HVAC-Final Cleaned
HVAC-Final Cleaned
HVAC-Final Cleaned
HEATING
VENTILATION
AIR CONDITIONING
PREVENTATIVE
MAINTENANCE
MANUAL
CONTENTS
SECTION
3. COOLING TOWER
6. BOILER
7. HEAT EXCHANGER –
MAINLY IN OFFICE BUILDINGS
8. FURNACE –
TOWNHOMES/APARTMENTS
9. HEAT PUMP
SECTION 1
ELECTRIC – HEAT EXCHANGER/
COMPRESSOR AND COOLING
SPRING AND SUMMER MAINTENANCE TASKS
• Check condition of belts and pulleys for fraying and breakage, and replace as needed.
• Check refrigerant charge with pressure gauge and inspect for leaks if charge is low.
Add additional refrigerant as required.
• Check condition of belts and pulleys for fraying and breakage, and replace as needed.
• Check operation of fan and blower motor with static pressure reading device and
adjust if needed.
• Inspect ignition and burner assembly for dirt, dust, and grime, and clean as required.
• Inspect heat exchanger for dirt and corrosion. Call professional heat exchanger cleaner
if any signs of dirt, grime, or corrosion are visible.
• Clean dirt, leaves and debris from inside cabinet. Keep these areas cleaned at all times.
• Inspect coil and cabinet for dirt and corrosion and unusual wear – clean as needed.
• All control box and electrical parts should be checked for wear or damage by checking
conductivity. Report low conductivity readings to a licensed HVAC contractor.
• Inspect unit for proper refrigerant level using a pressure gauge and add new refrigerant
if necessary.
• Inspect base pan for restricted drain openings – remove obstructions as necessary.
• Inspect fan motor and fan blades for fraying and breakage – on older models lubricate
as needed.
• Inspect compressor and associated tubing for leaks and bad connections. Report leaks
and bad connections to a licensed HVAC contractor.
INDOOR UNITS
• Check combustion blower housing for lint and debris and clean as necessary.
• Inspect for gas leaks in gas furnaces. Report leaks immediately to a licensed HVAC
contractor.
• Clean blower assembly (includes blower housing, blower wheel and motor).
• On older models, lubricate motor and inspect and replace fan belt that is frayed or
showing signs of breakage.
• Inspect evaporator coil, drain pan and condensate drain lines for clogging, leaks, and
cleanliness. Unclog, repair leaks, and clean as necessary.
• Inspect heat exchanger or heating elements for damage. Report damage to a licensed
HVAC contractor.
• Inspect flue system – check for proper attachment to the furnace, any dislocated
sections, and for signs of corrosion. Replace/repair if necessary.
• Inspect control box, associated controls, wiring and connections for conductivity and
report any conductivity issues to a licensed HVAC contractor.
• Inspect conditioned airflow system (ductwork) – check for and seal leaks.
• Check vent system for a whistling noise. If present, report to a licensed HVAC contractor.
SECTION 2
GAS FIRED – HEAT AND COOLING
• Inspect the area near the unit to be sure that there is no combustible material nearby.
Clearance from combustibles should be at least 3 feet.
• Remove any dirt, dust, or other foreign matter from the burners using a wire brush and/
or compressed air. Ensure that all parts are unobstructed. Inspect and clean pilot burner if
necessary with a soft brush.
• Check and test the operational functions of all safety devices supplied with your unit
included in your System Guide.
• Turn off the manual gas valve and electrical power to the gas duct furnace to verify
operational status.
• To clean or replace the main burners, remove the bottom panel and compress the
spring by moving the burner toward the manifold. Slide the opposite end of the burner
downward from the locating slot while retaining spring is still compressed. Pull the
burners away from the manifold.
• With the burners removed, wire brush the inside surfaces of the heat exchanger.
• Check all gas control valves and pipe connections for leaks. Report leaks to a licensed
contractor immediately.
• Check the operation of the automatic gas valve by lowering the setting of the thermostat,
stopping the operation of the gas duct furnace. The gas valve should close tightly,
completely extinguishing the flame on the main burners.
• Inspect the blower section of the system for dust and dirt, and clean as necessary with
compressed air.
SECTION 4
CHILLER – ELECTRIC AND GAS FIRED
• With a pressure washer, clean tubes annually for efficient heat transfer.
• Treat condenser water to prevent scale and corrosion with chemicals as prescribed by
manufacturer.
• Analyze compressor oil - Send a sample of the lubrication oil to a laboratory for a
“spectrometric” chemical analysis once a year.
• Check oil level and operation of the purge pump. Refill oil to the level required
by manufacturer’s specification.
• Visually inspect chiller for leaks and report leaks to a licensed contractor .
• Check the lithium bromide solution to adjust inhibitors, and add a lithium
bromide solution as required by manufacturer’s specification.
• Check water flows and interlocks for clogs, and clear clogs.
These maintenance items should be done once a year by a licensed heating contractor
between heating seasons (May to September):
• Clean low water cut-off.
• Check fuel oil levels.
• Inspect and clean fireside surfaces.
• Inspect all burner refractory material.
• Inspect all gaskets for leaks.
• Inspect and test all system valves.
• Recalibrate all operating controls.
• Clean condensate receiver.
• Inspect electrical terminals.
PERIODIC MAINTENANCE
These items should be addressed by the building’s maintenance staff on a continual basis, or
as often as indicated below:
• Clean oil filters at least twice a week.
• Check oil pressure reading at the burners quarterly. Report irregularities to a licensed
boiler contractor.
• Keep sight glasses clean. This allows for a clear view of the burner flame and any
carbon build-up on the boiler’s combustion chamber.
• Keep air filters clean.
• Flush drain low water cut-offs/sidearm oil pre-heater (twice a week).
• Conduct boiler bottom blowdown to clear sludge and sediment, control high water, and
control chemical treatment concentrations (monthly or as needed).
• Inspect smoke alarm on a weekly basis:
• Maintain a rigorous boiler chemical feed water treatment program, based on
manufacturer’s specifications.
• Maintain a boiler room log to record any problems and routine maintenance.
• Conduct pipe inspection program to ensure all pipes are pitched in the direction of
steam source (one-pipe steam systems) or condensate drainage (two-pipe systems).
SECTION 8
FURNACE –
TOWNHOMES/APARTMENTS
TURN THE FURNACE AND GAS OFF
After visual inspection, turn the thermostat off and flip the power switch off on the
furnace (or turn off the breaker if the furnace doesn’t have a switch). It’s very important
that if you are performing any kind of gas furnace maintenance that you turn off the
gas line. The gas line should have shut off valve near your gas meter. After cleaning or
inspection of the furnace, replace the furnace panels and turn the furnace power and
gas back on. You may need to relight the pilot light. Inspect and change the filter if dirty.
• Remove foliage and clutter from around the outdoor unit weekly.
• Check ducts, filters, blower, and indoor coil for dirt and other obstructions, and
clean as necessary.
• Check for refrigerant leaks and report any leaks to a licensed HVAC contractor.
• Clean the supply and return registers and straighten their fins if bent.
• Lubricate motors and inspect belts for tightness and wear, and replace any
belts that are frayed or cracked.
• Remove foliage and clutter from around the outdoor unit weekly.
• Check ducts, filters, blower, and outdoor coil for dirt, other obstructions and
clean as necessary.
• Check for refrigerant leaks. Report any leaks to a licensed HVAC contractor.
• Clean the supply and return registers and straighten their fins if bent.
• Lubricate motors, and inspect belts for tightness and wear. Repair any belts that
are frayed or cracked.
• Check that all moving parts are free of cracks and excessive wear. Report any
damages to a licensed HVAC contractor.
• Check that dampers are free of dirt accumulations, and clean as necessary.
• Check that coils are cleaned at least every six months by a licensed HVAC
contractor.
• Check that all coils, refrigerant lines, valves, fittings, etc. are free of leaks.
Report leaks to a licensed contractor.
• Check that condensation pans and drains are rust free; wire brush and paint
over any corrosion.
• Check that bearing collar set screws on fan shaft are tight and tighten screws
as needed.
• Check that damper actuators and linkages are operational and aligned and
correct as needed.
• Check that all mechanical connections and dampers are properly lubricated
and lubricate as needed.
• Check that all belts are free of wear and cracks and replace belts that are
frayed or cracked.
• Check the drain hose for blockages and clear blockages with compressed air.