1PB CIRCUIT

CIRCUIT SWITCHES LOAD DESCRIPTION WATTS VOLTS AMPERES WIRE SIZE


BREAKER mm2 THHN
W V A
M NO. Sa Sab Sabc 2Sa 2Sab C.O L.O DES AT

2-# 8 MM2 THHN/THWN CU. WIRE & 1 3 3 - 2 - 12 LED 300 230 1.304 15 2-2.0

1-# 8 MM2 THHN/THWN CU. WIRE 2 4 - 1 - 1 16 LED 400 230 1.740 15 2-3.50

PB (GROUNDING) IN 25 MM DIA. IMC PIPE 3 RANGE 3000 230 13.04 20 2-3.50

4 REF 200 230 0.90 20 2-3.50


40A
5 9 2250 230 9.78 20 2-3.50
C1 15A 15A C2
6 SPARE 1000
C3 15A 20A C4
TOTAL 7150
C5 20A SPARE C6
FIRST 3000VA OR LESS AT 100% : 2375 ITOT = (7150 / 230 V ) X 100% DF = 31.09amps
RANGE 3000VA AT 80% D.F. : 2400 USE: 2-8mm2 THHN FOR SERVICE FEEDER IN 20mm Ø PVC
NET TOTAL : 4775 40 AMP FOR SERVICE EQUIPMENT

2PB CIRCUIT
CIRCUIT SWITCHES LOAD DESCRIPTION WATTS VOLTS AMPERES WIRE SIZE
BREAKER mm2 THHN
W V A
M NO. Sa Sab Sabc 2Sa 2Sab C.O L.O DES AT
1 2 2 - 1 - 13 LED 325 230 1.41 15 2-2.0
2-# 8 MM2 THHN/THWN CU. WIRE &
1-# 8 MM2 THHN/THWN CU. WIRE 2 3 2 - 2 - 15 LED 375 230 1.630 15 2-3.50

2PB (GROUNDING) IN 25 MM DIA. IMC PIPE 3 9 2250 230 9.78 20 2-3.50

4 SPARE 1000 230


40A
TOTAL 3950
C1 15A 15A C2
ITOT = (3950 / 230 V ) X 100% DF = 17.17amps
C3 20A SPARE C4
USE: 2-8mm2 THHN FOR SERVICE FEEDER IN 20mm Ø PVC
40 AMP FOR SERVICE EQUIPMENT

3PB CIRCUIT
CIRCUIT SWITCHES LOAD DESCRIPTION WATTS VOLTS AMPERES WIRE SIZE
BREAKER mm2 THHN
W V A
M NO. Sa Sab Sabc 2Sa 2Sab C.O L.O DES AT
1 1 3 - - 1 18 LED 450 230 1.95 15 2-2.0
2-# 8 MM2 THHN/THWN CU. WIRE &
1-# 8 MM2 THHN/THWN CU. WIRE 2 8 2000 230 8.70 20 2-3.50

3PB (GROUNDING) IN 25 MM DIA. IMC PIPE 3 SPARE 1000


4 SPARE
40A
TOTAL 3450
C1 15A 20A C2
ITOT = (3450 / 230 V ) X 100% DF = 15amps
C3 SPARE SPARE C4
USE: 2-8mm2 THHN FOR SERVICE FEEDER IN 20mm Ø PVC
40 AMP FOR SERVICE EQUIPMENT