Alternator Data Sheet PI734F

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8
At a glance
Powered by AI
The document provides technical specifications and performance curves for the PI734F industrial generator. It describes the generator components and design, efficiency curves, short circuit data, and dimensions.

Synchronous generators have a rotating magnetic field. They are separately excited by a permanent magnet generator (PMG) which provides clean power to the main exciter. The main exciter output is fed to the main rotor through a rectifier.

The MX341 AVR is two phase sensed with a voltage regulation of ±1%. The MX321 AVR is 3 phase rms sensed with a voltage regulation of 0.5% rms. The MX321 needs a current transformer for load sharing, while the MX341 does not.

PI734F - Technical Data Sheet

PI734F
SPECIFICATIONS & OPTIONS
STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards such as BS5000, VDE 0530, NEMA MG1-32, IEC60034, CSA C22.2-100, AS1359. Other standards and certifications can be considered on request. DESCRIPTION The STAMFORD PI range of synchronous ac generators are brushless with a rotating field. They are separately excited by the STAMFORD Permanent Magnet Generator (PMG). This is a shaft mounted, high frequency, pilot exciter which provides a constant supply of clean power via the Automatic Voltage Regulator (AVR) to the main exciter. The main exciter output is fed to the main rotor, through a full wave bridge rectifier, protected by surge suppression. VOLTAGE REGULATORS The PI range generators, complete with a PMG, are available with one of two AVRs. Each AVR has soft start voltage build up and built in protection against sustained over-excitation, which will de-excite the generator after a minimum of 8 seconds. Underspeed protection (UFRO) is also provided on both AVRs. The UFRO will reduce the generator output voltage proportional to the speed of the generator below a presettable level. The MX341 AVR is two phase sensed with a voltage regulation of 1 %. (see the note on regulation). The MX321 AVR is 3 phase rms sensed with a voltage regulation of 0.5% rms (see the note on regulation). The UFRO circuit has adjustable slope and dwell for controlled recovery from step loads. An over voltage protection circuit will shutdown the output device of the AVR, it can also trip an optional excitation circuit breaker if required. As an option, short circuit current limiting is available with the addition of current transformers. Both the MX341 and the MX321 need a generator mounted current transformer to provide quadrature droop characteristics for load sharing during parallel operation. Provision is also made for the connection of the STAMFORD power factor controller, for embedded applications, and a remote voltage trimmer. WINDINGS & ELECTRICAL PERFORMANCE All generator stators are wound to 2/3 pitch. This eliminates triplen (3rd, 9th, 15th ) harmonics on the voltage waveform and is found to be the optimum design for trouble-free supply of non-linear loads. The 2/3 pitch design avoids excessive neutral currents sometimes seen with higher winding pitches. A fully connected damper winding reduces oscillations during paralleling. This winding, with the 2/3 pitch and carefully selected pole and tooth designs, ensures very low levels of voltage waveform distortion. TERMINALS & TERMINAL BOX Standard generators feature a main stator with 6 ends brought out to the terminals, which are mounted on the frame at the non-drive end of the generator. A sheet steel terminal box contains the AVR and provides ample space for the customers' wiring and gland arrangements. It has removable panels for easy access. SHAFT & KEYS All generator rotors are dynamically balanced to better than BS6861:Part 1 Grade 2.5 for minimum vibration in operation. Two bearing generators are balanced with a half key. INSULATION/IMPREGNATION The insulation system is class 'H', and meets the requirements of UL1446. All wound components are impregnated with materials and processes designed specifically to provide the high build required for static windings and the high mechanical strength required for rotating components. QUALITY ASSURANCE Generators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001. NOTE ON REGULATION The stated voltage regulation may not be maintained in the presence of certain radio transmitted signals. Any change in performance will fall within the limits of Criteria 'B' of EN 61000-6-2:2001. At no time will the steady-state voltage regulation exceed 2%.
Note: Continuous development of our products entitles us to change specification details without notice, therefore they must not be regarded as binding. Front cover drawing is typical of the product range.

PI734F
WINDING 312
CONTROL SYSTEM A.V.R. VOLTAGE REGULATION SUSTAINED SHORT CIRCUIT INSULATION SYSTEM PROTECTION RATED POWER FACTOR STATOR WINDING WINDING PITCH WINDING LEADS MAIN STATOR RESISTANCE MAIN ROTOR RESISTANCE EXCITER STATOR RESISTANCE EXCITER ROTOR RESISTANCE R.F.I. SUPPRESSION WAVEFORM DISTORTION MAXIMUM OVERSPEED BEARING DRIVE END BEARING NON-DRIVE END 1 BEARING WEIGHT COMP. GENERATOR WEIGHT WOUND STATOR WEIGHT WOUND ROTOR WR INERTIA SHIPPING WEIGHTS in a crate PACKING CRATE SIZE 3840 kg 1908 kg 1609 kg 49.3409 kgm 3913kg 216 x 105 x 154(cm) 50 Hz TELEPHONE INTERFERENCE COOLING AIR VOLTAGE STAR kVA BASE RATING FOR REACTANCE VALUES Xd DIR. AXIS SYNCHRONOUS X'd DIR. AXIS TRANSIENT X''d DIR. AXIS SUBTRANSIENT Xq QUAD. AXIS REACTANCE X''q QUAD. AXIS SUBTRANSIENT XL LEAKAGE REACTANCE X2 NEGATIVE SEQUENCE X0 ZERO SEQUENCE REACTANCES ARE SATURATED T'd TRANSIENT TIME CONST. T''d SUB-TRANSTIME CONST. T'do O.C. FIELD TIME CONST. Ta ARMATURE TIME CONST. SHORT CIRCUIT RATIO 380/220 2020 2.93 0.18 0.13 1.89 0.26 0.03 0.19 0.02 THF<2% 2.69 m/sec 5700 cfm 400/231 2080 2.73 0.17 0.12 1.75 0.25 0.03 0.17 0.02 415/240 2080 2.53 0.15 0.11 1.63 0.23 0.03 0.16 0.02 440/254 2040 2.21 0.13 0.10 1.42 0.20 0.03 0.14 0.02 416/240 2340 3.54 0.21 0.16 2.28 0.32 0.04 0.23 0.03
2

SEPARATELY EXCITED BY P.M.G. MX341 1% MX321 0.5 % With 4% ENGINE GOVERNING

REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7) CLASS H IP23 0.8 DOUBLE LAYER LAP TWO THIRDS 6 0.00076 Ohms PER PHASE AT 22C STAR CONNECTED 2.31 Ohms at 22C 17.5 Ohms at 22C 0.048 Ohms PER PHASE AT 22C BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0% 2250 Rev/Min BALL. 6232 C3 BALL. 6319 C3 2 BEARING 3807 kg 1908 kg 1565 kg 48.424 kgm2 3876kg 216 x 105 x 154(cm) 60 Hz TIF<50 3.45 m/sec 7300 cfm 440/254 2500 3.38 0.20 0.15 2.18 0.31 0.04 0.22 0.03 460/266 2550 3.16 0.19 0.14 2.03 0.29 0.04 0.20 0.02 480/277 2600 2.96 0.18 0.13 1.90 0.27 0.03 0.19 0.02

VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED 0.154s 0.02s 2.54s 0.02s 1/Xd

50 Hz

PI734F
Winding 312 THREE PHASE EFFICIENCY CURVES

PI734F
Winding 312 THREE PHASE EFFICIENCY CURVES

60 Hz

PI734F
Winding 312 Locked Rotor Motor Starting Curve

50
30

Hz

346V

380V

400V

415V

440V

25

20
PER CENT TRANSIENT VOLTAGE DIP

15

10

0 0 1000 2000 3000


LOCKED ROTOR kVA

4000

5000

6000

60
30

Hz

380V

416V

440V

460V

480V

25

20
PER CENT TRANSIENT VOLTAGE DIP

15

10

0 0 1000 2000 3000 4000 5000 6000 7000


LOCKED ROTOR kVA

PI734F
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed Based on star (wye) connection.

50 Hz

100000

SYMMETRICAL ASYMMETRICAL

CURRENT (Am ps)

10000

1000 0.001

0.01

TIME (secs)

0.1

10

Sustained Short Circuit = 6,850 Amps

60 Hz

100000

SYMMETRICAL ASYMMETRICAL

CURRENT (Am ps)

10000

1000 0.001

0.01

TIME (secs)

0.1

10

Sustained Short Circuit = 8,900 Amps


Note 1 The following multiplication factors should be used to adjust the values from curve between time 0.001 seconds and the minimum current point in respect of nominal operating voltage :
Voltage 380v 400v 415v 440v

Note 2 The following multiplication factor should be used to convert the values calculated in accordance with NOTE 1 to those applicable to the various types of short circuit :
3-phase 2-phase L-L 1-phase L-N x 1.30 x 3.20 x 2.50 2 sec.

50Hz

Factor x 1.00 x 1.05 x 1.09 x 1.16

Voltage 416v 440v 460v 480v

60Hz

Factor x 1.00 x 1.06 x 1.10 x 1.15

Instantaneous x 1.00 x 0.87 Minimum x 1.00 x 1.80 Sustained x 1.00 x 1.50 Max. sustained duration 10 sec. 5 sec. All other times are unchanged

The sustained current value is constant irrespective of voltage level

Note 3 Curves are drawn for Star (Wye) connected machines.

PI734F
Winding 312 / 0.8 Power Factor RATINGS
Class - Temp Rise Cont. F - 105/40C 380 400 1935 1548 96.5 1604 415 1935 1548 96.6 1602 440 1900 1520 96.6 1573 Cont. H - 125/40C 380 2020 1616 96.3 1678 400 2080 1664 96.4 1726 415 2080 1664 96.4 1726 440 2040 1632 96.5 1691 Standby - 150/40C 380 2105 1684 96.2 1751 400 2170 1736 96.3 1803 415 2170 1736 96.4 1801 440 2125 1700 96.5 1762 Standby - 163/27C 380 2165 1732 96.2 1800 400 2230 1784 96.2 1854 415 2230 1784 96.3 1853 440 2185 1748 96.4 1813

50Hz

Star (V)

kVA 1880 kW 1504 Efficiency (%) 96.5 kW Input 1559

60Hz

Star (V)

416

440 2325 1860 96.5 1927

460 2370 1896 96.5 1965

480 2420 1936 96.6 2004

416 2340 1872 96.4 1942

440 2500 2000 96.4 2075

460 2550 2040 96.4 2116

480 2600 2080 96.5 2155

416 2435 1948 96.3 2023

440 2600 2080 96.3 2160

460 2650 2120 96.4 2199

480 2705 2164 96.4 2245

416 2505 2004 96.2 2083

440 2675 2140 96.2 2225

460 2730 2184 96.3 2268

480 2785 2228 96.3 2314

kVA 2180 kW 1744 Efficiency (%) 96.5 kW Input 1807

DIMENSIONS

2004 Newage International Limited. Reprinted with permission of N.I. only. Printed in England.

Barnack Road Stamford Lincolnshire PE9 2NB Tel: 00 44 (0)1780 484000 Fax: 00 44 (0)1780 484100 Website: www.newage-avkseg.com TD_PI734F.GB_05.04_02_GB