inverter fault.

Figure 6.10 V/F curve setting diagram.

.52.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
Slip
P4.09 compensation 0.00~200.0% 0.00~200.00 0.0%
limit
The slip compensation function calculates the torque of motor according to the output
current and compensates for output frequency. This function is used to improve speed
accuracy when operating with a load. P4.09 sets the slip compensation limit as a
percentage of motor rated slip, the slip compensation limit is calculated as the formula:
P4.09=fb-n*p/60
Fb= Motor rated frequency (P2.02)
N= Motor rated speed (P2.03)
P= Motor poles
Function Setting Factory
Name Description
Code Range Setting
Auto energy
0: Disabled
P4.10 saving 0~1 0
1: Enabled
selection
When P4.10 is set to be 1, while there is a light load such as pumps or fans, it will reduce
the inverter output voltage and save energy.
Function Setting Factory
Name Description
Code Range Setting
Low-frequency
threshold of
P4.11 0~10 0~10 2
restraining
oscillation
High-frequency
threshold of
P4.12 0~10 0~10 0
restraining
oscillation
Boundary of
P4.13 restraining 0.0~P3.03 0.0~P3.03 30Hz
oscillation
P4.11~P4.12 are only valid in the V/F control mode, When set P4.11 and P4.12 to be 0, the
restraining oscillation is invalid. While set the values to be 1~3 will have the effect of
.53.
CHF100A series high performance universal inverter

restraining oscillation.When the running frequency is lower than P4.13, P4.11 is valid,
when the running frequency higher than P4.13, P4.12 is valid.
6.6 P5 Group--Input Terminals
Function Setting Factory
Name Description
Code Range Setting
0: High speed pulse input
P5.00 HDI selection 0~1 0
1: ON-OFF input
S1 terminal Programmable multifunctional
P5.01 0~39 1
function terminal
S2 terminal Programmable multifunctional
P5.02 0~39 4
function terminal
S3 terminal Programmable multifunctional
P5.03 0~39 7
function terminal
S4 terminal Programmable multifunctional
P5.04 0~39 0
function terminal
S5 terminal Programmable multifunctional
P5.05 0~39 0
function terminal
P5.06 S6 terminal Programmable multifunctional
0~39 0
function terminal
P5.07 S7 terminal Programmable multifunctional
0~39 0
function terminal
P5.08 HDI terminal Programmable multifunctional
0-39 0
function terminal
Notice: P5.08 is only used when P5.00 is set to be 1.
The meaning of each setting is shown in following table.
Setting
Function Description
value
Please set unused terminals to be invalid to avoid
0 Invalid
malfunction
1 Forward
Please refer to description of P5.10.
2 Reverse
3 3-wire control Please refer to description of P5.10.
4 Jog forward
Please refer to description of P8.06~P8.08.
5 Jog reverse
6 Coast to stop The inverter blocks the output immediately. The motor
.54.
CHF100A series high performance universal inverter

Setting
Function Description
value
coasts to stop by its mechanical inertia.
Resets faults that have occurred. It has the same function
7 Reset fault
as STOP/RST.
When this terminal takes effect, inverter decelerates to
stop and save current status, such as PLC, traverse
8 Pause running
frequency and PID. When this terminal takes no effect,
inverter restores the status
External fault Stop the inverter and output an alarm when a fault occurs
9
input in a peripheral device.
The reference frequency of inverter can be adjusted by UP

10 Up command command and DOWN command.

DOWN
11
command

Clear
12
UP/DOWN Use this terminal to clear UP/DOWN setting. Please refer
to description of P0.02.
Switch between
13 P3.04
A and B A B A+B
Terminal action
Switch between
14 13 valid B A
A and A+B
14 valid A+B A
Switch between
15 15 valid A+B B
B and A+B
Multi-step speed
16
reference1
16 steps speed control can be realized by the combination
Multi-step speed
17 of these four terminals. For details, please refer to:
reference 2
Multi-step speed reference terminal status and according
Multi-step speed
18 step value table:
reference 3
19 Multi-step speed

.55.
CHF100A series high performance universal inverter

Setting
Function Description
value
reference 4
Multi-step speed Keep current step unchanged no matter what the input
20
pause status of four multi-step speed terminals is.
4 groups of ACC/DEC time can be selected by the
combination of these two terminals.
ACC/DEC time
21 ACC/DEC time ACC/DEC time
selection1 ACC/DEC time
selection 2 selection 1

ACC/DEC time 0
OFF OFF
(P0.11、P0.12)
ACC/DEC time 1
OFF ON
(P8.00、P8.01)
ACC/DEC time
22 ACC/DEC time 2
selection 2 ON OFF
(P8.02、P8.03)
ACC/DEC time 3
ON ON
(P8.04、P8.05)
When simple PLC stops, the status of PLC such as
Reset simple
23 running step, running time and running frequency will be
PLC when stop
cleared when this terminal is enabled.
Inverter runs at zero frequency and PLC pauses the timing
Pause simple when this terminal is enabled. If this terminal is disabled,
24
PLC inverter will start and continue the PLC operation from the
status before pause.
PID adjustment will be paused and inverter keeps output
25 Pause PID
frequency unchanged.
Inverter keeps output frequency unchanged. If this
Pause traverse
26 terminal is disabled, inverter will continue traverse
operation
operation with current frequency.
Reset traverse Reference frequency of inverter will be forced as center
27
operation frequency of traverse operation.
28 Reset counter Clear the value of counter.

29 Forbid torque Torque control is forbided and switch inverter to run in

.56.
CHF100A series high performance universal inverter

Setting
Function Description
value
control mode speed control mode.
Forbid the ACC/DEC is invalid and maintains output frequency if it is
30 function of enabled.
ACC/DEC
The pulse input terminal of internal counter. Maximum
31 Counter input
pulse frequency: 200Hz.
UP/DOWN UP/DOWN setting is invalid but will not be cleared. When
32 invalid this terminal is disabled, UP/DOWN value before will be
temporarily valid again.
33~39 Reserved Reserved
Multi-step speed reference terminal status and according step value table:
Multi-step Multi-step Multi-step Multi-step
Terminal
speed speed speed speed
Step
reference1 reference2 reference3 reference4
0 OFF OFF OFF OFF
1 ON OFF OFF OFF
2 OFF ON OFF OFF
3 ON ON OFF OFF
4 OFF OFF ON OFF
5 ON OFF ON OFF
6 OFF ON ON OFF
7 ON ON ON OFF
8 OFF OFF OFF ON
9 ON OFF OFF ON
10 OFF ON OFF ON
11 ON ON OFF ON
12 OFF OFF ON ON
13 ON OFF ON ON
14 OFF ON ON ON
15 ON ON ON ON

.57.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
AI1 lower limit
P5.13 corresponding -100.0%~100.0% -100.0~100.0 0.0%
setting

P5.14 AI1 upper limit -10.00V~10.00V -10.00~10.00 10.00V

AI1 upper limit


P5.15 corresponding -100.0%~100.0% -100.0~100.0 100.0%
setting
AI1 filter time
P5.16 0.00s~10.00s 0.00~10.00 0.10s
constant
These parameters determine the relationship between analog input voltage and the
corresponding setting value. When the analog input voltage exceeds the range between
lower limit and upper limit, it will be regarded as the upper limit or lower limit.
The analog input AI1 can only provide voltage input, and the range is -10V~10V.
For different applications, the corresponding value of 100.0% analog setting is different.
For details, please refer to description of each application.
Notice: AI1 lower limit must be less or equal to AI1 upper limit.

Figure 6.15 Relationship between AI and corresponding setting.


AI1 filter time constant is effective when there are sudden changes or noise in the analog
input signal. Responsiveness decreases as the setting increases.
Function Setting Factory
Name Description
Code Range Setting
P5.17 AI2 lower limit 0.00V~10.00V 0.00~10.00 0.00V
AI2 lower limit
P5.18 corresponding -100.0%~100.0% -100.0~100.0 0.0%
setting
.60.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting

P5.19 AI2 upper limit 0.00V~10.00V 0.00~10.00 10.00V

AI2 upper limit


P5.20 corresponding -100.0%~100.0% -100.0~100.0 100.0%
setting
AI2 filter time
P5.21 0.00s~10.00s 0.00~10.00 0.10s
constant
Please refer to description of AI1. When AI2 is set as 0~20mA current input, the
corresponding voltage range is 0~5V.
Function Setting Factory
Name Description
Code Range Setting
HDI lower
P5.22 0.0 kHz ~50.0kHz 0.0~50.0 0.0kHz
limit
HDI lower
limit
P5.23 -100.0%~100.0% -100.0~100.0 0.0%
corresponding
setting
HDI upper
P5.24 0.0 kHz ~50.0kHz 0.0~50.0 50.0kHz
limit
HDI upper
limit
P5.25 -100.0%~100.0% -100.0~100.0 100.0%
corresponding
setting
HDI filter time
P5.26 0.00s~10.00s 0.00~10.00 0.10s
constant
The description of P5.22~P5.26 is similar to AI1.

6.7 P6 Group--Output Terminals


Function Setting Factory
Name Description
Code Range Setting
HDO
P6.00 ON-OFF output 1 1
selection
ON-OFF output: Please refer to description of P6.01.
.61.
CHF100A series high performance universal inverter

Notice: The output of HDO terminal is OC (open collector) output.


Function Setting Factory
Name Description
Code Range Setting
HDO ON-OFF
P6.01 output Open-collector output 0~20 1
selection

Relay 1 output
P6.02 Relay output 0~20 4
selection

Relay 2 output
selection
P6.03 Relay output 0~20 0
(4.0kW and
above)

OC/Relay output functions are indicated in the following table:


Setting
Function Description
Value
0 No output Output terminal has no function.
1 Running ON: Run command is ON or voltage is being output.
2 Run forward ON: During forward run.
3 Run reverse ON: During reverse run.
4 Fault output ON: Inverter is in fault status.
5 FDT reached Please refer to description of P8.21, P8.22.
Frequency
6 Please refer to description of P8.23.
reached
Zero speed ON: The running frequency of inverter and setting
7
running frequency are zero.

Preset count
8 Please refer to description of P8.18.
value reached

Specified count
9 Please refer to description of P8.19.
value reached

overload
10 pre-warming of Please refer to description of Pb.04~Pb.06
inverter

.62.
CHF100A series high performance universal inverter

Setting
Function Description
Value
Simple PLC step After simple PLC completes one step, inverter will
11
completed output ON signal for 500ms.
PLC cycle After simple PLC completes one cycle, inverter will
12
completed output ON signal for 500ms.
Running time ON: The accumulated running time of inverter
13
reached reaches the value of P8.20.
Upper frequency
14 ON: Running frequency reaches the value of P0.04.
limit reached
Lower frequency
15 ON: Running frequency reaches the value of P0.05.
limit reached
16 Ready ON: Inverter is ready (no fault, power is ON).
17~20 Reserved Reserved

Function Setting Factory


Name Description
Code Range Setting
AO1 function
P6.04 Multifunctional analog output 0~10 0
selection
AO2 function
P6.05 Multifunctional analog output 0~10 0
selection

P6.06 Reserved Reserved 0~10 0

AO output functions are indicated in the following table:


Setting
Function Range
Value
0 Running frequency 0~maximum frequency (P0.03)
1 Reference frequency 0~ maximum frequency (P0.03)
2 Running speed 0~2* rated synchronous speed of motor
3 Output current 0~2* inverter rated current
4 Output voltage 0~1.5* inverter rated voltage
5 Output power 0~2* rated power
6 Setting torque 0~2*rated current of motor
7 Output torque 0~2*rated current of motor

.63.
CHF100A series high performance universal inverter

Setting
Function Range
Value
8 AI1 voltage -10~10V
9 AI2 voltage/current 0~10V/0~20mA
10 HDI frequency 0.1~50.0kHz

Function Setting Factory


Name Description
Code Range Setting
P6.07 AO1 lower limit 0.0%~100.0% 0.0~100.0 0.0%
AO1 lower limit
P6.08 corresponding 0.00V ~10.00V 0.00~10.00 0.00V
output
AO1 upper
P6.09 0.0%~100.0% 0.0~100.0 100.0%
limit
AO1 upper
limit
P6.10 0.00V ~10.00V 0.00~10.00 10.00V
corresponding
output
These parameters determine the relationship between analog output voltage/current and
the corresponding output value. When the analog output value exceeds the range
between lower limit and upper limit, it will output the upper limit or lower limit.
When AO1 is current output, 1mA is corresponding to 0.5V.
For different applications, the corresponding value of 100.0% analog output is different.
For details, please refer to description of each application.

Figure 6.16 Relationship between AO and corresponding setting.

.64.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting

P6.11 AO2 lower limit 0.0~100.0% 0.0~100.0 0.0%

AO2 lower limit


P6.12 corresponding 0~10.00V 0~10.00 0.00V
output
AO2 upper
P6.13 0.0~100.0% 0.0~100.0 100.0%
limit
AO2 upper
limit
P6.14 0.00~10.00V 0.00~10.00 10.00V
corresponding
output

.65.
CHF100A series high performance universal inverter

6.8 P7 Group—Display Interface


Function Setting Factory
Name Description
Code Range Setting
User
P7.00 0~65535 0~65535 0
password
The password protection function will be valid when P7.00 is set to be any nonzero data.
When P7.00 is set to be 00000, user’s password set before will be cleared and the
password protection function will be disabled.
After the password has been set and becomes valid, the user can not access menu if the
user’s password is not correct. Only when a correct user’s password is input, the user
can see and modify the parameters. Please keep user’s password in mind.
Function Setting Factory
Name Description
Code Range Setting
P7.01 Reserved 0~1 0
P7.02 Reserved 0~1 0
0: Display status switching
QUICK/JOG 1: Jog
P7.03 function 2: FWD/REV switching 0~4 0
selection 3: Clear UP/DOWN setting
4. Quick debugging mode
QUICK/JOG is a multifunctional key, whose function can be defined by the value
0. Display status switching
1: Jog: Press QUICK/JOG, the inverter will jog.
2: FWD/REV switching: Press QUICK/JOG, the running direction of inverter will reverse.
It is only valid if P0.02 is set to be 0.
3: Clear UP/DOWN setting: Press QUICK/JOG, the UP/DOWN setting will be cleared.
4. Quick debugging mode
Function Setting Factory
Name Description
Code Range Setting
0: Valid when keypad control
(P0.02=0)
STOP/RST
1: Valid when keypad or
P7.04 function 0~3 0
terminal control (P0.02=0 or
selection
1)
2: Valid when keypad or

.66.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
communication control
(P0.02=0 or 2)
3: Always valid
Notice:
l The value of P7.04 only determines the STOP function of STOP/RST.
l The RESET function of STOP/RST is always valid.
Function Setting Factory
Name Description
Code Range Setting
0: Preferential to external
keypad
Keypad 1: Both display, only external
P7.05 display key valid. 0~3 0
selection 2: Both display, only local key
valid.
3: Both display and key valid.
0: When external keypad exists, local keypad will be invalid.
1: Local and external keypad display simultaneously, only the key of external keypad is
valid.
2: Local and external keypad display simultaneously, only the key of local keypad is
valid.
3: Local and external keypad display simultaneously, both keys of local and external
keypad are valid.
Notice: This function should be used cautiously, otherwise it may cause
malfunction.
Function Setting Factory
Name Description
Code Range Setting
Running
P7.06 status display 0~0xFFFF 0~0xFFFF 0x07FF
selection 1
Running
P7.07 status display 0~0xFFFF 0~0xFFFF 0x0000
selection 2
P7.06 and P7.07 define the parameters that can be displayed by LED in running status.

.67.
CHF100A series high performance universal inverter

If Bit is 0, the parameter will not be displayed; If Bit is 1, the parameter will be displayed.
Press 》/SHIFT to scroll through these parameters in right order . Press DATA/ENT +
QUICK/JOG to scroll through these parameters in left order.
The display content corresponding to each bit of P7.06 is described in the following
table:
BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0

Output Line Rotation Output Output DC bus Reference Running


power speed speed current voltage voltage frequency frequency

BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8


Step No. Torque Output Input
Count PID PID Output
of PLC or setting terminal terminal
value feedback preset torque
multi-step value status status
For example, if user wants to display output voltage, DC bus voltage, Reference
frequency, Output frequency, Output terminal status, the value of each bit is as the
following table:
BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
0 0 0 0 1 1 1 1

BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8

0 0 0 1 0 0 0 0
The value of P7.06 is 100Fh.
Notice: I/O terminal status is displayed in decimal.
For details, please refer to description of P7.21 and P7.22.
The display content corresponding to each bit of P7.07 is described in the following
table:
BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
Load Load
HDI
Reserved Reserved Reserved percentage percentage AI2 AI1
frequency
of inverter of motor
BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8
Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved

.68.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
Stop status
P7.08 display 0~0xFFFF 0~0xFFFF 0x00FF
selection
P7.08 determines the display parameters in stop status. The setting method is similar
with P7.06.
The display content corresponding to each bit of P7.08 is described in the following
table:
BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
Output Input
PID PID DC bus Reference
AI2 AI1 terminal terminal
feedback preset voltage frequency
status status

BIT15 BIT14 BIT13 BIT12 BIT11 BIT10 BIT9 BIT8

Torque Step No. of


HDI
Reserved Reserved Reserved Reserved Reserved setting PLC or
frequency
value multi-step

Function Setting Factory


Name Description
Code Range Setting
Coefficient of
P7.09 0.1~999.9% 0.1~999.9 100.0%
rotation speed
This parameter is used to calibrate the bias between actual mechanical speed and
rotation speed. The formula is as below:
Actual mechanical speed = 120 * output frequency *P7.09 / Number of poles of motor.
Function Setting Factory
Name Description
Code Range Setting
Coefficient of
P7.10 0.1~999.9% 0.1~999.9 1.0%
line speed
This parameter is used to calculate the line speed based on actual mechanical speed.
The formula is as below:
Line speed = actual mechanical speed * P7.10

.69.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
Rectify
P7.11 module 0~100.0℃
temperature
IGBT module
P7.12 0~100.0℃
temperature
Software
P7.13
version
Inverter rated Depends
P7.14 0-3000KW
power on model
Inverter rated Depends
P7.15 0.0-6000A
current on model
Accumulated
P7.16 0~65535h
running time
Rectify module temperature: Indicates the temperature of rectify module. Overheat
protection point of different model may be different.
IGBT module temperature: Indicates the temperature of IGBT module. Overheat
protection point of different model may be different.
Software version: Indicates current software version of DSP.
Accumulated running time: Displays accumulated running time of inverter.
Notice: Above parameters are read only.
Function Setting Factory
Name Description
Code Range Setting
Third latest
P7.17 0~25
fault type
Second latest
P7.18 0~25
fault type
Latest fault
P7.19 0~25
type
These parameters record three recent fault types. For details, please refer to description
of chapter 7.

.70.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
Output
frequency
P7.20 Output frequency at current fault.
at current
fault
Output
current at
P7.21 Output current at current fault.
current
fault
DC bus
voltage at
P7.22 DC bus voltage at current fault.
current
fault
This value records ON-OFF input terminal
status at current fault. The meaning of
each bit is as below:
Input
BIT7 BIT6 BIT5 BIT4
terminal
HDI S7 S6 S5
P7.23 status at
BIT3 BIT2 BIT1 BIT0
current
S4 S3 S2 S1
fault
1 indicates corresponding input terminal is
ON, while 0 indicates OFF. Notice: This
value is displayed as decimal.
This value records output terminal status at
current fault. The meaning of each bit is as
Output
below:
terminal
BIT3 BIT2 BIT1 BIT0
P7.24 status at
Reserved RO2 RO1 HDO
current
1 indicates corresponding output terminal
fault
is ON, while 0 indicates OFF. Notice: This
value is displayed as decimal.

.71.
CHF100A series high performance universal inverter

6.9 P8 Group--Enhanced Function


Function Setting Factory
Name Description
Code Range Setting
Acceleration Depend
P8.00 0.1~3600.0s 0.1~3600.0
time 1 on model
Deceleration Depend
P8.01 0.1~3600.0s 0.1~3600.0
time 1 on model
Acceleration Depend
P8.02 0.1~3600.0s 0.1~3600.0
time 2 on model
Deceleration Depend
P8.03 0.1~3600.0s 0.1~3600.0
time 2 on model
Acceleration Depend
P8.04 0.1~3600.0s 0.1~3600.0
time 3 on model
Deceleration Depend
P8.05 0.1~3600.0s 0.1~3600.0
time 3 on model
For details, please refer to description of P0.11 and P0.12.
Function Setting Factory
Name Description
Code Range Setting
P8.06 Jog reference 0.00~P0.03 0.00~P0.03 5.00hz
Jog
Depand
P8.07 acceletation 0.1-3600.0s 0.1~3600.0
on Model
time
Jog
Depand
P8.08 deceleration 0.1~3600.0s 0.1~3600.0
on Model
time
Skip
P8.09 0.00~P0.03 0.00~P0.03 0.00hz
Frequency 1
Skip
P8.10 0.00~P0.03 0.00~P0.03 0.00hz
Frequency 2
Skip
P8.11 frequency 0.00~P0.03 0.00~P0.03 0.00hz
bandwidth
By means of setting skip frequency, the inverter can keep away from the mechanical
resonance with the load. P8.09 and P8.10 are centre value of frequency to be skipped.
.72.
CHF100A series high performance universal inverter

Notice:
l If P8.11 is 0, the skip function is invalid.
l If both P8.09 and P8.10 are 0, the skip function is invalid no matter what
P8.11 is.
l Operation is prohibited within the skip frequency bandwidth, but changes
during acceleration and deceleration are smooth without skip.
The relation between output frequency and reference frequency is shown in following
figure.

Figure 6.17 Skip frequency diagram.


Function Setting Factory
Name Description
Code Range Setting
Traverse
P8.12 0.0~100.0% 0.0~100.0 0.0%
amplitude
Jitter
P8.13 0.0-50.0% 0.0-50.0 0.0%
frequency
Rise time of
P8.14 0.1-3600.0s 0.1-3600.0 5.0s
traverse
Fall time of
P8.15 0.1-3600.0s 0.1-3600.0 5.0s
traverse
Traverse operation is widely used in textile and chemical fiber industry. The typical
application is shown in following figure.

.73.
CHF100A series high performance universal inverter

Figure 6.18 Traverse operation diagram.


Center frequency (CF) is reference frequency.
Traverse amplitude (AW) =center frequency (CF) * P8.12%
Jitter frequency = traverse amplitude (AW) * P8.13%
Rise time of traverse: Indicates the time rising from the lowest traverse frequency to the
highest traverse frequency.
Fall time of traverse: Indicates the time falling from the highest traverse frequency to the
lowest traverse frequency.
Notice: P8.12 determines the output frequency range which is as below: (1-P8.12%)
* reference frequency ≤ output frequency ≤ (1+P8.12%) * reference frequency.
Function Setting Factory
Name Description
Code Range Setting
Auto reset
P8.16 0~3 0~3 0
times
P8.17 Reset interval 0.1~100.0s 0.1~100.0 1.0s
Auto reset function can reset the fault in preset times and interval. When P8.16 is set to
be 0, it means “auto reset” is disabled and the protective device will be activated in case
of fault.
Notice: The fault such as OUT 1, OUT 2, OUT 3, OH1 and OH2 cannot be reset
automatically.
Function Setting Factory
Name Description
Code Range Setting
Preset count
P8.18 P8.19~65535 P8.19~65535 0
value
Specified
P8.19 0~P8.18 0~ P8.18 0
count value

.74.
CHF100A series high performance universal inverter

The count pulse input channel can be S1~S4 (≤200Hz) and HDI.
If function of output terminal is set as preset count reached, when the count value
reaches preset count value (P8.18), it will output an ON-OFF signal. Inverter will clear
the counter and restart counting.
If function of output terminal is set as specified count reached, when the count value
reaches specified count value (P8.19), it will output an ON-OFF signal until the count
value reaches preset count value (P8.18). Inverter will clear the counter and restart
counting.
Notice:
l Specified count value (P8.19) should not be greater than preset count value
(P8.18).
l Output terminal can be RO1, RO2.
This function is shown as following figure.

Figure 6.29 Timing chart for preset and specified count reached.
Function Setting Factory
Name Description
Code Range Setting
Preset
P8.20 0~65535h 0~65535 65535 h
running time
If function of output terminal is set as running time reached, when the accumulated
running time reaches the preset running time, it will output an ON-OFF signal.
Function Setting Factory
Name Description
Code Range Setting

P8.21 FDT level 0.00~ P0.03 0.00~ P0.03 50.00Hz

P8.22 FDT lag 0.0~100.0% 0.0~100.0 5.0%

When the output frequency reaches a certain preset frequency (FDT level), output
terminal will output an ON-OFF signal until output frequency drops below a certain

.75.
CHF100A series high performance universal inverter

frequency of FDT level (FDT level - FDT lag), as shown in following figure.

Figure 6.20 FDT level and lag diagram.


Function Setting Factory
Name Description
Code Range Setting
Frequency
arrive 0.0~100.0%
P8.23 0.0~100.0 0.0%
detecting (maximum frequency)
range
When output frequency is within the detecting range of reference frequency, an ON-OFF
signal will be output. The function can adjust the detecting range.

Figure 6.21 Frequency arriving detection diagram.


Function Setting Factory
Name Description
Code Range Setting
P8.24 Droop control 0.00~10.00Hz 0.00~10.00 0.00Hz
When several motors drive the same load, each motor's load is different because of the
difference of motor's rated speed. The load of different motors can be balanced through
droop control function which makes the speed droop along with load increase.

.76.
CHF100A series high performance universal inverter

When the motor outputs rated torque, actual frequency drop is equal to P8.24. User can
adjust this parameter from small to big gradually during commissioning. The relation
between load and output frequency is in the following figure.

Figure 6.22 Droop control diagram.


Function Setting Factory
Name Description
Code Range Setting
Brake
Depend
P8.25 threshold 115.0~140.0% 115.0~140.0
on model
voltage
When the DC bus voltage is greater than the value of P8.25, the inverter will start
dynamic braking.
Notice:
l Factory setting is 120% if rated voltage of inverter is 220V.
l Factory setting is 130% if rated voltage of inverter is 380V.
l The value of P8.25 is corresponding to the DC bus voltage at rated input
voltage.
Function Setting Factory
Name Description
Code Range Setting
Cooling fan 0: Auto stop mode
P8.26 0~1 0
control 1: Always working
0: Auto stop mode: The fan keeps working when the inverter is running. When the
inverter stops, whether the fan works or not depends on the module temperature of
inverter.

.77.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
0: Invalid
P8.27 Overmodulation 0~1 0
1: Valid
The function is applicable in the instance of low network voltage or heavy load for a long
time, inveter rises the output voltage with rising utilization rate of itself bus voltage.
Function Setting Factory
Name Description
Code Range Setting
0: PWM mode 1
P8.28 PWM mode 1: PWM mode 2 0~2 0
2: PWM mode 3
The features of each mode, please refer the following table:
Noise in lower Noise in higher
Mode Others
frequency frequency
PWM mode 1 Low high
Need to be derated, because
PWM mode 2 low
of higher temperature rise.
Be more effective to restrain
PWM mode 3 high
the oscillation

6.10 P9 Group--PID Control


PID control is a common used method in process control, such as flow, pressure and
temperature control. The principle is firstly to detect the bias between preset value and
feedback value, then calculate output frequency of inverter according to proportional
gain, integral and differential time. Please refer to following figure.

Figure 6.23 PID control diagram.


Notice: To make PID take effect, P0.07 must be set to be 6.

.78.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
0: Keypad
1: AI1
PID preset
2: AI2
P9.00 source 0~5 0
3: HDI
selection
4: Multi-step
5: Communication
Keypad PID
P9.01 0.0%~100.0% 0.0~100.0 0.0%
preset
0: AI1
PID feedback 1: AI2
P9.02 source 2: AI1+AI2 0~4 0
selection 3: HDI
4: Communication
These parameters are used to select PID preset and feedback source.
Notice:
l Preset value and feedback value of PID are percentage value.
l 100% of preset value is corresponding to 100% of feedback value.
l Preset source and feedback source must not be same, otherwise PID will be
malfunction.
Function Setting Factory
Name Description
Code Range Setting
PID output 0: Positive
P9.03 0~1 0
characteristic 1: Negative
0:Positive. When the feedback value is greater than the preset value, output frequency
will be decreased, such as tension control in winding application.
1: Negative. When the feedback value is greater than the preset value, output frequency
will be increased, such as tension control in unwinding application.
Function Setting Factory
Name Description
Code Range Setting
Proportional
P9.04 0.00~100.00 0.00~100.00 0.10
gain (Kp)
Integral time
P9.05 0.01~10.00s 0.01~10.00 0.10s
(Ti)

.79.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
Differential
P9.06 0.00~10.00s 0.00~10.00 0.00s
time (Td)
Optimize the responsiveness by adjusting these parameters while driving an actual load.
Adjusting PID control:
Use the following procedure to activate PID control and then adjust it while monitoring
the response.
1. Enabled PID control (P0.07=6)
2. Increase the proportional gain (Kp) as far as possible without creating oscillation.
3. Reduce the integral time (Ti) as far as possible without creating oscillation.
4. Increase the differential time (Td) as far as possible without creating oscillation.
Making fine adjustments:
First set the individual PID control constants, and then make fine adjustments.
l Reducing overshooting
If overshooting occurs, shorten the differential time and lengthen the integral time.

Figure 6.24 Reducing overshooting diagram.


l Rapidly stabilizing control status
To rapidly stabilize the control conditions even when overshooting occurs, shorten the
integral time and lengthen the differential time.
l Reducing long-cycle oscillation
If oscillation occurs with a longer cycle than the integral time setting, it means that
integral operation is strong. The oscillation will be reduced as the integral time is
lengthened.

.80.
CHF100A series high performance universal inverter

Figure 6.25 Reducing long-cycle oscillation diagram.


l Reducing short-cycle oscillation
If the oscillation cycle is short and oscillation occurs with a cycle approximately the same
as the differential time setting, it means that the differential operation is strong. The
oscillation will be reduced as the differential time is shortened.

Figure 6.26 Reducing short-cycle oscillation diagram.


If oscillation cannot be reduced even by setting the differential time to 0, then either
lower the proportional gain or raise the PID primary delay time constant.
Function Setting Factory
Name Description
Code Range Setting
Sampling
P9.07 0.01~100.00s 0.01~100.00 0.10s
cycle (T)
P9.08 Bias limit 0.0~100.0% 0.0~100.0 0.0%
Sampling cycle T refers to the sampling cycle of feedback value. The PI regulator
calculates once in each sampling cycle. The bigger the sampling cycle is, the slower the
response is.
Bias limit defines the maximum bias between the feedback and the preset. PID stops
operation when the bias is within this range. Setting this parameter correctly is helpful to
improve the system output accuracy and stability.

.81.
CHF100A series high performance universal inverter

Figure 6.27 Relationship between bias limit and output frequency.


Function Setting Factory
Name Description
Code Range Setting
Feedback lost
P9.09 detecting 0.0~100.0% 0.0~100.0 0.0%
value
Feedback lost
P9.10 0.0~3600.0s 0.0~3600.0 1.0s
detecting time
When feedback value is less than P9.09 continuously for the period determined by P9.10,
the inverter will alarm feedback lost failure (PIDE). Notice: 100% of P9.09 is the same
as 100% of P9.01.

6.11 PA Group--Simple PLC and Multi-step Speed Control


Simple PLC function can enable the inverter to change its output frequency and
directions automatically according to programmable controller PLC. For multi-step speed
function, the output frequency can be changed only by multi-step terminals.
Notice:
l Simple PLC has 16 steps which can be selected.
l If P0.07 is set to be 5, 16 steps are available for multi-step speed. Otherwise
only 15 steps are available (step 1~15).
Function Setting Factory
Name Description
Code Range Setting
0: Stop after one cycle
Simple PLC 1: Hold last frequency after
PA.00 0~2 0
mode one cycle
2: Circular run

.82.
CHF100A series high performance universal inverter

0: Stop after one cycle: Inverter stops automatically as soon as it completes one cycle,
and It needs run command to start again.
1: Hold last frequency after one cycle: Inverter holds frequency and direction of last step
after one cycle.
2: Circular run: Inverter continues to run cycle by cycle until receive a stop command.

Figure 6.28 Simple PLC operation diagram.


Function Setting Factory
Name Description
Code Range Setting
Simple PLC
0: Disabled
PA.01 status saving 0~1 0
1: Enabled
after power off
This parameter determines whether the running step and output frequency should be
saved when power off or not.
Function Setting Factory
Name Description
Code Range Setting
Multi-step
PA.02 -100.0~100.0% -100.0~100.0 0.0%
speed 0
th
0 Step
PA.03 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.04 -100.0~100.0% -100.0~100.0 0.0%
speed 1
st
1 Step
PA.05 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.06 -100.0~100.0% -100.0~100.0 0.0%
speed 2

.83.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
nd
2 Step
PA.07 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.08 -100.0~100.0% -100.0~100.0 0.0%
speed 3
rd
3 Step
PA.09 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.10 -100.0~100.0% -100.0~100.0 0.0%
speed 4
th
4 Step
PA.11 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.12 -100.0~100.0% -100.0~100.0 0.0%
speed 5
th
5 Step
PA.13 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.14 -100.0~100.0% -100.0~100.0 0.0%
speed 6
th
6 Step
PA.15 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.16 -100.0~100.0% -100.0~100.0 0.0%
speed 7
th
7 Step
PA.17 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.18 -100.0~100.0% -100.0~100.0 0.0%
speed 8
th
8 Step
PA.19 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.20 -100.0~100.0% -100.0~100.0 0.0%
speed 9
th
9 Step
PA.21 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.22 -100.0~100.0% -100.0~100.0 0.0%
speed 10

.84.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
th
10 Step
PA.23 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.24 -100.0~100.0% -100.0~100.0 0.0%
speed 11
th
11 Step
PA.25 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.26 -100.0~100.0% -100.0~100.0 0.0%
speed 12
th
12 Step
PA.27 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.28 -100.0~100.0% -100.0~100.0 0.0%
speed 13
th
13 Step
PA.29 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.30 -100.0~100.0% -100.0~100.0 0.0%
speed 14
th
14 Step
PA.31 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Multi-step
PA.32 -100.0~100.0% -100.0~100.0 0.0%
speed 15
th
15 Step
PA.33 0.0~6553.5 s(m) 0.0~6553.5 0.0s
running time
Notice:
l 100% of multi-step speed x corresponds to the maximum frequency (P0.04).
l If the value of multi-step speed x is negative, the direction of this step will be
reverse, otherwise it will be forward.
l The unit of x step running time is determined by PA.37.
Selection of step is determined by combination of multi-step terminals. Please refer to
following figure and table.

.85.
CHF100A series high performance universal inverter

Figure 6.29 Multi-steps speed operation diagram.


Multi-step Multi-step Multi-step Multi-step
Terminal
speed speed speed speed
Step
reference1 reference2 reference3 reference4
0 OFF OFF OFF OFF
1 ON OFF OFF OFF
2 OFF ON OFF OFF
3 ON ON OFF OFF
4 OFF OFF ON OFF
5 ON OFF ON OFF
6 OFF ON ON OFF
7 ON ON ON OFF
8 OFF OFF OFF ON
9 ON OFF OFF ON
10 OFF ON OFF ON
11 ON ON OFF ON
12 OFF OFF ON ON
13 ON OFF ON ON
14 OFF ON ON ON
15 ON ON ON ON

Function Setting Factory


Name Description
Code Range Setting
ACC/DEC
PA.34 time selection 0~0XFFFF 0~0XFFFF 0
for step 0~7

.86.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
ACC/DEC
PA.35 time selection 0~0XFFFF 0~0XFFFF 0
for step 8~15
These parameters are used to determine the ACC/DEC time from one step to next step.
There are four ACC/DEC time groups.
Function Step ACC/DEC ACC/DEC ACC/DEC ACC/DEC
Binary Digit
Code No. Time 0 Time 1 Time 2 Time 3
BIT1 BIT0 0 00 01 10 11
BIT3 BIT2 1 00 01 10 11
BIT5 BIT4 2 00 01 10 11
BIT7 BIT6 3 00 01 10 11
PA.34
BIT9 BIT8 4 00 01 10 11
BIT11 BIT10 5 00 01 10 11
BIT3 BIT12 6 00 01 10 11
BIT15 BIT14 7 00 01 10 11
BIT1 BIT0 8 00 01 10 11
BIT3 BIT2 9 00 01 10 11
BIT5 BIT4 10 00 01 10 11
BIT7 BIT6 11 00 01 10 11
PA.35
BIT9 BIT8 12 00 01 10 11
BIT11 BIT10 13 00 01 10 11
BIT3 BIT12 14 00 01 10 11
BIT15 BIT14 15 00 01 10 11
For example: To set the acceleration time of following table:
Step No. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
ACC/DEC
0 1 2 3 2 1 3 0 3 3 2 0 0 0 2 2
time group
The value of every bit of PA.34 and PA.35 is:
Low byte BIT 0 BIT 1 BIT 2 BIT 3 BIT 4 BIT 5 BIT 6 BIT 7
PA.34 0 0 1 0 0 1 1 1
PA.35 1 1 1 1 0 1 0 0

.87.
CHF100A series high performance universal inverter

High byte BIT 8 BIT 9 BIT 10 BIT 11 BIT 12 BIT 13 BIT 14 BIT 15
PA.34 0 1 1 0 1 1 0 0
PA.35 0 0 0 0 0 1 0 1
So the value of PA.34 should be: 0X36E4, the value of PA.35 should be: 0XA02F
Function Setting Factory
Name Description
Code Range Setting
Simple PLC 0: Restart from step 0
PA.36 restart 1: Continue from interrupted 0~1 0
selection step
0: Restart from step 0: If the inverter stops during running (due to stop command or fault),
it will run from step 0 when it restarts.
1: Continue from interrupted step: If the inverter stops during running (due to stop
command or fault), it will record the running time of current step. When inverter restarts,
it will resume from interrupted time automatically. For details, please refer to following
figure.

Figure 6.30 Simple PLC continues from interrupted step.


Function Setting Factory
Name Description
Code Range Setting
0: Second
PA.37 Time unit 0~1 0
1: Minute
This parameter determines the unit of x step running time.

6.12 PB Group-- Protection Function


Function Setting Factory
Name Description
Code Range Setting
Input
0: Disable
PB.00 phase-failure 0~1 1
1: Enable
protection
.88.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
Output
0: Disable
PB.01 phase-failure 0~1 1
1: Enable
protection
Notice: Please be cautious to set these parameters as disabled. Otherwise it may
cause inverter and motor overheat even damaged.
Function Setting Factory
Name Description
Code Range Setting
Motor 0: Disabled
PB.02 overload 1: Normal motor 0~2 2
protection 2: Variable frequency motor
1: For normal motor, the lower the speed is, the poorer the cooling effect is. Based on
this reason, if output frequency is lower than 30Hz, inverter will reduce the motor
overload protection threshold to prevent normal motor from overheat.
2: As the cooling effect of variable frequency motor has nothing to do with running speed,
it is not required to adjust the motor overload protection threshold.
Function Setting Factory
Name Description
Code Range Setting
Motor
overload
PB.03 20.0%~120.0% 20.0~120.0 100.0%
protection
current

Figure 6.31 Motor overload protection curve.


The value can be determined by the following formula:
Motor overload protection current = (Maximum load current / inverter rated current) *
100%
Notice:
l This parameter is normally used when rated power of inverter is greater than
.89.
CHF100A series high performance universal inverter

rated power of motor.


l Motor overload protection time: 60s with 200% of rated current. For details,
please refer to above figure.
Function Setting Factory
Name Description
Code Range Setting
Threshold of
PB.04 70.0~110.0% 70.0~110.0 80.0%
trip-free
Decrease rate
PB.05 0.00Hz~P0.03 0.00Hz~P0.03 0.00Hz
of trip-free
If PB.05 is set to be 0, the trip-free function is invalid.
Trip-free function enables the inverter to perform low-voltage compensation when DC
bus voltage drops below PB.04. The inverter can continue to run without tripping by
reducing its output frequency and feedback energy via motor.
Notice: If PB.05 is too big, the feedback energy of motor will be too large and may
cause over-voltage fault. If PB.05 is too small, the feedback energy of motor will be
too small to achieve voltage compensation effect. So please set PB.05 according
to load inertia and the actual load.
Function Setting Factory
Name Description
Code Range Setting
Over-voltage 0: Disabled
PB.06 0~1 1
stall protection 1: Enabled
Over-voltage
PB.07 stall protection 110~150% 110~150 120%
point
During deceleration, the motor’s decelerating rate may be lower than that of inverter’s
output frequency due to the load inertia. At this time, the motor will feed the energy back
to the inverter, resulting in rise of DC bus voltage rise. If no measures taken, the inverter
will trip due to over voltage.
During deceleration, the inverter detects DC bus voltage and compares it with
over-voltage stall protection point. If DC bus voltage exceeds PB.07, the inverter will stop
reducing its output frequency. When DC bus voltage become lower than PB.07, the
deceleration continues, as shown in following figure.

.90.
CHF100A series high performance universal inverter

Figure 6.32 Over-voltage stall function.


Function Setting Factory
Name Description
Code Range Setting
G Model:
Auto current
160%
PB.08 limiting 50~200% 50~200
P Model:
threshold
120%
Frequency
decrease rate
PB.09 0.00~100.00Hz/s 0.00~100.00 10.00Hz/s
when current
limiting
Auto current 0: Enabled
PB.10 limiting 1: Disabled when constant 0~1 0
selection speed
Auto current limiting is used to limit the current of inverter smaller than the value
determined by PB.08 in real time. Therefore the inverter will not trip due to surge
over-current. This function is especially useful for the applications with big load inertia or
step change of load.
PB.08 is a percentage of the inverter’s rated current.
PB.09 defines the decrease rate of output frequency when this function is active. If
PB.08 is too small, overload fault may occur. If it is too big, the frequency will change too
sharply and therefore, the feedback energy of motor will be too large and may cause
over-voltage fault. This function is always enabled during acceleration or deceleration.
Whether the function is enabled in constant
Speed running is determined by PB.10.
Notice:
l During auto current limiting process, the inverter’s output frequency may
.91.
CHF100A series high performance universal inverter

change; therefore, it is recommended not to enable the function when


inverter needs to output stable frequency
l During auto current limiting process, if PB.08 is too low, the overload
capacity will be impacted.
Please refer to following figure.

Figure 6.33 Current limiting protection function.


Function Setting Factory
Name Description
Code Range Setting
0:No detection
1 : Valid detection of
overtorque during running,
then continue running
2 : Valid detection of
overtorque during running,
Selection of
then warning and stop
PB.11 overtorque 0~4 1
3 : Valid detection of
(OL3)
overtorque during constant
speed running, then continue
running 4:Valid detection of
overtorque during constant
speed running, then warning
and stop.
G model:
Detection
150%
PB.12 level of 10.0%~200.0% 10.0~200.0
P model:
overtorque
120%

.92.
CHF100A series high performance universal inverter

This value is depending on model.


Function Setting Factory
Name Description
Code Range Setting
Detection time
PB.13 0.0~60.0s 0~60 0.1s
cof overtorque

Figure 6.34 Overtorque control function.


If PB.11 is set to be 1or 3, and if the output torque of inverter reaches to PB.12, and with
delay of PB.13, this will output the overtorque. And the TRIP light will reflash. If P6.01
~P6.03 are set to be10, the output will be valid.
If PB.11 is set to be 2 or 4, when overtorque signal meets the output conditions, inverter
proforms warming signal OL3,and meanwhile stops the output.

6.13 PC Group--Serial Communication


Function Setting Factory
Name Description
Code Range Setting
PC.00 Local address 0~247 0~247 1
This parameter determines the slave address used for communication with master. The
value “0” is the broadcast address.
Function Setting Factory
Name Description
Code Range Setting
0: 1200BPS
1: 2400BPS
PC.01 Baud rate 2: 4800BPS
0~5 4
selection 3: 9600BPS
4: 19200BPS
5: 38400BPS
This parameter can set the data transmission rate during serial communication.
Notice: The baud rate of master and slave must be the same.

.93.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
0: RTU, 1 start bit, 8 data bits,
no parity check, 1 stop bit.
1: RTU, 1 start bit, 8 data bits,
even parity check, 1 stop bit.
2: RTU, 1 start bit, 8 data bits,
odd parity check, 1 stop bit.
PC.02 Data format 0~5 1
3: RTU, 1 start bit, 8 data bits,
no parity check, 2 stop bits.
4: RTU, 1 start bit, 8 data bits,
even parity check, 2 stop bits.
5: RTU, 1 start bit, 8 data bits,
odd parity check, 2 stop bits.
This parameter defines the data format used in serial communication protocol.
Function Setting Factory
Name Description
Code Range Setting
Communication
PC.03 0~200ms 0~200 5ms
delay time
This parameter can be used to set the response delay in communication in order to
adapt to the MODBUS master. In RTU mode, the actual communication delay should be
no less than 3.5 characters’ interval.
Function Setting Factory
Name Description
Code Range Setting
Communication 0.0: Disabled
PC.04 0.0~100.0 0.0s
timeout delay 0.1~100.0s
When the value is zero, this function will be disabled. When communication interruption
is longer than the non-zero value of PC.04, the inverter will alarm communication error
(CE).
Function Setting Factory
Name Description
Code Range Setting
0: Alarm and coast to stop
Communication 1: No alarm and continue to
PC.05 0~3 1
error action run
2: No alarm but stop

.94.
CHF100A series high performance universal inverter

Function Setting Factory


Name Description
Code Range Setting
according to P1.06 (if
P0.01=2)
3: No alarm but stop
according to P1.06
0: When communication error occurs, inverter will alarm (CE) and coast to stop.
1: When communication error occurs, inverter will omit the error and continue to run.
2: When communication error occurs, if P0.01=2, inverter will not alarm but stop
according to stop mode determined by P1.06. Otherwise it will omit the error.
3: When communication error occurs, inverter will not alarm but stop according to stop
mode determined by P1.06.
Function Setting Factory
Name Description
Code Range Setting
Unit’s place of LED
0: Response to writing
1: No response to writing
Response Ten’s place of LED
PC.06 00~11 00
action 0: Reference not saved when
power off
1: Reference saved when
power off

Figure 6.35 Meaning of PC.06.


A stands for: Unit’s place of LED.
B stands for: Ten’s place of LED

.95.
CHF100A series high performance universal inverter

6.14 PD Group--Supplementary Function


Function Setting Factory
Name Description
Code Range Setting
PD.00-PD.09 Reserved

6.15 PE Group—Factory Setting


This group is the factory-set parameter group. It is prohibited for user to access.

.96.
CHF100A series high performance universal inverter

Fault
Fault Type Reason Solution
Code
1.Open phase occurred with
power supply.
2.Momentary power loss
DC bus occurred Inspect the input power
UV
Under-voltage 3.Wiring terminals for input supply or wiring.
power supply are loose.
4.Voltage fluctuations in
power supply are too large.
1. Select variable
1. Motor drive heavy load at
frequency motor.
low speed for a long time.
2. Check and adjust
2. Improper V/F curve
OL1 Motor overload V/F curve.
3. Improper motor’s overload
3. Check and adjust
protection threshold (PB.03)
PB.03
4. Sudden change of load.
4. Check the load.
1. Increase Acc/Dec
1. Load is too heavy or time or select bigger
Acc/Dec time is too short. capacity inverter.
Inverter
OL2 2. Improper V/F curve 2. Check and adjust
overload
3. Capacity of inverter is too V/F curve.
small. 3. Select bigger
capacity inverter.
1.Open-phase occurred in
power supply.
2.Momentary power loss
occurred.
3. Wiring terminals for Check the wiring,
Input phase
SPI input power supply are installation and power
failure
loose. supply.
4.Voltage fluctuations in
power supply are too large.
5.Voltage balance between
phase is bad.

.98.
CHF100A series high performance universal inverter

Fault
Fault Type Reason Solution
Code
Press STOP/RESET to
Read/Write fault of control
EEP EEPROM fault reset
parameters
Ask for support
1. PID feedback 1. Inspect PID
PID feedback disconnected. feedback signal wire.
PIDE
fault 2. PID feedback source 2. Inspect PID
disappears. feedback source.
1. Braking circuit failure or
1. Inspect braking unit,
brake tube damaged.
replace braking tube.
BCE Brake unit fault 2. Too low resistance of
2. Increase braking
externally connected braking
resistance.
resistor.
Time reach of
END 1. Reach the working time 1.As for service
factory setting
1.Increase the
acceleration time
2.Avoid to restart after
1. More fast acceleration stop
2.Restart the running motor 3.Check the DC bus
OL3 Overtorque
3. Lower DC bus voltage voltage
4.Bigger load 4. Use the bigger power
rating inverter
5.Set PB.11 to be the
correct value

7.2 Common Faults and Solutions


Inverter may have following faults or malfunctions during operation, please refer to the
following solutions.
No display after power on:
l Inspect whether the voltage of power supply is the same as the inverter rated
voltage or not with multi-meter. If the power supply has problem, inspect and solve
it.
l Inspect whether the three-phase rectify bridge is in good condition or not. If the

.100.
CHF100A series high performance universal inverter

rectification bridge is burst out, ask for support.


l Check the CHARGE light. If the light is off, the fault is mainly in the rectify bridge or
the buffer resistor. If the light is on, the fault may be lies in the switching power
supply. Please ask for support.
Power supply air switch trips off when power on:
l Inspect whether the input power supply is grounded or short circuit. Please solve
the problem.
l Inspect whether the rectify bridge has been burnt or not. If it is damaged, ask for
support.
Motor doesn’t move after inverter running:
l Inspect if there is balanced three-phase output among U, V, W. If yes, then motor
could be damaged, or mechanically locked. Please solve it.
l If the output is unbalanced or lost, the inverter drive board or the output module
may be damaged, ask for support..
Inverter displays normally when power on, but switch at the input side trips when
running:
l Inspect whether the output side of inverter is short circuit. If yes, ask for support.
l Inspect whether ground fault exists. If yes, solve it.
l If trip happens occasionally and the distance between motor and inverter is too far,
it is recommended to install output AC reactor.

.101.
CHF100A series high performance universal inverter

Main inspections Criteria


Items to be
Inspection
checked Frequency Means/methods
content
heating 2. comprehensive 2. fan is working in good
3. noise observation condition. Speed and air flow
3. listening are normal. No abnormal
heat.
3. No abnormal noise
1. comprehensive
1. No abnormal vibration and
1. vibration observation
no abnormal noise.
Motor 2. heat 2. point
2. No abnormal heat.
3. noise thermometer
3. No abnormal noise.
3. listening
1. power input
voltage 1. voltmeter
1. satisfying the specification
2. inverter 2. rectifying
Operation 2. satisfying the specification
output voltage voltmeter
status 3. satisfying the specification
3. inverter 3. ammeter
parameters 4. temperature rise is lower
output current 4. point
than 40℃
4. internal thermometer
temperature

8.2 Periodic Maintenance


Customer should check the drive every 3 months or 6 months according to the actual
environment
8.2.1 Check whether the screws of control terminals are loose. If so, tighten them with
a screwdriver;
8.2.2 Check whether the main circuit terminals are properly connected; whether the
mains cables are over heated;
8.2.3 Check whether the power cables and control cables are damaged, check
especially for any wear on the cable tube;
8.2.4 Check whether the insulating tapes around the cable lugs are stripped;
8.2.5 Clean the dust on PCBs and air ducts with a vacuum cleaner;
8.2.6 For drives that have been stored for a long time, it must be powered on every 2
years. When supplying AC power to the drive, use a voltage regulator to raise the input

.103.
CHF100A series high performance universal inverter

voltage to rated input voltage gradually. The drive should be powered for 5 hours without
load.
8.2.7 Before performing insulation tests, all main circuit input/output terminals should
be short-circuited with conductors. Then proceed insulation test to the ground. Insulation
test of single main circuit terminal to ground is forbidden; otherwise the drive might be
damaged. Please use a 500V Mega-Ohm-Meter.
8.2.8 Before the insulation test of the motor, disconnect the motor from the drive to
avoid damaging it.

8.3 Replacement of wearing parts


Fans and electrolytic capacitors are wearing part, please make periodic replacement to
ensure long term, safety and failure-free operation. The replacement periods are as
follows:
◆Fan: Must be replaced when using up to 20,000 hours;

◆Electrolytic Capacitor: Must be replaced when using up to 30,000~40, 000 hours.

.104.
CHF100A series high performance universal inverter

9. COMMUNICATION PROTOCOL
9.1 Interfaces
RS485: asynchronous, half-duplex.
Default: 8-E-1, 19200bps. See Group PC parameter settings.

9.2 Communication Modes


9.2.1 The protocol is Modbus protocol. Besides the common register Read/Write
operation, it is supplemented with commands of parameters management.
9.2.2 The drive is a slave in the network. It communicates in ‘point to point’ master-slave
mode. It will not respond to the command sent by the master via broadcast address.
9.2.3 In the case of multi-drive communication or long-distance transmission, connecting
a 100~120Ω resistor in parallel with the master signal line will help to enhance the
immunity to interference.

9.3 Protocol Format


Modbus protocol supports both RTU. The frame format is illustrated as follows:

Modbus adopts “Big Endian” representation for data frame. This means that when a
numerical quantity larger than a byte is transmitted, the most significant byte is sent first.
RTU mode
In RTU mode, the Modbus minimum idle time between frames should be no less than
3.5 bytes. The checksum adopts CRC-16 method. All data except checksum itself sent
will be counted into the calculation. Please refer to section: CRC Check for more
information. Note that at least 3.5 bytes of Modbus idle time should be kept and the start
and end idle time need not be summed up to it.
The table below shows the data frame of reading parameter 002 from slave node
address 1.
Node addr. Command Data addr. Read No. CRC
0x01 0x03 0x00 0x02 0x00 0x01 0x25 0xCA
The table below shows the reply frame from slave node address 1

.105.
CHF100A series high performance universal inverter

Node addr. Command Bytes No. Data CRC


0x01 0x03 0x02 0x00 0x00 0xB8 0x44

9.4 Protocol function


Different respond delay can be set through drive’s parameters to adapt to different needs.
For RTU mode, the respond delay should be no less than 3.5 bytes interval, and for
ASCII mode, no less than 1ms.
The main function of Modbus is to read and write parameters. The Modbus protocol
supports the following commands:
0x03 Read inverter’s function parameter and status parameters
0x06 Write single function parameter or command parameter to inverter
All drive’s function parameters, control and status parameters are mapped to Modbus
R/W data address.
The data address of control and status parameters please refer to the following table.
Parameter R/W
Address Meaning of value
Description Feature
0001H: Forward
0002H: Reverse
0003H: JOG forward
Control 0004H: JOG reverse
1000H W/R
command 0005H: Stop
0006H: Coast to stop
0007H: Reset fault
0008H: JOG stop
0001H: Forward running
0002H: Reverse running
Inverter status 1001H 0003H: Standby R
0004H: Fault
0005H: Status of inverter POFF
Communication Setting Range
(-10000~10000)
Communication Note: the communication setting is
setting 2000H the percentage of the relative value W/R
(-100.00%~100.00%). If it is set as
frequency source, the value is the
.106.
CHF100A series high performance universal inverter
Parameter R/W
Address Meaning of value
Description Feature
percentage of the maximum
frequency (P0.04). If it is set as PID
(preset value or feedback value), the
value is the percentage of the PID.
PID setting,
2001H W/R
Range: 0~1000,1000 means100.0%
PID fedback,
2002H W/R
Range: 0~1000,1000 means100.0%
Setting value of torque
2003H Range: -1000~1000,1000 W/R
means100.0%
Setting value of upper limit frequency
2004H W/R
(0~Fmax)
Status 3000H Output frequency R
parameters 3001H Reference frequency R
3002H DC Bus voltage R
3003H Output voltage R
3004H Output current R
3005H Rotation speed R
3006H Output power R
3007H Output torque R
3008H PID preset value R
3009H PID feedback value R
300AH Input terminal status R
300BH Output terminal status. R
300CH Input of AI1 R
300DH Input of AI2 R
300EH Reserved R
300FH Reserved R
3010H HDI frequency R
3011H Reserved R
3012H Step No. of PLC or multi-step R

.107.
CHF100A series high performance universal inverter
Parameter R/W
Address Meaning of value
Description Feature
3013H Reserved R
3014H External counter input R
3015H Torque setting R
3016H Device code R
0X00H: No fault
0X01H: OUT1
0X02H: OUT2
0X03H: OUT3
0X04H: OC1
0X05H: OC2
0X06H: OC3
0X07H: OV1
0X08H: OV2
0X09H: OV3
0x0A: UV
0x0B: OL1
Inveter fault info 0x0C:OL2
5000H R
address 0x0D: SPI
0x0E: SPO
0x0F: OH1
0x10: OH2
0x11: EF
0x12: CE
0x13: ItE
0x14: tE
0x15: EEP
0x16:PIDE
0x17: bCE
0x18: END
0x19: OL3
The above shows the format of the frame. Now we will introduce the Modbus command
and data structure in details, which is called protocol data unit for simplicity. Also MSB
stands for the most significant byte and LSB stands for the least significant byte for the

.108.
CHF100A series high performance universal inverter

same reason. The description below is data format in RTU mode.


Protocol data unit format of reading parameters:
Request format:
Protocol data unit Data length(bytes) Range
Command 1 0x03
Data Address 2 0~0xFFFF
Read number 2 0x0001~0x0010
Reply format (success):
Protocol data unit Data length(bytes) Range
Command 1 0x03
Returned byte number 2 2* Read number
Content 2* Read number
If the command is reading the type of inverter (data address 0x3016), the content value
in reply message is the device code:
The high 8 bit of device code is the type of the inverter, and the low 8 bit of device code
is the sub type of inverter.
For details, please refer to the following table:
High byte Meaning Low byte Meaning
01 Vector control type
02 For water supply
00 CHV
03 Middle frequency 1500Hz
04 Middle frequency 3000Hz
01 Vector control type
01 CHE
02 Middle frequency 1500Hz
01 Universal type
02 CHF
02 Vector type CHF100A
If the operation fails, the inverter will reply a message formed by failure command and
error code. The failure command is (Command+0x80). The error code indicates the
reason of the error; see the table below.
Value Name Mean
The command from master can not be executed. The
Illegal reason maybe:
01H
command 1 This command is only for new version and this version can
not realize.

.109.
CHF100A series high performance universal inverter

Value Name Mean


2 Slave is in fault status and can not execute it.
Illegal data Some of the operation addresses are invalid or not allowed
02H
address. to access.
When there are invalid data in the message framed received
by slave.
03H Illegal value Note: This error code does not indicate the data value to
write exceed the range, but indicate the message frame is a
illegal frame.
06H Slave busy Inverter is busy(EEPROM is storing)
Password The password written to the password check address is not
10H
error same as the password set by P7.00.
11H Check error The CRC (RTU mode) check not passed.
It only happen in write command, the reason maybe:
1 The data to write exceed the range of according
Written not
12H parameter
allowed.
2 The parameter should not be modified now.
3 The terminal has already been used.
When password protection take effect and user does not
System
13H unlock it, write/read the function parameter will return this
locked
error.
Protocol data unit format of writing single parameter:
Request format:
Protocol data unit Data length(bytes) Range
Command 1 0x06
Data Address 2 0~0xFFFF
Write Content 2 0~0xFFFF
Reply format (success):
Protocol data unit Data length(bytes) Range
Command 1 0x06
Data Address 2 0~0xFFFF
Write Content 2 0~0xFFFF
If the operation fails, the inverter will reply a message formed by failure command and
error code. The failure command is (Command+0x80). The error code indicates the
reason of the error; see table 1.
.110.
CHF100A series high performance universal inverter

9.5 Note:
9.5.1 Between frames, the span should not less than 3.5 bytes interval, otherwise, the
message will be discarded.
9.5.2 Be cautious to modify the parameters of PC group through communication,
otherwise may cause the communication interrupted.
9.5.3 In the same frame, if the span between two .near bytes more than 1.5 bytes
interval, the behind bytes will be assumed as the start of next message so that
communication will failure.

9.6 CRC Check


For higher speed, CRC-16 uses tables. The following are C language source code for
CRC-16.
unsigned int crc_cal_value(unsigned char *data_value,unsigned char data_length)
{
int i;
unsigned int crc_value=0xffff;
while(data_length--)
{
crc_value^=*data_value++;
for(i=0;i<8;i++)
{
if(crc_value&0x0001)crc_value=(crc_value>>1)^0xa001;
else crc_value=crc_value>>1;
}
}
return(crc_value);
}

9.7 Example
RTU mode, read 2 data from 0004H
The request command is:
START T1-T2-T3-T4 (transmission time of 3.5 bytes)
Node address 01H
Command 03H

.111.
CHF100A series high performance universal inverter
High byte of start address 00H
Low byte of start address 04H
High byte of data number 00H
Low byte of data number 02H
Low byte of CRC 85H
High byte of CRC CAH
END T1-T2-T3-T4 (transmission time of 3.5 bytes)
The reply is :
START T1-T2-T3-T4 (transmission time of 3.5 bytes)
Node address 01H
Command 03H
Returned byte number 04H
Higher byte of 0004H 00H
Low byte of 0004H 00H
High byte of 0005H 00H
Low byte of 0005H 00H
Low byte of CRC 43H
High byte of CRC 07H
END T1-T2-T3-T4 (transmission time of 3.5 bytes)

.112.
CHF100A series high performance universal inverter

Appendix A: External Dimension


A.1 380V

Figure A-1 Dimensions (15kW and below).

Figure A-2 Dimensions (18.5 ~110kW).

.113.
CHF100A series high performance universal inverter

Figure A-3 Dimensions (132~315kW with base or without base).

Figure A-4 Dimensions (350~500kW).

.114.
CHF100A series high performance universal inverter

A B H W D
Installation
Power (mm) (mm) (mm) (mm) (mm)
Hole Notice
(kW) Installation
External Dimension (mm)
Dimension
1.5~5.5 147.5 237.5 250 160 175 5 ——
7.5~15 206 305.5 320 220 180 6 ——
18.5~30 176 454.5 467 290 215 6.5 ——
37~55 230.0 564.5 577.0 375.0 270.0 7.0 ——
75~110 320.0 738.5 755.0 460.0 330.0 9.0 ——
Without
270 1233 1275 490 391 13
base
132~185
With
—— —— 1490 490 391 ——
base
Without
500 1324 1358 750 402 12.5
base
200~315
With
—— —— 1670 750 402 ——
base
350~500 —— —— 1900 1505 502 —— ——

A.2 220V

Figure A-5 7.5kW and lower Figure A-6 11kW~18.5kW

.115.
CHF100A series high performance universal inverter

Figure A-7 22~55kW


A B H W D
Installation
(mm) (mm) (mm) (mm) (mm)
Model Hole
Installation
External Dimension (mm)
Dimension
CHF100A-1R5G-2
CHF100A-2R2G-2
147.5 237.5 250 160 175 5
CHF100A-004G-2
CHF100A-5R5G-2
CHF100A-7R5G-2 206 305.5 320 220 180 6
CHF100A-011G-2
CHF100A-015G-2 176 454.5 467 290 215 6.5
CHF100A-018G-2
CHF100A-022G-2
CHF100A-030G-2 166 510 525 260 280 5
CHF100A-037G-2
CHF100A-045G-2
178 663 680 300 280 6
CHF100A-055G-2

.116.
CHF100A series high performance universal inverter

A.3 Installation Space

Figure A-8 Installation of multiple inverters. Figure A-9 Safety space.

Notice: Add the air deflector when apply the up-down installation.

A.4 Dimensions of External small Keypad


67.4±0.2
87.4±0.2

Figure A-10 Dimension of small keypad. Figure A-11 installation of small keypad

.117.
CHF100A series high performance universal inverter

A.5 Dimensions of External big Keypad

Figure A-12 Dimension of big keypad. Figure A-13 installation of big keypad

A.6 Disassembly

Figure A-14 Disassembly of plastic cover.

.118.
CHF100A series high performance universal inverter

FigureA-15 Disassembly of metal plate cover.

.119.
CHF100A series high performance universal inverter

Figure A-16 Open inverter cabinet.

.120.
CHF100A series high performance universal inverter

Appendix B Specifications of Breaker, Cable,


Contactor and Reactor
B.1 Specifications of breaker, cable and contactor
Circuit Input/Output AC
Model No. 2
Breaker (A) Cable (mm ) Contactor (A)
3AC 220V ±15%
CHF100A -1R5G-2 20 4 16
CHF100A -2R2G-2 32 6 20
CHF100A -004G-2 40 6 25
CHF100A-5R5G-2 63 6 32
CHF100A-7R5G-2 100 10 63
CHF100A -011G-2 125 25 95
CHF100A -015G-2 160 25 120
CHF100A -018G-2 160 25 120
CHF100A -022G-2 200 35 170
CHF100A -030G-2 200 35 170
CHF100A -037G-2 200 35 170
CHF100A -045G-2 250 70 230
CHF100A-055G-2 315 70 280
3AC 380V ±15%
CHF100A-1R5G-4 16 2.5 10
CHF100A-2R2G-4 16 2.5 10
CHF100A -004G/5R5P-4 25 4 16
CHF100A -5R5G/7R5P-4 25 4 16
CHF100A-7R5G/011P-4 40 6 25
CHF100A-011G/015P-4 63 6 32
CHF100A-015G/018P-4 63 6 50
CHF100A-018G/022P-4 100 10 63
CHF100A-022G/030P-4 100 16 80
CHF100A-030G/037P-4 125 25 95
CHF100A-037G/045P-4 160 25 120
CHF100A-045G/055P-4 200 35 135

.121.
CHF100A series high performance universal inverter

Circuit Input/Output AC
Model No. 2
Breaker (A) Cable (mm ) Contactor (A)
CHF100A-055G/075P-4 200 35 170
CHF100A-075G/090P-4 250 70 230
CHF100A-090G/110P-4 315 70 280
CHF100A-110G/132P-4 400 95 315
CHF100A-132G/160P-4 400 150 380
CHF100A-160G/185P-4 630 185 450
CHF100A-185G/200P-4 630 185 500
CHF100A-200G/220P-4 630 240 580
CHF100A-220G/250P-4 800 150x2 630
CHF100A-250G/280P-4 800 150x2 700
CHF100A-280G/315P-4 1000 185x2 780
CHF100A-315G/350P-4 1200 240x2 900
CHF100A-350G-4 1280 240x2 960
CHF100A-400G-4 1380 185x3 1035
CHF100A-500G-4 1720 185x3 1290

B.2 Specifications of AC input/output reactor and DC reactor


AC Input reactor AC Output reactor DC reactor
Model No. Current Inductance Current Inductance Current Inductance
(A) (mH) (A) (mH) (A) (mH)
CHF100A-1R5G-4 5 3.8 5 1.5 - -
CHF100A-2R2G-4 7 2.5 7 1 - -
CHF100A-004G/5R5P-4 10 1.5 10 0.6 - -

CHF100A-5R5G/7R5P-4 15 1.4 15 0.25 - -

CHF100A-7R5G/011P-4 20 1 20 0.13 - -
CHF100A-011G/015P-4 30 0.6 30 0.087 - -
CHF100A-015G/018P-4 40 0.6 40 0.066 - -
CHF100A-018G/022P-4 50 0.35 50 0.052 80 0.4
CHF100A-022G/030P-4 60 0.28 60 0.045 80 0.4
CHF100A-030G/037P-4 80 0.19 80 0.032 80 0.4
CHF100A-037G/045P-4 90 0.19 90 0.03 110 0.25

.122.
CHF100A series high performance universal inverter

AC Input reactor AC Output reactor DC reactor


Model No. Current Inductance Current Inductance Current Inductance
(A) (mH) (A) (mH) (A) (mH)
CHF100A-045G/055P-4 120 0.13 120 0.023 110 0.25
CHF100A-055G/075P-4 150 0.11 150 0.019 110 0.25
CHF100A-075G/090P-4 200 0.08 200 0.014 180 0.18
CHF100A-090G/110P-4 200 0.08 200 0.014 180 0.18
CHF100A-110G/132P-4 250 0.065 250 0.011 250 0.2
CHF100A-132G/160P-4 290 0.065 290 0.011 326 0.215
CHF100A-160G/185P-4 330 0.05 330 0.01 494 0.142
CHF100A-185G/200P-4 400 0.044 400 0.008 494 0.142
CHF100A-200G/220P-4 400 0.044 400 0.008 494 0.142
CHF100A-220G/250P-4 490 0.035 490 0.005 494 0.126
CHF100A-250G/280P-4 530 0.04 530 0.005 700 0.1
CHF100A-280G/315P-4 600 0.04 600 0.005 700 0.1
CHF100A-315G/350P-4 660 0.025 660 0.004 800 0.08
CHF100A-350G-4 400*2 0.04 400*2 0.005 460*2 0.12
CHF100A-400G-4 490*2 0.03 490*2 0.004 460*2 0.12
CHF100A-500G-4 530*2 0.03 530*2 0.003 650*2 0.11

B.3 Specifications of AC input/output filter


Model No. Input filter Output filter
CHF100A -1R5G-2 NF241B10/01
CHF100A -2R2G-2 NF241B20/01
CHF100A-1R5G-4 NFI-005 NFO-005
CHF100A-2R2G-4 NFI-010 NFO-010
CHF100A -004G/5R5P-4 NFI-010 NFO-010
CHF100A -5R5G/7R5P-4 NFI-020 NFO-020
CHF100A-7R5G/011P-4 NFI-020 NFO-020
CHF100A-011G/015P-4 NFI-036 NFO-036
CHF100A-015G/018P-4 NFI-036 NFO-036
CHF100A-018G/022P-4 NFI-050 NFO-050
CHF100A-022G/030P-4 NFI-050 NFO-050

.123.
CHF100A series high performance universal inverter

Model No. Input filter Output filter


CHF100A-030G/037P-4 NFI-065 NFO-065
CHF100A-037G/045P-4 NFI-080 NFO-080
CHF100A-045G/055P-4 NFI-100 NFO-100
CHF100A-055G/075P-4 NFI-150 NFO-150
CHF100A-075G/090P-4 NFI-150 NFO-150
CHF100A-090G/110P-4 NFI-200 NFO-200
CHF100A-110G/132P-4 NFI-250 NFO-250
CHF100A-132G/160P-4 NFI-250 NFO-250
CHF100A-160G/185P-4 NFI-300 NFO-300
CHF100A-185G/200P-4 NFI-400 NFO-400
CHF100A-200G/220P-4 NFI-400 NFO-400
CHF100A-220G/250P-4 NFI-600 NFO-600
CHF100A-250G/280P-4 NFI-600 NFO-600
CHF100A-280G/315P-4 NFI-900 NFO-900
CHF100A-315G/350P-4 NFI-900 NFO-900
CHF100A-350G-4 NFI-1200 NFO-1200
CHF100A-400G-4 NFI-1200 NFO-1200

B.4 Specifications of braking unit and braking resistor


B.4.1 Specifications of braking unit
Braking resistor
Braking unit
Model No. (100% braking torque)
Order No. Quantity Specification Quantity
3AC 220V ±15%
CHF100A -1R5G-2 1 130Ω/260W 1
CHF100A -2R2G-2 1 80Ω/260W 1
Built-in
CHF100A -004G-2 1 48Ω/400W 1
CHF100A -5R5G-2 1 35Ω/550W 1
CHF100A -7R5G-2 1 26Ω/780W 1
CHF100A -011G-2 1 17Ω/1100W 1
CHF100A -015G-2 DBU-055-2 1 13Ω/1800W 1
CHF100A -018G-2 1 10Ω/2000W 1
CHF100A -022G-2 1 8Ω/2500W 1

.124.
CHF100A series high performance universal inverter

Braking resistor
Braking unit
Model No. (100% braking torque)
Order No. Quantity Specification Quantity
CHF100A -030G-2 2 13Ω/1800W 2
CHF100A -037G-2 2 10Ω/2000W 2
DBU-055-2
CHF100A -045G-2 2 8Ω/2500W 2
CHF100A -055G-2 2 6.5Ω/3000W 2

Model: 380V

Braking resistor
Braking unit
Model No. (100% braking torque)
Order No. Quantity Resistor Power Quantity
1.5(2) 1 400Ω 260W 1
2.2(3) 1 150Ω 390W 1
4(5) 1 150Ω 390W 1
5.5(7.5) Built-in 1 100Ω 520W 1
7.5(11) 1 50Ω 1040W 1
11(15) 1 50Ω 1040W 1
15(20) 1 40Ω 1560W 1
18.5(25) 1 20Ω 6000W 1
22(30) 1 20Ω 6000W 1
30(40) 1 20Ω 6000W 1
37(50) 1 13.6Ω 9600W 1
45(60) DBU-055-4 1 13.6Ω 9600W 1
55(75) 1 13.6Ω 9600W 1
75(100) 2 13.6Ω 9600W 2
90(120) 2 13.6Ω 9600W 2
110(150) 2 13.6Ω 9600W 2
132(180) 1 4Ω 30000W 1
DBU-160-4
160(215) 1 4Ω 30000W 1
185(250) 1 3Ω 40000W 1
200(270) DBU-220-4 1 3Ω 40000W 1
220(300) 1 3Ω 40000W 1

.125.
CHF100A series high performance universal inverter

Braking resistor
Braking unit
Model No. (100% braking torque)
Order No. Quantity Resistor Power Quantity
250(340) 1 2Ω 60000W 1
280(380) DBU-315-4 1 2Ω 60000W 1
315(430) 1 2Ω 60000W 1
350(470) 2 3Ω 40000W 2
DBU-220-4
400(540) 2 3Ω 40000W 2
500(680) 2 2Ω 60000W 2
560(760) DBU-315-4 2 2Ω 60000W 2
630(860) 2 2Ω 60000W 2
B.4.2 Connection
1. Connection of brake resistor
For D size and lower inverter, please refer to the figure B-1.

Figure B-1 Connection of brake resistor


2. Connection of brake unit, please refer to figure B-2.

.126.
CHF100A series high performance universal inverter

Figure B-2 Connection of braking unit


3. Parallel connection of braking unit

Figure B-3 Parallel connection of brake unit and inverter

.127.
CHF100A series high performance universal inverter

Appredix C: LIST OF FUNCTION PARAMETERS


Notice:
l PE group is factory reserved, users are forbidden to access these
parameters.
l The column “Modify” determines the parameter can be modified or not.
“○ ” indicates that this parameter can be modified all the time.
“◎”indicates that this parameter cannot be modified during the inverter is
running.
“● ” indicates that this parameter is read only.
l “Factory Setting” indicates the value of each parameter while restoring the
factory parameters, but those detected parameters or record values cannot
be restored.
Seri
Function Factory
Name Description Modify al
Code Setting
No.
P0 Group: Basic Function
0: V/F control
1: Sensorless vector
control
P0.00 Control model 0 ¥ 0
2: Torque control
( sensorless vector
control)
0: Keypad (LED
extinguished)
Run command 1: Terminal (LED
P0.01 0 ● 1
source flickering)
2: Communication (LED
lights on)

.128.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
0: Valid, save UP/DOWN
value when power off
1: Valid, do not save
UP/DOWN value when
P0.02 UP/DOWN setting 0 ● 2
power off
2: Invalid
3: Valid during running,
clear when stop.
Maximum
P0.03 10.00~400.00Hz 50.00Hz ¥ 3
frequency
Upper frequency
P0.04 P0.05~P0.03 50.00Hz ¥ 4
limit
Lower frequency
P0.05 0.00~P0.04 0.00Hz O 5
limit
Keypad reference
P0.06 0.00~P0.03 50.00Hz O 6
frequency
0: Keypad
1: AI1
2. AI2
Frequency A 3: HDI
P0.07 0 O 7
command source 4. Simple PLC
5: Multi-step speed
6: PID
7: Communication
0:AI1
Frequency B
P0.08 1:AI2 0 O 8
command source
2:HDI

Scale of frequency 0: Maximum frequency


P0.09 0 ¥ 9
B command 1: Frequency A command

.129.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
0: A
Frequency
1: B
P0.10 command 0 O 10
2: A+B
selection
3: Max(A, B)
Acceleration time Depend on
P0.11 0.1~3600.0s O 11
0 model
Deceleration time
P0.12 0.1~3600.0s 0 ¥ 12
0
0: Forward
Running direction
P0.13 1: Reverse 0 ¥ 13
selection
2: Forbid reverse
Depend on
P0.14 Carrier frequency 1.0~15.0kHz 14
model
P0.15 AVR function 0~2 1 15
0: No action
Motor parameters
P0.16 1: Rotation autotuning 0 16
autotuning
2: Static autotuning
0: No action
Restore
P0.17 1: Restore factory setting 0 17
parameters
2: Clear fault records
P1 Group: Start and Stop Control
0: Start directly
1: DC braking and start
P1.00 Start Mode 0 ¥ 18
2: Speed tracking and
start
P1.01 Starting frequency 0.00~10.00Hz 0.00Hz ¥ 19
Hold time of
P1.02 0.0~50.0s 0.0s ¥ 20
starting frequency
DC Braking
P1.03 current before 0.0~150.0% 0.0% ¥ 21
start

.130.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
DC Braking time
P1.04 0.0~50.0s 0.0s ¥ 22
before start
Acceleration /
0: Linear
P1.05 Deceleration 0 ¥ 23
1: reserved
mode
0: Deceleration to stop
P1.06 Stop mode 0 O 24
1: Coast to stop
Starting frequency
P1.07 0.00~P0.03 0.00Hz O 25
of DC braking
Waiting time
P1.08 before 0.0~50.0s 0.0s O 26
DC braking
DC braking
P1.09 0.0~150.0% 0.0% O 27
current
P1.10 DC braking time 0.0~50.0s 0.0s O 28
Dead time of
P1.11 0.0~3600.0s 0.0s O 29
FWD/REV
Action when 0: Running at the lower
running frequency frequency limit
P1.12 0 ¥ 30
is less than lower 1: Stop
frequency limit 2: Stand-by
Delay time for
P1.13 0.0~3600.0s 0.0s O 31
restart
Restart after 0: Disabled
P1.14 0 O 32
power off 1: Enabled
Waiting time of
P1.15 0.0~3600.0s 0 O 33
restart
Terminal function
0: Disabled
P1.16 examined when 0 ¥ 33
1: Enabled
power is on

.131.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
P1.17~
Reserved 0 ¥ 34
P1.19
P2 Group: Motor Parameters
0: G model
P2.00 Inverter model 0 ¥ 36
1: P model
Depend on
P2.01 Motor rated power 0.4~3000.0kW 37
model
Motor rated
P2.02 10.00Hz~P0.03 50.00Hz ¥ 38
frequency
Depend on
P2.03 Motor rated speed 0~36000rpm ¥ 39
model
Motor rated Depend on
P2.04 0~800V ¥ 40
voltage model
Motor rated Depend on
P2.05 0.8~6000.0A ¥ 41
current model
Motor stator Depend on
P2.06 0.001~65.535Ω O 42
resistance model
Motor rotor Depend on
P2.07 0.001~65.535Ω O 43
resistance model
Motor leakage Depend on
P2.08 0.1~6553.5mH O 44
inductance model
Motor mutual Depend on
P2.09 0.1~6553.5mH O 45
inductance; model
Current without Depend on
P2.10 0.01~6553.5A O 46
load model
P3 Group: Vector Control
ASR proportional
P3.00 0~100 20 O 47
gain Kp1
ASR integral time
P3.01 0.01~10.00s 0.50s 48
Ki1

.132.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
ASR switching
P3.02 0.00Hz~P3.05 5.00Hz 49
point 1
ASR proportional
P3.03 0~100 25 50
gain Kp2
ASR integral time
P3.04 0.01~10.00s 1.00s 51
Ki2
ASR switching
P3.05 P3.02~P0.03 10.00Hz 52
point 2
Slip compensation
P3.06 50.0%~200.0% 100% 53
rate of VC
Depend on
P3.07 Torque upper limit 0.0~200.0% 54
model
0: Keypad (P3.09)
1:AI1
Torque setting 2:AI2
P3.08 0 55
source 3:HDI
4:Multi-step speed
5:Communication
Keypad torque
P3.09 -200.0%~200.0% 50.0% 56
setting
0: Keypad (P0.04)
1: AI1
Upper frequency 2: AI2
P3.10 0 57
setting source 3: HDI
4: Multi-step
5: Communication
P4 Group: V/F Control

.133.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
0:Linear curve
1: User-defined curve
2: Torque_stepdown
V/F curve curve (1.3 order)
P4.00 0 ¥ 58
selection 3: Torque_stepdown
curve (1.7 order)
4: Torque_stepdown
curve (2.0 order)
0.0%: (auto)
P4.01 Torque boost 0.0% O 59
0.1%~10.0%
P4.02 Torque boost 0.0%~50.0% (motor rated 20.0%
¥ 60
cut-off frequency)
P4.03 V/F frequency 1 0.00Hz~ P4.05 0.00Hz O 61
P4.04 V/F voltage 1 0.0%~100.0% 0.00% O 62
P4.05 V/F frequency 2 P4.03~ P4.07 30.00Hz ¥ 63
P4.06 V/F voltage 2 0.0%~100.0% 00.0% ¥ 64
P4.07 V/F frequency 3 P4.05~ P2.02 00.00Hz O 65
P4.08 V/F voltage 3 0.0%~100.0% 0.0% ¥ 66
Slip compensation
P4.09 0.00~200.0% 0.0% O 67
limit
Auto energy 0: Disabled
P4.10 0 ¥ 68
saving selection 1: Enabled
Low-frequency
threshold of
P4.11 0~10 2 69
restraining
oscillation
High-frequency
threshold of
P4.12 0~10 0 70
restraining
oscillation

.134.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
Boundary of
P4.13 restraining 0.0~P3.03 30Hz 71
oscillation
P5 Group: Input Terminals
0: High speed pulse input
P5.00 HDI selection 0 ¥ 72
1: ON-OFF input
0: Invalid
1: Forward
2: Reverse
S1 Terminal 3: 3-wire control
P5.01 1 ¥ 73
function 4: Jog forward
5: Jog reverse
6: Coast to stop
7: Reset fault

S2 Terminal 8: Pause running


P5.02 4 ¥ 74
function 9: External fault input
10: Up command
S3 Terminal
P5.03 11: DOWN command 7 ¥ 75
function
12: Clear UP/DOWN
S4 Terminal
P5.04 13: Switch between A and 0 ¥ 76
function
B
S5 terminal
P5.05 14: Switch between A and 0 77
function
A+B
P5.06 S6 terminal
15: Switch between B and 0 78
function
A+B
P5.07 S7 terminal
16: Multi-step speed 0 79
function

.135.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
reference1
17: Multi-step speed
reference 2
18: Multi-step speed
reference 3
19: Multi-step speed
reference 4
20: Multi-step speed
pause
21: ACC/DEC time
selection1n time
22: ACC/DEC time
selection 2
HDI terminal 23: Reset simple PLC
P5.08 0 ¥ 80
function when stop
24: Pause simple PLC
25: Pause PID
26: Pause traverse
operation
27: Reset traverse
operation
28: Reset counter
29: Reset length
30: ACC/DEC ramp hold
31: Counter input
32: UP/DOWN invalid
temporarily
33-39: Reserved
P5.09 ON-OFF filter times 1~10 5 O 81
0: 0: 2-wire control mode 1
FWD/REV control
P5.10 1: 1: 2-wire control mode 2 0 ¥ 82
mode
2: 2: 3-wire control mode 1

.136.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
3: 3-wire control mode 2
UP/DOWN setting
P5.11 0.01~50.00Hz/s 0.50Hz/s O 83
change rate
P5.12 AI1 lower limit -10.00V~10.00V 0.00V O 84
AI1 lower limit
P5.13 corresponding -100.0%~100.0% 0.0% O 85
setting
P5.14 AI1 upper limit -10.00V~10.00V 10.00V O 86
AI1 upper limit
P5.15 corresponding -100.0%~100.0% 100.0% O 87
setting
AI1 filter time
P5.16 0.00s~10.00s 0.10s O 88
constant
P5.17 AI2 lower limit 0.00V~10.00V 0.00V O 89
AI2 lower limit
P5.18 corresponding -100.0%~100.0% 0.0% O 90
setting
P5.19 AI2 upper limit 0.00V~10.00V 10.00V O 91
AI2 upper limit
P5.20 corresponding -100.0%~100.0% 100.0% O 92
setting
AI2 filter time
P5.21 0.00s~10.00s 0.10s O 93
constant
P5.22 HDI lower limit 0.0 kHz ~50.0kHz 0.0KHz O 94
HDI lower limit
P5.23 corresponding -100.0%~100.0% 0.0% O 95
setting
P5.24 HDI upper limit 0.0 KHz~50.0KHz 50.0KHz O 96
HDI upper limit
P5.25 corresponding -100.0%~100.0% 100.0% O 97
setting

.137.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
HDI filter time
P5.26 0.00s~10.00s 0.10s O 98
constant
P6 Group: Output Terminals

P6.00 HDO selection ON-OFF output 1 ● 99

0: No output
1: Running
2: Run forward
HDO ON-OFF
P6.01 3: Run reverse 1 O 100
output selection
4: Fault output
5: FDT reached
6: Frequency reached
7: Zero speed running
8: Preset count value
reached
9: Specified count value
reached

Relay 1 output 10: Length reached


P6.02 4 O 101
selection 11: Simple PLC step
completed
12: PLC cycle completed
13: Running time reached
14: Upper frequency limit
reached
15: Lower frequency limit
reached
Relay 2 output 16: Ready
P6.03 selection (4.0kW 17: Auxiliary motor 1 started 0 O 102
and above) 18: Auxiliary motor 2 started
19-20: reserved

.138.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.

AO1 function
P6.04 0 O 103
selection

0: Running frequency
1: Reference frequency
2: Motor speed
3: Output current
4: Output voltage
5: Output power
AO2 function
P6.05 6: Output torque 0 104
selection
7: AI1 voltage
8: AI2 voltage/current
9: HDI frequency

P6.06 Reserved Reserved 0 O 105

P6.07 AO1 lower limit 0.0%~100.0% 0.0% O 106


AO1 lower limit
P6.08 corresponding 0.00V ~10.00V 0.00V O 107
output
P6.09 AO1 upper limit 0.0%~100.0% 100.0% O 108
AO1 upper limit
P6.10 corresponding 0.00V ~10.00V 10.00V O 109
output

P6.11 AO2 lower limit 0.0~100.0% 0.0% 110

AO2 lower limit


P6.12 corresponding 0~10.00V 0.00V 111
output

.139.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.

P6.13 AO2 upper limit 0.0~100.0% 100.0% 112

AO2 upper limit


P6.14 corresponding 0.00~10.00V 10.00V 113
output
P7 Group: Display Interface
P7.00 User password 0~65535 0 O 118
P7.01 Reserve 0 O 119
P7.02 Reserve 0 ¥ 120
0: Display status switching
1: Jog
QUICK/JOG
P7.03 2: FWD/REV switching 0 O 121
function selection
3: Clear UP/DOWN setting
4.QUICK set mode
0: Valid when keypad
control (P0.03=0)
1: Valid when keypad or
terminal control (P0.03=0
STOP/RST
P7.04 or 1) 0 O 122
function selection
2: Valid when keypad or
communication control
(P0.03=0 or 2)
3: Always valid
0: Preferential to external
keypad
1: Both display, only
Keypad display external key valid.
P7.05 0 O 123
selection 2: Both display, only local
key valid.
3: Both display and key
valid.

.140.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
0~0XFFFF
BIT0: running frequency
BIT1: Reference
frequency
BIT2: DC bus voltage
BIT3: Output voltage
BIT4: Output current
BIT5: Rotation speed
BIT6: Line speed
BIT7: Output power
Running status BIT8: Output torque
P7.06 0X07FF O 124
display selection 1 BIT9: PID preset
BIT10: PID feedback
BIT11: Input terminal
status
BIT12: Output terminal
status
BIT13: Torque setting
value
BIT14: Count value
BIT15: Step No. of PLC or
multi-step
0~0XFFFF
BIT0: AI1
BIT1: AI2
BIT2: HDI frequency
Running status BIT3: Load percentage of
P7.07 0X0000 O 125
display selection 2 motor
BIT4: Load percentage of
inverter
BIT 5: Accumulated
running time

.141.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
BIT6~15: Reserved
0~0XFFFFF
BIT0: Reference
frequency
BIT1: DC bus voltage
BIT2: Input terminal status
BIT3: Output terminal
status
BIT4: PID preset
Stop status
P7.08 BIT5: PID feedback 0x00FF O 126
display selection
BIT6: AI1
BIT7: AI2
BIT8: HDI frequency
BIT9: Step No. of PLC or
multi-step
BIT10: Torque setting
value
BIT11~15: Reserved
0.1~999.9%
Actual mechanical speed
Coefficient of
P7.09 = 120 * output frequency 100.0% O 127
rotation speed
*P7.09 / Number of poles
of motor
0.1~999.9%
Coefficient of line
P7.10 Line speed = actual 1.0% O 128
speed
mechanical speed * P7.10
Rectify module
P7.11 0~100.0°C ● 129
temperature
IGBT module
P7.12 0~100.0°C ● 130
temperature
P7.13 Software version ● 131

.142.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
Depen
Inverter rated
P7.14 0-3000KW ds on 132
power
model
Depen
Inverter rated
P7.15 0.0-6000A ds on 133
current
model
Accumulated
P7.16 0~65535h ● 134
running time
Third latest fault 0: Not fault
P7.17 ● 135
type 1: IGBT Ph-U fault(OUT1)
2: IGBT Ph-V fault(OUT2)
3: IGBT Ph-W fault(OUT3)
4: Over-current when
Second latest acceleration(OC1)
P7.18 ● 136
fault type 5: Over-current when
deceleration(OC2)
6: Over-current when
constant speed running
(OC3)
7: Over-voltage when
acceleration(OV1)
8: Over-voltage when
deceleration(OV2)
9: Over-voltage when
constant speed
P7.19 Latest fault type ● 137
running(OV3)
10: DC bus
Under-voltage(UV)
11: Motor overload (OL1)
12: Inverter overload
(OL2)
13: Input phase failure

.143.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
(SPI)
14: Output phase failure
(SPO)
15: Rectify overheat
(OH1)
16: IGBT overheat (OH2)
17: External fault (EF)
18: Communication fault
(CE)
19: Current detection fault
(ITE)
20: Autotuning fault (TE)
21: EEPROM fault (EEP)
22: PID feedback fault
(PIDE)
23: Brake unit fault (BCE)
24: Reserved
Output frequency
P7.20 ● 138
at current fault
Output current at
P7.21 ● 139
current fault
DC bus voltage at
P7.22 ● 140
current fault
Input terminal
P7.23 status ● 141
at current fault
Output terminal
P7.24 status at current ● 142
fault
P8 Group: Enhanced Function
Depend on
P8.00 Acceleration time 1 0.1~3600.0s O 143
model
.144.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
Depend on
P8.01 Deceleration time 1 0.1~3600.0s O 144
model
Depend on
P8.02 Acceleration time 2 0.1~3600.0s O 145
model
Depend on
P8.03 Deceleration time 2 0.1~3600.0s O 146
model
Depend on
P8.04 Acceleration time 3 0.1~3600.0s O 147
model
Depend on
P8.05 Deceleration time 3 0.1~3600.0s O 148
model
P8.06 Jog reference 0.00~P0.03 5.00hz 149
Jog acceletation Depand on
P8.07 0.1-3600.0s 150
time Model
Jog deceleration Depand on
P8.08 0.1~3600.0s 151
time Model
P8.09 Skip Frequency 1 0.00~P0.03 0.00Hz 152
P8.10 Skip Frequency 2 0.00~P0.03 0.00Hz 153
Skip frequency
P8.11 0.00~P0.03 0.00hz 154
bandwidth
1P8.12 Traverse amplitude 0.0~100.0% 0.0% O 155
P8.13 Jitter frequency 0.0~50.0% 0.0% O 156
Rise time of
P8.14 0.1~3600.0s 5.0s O 157
traverse
P8.15 Fall time of traverse 0.1~3600.0s 5.0s O 158
P8.16 Auto reset times 0~3 0 O 159
P8.17 Reset interval 0.1~100.0s 1.0s O 160
P8.18 Preset count value P8.19~65535 0 O 161
Specified count
P8.19 0~P8.18 0 O 162
value
Preset running
P8.20 0~65535h 65535h O 163
time

.145.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
P8.21 FDT level 0.00~ P0.03 50.00Hz O 164
P8.22 FDT lag 0.0~100.0% 5.0% O 165
Frequency arrive 0.0~100.0%(maximum
P8.23 0.0% O 166
detecting range frequency)
P8.24 Droop control 0.00~10.00Hz 0.00Hz O 167
Brake threshold Depend on
P8.25 115.0~140.0% O 168
voltage model
Cooling fan 0: Auto stop mode
P8.26 0 O 169
control 1: Always working
Restrain 0: Enabled
P8.27 1 O 170
oscillation 1: Disabled
0: PWM mode 1
P8.28 PWM mode 1: PWM mode 2 0 ¥ 171
2: PWM mode 3
P9 Group: PID Control
0: Keypad
1: AI1
PID preset source 2: AI2
P9.00 0 O 172
selection 3: HDI
4: Multi-step
5: Communication
Keypad PID
P9.01 0.0%~100.0% 0.0% O 173
preset
0: AI1
1: AI2
PID feedback
P9.02 2: AI1+AI2 0 O 174
source selection
3: HDI
4: Communication
PID output 0: Positive
P9.03 0 O 175
characteristic 1: Negative

.146.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
Proportional gain
P9.04 0.00~100.00 0.10 O 176
(Kp)
P9.05 Integral time (Ti) 0.01~10.00s 0.10s O 177
Differential time
P9.06 0.00~10.00s 0.00s O 178
(Td)
P9.07 Sampling cycle (T) 0.00~100.00s 0.10s O 179
P9.08 Bias limit 0.0~100.0% 0.0% O 180
Feedback lost
P9.09 0.0~100.0% 0.0% O 181
detecting value
Feedback lost
P9.10 0.0~3600.0s 1.0s O 182
detecting time
PA Group: Simple PLC and Multi-step Speed Control
0: Stop after one cycle
1: Hold last frequency
PA.00 Simple PLC mode 0 O 183
after one cycle
2: Circular run
Simple PLC status
0: Disabled
PA.01 saving after power 0 O 184
1: Enabled
off
PA.02 Multi-step speed 0 -100.0~100.0% 0.0% O 185
0th Step running
PA.03 0.0~6553.5s(h) 0.0s O 186
time
PA.04 Multi-step speed 1 -100.0~100.0% 0.0% O 187
1st Step running
PA.05 0.0~6553.5s(h) 0.0s O 188
time
PA.06 Multi-step speed 2 -100.0~100.0% 0.0% O 189
2nd Step running
PA.07 0.0~6553.5s(h) 0.0s O 190
time
PA.08 Multi-step speed 3 -100.0~100.0% 0.0% O 191
3rd Step running
PA.09 0.0~6553.5s(h) 0.0s O 192
time

.147.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
PA.10 Multi-step speed 4 -100.0~100.0% 0.0% O 193
4th Step running
PA.11 0.0~6553.5s(h) 0.0s O 194
time
PA.12 Multi-step speed 5 -100.0~100.0% 0.0% O 195
5th Step running
PA.13 0.0~6553.5s(h) 0.0s O 196
time
PA.14 Multi-step speed 6 -100.0~100.0% 0.0% O 197
6th Step running
PA.15 0.0~6553.5s(h) 0.0s O 198
time
PA.16 Multi-step speed 7 -100.0~100.0% 0.0% O 199
7th Step running
PA.17 0.0~6553.5s(h) 0.0s O 200
time
PA.18 Multi-step speed 8 -100.0~100.0% 0.0% O 201
8th Step running
PA.19 0.0~6553.5s(h) 0.0s O 202
time
PA.20 Multi-step speed 9 -100.0~100.0% 0.0% O 203
9th Step running
PA.21 0.0~6553.5s(h) 0.0s O 204
time
Multi-step speed
PA.22 -100.0~100.0% 0.0% O 205
10
10th Step running
PA.23 0.0~6553.5s(h) 0.0s O 206
time
Multi-step speed
PA.24 -100.0~100.0% 0.0% O 207
11
11th Step running
PA.25 0.0~6553.5s(h) 0.0s O 208
time
Multi-step speed
PA.26 -100.0~100.0% 0.0% O 209
12
12th Step running
PA.27 0.0~6553.5s(h) 0.0s O 210
time

.148.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
Multi-step speed
PA.28 -100.0~100.0% 0.0% O 211
13
13th Step running
PA.29 0.0~6553.5s(h) 0.0s O 212
time
Multi-step speed
PA.30 -100.0~100.0% 0.0% O 213
14
14th Step running
PA.31 0.0~6553.5s(h) 0.0s O 214
time
Multi-step speed
PA.32 -100.0~100.0% 0.0% O 215
15
th
15 Step running
PA.33 0.0~6553.5s(h) 0.0s O 216
time
ACC/DEC time
PA.34 selection for step 0~0XFFFF 0 O 217
0~7
ACC/DEC time
PA.35 selection for step 0~0XFFFF 0 O 218
8~15
0: Restart from step 0
Simple PLC
PA.36 1: Continue from paused 0 ¥ 219
restart selection
step
0: Second
PA.37 Time unit 0 ¥ 220
1: Minute
PB Group: Protection Function
Input phase-failure 0: Disable
PB.00 1 O 221
protection 1: Enable
Output
0: Disabled
PB.01 phase-failure 1 O 222
1: Enabled
protection

.149.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
0: Disabled
Motor overload 1: Normal motor
PB.02 2 ¥ 223
protection 2: Variable frequency
motor
Motor overload 20.0% ~ 120.0% (rated
PB.03 100.0% O 224
protection current current of the motor)
Threshold of 70.0.0~110.0% (standard
PB.04 80.0% O 225
trip-free bus voltage)
Decrease rate of
PB.05 0.00Hz~P0.03 0.00Hz O 226
trip-free
Over-voltage stall 0: Disabled
PB.06 1 O 227
protection 1: Enabled
380V:
130%
Over-voltage stall
PB.07 110~150% O 228
protection point
220V:
120%
G Model:
Auto current 160%
PB.08 50~200% O 229
limiting threshold P Model:
120%
Frequency
decrease rate
PB.09 0.00~50.00Hz/s 10.00Hz/s O 230
when current
limiting
0: Enabled
Auto current
PB.10 1: Disabled when constant 0 O 231
limiting selection
speed

.150.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
0:No detection
1 : Valid detection of
overtorque during running,
then continue running
2 : Valid detection of
overtorque during running,
then waring and stop
Selection of
PB.11 3 : Valid detection of 1 232
overtorque (OL3)
overtorque during
constant speed running,
then continue running
4 : Valid detection of
overtorque during
constant speed running,
then waring and stop.
Detection level of Depends
PB.12 1.0%~200.0% 233
overtorque on model
Detection time cof
PB.13 0.0~60.0s 0.1s 234
overtorque
PC Group: Serial Communication
0~247, 0 stands for the
PC.00 Local address 1 O 235
broadcast address
0: 1200BPS
1: 2400BPS
Baud rate 2: 4800BPS
PC.01 4 O 236
selection 3: 9600BPS
4: 19200BPS
5: 38400BPS
0: RTU, 1 start bit, 8 data
bits, no parity check, 1
PC.02 Data format 1 O 237
stop bit.
1: RTU, 1 start bit, 8 data
.151.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
bits, even parity check, 1
stop bit.
2: RTU, 1 start bit, 8 data
bits, odd parity check, 1
stop bit.
3: RTU, 1 start bit, 8 data
bits, no parity check, 2
stop bits.
4: RTU, 1 start bit, 8 data
bits, even parity check, 2
stop bits.
5: RTU, 1 start bit, 8 data
bits, odd parity check, 2
stop bits.
Communication
PC.03 0~200ms 5ms O 238
delay time
Communication 0.0: Disabled
PC.04 0.0s O 239
timeout delay 0.1~100.0s
0: Alarm and coast to stop
1: No alarm and continue
to run
Communication 2: No alarm but stop
PC.05 1 O 240
error action according to P1.06 (if
P0.03=2)
3: No alarm but stop
according to P1.06
Unit’s place of LED
0: Response to writing
1: No response to writing
PC.06 Response action 0 O 241
Ten’s place of LED
0: Reference not saved
when power off

.152.
CHF100A series high performance universal inverter

Seri
Function Factory
Name Description Modify al
Code Setting
No.
1: Reference saved when
power off
PD Group: Supplementary Function
PD.00-P
Reserved ● 242
D.09
PE Group: Factory Setting
PE.00 Factory password 0~65535 ***** O 243

.153.

You might also like