Critical Spares

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 13

S.No. Material description Item Code Qty.

Remarks
1 PG clamp ZEBRA to ZEBRA ELECGENE0971 23
2 PG clamp ZEBRA to PANTHER ELECGENE0972 8
3 PG clamp PANTHER to PANTHER ELECGENE0935 10
4 PG clamp 16mm 9
5 T clamp 16mm 3
6 T clamp ZEBRA to ZEBRA conductor 24
7 T clamp ZEBRA to PANTHER conductor ELECGENE0974 11
8 PT clamp 40mm; 4 way 6
9 PT clamp 30mm; 4way 6
10 PT clamp 40mm; 2 way 2
11 132 kV Breaker pole contact 3
12 T clamp 40mm dia to zebra conductor 3
13 132 kV Cable connector clamp 3
14 132 kV Breaker pole Clamp CIRCBRKR0598 1set
15 Surge counter ; make CG MEASMETR0357 5
16 GATE VALVE CI 1" FLANGE TYPE PFITVALV0048 1
17 Breather unit 5kG ELECTRSP0129 6
18 Breather unit 1kG 2
19
CORK SHEET 3 MM THICK,SIZE 915 MM X 610 MM, MAKE NU-
CORK, Grade RC 70C GASKSEAL0351 10
20
CORK SHEET 6 MM THICK,SIZE 915 MM X 610 MM, MAKE NU-
CORK, RC 70C GASKSEAL0352 5
21
CORK SHEET 10 MM THICK,SIZE 915 MM X 610 MM, MAKE NU-
CORK, RC 70C GASKSEAL0353 5
22
CORK SHEET 12 MM THICK,SIZE 915 MM X 610 MM, MAKE NU-
CORK, RC 70C GASKSEAL0451 5
23
CORK SHEET 8 MM THICK,SIZE 915 MM X 610 MM, MAKE NU-
CORK, RC 70C GASKSEAL0452 10
24 Gate Valve Brass 25mm non flange type 6
25
SF6 GAS FILLING DEVICE, PART NO. S4799095001, SPARE
SUITABLE FOR 145 KV / 245 KV,40 KA, SF6 BREAKER TYPE 3 AP ,
MAKE SIEMENS/ABB ELECGENE1103 1
26 SF6 Gas Cylinder 18kG 1 Old (used)
27 Earthing Rod ELECSPAR0131 9
28 220kV Isolator earth switch driving unit 2
29 245 kV Isolator Centre break with male & female contacts 2 set
30
FAST RED COLOR CONCENTRATED,MAKE - PIDILIT OR ASIAN OR
BERGER, FOR MIXING IN DISTEMPER PNTSOTHR0039 4
31
FASTY ELLOW COLOR CONCENTRATED,MAKE - PIDILIT OR ASIAN
OR BERGER, FOR MIXING IN DISTEMPER PNTSOTHR0040 3
32 NUMERICAL MASTER TRIP RELAY, MVAJ 205, ALSTOM MAKE ELECRELY0639 4
33 NUMERICAL MASTER TRIP RELAY, MVAJ 105, ALSTOM MAKE ELECRELY0640 3
34 Earth resistance measurement instrument Make- WACO 1
35 Bevel gear for OLTC (new) 1
36 Bevel gear for OLTC (old from TR-4) 1
37 Device for collecting gas from Buchholz relay 3
38 Rotary cam switch ; make Kaycee; 4 pole 2
39 Rotary cam switch ; make Kaycee; 2 pole 1
40
SPAJ 140C 3P IDMT + INST O/C &E/F RELAY IDMT E/F:0.1-0.8 I.INST
O/C:0.5-40 I . INST E/F:1-10 I NON-DRAWOUT FLUSH
CASE:162(H)X142(W)X250(D) CONTACTS:3 NO SR WITH HR LED .
AUX. VOLT:80-265 V DC I :1/5 A.FREQ.50 HZ. IDMT O/C:.5-2.5I
MAKE ABB ELECRELY0251 1
41 Digital Voltmeter; Make Conzerv; Cl- 1, 110V AC, 132kV 2
42 Digital Ammeter; Make Conzerv; Cl- 1, 110V AC, 1200/1 A 1
43 Galvanometer for polarity check 1
44 Siemens P50 Power meter 8
45 Tap Changing indicaior ; Make EMCO ELECTRSP0163 1
46 Tap Changing indicaior ; Make Pradeep 3
47 LA counter (old) ; make CG 9
48
DIAL TYPE WINDING TEMP. INDICATOR WITH 4-SETS OF
CONTACTS.( WITH MICRO SWITCH) 0-150 0C 5 A, 240 V AC/DC
(MODEL NO. PC252/1005) MAKE PERFECT CONTROL, SPARE FOR
65/75 MVA,132/11 KV VOLT-AMP MAKE TRANSFORMER (JN NO.
21403) ELECTRSP0137 1 NEW
49
DIAL TYPE WINDING TEMP. INDICATOR WITH 4-SETS OF
CONTACTS.( WITH MICRO SWITCH) 0-150 0C 5 A, 240 V AC/DC
(MODEL NO. PC252/1005) MAKE PERFECT CONTROL, SPARE FOR
65/75 MVA,132/11 KV VOLT-AMP MAKE TRANSFORMER (JN NO.
21403) ELECTRSP0137 1 OLD
50
OIL TEMPERATURE INDICATOR WITHFOUR MERCURY SWITCHES
AND 3 METERS CAPILLARY 0-150 DEGREECENTRIGARDE FOR 20
MVA TRANSFORMER ELECTRSP0014 2 OLD
51
LEAKAGE CURRENT MONITOR FOR SURGE ARRESTOR, SA 30I,
TOTAL LEAKAGE CURRENT 1 MICRO AMP TO 10M AMP, SERIAL
PORT COMMUNICATION, ACCURACY +/- 5 %; BATTERY-12V DC ,
2.4AH SLA RECHARGABLE BATTERY ,INPUT 230VAC, 50HZ, 0-50
DEG C, ELECGENE1834 1
52
TRANSFORMER TURNS RATIO TEST KIT, TTR THREE PHASE, 230V
AC, 50HZ, 100VA, +/- 0.1 % ACCURACY, INTERFACE THROUGH RS-
232C , EXCITATION CURENT RANGE:- 0 TO 500MA, 5.0 INCH
DISPLAY,NUMERIC KEYPAD, 0-50 DEG C. ELECGENE1835 1
53
WINDING RESISTANCE METER FOR EHV
TRANSFORMER,230VAC,50HZ, +/- 0.25 % ACCU.;17 KEYBOARD,
INTERFACE WITH PC TH. RS232C PORT, INTERFACE
SOFTWARE,CURR RANGE 10MA TO 25A, RESIST.RANGE 0.1
MICRO OHM TO 2K OHM,BUILT IN PRINTER,5" DISP. 0-50DEG C ELECGENE1833 1
54 132 kV CT 3-core, 0.5/5P/PS, 300-150/1A 3 ABB
55 132 kV CT 3-core, PS/5P/0.5, 150-300/1A 3 MEHRU
56 120 kV LA ; Make ELPRO 3 OLD
57 220 kV CT 300-400/1A, 0.2/5P/5P-PS/5P-PS, 4 core 6
OLD; removed from
220kV Side TR-1 & 2
58 220 kV PT 220kv/sqrt(3)/110V, 3P/0.2/3P, 3 core 6
OLD; removed from
220kV Side TR-1 & 2
59 220kV CVT ,3 core, 0.2/0.2/0.2 TRANSFMR0285 1 NEW
60 220kV Line CT, 400-800/1A, 3core, 0.2S/0.2S/0.2S 1 NEW
61 220 kV SF6 CB set 2 1 set healthy
62 220 kV Bus coupler control panel set 2
63 220 kV CT 400-600/1A, 3 core, 0.2/5P/PS 6
64 132 kV CT 400-600/1A, 3 core, 0.2/5P/PS 1
65 220 kV CT 400-800/1 A , 5 core, PS/PS/PS/0.5/PS 3
66 220 kV LA , 198kV(78kV top & 120kV Bottom) ; Make CG 4set
67 Aerial Maintenance Platform UTILLITY0188 1
68 Metering panel Mogu Engineer's MEASMETR0519 2
69 HT trivector Secure meter APEX 100 INSTGENE0866 2
70 Software for ABT meter INSTGENE0867 1
71 Modem ECD 210 for ABT meter INSTGENE0868 1
72 Areva distance protection relay, P430 ELECRELY0073 1
73 Siemens cable differential relay 7SD600 1
74 16 window Facia annunciator INSTGENE0658 1
75 Valve Brass 25mm flange type ELECGENE1533 6
76 Gasket cutting machine UTILLITY0033 1
77
ZINC OXIDE,GAPLESS,MOGARD"SURGE ARRESTER,MODL
9LO2BNH132,STATION TYPE,1 POLE, H.DUTY,MAX.SYSTEM
VOLT.145 KV,R/VOLT 132KV,LINE DISCHG CLAS III,NOMINAL
DISCHG CURR.10 KAP,PR.RELIEF CURR 40 KA, MCOV 112
KV,WITH INSULATOR OF 31MM/KV,MAKE- ELPRO ELECGENE1380 6
78
GATE VALVE FOR BUCHHOLZ RELAY, SIZE: 80 MM DIA., DSF TYPE
WITH GASKETS FOR 20/25 MVA, 132/6.9 KV VOLTAMP MAKE
TRANSFORMER BEARING SR. NO: JN 21060 (ITEM NO.: 25 OF
OUR ATTACHED DRG,NO.: 3GA-21060/A) ELECTRSP1048 1
79
L.V. ADD. NEUTRAL PORCELAIN BUSHING WITH METAL
PART,RATING: 17.5KV/3150 AMP .AS PER IS-8603, CREEPAGE: 31
MM /KV--SUITABLE FOR YOUR 30/35 MVA,TRANSFORMER, 132/11
KV VOLTAMP MAKETRANSFORMER BEARING JN-22046/1-2. ELECTRSP1049 1
80
L.V. PORCELAIN BUSHING WITH METAL PART,RATING:
17.5KV/3150 AMP .AS PER IS-8603, CREEPAGE: 31 MM /KV--
SUITABLE FOR YOUR 30/35 MVA,TRANSFORMER, 132/11 KV
VOLTAMP MAKETRANSFORMER BEARING JN-22046/1-2. ELECTRSP1050 1
81
OIL SEALS FOR HV/LV BUSHINGS FOR YOUR 30/35 MVA, 132/11
KV VOLTAMP MAKE TRANSFORMER BEARING JN-22046/1-2. ELECTRSP1051 1
82
RELAY DOUBLE FLOAT BUCHHOLY SPARE FOR 20/25MVA 132/6.9
KV ELECRELY0096 2
83
CONCRETE EARTH PITS CHAMBER WITH CEMENT COVER (SIZE
450X450X450) ELECGENE1910 12
84 SILICA GEL BLUE MANTNLUB0062 30KG
85
OIL FOR POWER TRANSFORMER SERVOELECTRA, IN 210
LTRS.,IN STD.PACKING 210 LTR MANTOILS0001 630LTR
86 MANILA ROPE PULLEY BLOCK 2 SHEAVE 6" DIA 1" ROPE LIFTPULY0002 4
87
OVER HAULING KIT FOR THREE POLE COLUMN FOR 145KV SF6
SPRINGOPERATED CIRCUIT BREAKER TYPELTBD1 BLK222 PART
NO.PTHV-LTBD01-R3 PTHV-LTBD01-R3 BRKRSPAR0002 4
88
CLOSE/TRIP ELECTRO MAGNET WITH COIL 220VDC FOR ABB
CIRCUIT BREAKER 145KV LTB 145 D1/B WITH BLK 222 DRIVE,
DRAWING NO. 1HSB535272B3 CIRCBRKR0639 1
89
SPRING CHARGING MOTOR- M 220V FOR ABB CIRCUIT BREAKER
145KV LTB 145 D1/B WITH BLK 222 DRIVE, DRAWING NO.
1HSB534460-2 CIRCBRKR0640 1
90
DRIVING UNIT WITHOUT MOTOR FOR ABB CIRCUIT BREAKER
145KV LTB 145 D1/B WITH BLK 222 DRIVE, DRAWING NO.
1HSB532361-A CIRCBRKR0641 1
91
HT TRI VECTOR ABT METER ACCURACY CL 0.2s, TYPE ER 300P,
CT 1 AMP, PT 110 V AC, AUX. SUPPLY 110- 220 V DC & 240 V AC,
MAKE L&T MEASMETR0204 2
1
EARTH RESISTANCE TESTER,DIGITAL 4 TERMINALS SPIKES TYPE
WITH RECHARGABLE BATTERY AND CHARGER, RANGE-0-20-2000
OHM WITH ACC.(SPIKES,CABLE REEL,ALLIGATOR CLIPS AND
HAMMER ETC.) TOOLTAKL1924 1
2
FIXED CONTACT ASSEMBLY HAVING CONTACT SS SPRING,
NYLON SPACERS, WITH FEMALE/FIXED COPPER CONTACT JAW
(2PAIRS) FOR 132KV,1250A,TRIPLE POLE DOUBLE BREAK
ISOLATOR, MAKE- GR POWER SWITCHGEAR LTD CONTACTS0437 3
3
DASHPOT/SHOCK ABSORBER/ DAMPER FOR ABB CIRCUIT
BREAKER(3-POLE) 145KV LTB 145 D1/B WITH FSA1 MECHANISM,
DRAWING NO. 1HYB300862-A CIRCBRKR0713 1
4
CLOSING COIL,110 V DC (PART NO-EXIN400834-R9) FOR 145 KV
SF6 OUT DOOR CIRCUIT BREAKER,TYPE-LTB145D1/B,OPERATING
MECH -FSA1 CIRCBRKR0491 3
5
TRIPING COIL NO-2,110 V DC (PART NO-EXIN400833-R9) FOR 145
KV SF6 OUT DOOR CIRCUIT BREAKER,TYPE-
LTB145D1/B,OPERATING MECH -FSA1 CIRCBRKR0493 2
6
TRIPPING LATCH DEVICE ASSEMBLY(PART NO-EXIN200410-R1)
FOR 145 KV SF6 OUT DOOR CIRCUIT BREAKER,TYPE-
LTB145D1/B,OPERATING MECH -FSA1 CIRCBRKR0489 1
7
CLOSING LATCH DEVICE ASSEMBLY(PART NO-EXIN200416-R1)
FOR 145 KV SF6 OUT DOOR CIRCUIT BREAKER,TYPE-
LTB145D1/B,OPERATING MECH -FSA1 CIRCBRKR0490 1
8
MOTOR,TYPE-110 V DC(PART NO-EXIN300202-R1) FOR 145 KV SF6
OUT DOOR CIRCUIT BREAKER,TYPELDB145D1/B,OPERATING
MECH -FSA1 CIRCBRKR0494 1
9
3 PHASE VARIAC, INPUT: 415VAC 3 PHASE, OUTPUT: 0 -1100VAC 3
PHASE, 20 AMP TOOLTAKL2547 1
10
ELECTRICAL INSULATION MATS, BLUE COLOUR,THICK 2.5
MM,MAX USE VOLT3.3 TO 11KV,AC PROOF VOLT 22 KV FOR 3
MIN,AC DI-ELECTRIC STRENGTH:45 KV,FLAME RETARDANCE:5.0
SEC,TENSILE STRENGTH:15 N/MM2,LEAKAGE 10MAMP @ 11 KV
CONFIRMING TO IS:15652-2006
ELECMATS0004 100m
11
DISCHARGE ROD (EARTHING ROD) SUITABLE FOR 11 KV WITH
DR HEAD AND 16 SQ M EARTHING CABLE OF 3METER LENGTH
WITH CROCODILE EARTH CLAMP DR, FOR 11 KV/ 6.6 KV
SWITCHGEAR ROOM ELECGENE0336 2
12
SF6 GAS- 9 KG CYLINDER, PART NO. S4799040701, SPARE
SUITABLE FOR 145 KV / 245 KV,40 KA, SF6 BREAKER TYPE 3
AP,MAKE SIEMENS/ABB ELECGENE1102 1
13 12kV Siemens spares for 3AK type VCB & 3AH type
14
Conservator shutter valve for 35MVA/100MVA/25MVA transformer
(TSPL/CTR/SERGI)
2
100 MVA & 35MVA
same
15 P14NB Feeder protection Relay
ELECRELY0705 3
16
Discrepancy type control S/W with built- in LED & flasher Lamp; Model:-
MK-2311, Aux. Vol.= 110VDC, Knob size = 60mm dia. , 6trip + 3 close
& 3NAT+ 3NAC; cut out 42 mm, Make - Multimode
ELECGENE2043 2
132 kV & 220kV C& R
panel
17
EMENGENCY PUSH BUTTON LOCKOUT, MODEL - KRM- K-EPL -R
LARGE, MAKE KRM CORPORATION
ELECGENE2049 10
18 OLTC Spares
Review & offer
evaluation spares for
30/35MVA U/P and for
common spares as well.
Pending & Required Inventory
Location
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD new store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD store
220 kV SWYD CCR
220 kV SWYD CCR
220 kV SWYD CCR
132 kV SWYD
132 kV SWYD
132 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 kV SWYD
220 Kv SWYD
Central Store
Central Store
Central Store
Central Store
Central Store
Central Store
220Kv SWYD
Central Store
Central Store
Central Store
Central Store
Central Store
Central Store
Central Store
220 Kv SWYD
Indent no.- 314557
Indent no.- 316458
Indent no.- 316487
Indent no.- 316487
Indent no.- 316487
Indent no.- 316487
Indent no.- 316487
Indent no.- 316487
Indent no.- 321659
Indent no. - 315525
Pending & Required Inventory
S. No.
1
Segregation of separate DC source for HT panels 6.6kV & 132kV , SERGI
panel at LC-03 and separate logic for the system
2
Configuring new cable diff. Relay Siemens 7SD610 at 132kv tie Feeder at
220kV SWYD for inline with the system configuration
3
RAS - BWR line CB status feedback/ auto synch feature to be checked
ion Siemens HMI at 220kV SWYD
4
Oil replacement of TR-4 OLTC for lower BDV Value; GT-7 & 8 OLTC as
well . (Ref:- Oil Testing report_NDL)
5
U-09 & 10 132 kV 132kV CB inputs to Existing Siemens HMI at 220kV
SWYD
6 New DC lighting arrangement at 220kV CCR & U-09 & 10 LC
7 Load shedding Relay (df/dt) setting at LC-28 for U-X
8
Configuring Cable differential 7SG18 for 11kV U-09 & 10 O/G feeders and
U-09 & 10 crusher at 220kV SWYD.
9 35 MVA TR-2 TSPL Nitrogen fire protection system to be take in line.
10 35 MVA TR-2 NGR doors kept open; not properly enclosed.
11 HT Cable entry to U-09 & 10 Load centre covering & sheilding job
12 Intertripping of 35 MVA tr-1 & 2 11/132kV CB. Cable laying done.
13 132 kV B/C at 220kV SWYD to be taken in line. (System healthy)
14
Civil Jobs at near by 220kV SWYD CCR , gravelling , levelling , gardening
at 220kV SWYD to be done.
15
Replacement of 2x400 W HPSV fittings for Lighting Mast at 220 kV
SWYD with LED Lighting
16 New P&V commissioning job for U-09 & 10 LC at 220 kV SWYD.
17 Fire proof doors to be erected at U-09 & 10 LC
18
Rain water leakage from U-09 & 10 LC from Load centre Ceiling( water
proofing job.)
19 Colour code paint work at all sruructures of 220kV SWYD
20 Requirement of transformer Oil (1050Ltrs.)
21
Replacement of PT/CT/CB clamps of R-phase of 35 MVA tr-1 on
oppurtunity basis . Clamps Indented
22
245 kV CVT , 145 kV PT Make- Mehru faulty/burst out to be send to OEM
works for complete diagnosis & testing/ upgradation.
23
Secure Energy metering panel(DLMS protocol) with Energy meters &
access. to be send to Bihar GU.
24 Fencing covering at boundary nearby U-09 & 10 _35 MVA transformer
Pending jobs & Requirements
25 Commsisioning of P14NB relays at O/G feeders
26 145 kv Spare PT 0.2/3P/0.2 to be indented.
27 All Micom relay communication (x2, x3, x4) platform relays.
28 New marshalling panel for 25 MVA transformer-4 to be installed.
29 10/12.5 MVA transformer 6.6kV side Leakage from TB
30
Condition monitoring check points to be attended at 132kV & 220kV
(Thermography)
1 Disc insulator replacement job due to broken discs at Tower no.62
2 132 kV RAS- BWR Line CB Make ABB overhauling job.
3
Heat shrinkable sleeve insulation over Panther conductor at 132kV SWYD
nearby 132 kV gantry to tower no. 115
4
Line side Isolator replacement job in 132 kV Ras BWR line .
5
RTV Silicon rubber coating on PT/LA/CB/CT of 132kv Ras- BWR Line
RAS BWR Line JOBS to be arrested
O&M
O&M
O&M
O&M
O&M
O&M
O&M
Project
Project
Project
O&M
O&M
O&M
O&M
O&M
Project
Project
Project
O&M
O&M
O&M
O&M
O&M
Project
Pending jobs & Requirements
O&M
O&M
O&M
O&M
O&M
O&M
04th -July
2014
O&M
O&M
O&M
O&M
O&M
RAS BWR Line JOBS to be arrested
S.No. Material description Item Code Qty. Remarks Unit Rate
1 220 kV CT 300-400/1A, 0.2/5P/5P-PS/5P-PS, 4 core TRANSFMR0427 6
OLD; removed from 220kV Side TR-
1 & 2
250000
2 220 kV PT 220kv/sqrt(3)/110V, 3P/0.2/3P, 3 core TRANSFMR0428 5
OLD; removed from 220kV Side TR-
1 & 2
250000
3 220 kV CT 400-600/1A, 3 core, 0.2/5P/PS 6 250000
4 220 kV Tower material 25
For all the type of tower,material is
incomplete (approx. MT)
45000
5 APFC Panel (50kVAR*8) CAPABANK0010 4 300000
6 HT motor capacitor with inductor 7.2kV 178kVAR , 14.27 Amp CAPACITR0072 1 100000
7 HT motor capacitor with inductor 7.2kV 190kVAR , 15.24 Amp CAPACITR0072 1 100000
8
245kV SF6, 3150A,40kA/3s, Circuit Breaker with control panel having
control supply 110VDC, operating mechanism voltage-240VAC; Make
Siemens
1 5000000
9
ON LOAD TAP CHANGER, MAKE: CTR, TYPE:GQ16, MOTOR 415V,
CONTROL 110V, SERVICE VOLTAGE 132KV, NORMAL WORKING
CURRENT 61A, MAX. RATED THROUGH CURRENT: 300A, PHASES-
3, FREQ.-50HZ, STEP VOLTAGE 953VOLTS
ELECGENE1212 1 10/12.5 MVA Trafo, 450000
TOTAL
Amount
1500000
1250000
1500000
1125000
1200000
100000
100000
5000000
450000
12225000
Disc insulator replacement job due to broken discs at Tower no.62
and tower no. 97 due to flashover
One disc insulator damaged of one of the phases at tower no. 100
B-phase cross arm bend of tower no. 96
Arcing horn missing in string insulators in one of the phases in tower
no. 11 & 34
One disc insulator damaged in Y- phase at tower no. 15

You might also like