Daikin RXC-B (R32) Manual Service
Daikin RXC-B (R32) Manual Service
Daikin RXC-B (R32) Manual Service
Service
Manual
Inverter Split
Wall Mounted Type (A)FTXC Series
DAMA-SM-20-002
[Applied Models]
z Inverter Split : Heat Pump Unit
DAMA-SM-20-002
Introduction .................................................................................... 1
1. Safety Cautions.......................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers.............................2
1.2 Warnings and Cautions Regarding Safety of Users.................................8
2. Icons Used ............................................................................................10
3. Revision History ....................................................................................11
Part 2 Specifications.................................................................... 18
1. Specification Data .................................................................................19
2. Functions...............................................................................................25
i Table of Contents
DAMA-SM-20-002
Table of Contents ii
DAMA-SM-20-002
Introduction
1. Safety Cautions.......................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers.............................2
1.2 Warnings and Cautions Regarding Safety of Users.................................8
2. Icons Used ............................................................................................10
3. Revision History ....................................................................................11
Introduction 1
Safety Cautions DAMA-SM-20-002
1. Safety Cautions
Be sure to read the following safety cautions before conducting repair work.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer.
This manual is for the This appliance is
person in charge of filled with R-32.
maintenance and
inspection.
Caution Items The caution items are classified into Warning and Caution. The Warning items are
especially important since death or serious injury can result if they are not followed closely. The
Caution items can also lead to serious accidents under some conditions if they are not
followed. Therefore, be sure to observe all the safety caution items described below.
Pictograms This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown in the illustration or near the symbol.
2 Introduction
DAMA-SM-20-002 Safety Cautions
Warning
Do not turn the air conditioner on or off by plugging in or
unplugging the power cable.
Plugging in or unplugging the power cable to operate the equipment may
cause an electrical shock or fire.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
Caution
Do not repair electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Be sure to turn off the power switch and unplug the power cable
when cleaning the equipment.
The internal fan rotates at a high speed, and may cause injury.
Introduction 3
Safety Cautions DAMA-SM-20-002
Safety Checklist
Checking the area
Before beginning work, conduct safety checks to minimise the risk of ignition. When
repairing the refrigerating system, take the following precautions before work.
Work procedure
Work shall be conducted under a controlled procedure so as to minimise the risk of working
in the presence of R-32 or vapour.
No ignition sources
During work on a refrigeration system which involves exposing any piping work that contains
or has contained R-32, any sources of ignition shall not be used in a manner that may lead
to the risk of fire or explosion. All possible ignition sources, including cigarette smoking,
should be kept at a safe distance from the site of installation, repairing, or removing space.
Before starting work, the area around the equipment shall be examined to make sure that
there are no flammable hazard or ignition risks. No Smoking signs shall be displayed.
Ventilated area
Ensure that the working area is open or that it is adequately ventilated before work.
Adequate ventilation shall be maintained during the entire period of work.
The ventilation should disperse any released refrigerant and preferably discharge it into the
external atmosphere.
4 Introduction
DAMA-SM-20-002 Safety Cautions
Wiring
Check that wiring is not subject to wear, corrosion, excessive pressure, vibration, sharp
edges or any other adverse environmental effects. The check shall also take into account
the effects of ageing or continuous vibration from sources such as compressors or fans.
Detecting of R-32
Under no circumstances shall potential sources of ignition be used in the search for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall
not be used.
Introduction 5
Safety Cautions DAMA-SM-20-002
Leak detection fluids are suitable for use with most refrigerants but the use of detergents
containing chlorine shall be avoided as the chlorine may react with the refrigerant and
corrode the copper piping work.
If a leak is suspected, all naked flames shall be removed or extinguished.
If a refrigerant leakage which requires brazing is found, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the system
remote from the point of the leakage. Oxygen free nitrogen (OFN) shall then be purged
through the system both before and during the brazing process.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and that
there is ventilation available.
Charging procedures
In addition to conventional charging procedures, the following requirements shall be met.
Ensure that the charging equipment to be used is not contaminated by different refrigerants.
Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained
in them.
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed before charging the system with
refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system.
Before recharging, the system shall be tested for leakage with OFN. On completion of
charging, the system shall be tested before commissioning. Follow up leakage test shall be
carried out before leaving the site.
6 Introduction
DAMA-SM-20-002 Safety Cautions
Labelling
Equipment shall be labelled stating that it has been decommissioned and emptied of
refrigerant. The label shall be dated and signed. Ensure that there are labels on the
equipment stating the equipment contains R-32.
Refrigerant recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended to conduct training so that all refrigerants can be removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are used.
Ensure that the correct number of cylinders for holding the total system charge are available.
All cylinders to be used must be designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be equipped
with a pressure relief valve and associated shut-off valves in good working order. If possible,
empty recovery cylinders shall be cooled in a separate place before recovery is conducted.
The recovery equipment shall be in good working order with instructions concerning the
equipment at hand, and shall be suitable for the recovery of R-32. In addition, a set of
calibrated weighing scales shall be available and in good working order. Hoses shall be
equipped with leak-free disconnect couplings and in good condition. Before using the
recovery device, check that it has undergone proper maintenance, that it is in satisfactory
working order, and that any associated electrical components are sealed to prevent ignition
in the event of a refrigerant leakage. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
cylinder, with the relevant Waste Transfer Note attached. Do not mix refrigerants in recovery
units and especially not in cylinders.
If compressors or compressor oil are to be removed, ensure that the refrigerant melted into
the oil has been evacuated to an acceptable level to make certain that R-32 does not remain
within the oil. The evacuation process shall be carried out before returning the compressor
to the supplier. Only electric heating to the compressor body shall be employed to accelerate
this process. Oil drained from the system shall be treated safely.
Introduction 7
Safety Cautions DAMA-SM-20-002
Be sure to use parts listed in the service parts list of the applicable
model and appropriate tools to conduct repair work. Never attempt
to modify the equipment.
The use of inappropriate parts or tools may cause an electrical shock,
excessive heat generation or fire.
If the power cable and lead wires are scratched or have deteriorated,
be sure to replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and
repair it before charging the refrigerant. After charging the
refrigerant, make sure that there is no leak.
If the leaking point cannot be located and the repair work must be
stopped, be sure to pump-down, and close the service valve, to prevent
refrigerant gas from leaking into the room. Refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such
as those from fan type and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation
site has sufficient strength to withstand the weight of the
equipment.
If the installation site does not have sufficient strength or the installation
work is not conducted securely, the equipment may fall and cause injury.
8 Introduction
DAMA-SM-20-002 Safety Cautions
Warning
Check to make sure that the power cable plug is not dirty or loose,
then insert the plug into a power outlet securely.
If the plug is dusty or has a loose connection, it may cause an electrical
shock or fire.
Caution
Installation of a leakage breaker is necessary in some cases
depending on the conditions of the installation site, to prevent
electrical shocks.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause water to enter the room and wet the furniture
and floor.
Introduction 9
Icons Used DAMA-SM-20-002
2. Icons Used
The following icons are used to attract the attention of the reader to specific information.
Icon Type of Description
Information
Warning Warning is used when there is danger of personal injury.
Warning
Caution Caution is used when there is danger that the reader,
Caution through incorrect manipulation, may damage equipment,
lose data, get an unexpected result or have to restart (part
of) a procedure.
Note Note provides information that is not indispensable, but
Note may nevertheless be valuable to the reader, such as tips
and tricks.
Reference Reference guides the reader to other places in this binder
Reference or in this manual, where he/she will find additional
information on a specific topic.
10 Introduction
DAMA-SM-20-002 Revision History
3. Revision History
Month/Year Version Revised contents
11/ 2020 DAMA-SM-20-002 First edition
Introduction 11
DAMA-SM-20-002
Part 1
General Information
1. What is Inverter? ...................................................................................13
2. Inverter Basics ......................................................................................14
3. Names and Functions of Inverter Components.....................................15
4. Applicable Models .................................................................................16
Chapter
1 Basics of Inverter Control
1. What is Inverter?
Maybe you have seen or heard the word “inverter” in various products such as inverter lights, inverter washing
machines, or inverter refrigerators.
The inverter is frequency converting equipment, indicating the technology to control voltage, current, and
frequency.
Inverter air conditioners can “save energy” since the inverter technology allows precise control of the compressor,
which plays a key role to cool or heat air, or the number of revolutions of the motor to drive fans. Non-inverter air
conditioners can only provide simple ON/OFF operation for temperature control, in other words, operation stops
when the set temperature is reached and starts when the temperature rises (or falls, in the case of heating).
Inverter air conditioners enable full-power operation until the set temperature is reached and then switching to
low-speed operation once it is reached, resulting in reduced power consumption compared to non-inverter air
conditioners.
7HPS
5DSLGFRROLQJ 6PDOOWHPS
GLíHUHQFH 6RPHZKDWKRW
&RPIRUWDEOH
6HW ,QYHUWHU
WHPS
1RQLQYHUWHU
7RRFROG
2SHUDWLRQVWDUWV7LPH
,QYHUWHUDLUFRQGLWLRQHUVKDYHDODUJH
QXPEHURIFRPSRQHQWVZKLFK
PDNHVVHUYLFHGLDJQRVLVGLîFXOW
7KHUHIRUHWKHLQYHUWHUGLDJQRVWLF
WHFKQLTXHLVFUXFLDO
1. Time until the room temperature 1. Relatively takes time due to 1. Takes short time by increasing capacity
reaches the set temperature fixed capacity
2. Changes in temperature after 2. Large changes due to 2. Small changes due to operating capacity
the set temperature is reached operation ON/OFF responding to the load (comfortable)
3. Inrush current when compressor 3. 5-6 times of rated current 3. 1.5 times of rated current due to precise
starts up current control
4. Heating operation 4. Performance decreases 4. Increased rotation speed makes up for
characteristics at low outdoor air decreased performance
temperature
5. Defrost operation time 5. Relatively takes time due to 5. Operation at full capacity makes it short
fixed capacity
6. Apparatus configuration 6. Relatively simple
7. Service diagnosis 7. Relatively easy
General Information 13
Inverter Basics DAMA-SM-20-002
2. Inverter Basics
An inverter is a device to convert DC (direct current) into AC (alternating current).
For air conditioners, an inverter is a device to convert current from commercial AC power supply to AC having an
arbitrary frequency and voltage, including the converter function to convert AC into DC. The inverter freely varies the
rotation speed of the compressor motor.
$& '&
/RZIUHTXHQF\ +LJKIUHTXHQF\
6PDOOQXPEHURIUHYV /DUJHQXPEHURIUHYV
,QYHUWHUIUHHO\YDULHV
WKHURWDWLRQVSHHGRI
$& WKHPRWRU
&RPPHUFLDO$&
SRZHUVXSSO\ '&9ROWDJH
9DULDEOHYROWDJH
/
$& 1
3RZHU 9DULDEOHIUHTXHQF\
0RWRU
0RGXOH $&
'&
'%
−
&RQYHUWLQJ$& &RQYHUWLQJ'&
LQWR'& LQWR$&
&RQYHUWHU ,QYHUWHU
14 General Information
DAMA-SM-20-002 Names and Functions of Inverter Components
,QYHUWHU
FRQWUROOHU
Name Function
(1)Diode module Rectifies AC into DC
ڀ
(2)Smoothing capacitor Smooths out pulsating
current by charging and
discharging into
smoothed DC ڀ
(3)Reactor Reduces pulsating
current
ڀ
(4)Power module (IPM) Chops DC at high speed
into sine-wave AC
ڀ
(5)Inverter controller Generates 1/0 digital
signals for converting DC
into AC from operation/ 8 2)) 21
frequency commands and
sends them out to IPM 9 2)) 21
: 2)) 21
General Information 15
Applicable Models DAMA-SM-20-002
4. Applicable Models
Nomenclature
FTXC20BV1B RXC20BV1B
FTXC25BV1B RXC25BV1B
FTXC35BV1B RXC35BV1B
FTXC50BV1B RXC50BV1B
FTXC60BV1B RXC60BV1B
FTXC71BV1B RXC71BV1B
1Phase, 220-240V, 50Hz
ATXC20BV1B ARXC20BV1B
ATXC25BV1B ARXC25BV1B
ATXC35BV1B ARXC35BV1B
ATXC50BV1B ARXC50BV1B
ATXC60BV1B ARXC60BV1B
ATXC71BV1B ARXC71BV1B
16 General Information
DAMA-SM-20-002 Applicable Models
Nomenclature
Indoor Unit
Definition Description
Market B : Europe
Outdoor Unit
Definition Description
Market B : Europe
Remark:
*Capacity value under Nomenclature is an indication.
Please refer to Engineering and Physical Data for exact capacity value.
General Information 17
DAMA-SM-20-002
Part 2
Specifications
1. Specification Data .................................................................................19
2. Functions...............................................................................................25
Part 2 Specifications 18
Specification Data DAMA-SM-20-002
1. Specification Data
INDOOR UNIT FTXC20B FTXC25B
MODEL RXC20B RXC25B
OUTDOOR UNIT
Cooling Heating Cooling Heating
kW 2.00 (1.30 ~ 3.00) 2.50 (1.30 ~ 4.00) 2.56 (1.30 ~ 3.00) 2.84 (1.30 ~ 4.00)
Rated Capacity (Min. ~ Max.)
Btu/h 6800 (4400 ~ 10200)8500 (4400 ~ 13600) 8700 (4400 ~ 10200) 9700 (4400 ~ 13600)
Rated Running Current (Min. ~ Max.) A 3.43 (1.86 ~ 5.13) 3.16 (1.74 ~ 5.95) 3.47 (1.86 ~ 5.13) 3.45 (1.74 ~ 5.95)
Rated Power Consumption (Min. ~ Max.) W 595 (300 ~ 1150) 670 (275 ~ 1350) 765 (300 ~ 1150) 750 (275 ~ 1350)
EER W/W 3.36 N/A 3.35 N/A
SEER 6.89 N/A 6.84 N/A
COP W/W N/A 3.73 N/A 3.79
SCOP (Average Climate) N/A 4.40 N/A 4.45
SCOP (Warm Climate) N/A 5.78 N/A 5.81
Power Factor (Rated) 0.754 0.922 0.959 0.945
Piping Liquid mm 6.4
Connections Gas mm 9.5
Type R32
Refrigerant
Charge kg 0.55
Max. Interunit Piping Length m 20
Max. Interunit Height Difference m 15
INDOOR UNIT FTXC20B FTXC25B
Front Panel Colour WHITE
Turbo CFM 410
High CFM 380
Airflow Rate Medium CFM 310
Low CFM 230
Quiet CFM 190
Sound Pressure Level (H/M/L/Q) dBA 38/33/26/20
Type CROSS FLOW
Fan
Drive DIRECT
Type DIRECT CURRENT
Motor Output W 38
Fan Motor
Running Current (Rated) A 0.14
Power Consumption (Rated) W 16
Air Direction Control UP, DOWN, LEFT, RIGHT
Air Filter CATECHIN
Dimensions (H X W X D) mm 288 X 785 X 250
Packaged Dimensions (H X W X D) mm 327 X 830 X 363
Weight kg 9.0
Condensate Drain Size mm 19.05
OUTDOOR UNIT RXC20B RXC25B
Casing Colour IVORY WHITE
Airflow Rate CFM 930
Sound Pressure Level dBA 45
Type PROPELLER
Fan
Drive DIRECT
Type DIRECT CURRENT
Index of protection (IP) 24
Insulation Grade E
Fan Motor Running Current (Rated) A 0.28
Power Consumption (Rated) W 29
Motor Output W 26
Poles 8
Type HERMETIC SWING
Oil type DAPHNE FW68DA
Compressor Oil amount cm3 375
Running Current (Rated) A N/A
Power Consumption (Rated) W N/A
Heat Exchanger Type FIN TUBE
Dimensions (H X W X D) mm 550 X 658 X 273
Packaged Dimensions (H X W X D) mm 610 X 781 X 363
Weight kg 24
Document No. (Set) 3D117996 C
1) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT).
2) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
COOLING HEATING
INDOOR: 27°CDB / 19°CWB INDOOR: 20°CDB
OUTDOOR: 35°CDB OUTDOOR: 7°CDB / 6°CWB
19 Specifications
DAMA-SM-20-002 Specification Data
COOLING HEATING
INDOOR: 27°CDB / 19°CWB INDOOR: 20°CDB
OUTDOOR: 35°CDB OUTDOOR: 7°CDB / 6°CWB
Specifications 20
Specification Data DAMA-SM-20-002
COOLING HEATING
INDOOR: 27°CDB / 19°CWB INDOOR: 20°CDB
OUTDOOR: 35°CDB OUTDOOR: 7°CDB / 6°CWB
21 Specifications
DAMA-SM-20-002 Specification Data
COOLING HEATING
INDOOR: 27°CDB / 19°CWB INDOOR: 20°CDB
OUTDOOR: 35°CDB OUTDOOR: 7°CDB / 6°CWB
Specifications 22
Specification Data DAMA-SM-20-002
COOLING HEATING
INDOOR: 27°CDB / 19°CWB INDOOR: 20°CDB
OUTDOOR: 35°CDB OUTDOOR: 7°CDB / 6°CWB
23 Specifications
DAMA-SM-20-002 Specification Data
COOLING HEATING
INDOOR: 27°CDB / 19°CWB INDOOR: 20°CDB
OUTDOOR: 35°CDB OUTDOOR: 7°CDB / 6°CWB
Specifications 24
Functions DAMA-SM-20-002
2. Functions
FTXC20/25/35B
RXC20/25/35B
FTXC60/71B
RXC60/71B
FTXC50B
RXC50B
Category Functions
Inverter
Innovaire Technology — — —
Operation Limit for Cooling (°CDB)(O/D) 10 - 46 -10 - 46 -10 - 46
Basic Function
Operation Limit for Cooling (°FDB)(O/D) 50 - 114.8 14 - 114.8 14 - 114.8
Operation Limit for Heating (°CWB)(O/D) -15 - 18 -15 - 18 -15 - 18
Operation Limit for Heating (°FWB)(O/D) 5 - 64.4 5 - 64.4 5 - 64.4
Scroll Compressor — — —
Compressor Swing Compressor
Rotary Compressor — — —
Power-airflow flap —
Power-airflow dual flaps — —
Power-airflow diffuser — — —
Wide angle louvers
Comfortable Airflow
Vertical Auto-Swing (Up and Down)
Horizontal Auto-Swing (Right and Left) — — —
3D Airflow — — —
Breeze Airflow — — —
Auto Fan Speed
Indoor/Outdoor Unit Quiet Operation
Comfort Control
Intelligent Eye Operation — — —
Automatic Defrosting
Automatic Operation
Operation Programme Dry Operation
Fan Only
Powerful Operation (Non Inverter) — — —
Inverter Powerful Operation
Energy Saving Function
Sleep Mode
Lifestyle Convenience
Indoor Unit On/Off button
Remote Controller with Backlight
Signal receiving sign (Remote Controller)
Set Temperature Display (Remote Controller)
Saranet Filter — — —
Catechin Filter / Green Tea Filter
Titanium Apatite Air-Purifying Filter
Health & Clean PM 2.5 Filter — — —
Streamer — — —
Plasma — — —
Wipe clean flat panel
Weekly Timer Operation — — —
Timer
24-hour ON/OFF Timer
Auto Restart (after Power Failure)
Worry Free
Self-Diagnosis (Handset) Display
(Reliability & Durability)
Anticorrosion Treatment of Outdoor Heat Exchanger
Pre charged piping length 7.5m 7.5m 7.5m
Flexibility
Either Side Drain (Right or Left)
BAG Connectivity
Remote Control WIFI Connectivity
DIII-NET Connectivity
Wireless (BRC52B66)
Remote Controller
Wired * * *
Note: : Available
— : Not available
* : Optional (Refer to DAMA Spare Part Team for more details on optional items.)
25 Specifications
DAMA-SM-20-002 Functions
ARXC20/25/35B
ATXC20/25/35B
ARXC60/71B
ATXC60/71B
ARXC50B
ATXC50B
Category Functions
Inverter
Innovaire Technology — — —
Operation Limit for Cooling (°CDB)(O/D) 10 - 46 -10 - 46 -10 - 46
Basic Function
Operation Limit for Cooling (°FDB)(O/D) 50 - 114.8 14 - 114.8 14 - 114.8
Operation Limit for Heating (°CWB)(O/D) -15 - 18 -15 - 18 -15 - 18
Operation Limit for Heating (°FWB)(O/D) 5 - 64.4 5 - 64.4 5 - 64.4
Scroll Compressor — — —
Compressor Swing Compressor
Rotary Compressor — — —
Power-airflow flap —
Power-airflow dual flaps — —
Power-airflow diffuser — — —
Wide angle louvers
Comfortable Airflow
Vertical Auto-Swing (Up and Down)
Horizontal Auto-Swing (Right and Left) — — —
3D Airflow — — —
Breeze Airflow — — —
Auto Fan Speed
Indoor/Outdoor Unit Quiet Operation
Comfort Control
Intelligent Eye Operation — — —
Automatic Defrosting
Automatic Operation
Operation Programme Dry Operation
Fan Only
Powerful Operation (Non Inverter) — — —
Inverter Powerful Operation
Energy Saving Function
Sleep Mode
Lifestyle Convenience
Indoor Unit On/Off button
Remote Controller with Backlight
Signal receiving sign (Remote Controller)
Set Temperature Display (Remote Controller)
Saranet Filter — — —
Catechin Filter / Green Tea Filter
Titanium Apatite Air-Purifying Filter
Health & Clean PM 2.5 Filter — — —
Streamer — — —
Plasma — — —
Wipe clean flat panel
Weekly Timer Operation — — —
Timer
24-hour ON/OFF Timer
Auto Restart (after Power Failure)
Worry Free
Self-Diagnosis (Handset) Display
(Reliability & Durability)
Anticorrosion Treatment of Outdoor Heat Exchanger
Pre charged piping length 7.5m 7.5m 7.5m
Flexibility
Either Side Drain (Right or Left)
BAG Connectivity
Remote Control WIFI Connectivity
DIII-NET Connectivity
Wireless (BRC52B66)
Remote Controller
Wired * * *
Note: : Available
— : Not available
* : Optional (Refer to DAMA Spare Part Team for more details on optional items.)
Specifications 26
DAMA-SM-20-002
Part 3
Functions and Control
1. Main Functions......................................................................................28
1.1 Temperature Control ..............................................................................28
1.2 Frequency Control..................................................................................28
1.3 Airflow Direction Control.........................................................................30
1.4 Fan Speed Control for Indoor Unit .........................................................30
1.5 Dry Mode................................................................................................31
1.6 Automatic Operation...............................................................................32
1.7 Thermostat Control.................................................................................33
1.8 ECO+ Operation ....................................................................................34
1.9 Sleep Mode ............................................................................................35
1.10 POWERFUL Operation ..........................................................................35
1.11 Other Functions......................................................................................36
2. Thermistor Functions ............................................................................37
3. Control Specification .............................................................................38
3.1 Mode Hierarchy ......................................................................................38
3.2 Frequency Control..................................................................................39
3.3 Standby Electricity Saving (Suspend Function) .....................................41
3.4 Controls at Mode Changing/Start-up......................................................41
3.5 Discharge Pipe Temperature Control.....................................................43
3.6 Input Current Control..............................................................................44
3.7 Freeze-up Protection Control .................................................................45
3.8 Heating Peak-cut Control .......................................................................46
3.9 Outdoor Fan Control...............................................................................47
3.10 Liquid Compression Protection Function................................................48
3.11 Defrost Control .......................................................................................48
3.12 Electronic Expansion Valve Control .......................................................49
3.13 Malfunctions ...........................................................................................53
1. Main Functions
1.1 Temperature Control
Definitions of The definitions of temperatures are classified as following.
Temperatures
Room temperature: temperature of lower part of the room
Set temperature: temperature set by remote controller
Room thermistor temperature: temperature detected by room temperature thermistor
Target temperature: temperature determined by microcomputer
Target temperature
Set temperature
Room temperature
Temperature The temperature of the room is detected by the room temperature thermistor. However, there is
Control a difference between the temperature detected by room temperature thermistor and the
temperature of lower part of the room, depending on the type of the indoor unit or installation
condition. In practice, the temperature control is done by the target temperature appropriately
adjusted for the indoor unit and the temperature detected by room temperature thermistor.
Inverter Principle To regulate the capacity, a frequency control is needed. The inverter makes it possible to
control the rotation speed of the compressor. The following explain the inverter principle:
Phase 1
The supplied AC power source is converted into the DC power source for the present.
Phase 2
The DC power source is reconverted into the three phase AC power source with variable
frequency.
When the frequency increases, the rotation speed of the compressor increases resulting in
an increase of refrigerant circulation. This leads to a larger amount of heat exchange per
unit.
When the frequency decreases, the rotation speed of the compressor decreases resulting in
a decrease of refrigerant circulation. This leads to a smaller amount of heat exchange per
unit.
high speed
Amount of heat Amount of heat
exchanged air (large) high f exchanged air (large)
power
power
DC
AC
Amount of heat low f Amount of heat
exchanged air (small) exchanged air (small)
low speed
freq= 50 Hz capacity=
constant 60 Hz freq=variable variable
Frequency Limits The following functions regulate the minimum and maximum frequency:
Compressor protection function. Refer to page 41.
Discharge pipe temperature control. Refer to page 43.
Input current control. Refer to page 44.
Freeze-up protection control. Refer to page 45.
Cooling/Dry
During cooling or dry operation, the flap retracts into the indoor unit. Then, cool air can be blown
far and distributed all over the room.
Wide-Angle The louvers, made of elastic synthetic resin, provide a wide range of airflow that guarantees
Louvers comfortable air distribution.
Auto-Swing The followings explain the auto-swing process for cooling, dry and fan:
0°
A°
B°
(A)FTXC Outline Phase control and fan speed control contains 5 steps: SL, L, M, H, SH.
On heating mode, the indoor fan speed will be regulated according to the indoor heat exchanger
temperature and the difference between the room temperature and the required set
temperature.
Automatic Fan In automatic fan speed operation, the step SL, & SH is not available.
Speed Control
Step Cooling Heating
L
M
H
= The airflow rate is automatically controlled within this range when FAN setting button is
set to automatic.
Series SL L M H SH
(A)FTXC20/25 190 230 310 380 410
(A)FTXC35 190 230 320 380 400
(A)FTXC50 260 290 360 430 450
(A)FTXC60/71 360 480 560 720 770
Cooling
The following drawings explain the principle of fan speed control for cooling.
Room thermistor temperature – set temperature
Fan speed
+2°C
H
+1.5°C
+1.5°C
L
+0.5°C
Heating
The following drawings explain the principle of fan speed control for heating.
On heating mode, the indoor fan speed will be regulated according to the heat exchanger
temperature and the difference between the room temperature and the required target
temperature.
Room thermistor temperature – set temperature
Fan speed
+3°C
H
+2.5°C
+0.5°C 1°C
0°C L
Details The microcomputer automatically sets the airflow rate. The difference between the room
thermister temperature and the set temperature is divided into zones. Then, the unit operates in
an appropriate capacity for each zone to maintain the temperature and humidity at a
comfortable level.Zone B continues to stay for 120 seconds before the unit will turn to
thermostat ON.
X
Zone C - Thermostat ON
Zone B Zone B
Y
+0.5°C (0.9°F)
Details 1. Remote controller setting temperature is set as automatic cooling / heating setting
Explanation of temperature 16°C to 30°C.
the Function 2. Main unit setting temperature equals remote controller setting temperature.
3. Operation ON / OFF point and mode switching point are as follows.
a Heating Cooling switching point:
Room temperature ≥ Main unit setting temperature +2.5 deg.
b Cooling Heating switching point:
Room temperature < Main unit setting temperature -2.5 deg.
c Thermostat ON / OFF point is the same as the ON / OFF point of cooling or heating
operation.
4. During initial operation
Room temperature ≥ Remote controller setting temperature: Cooling operation
Room temperature < Remote controller setting temperature: Heating operation
Cooling Operation
Set point +2.5°C
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling/Dry/Heating: 2 minutes)
Cooling/Dry
Room thermistor temperature – set temperature
ON
Cooling : –0.5°C
Zone C Dry : –0.5°C
–1.0°C
Zone B
Cooling/Dry : –1.5°C
Zone A
OFF
Heating
Room temperature – set temperature
OFF
A
1.5°C
B
C
0.5°C
ON
Details
Cool mode
24
User set
User set temperature < temp
24°C
ECO+ activated
User
set temp
User set temperature ≥
24°C 24
ECO+ activated
User set
User set temperature > temp
20°C 20
ECO+ activated
20
User set
User set temperature ≤ temp (User set temp - 1°C/2°F)
20°C
ECO+ activated
Details SLEEP Mode continues operation at the target temperature for the first hour, then automatically
raises the target temperature slightly in case of cooling, or lowers it slightly in case of heating.
This prevents excessive cooling in summer and excessive heating in winter to ensure
comfortable sleeping conditions and also saves electricity.
1hr 1hr
(no offset on target
temperature)
target temperature
<COOL or DRY> (shift 0.5°C/0.9°F) (shift 1.0°C/1.8°F)
Details When POWERFUL button is pressed, the fan speed and target temperature are converted to
the following states for 20 minutes.
Operation mode Fan speed Target temperature
COOL H tap + A rpm Setting temperature -4°C
HEAT H tap + A rpm Setting temperature +6°C
H = high fan
A = refer table below
Mode Model 20/25 35/50 60/71
COOL/HEAT (A)FTXC 70 50 70
ON/OFF
switch
Note Forced cooling operation will not be started if the ON/OFF switch is pressed for 10 seconds or
more.
Note It takes 3 minutes to restart the operation because 3-minute standby function is activated.
Note *The cold air blast is also prevented using a similar control when the defrosting operation is
started or when the thermostat gets turned ON.
2. Thermistor Functions
(A)FTXC series only
(2) Outdoor Heat
(5) Room
Exchanger
Temperature
(3) Outdoor Thermistor
Expansion valve Thermistor
Temperature
Thermistor
(1) Discharge The discharge pipe thermistor is used for controlling discharge pipe temperature. If the
Pipe Thermistor discharge pipe temperature (used in place of the inner temperature of the compressor) rises
abnormally, the operating frequency becomes lower or the operation halts.
The discharge pipe thermistor is used for detecting disconnection of the discharge pipe
thermistor.
(2) Outdoor Heat The outdoor heat exchanger thermistor is used for controlling the target discharge pipe
Exchanger temperature. The system sets the target discharge pipe temperature according to the
Thermistor outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve
opening so that the target discharge pipe temperature can be obtained.
In cooling operation, the outdoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature drops
below the outdoor heat exchanger temperature by more than a certain value, the discharge
pipe thermistor is judged as disconnected.
In cooling operation, the outdoor heat exchanger thermistor is used for high pressure
protection.
(3) Outdoor The outdoor temperature thermistor detects the outdoor air temperature and is used for
Temperature refrigerant shortage detection, input current control, outdoor fan control, liquid compression
Thermistor protection function, and so on.
(4) Indoor Heat The indoor heat exchanger thermistor is used for controlling the target discharge pipe
Exchanger temperature. The system sets the target discharge pipe temperature according to the
Thermistor outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve
opening so that the target discharge pipe temperature can be obtained.
In cooling operation, the indoor heat exchanger thermistor is used for freeze-up protection
control. If the indoor heat exchanger temperature drops abnormally, the operating frequency
becomes lower or the operation halts.
During heating, the indoor heat exchanger thermistor is used for detecting disconnection of
the discharge pipe thermistor.
When the discharge pipe temperature becomes lower than the indoor heat exchanger
temperature, the discharge pipe thermistor is judged as disconnected.
The indoor heat exchanger thermistor is also used for preventing abnormal high pressure.
(5) Room The room temperature thermistor detects the room air temperature and is used for
Temperature controlling the room air temperature.
Thermistor
3. Control Specification
3.1 Mode Hierarchy
Outline The air conditioner control has normal operation mode, forced operation mode, and power
transistor test mode for installation and servicing.
Details There are following modes; Fan, Cooling (includes drying), Stop.
Stop
There are following modes; Cooling (includes drying), Heating (includes defrosting), Stop.
Cooling
Heating
Defrosting
Stop mode (except for cooling/heating modes by indoor command)
Discharging from capacitor
Stop
Note Unless specified otherwise, dry operation command is regarded as cooling operation.
Dropping function
Input current control, etc.
Initial Frequency When starting the compressor, the frequency is initialized according to the ΔD value of the
indoor unit.
PI Control 1. P control
ΔD value is calculated in each sampling time (20 seconds), and the frequency is adjusted
according to its difference from the frequency previously calculated.
2. I control
If the operating frequency does not change for more than a certain fixed time, the frequency
is adjusted according to ΔD value.
When ΔD is low, the frequency is lowered.
When ΔD is high, the frequency is increased.
Details Standby electricity saving function can be activated/deactivated from the service mode of
the remote controller.
When standby electricity saving is ON, the system enters suspend state if both indoor and
outdoor units are not in operation.
The system will not go into suspend state when some voltage is applied to the outdoor unit
for protection purpose even if the indoor unit is not in operation.
In suspend state, power supply to the outdoor unit is halted and there is no communication
between the indoor unit and the outdoor unit.
Also the service monitor LED (LED A) lights off.
To return from the suspend state, start fan or other operation to turn on the indoor unit.
112Hz
90Hz
72Hz
54Hz
40Hz
(sec.)
Time
(Hz)
Frequency
98Hz
85Hz
70Hz
55Hz
(sec.)
Time
Details
Stop zone
A°C
B°C
Dropping zone
C°C
Keep zone
D°C
Up zone
E°C
Reset zone
Discharge pipe
temperature
Zone Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Up zone The upper limit of frequency increases.
Reset zone The upper limit of frequency is cancelled
FTXC* BV1B
20/25/35 50/60/71
A (°C) 110 118
B (°C) 103 108
C (°C) 98 103
D (°C) 93 97
E (°C) 88 85
Details
Compressor Stop
(A)
Stop zone
A
Dropping zone
Keep zone
C
Zone Control
Stop zone After the input current remains in the stop zone for 2.5 seconds, the compressor is stopped.
Dropping The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is lowered by 2 Hz every second until it reaches the keep zone.
Keep zone The present maximum frequency goes on.
Reset zone Limit of the frequency is cancelled.
Limitation of current dropping and stop value according to the outdoor temperature
The current drops when outdoor temperature becomes higher than a certain level
(depending on the model).
Details The operating frequency limitation is judged with the indoor heat exchanger temperature.
Indoor heat exchanger
thermistor temperature
13°C
Reset zone
A°C
Up zone
B°C
Keep zone
C°C
Dropping zone
0°C
Stop zone
Zone Control
Reset zone The upper limit of frequency is cancelled
Up zone The upper limit of frequency increases
Keep zone The upper limit of frequency is kept
Dropping zone The upper limit of frequency decreases
Stop zone When indoor coil temperature <0°C for >80s, compressor is stopped
Stop zone
A°C
B°C
Dropping zone
C°C
Keep zone
D°C
Heat exchanger Up zone
thermistor E°C
Reset zone
temperature
Frequency control in each zone
Zone Control
Stop zone When indoor coil temperature stop zone, the compressor stops
Dropping zone The upper limit of frequency decreases
Keep zone The upper limit of frequency is kept
Up zone The upper limit of frequency increases
Reset zone The upper limit of frequency is cancelled
RXC20/25/35BV1B RXC50/60/71BV1B
A (°C) 65 60
B (°C) 53 53
C (°C) 50 50
D (°C) 48 48
E (°C) 43 43
RXC35BV1B Others
Temperature 7°C 0°C
PI control
Frequency
0Hz B
0Hz
A D C
Compressor ON
OFF
ON
Four way valve
OFF
5sec. 5sec.
ON
Fan
OFF
E H
F G
Electronic expansion
valve opening Initial opening
3RZHU213RZHU6XSSO\5HVHW
3URFHVVHVZKLOHWKHFRPSUHVVRULVRSHUDWLQJ
2SHQFRQWURO
(OHFWURQLFH[SDQVLRQ +LJKGLVFKDUJHSLSH
YDOYHFRQWURO WHPSHUDWXUHFRQWURO
DWVWDUWXS
5HKHDW
GHKXPLGLrFDWLRQ
FRQWURO
)HHGEDFNFRQWURO 'HIURVWFRQWURO
3URFHVVZKHQ
+LJKGLVFKDUJHSLSH WKHFRPSUHVVRUVWRSV
7DUJHWGLVFKDUJH WHPSHUDWXUHFRQWURO
SLSH GRHVQRWIXQFWLRQ
WHPSHUDWXUH ZKHQWKHGLVFKDUJH
3UHVVXUH
FRQWURO SLSHWKHUPLVWRULV
HTXDOL]DWLRQFRQWURO
GLVFRQQHFWHG
SXOVHV
SXOVHV
SXOVH
/RZHUOLPLWRIWKH
HOHFWURQLFH[SDQVLRQ
YDOYH YDOYHERG\
VWURNH
$
FRUUHFWLRQ +LJKGLVFKDUJHSLSHWHPS
FRQWUROVWDUWWHPSHUDWXUH
IDFWRU
5HVHW]RQH 'URSSLQJ]RQH
%
+LJKGLVFKDUJHSLSHWHPS
FRUUHFWLRQ FRQWUROUHOHDVHWHPSHUDWXUH
IDFWRU
RXC20/25/35 RXC50/60/71
A 102 105
B 100 100
嵣&RPSUHVVRULVRSHUDWLQJ
$1' 'URSSLQJ]RQH
嵣'LVFKDUJHSLSHWHPS!&
嵣&RPSUHVVRUVWRSV
嵣'LVFKDUJHSLSHWHPS۹& 5HVHW]RQH
25
嵣'LVFRQQHFWLRQRIGLVFKDUJHSLSH
WKHUPLVWRU
The electronic expansion valve opening and the target discharge pipe temperature are adjusted
every A seconds. The opening degree of the electronic expansion valve is adjusted by the
following.
Target discharge pipe temperature
Actual discharge pipe temperature
Previous discharge pipe temperature
A (seconds) 10 ~ 20
(depending on the model)
3.13 Malfunctions
3.13.1 Sensor Malfunction Detection
Sensor malfunction can be detected in the following thermistors in open or short circuit.
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Outdoor temperature thermistor
Details If the inverter current exceeds A A, the system shuts down the compressor.
If the OL (compressor head) temperature exceeds B°C, the compressor stops.
RXC20/25/35 RXC50/60/71
A 14.0 11.5
B 120.0
Part 4
Remote Controller
1. Applicable Remote Controller ...............................................................55
2. BRC52B66 ............................................................................................56
55 Remote Controller
BRC52B66 DAMA-SM-20-002
2. BRC52B66
GV: DENV
FTXC20/25/35/50/60/71BV1B
IR Signal Transmitter
• To enable signal
transmission, direct the
transmitter at the indoor
unit.
Note that in condition
Display (LCD)
where there is an obstacle
• Display the current that blocks between the
settings. transmitter and the indoor
(This illustration shows the unit, signal transmission
full display of the LCD might not be successful.
panel, including functions
for applicable remote
controller models only). Temperature Setting Button
• Increase / Decrease the
ON/OFF Button temperature setting.
• Start/Stops the operation. ON/OFF
POWERFUL Button
FAN Button TEMP • Enable / Disable
• Changes the operating fan POWERFUL function.
speed.
FAN POWERFUL SWING
UP-DOWN SWING Button
QUIET Button
• Enable / Disable QUIET QUIET MODE SLEEP • Direct the air flow in up-
function. down direction.
CLOCK Button
• Changes RTC selling.
56 Remote Controller
DAMA-SM-20-002
Part 5
Service Diagnosis
1. General Problem Symptoms and Check Items .....................................58
2. Troubleshooting with LED .....................................................................59
2.1 Indoor Unit..............................................................................................59
2.2 Outdoor Unit ...........................................................................................60
3. Error Diagnosis .....................................................................................60
3.1 To enter error diagnosis .........................................................................60
4. Troubleshooting ....................................................................................61
4.1 Error Codes and Description ..................................................................61
4.2 Indoor Unit PCB Abnormality .................................................................63
4.3 Freeze-up Protection Control .................................................................64
4.4 Indoor Fan Motor (DC Motor) or Related Abnormality ...........................65
4.5 Thermistor or Related Abnormality (Indoor Unit)....................................66
4.6 Thermistor or Related Abnormality (Indoor Unit)....................................67
4.7 Low-voltage Detection or Over-voltage Detection..................................68
4.8 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)......69
4.9 Installation error......................................................................................71
4.10 Outdoor Unit PCB Abnormality...............................................................72
4.11 OL Activation (Compressor Overload) ...................................................73
4.12 Compressor Lock ...................................................................................75
4.13 DC Fan Lock ..........................................................................................76
4.14 Input Overcurrent Detection ...................................................................77
4.15 Discharge Pipe Temperature Control.....................................................78
4.16 High Pressure Control in Cooling ...........................................................80
4.17 Compressor System Sensor Abnormality ..............................................82
4.18 Position Sensor Abnormality ..................................................................83
4.19 Thermistor or Related Abnormality (Outdoor Unit).................................84
4.20 Thermistor or Related Abnormality (Outdoor Unit).................................86
4.21 Thermistor or Related Abnormality (Outdoor Unit).................................88
4.22 Thermistor or Related Abnormality (Outdoor Unit).................................90
4.23 Electrical Box Temperature Rise............................................................92
4.24 Radiation Fin Temperature Rise ............................................................93
4.25 Output Overcurrent Detection ................................................................94
4.26 Four Way Valve Abnormality..................................................................96
5. Actuator Check......................................................................................98
5.1 Thermistor Resistance Check ................................................................98
5.2 Power Supply Waveform Check.............................................................99
5.3 Electronic Expansion Valve Check.........................................................99
5.4 Four Way Valve Performance Check ...................................................100
5.5 Inverter Unit Refrigerant System Check...............................................101
5.6 Rotation Pulse Check on the Outdoor Unit PCB ..................................101
5.7 Installation Condition Check.................................................................102
5.8 Discharge Pressure Check...................................................................102
5.9 Outdoor Fan System Check .................................................................103
5.10 Main Circuit Short Check......................................................................103
5.11 Power Module Check ...........................................................................105
Operation sometimes stops. Check the power supply. A power failure of 2 to 10 cycles can stop air
—
conditioner operation. (Operation lamp OFF)
Check the outdoor temperature. Cooling operation is not available when the
outdoor temperature is out of the operation
119
limit. Check the reference page for the
operation limit.
Diagnose with remote controller
— 61
indication.
The unit operates but does Check for wiring and piping errors in
not cool. the connection between the indoor — —
and outdoor units.
Check for thermistor detection errors. Check if the thermistor is mounted securely. —
Check for faulty operation of the Set the unit to cooling operation, and check
electronic expansion valve. the temperatures of the liquid pipe to see if —
the electronic expansion valve works.
Diagnose with remote controller
— 61
indication.
Diagnose by service port pressure Check for refrigerant shortage.
—
and operating current.
Large operating noise and Check the output voltage of the power
vibrations module. — 105
Service Diagnosis 58
Troubleshooting with LED DAMA-SM-20-002
ON/OFF
switch
LED A
LED A
59 Service Diagnosis
DAMA-SM-20-002 Error Diagnosis
3. Error Diagnosis
3.1 To enter error diagnosis
GV : Press [Timer CANCEL] to scroll to next
°C
TIMER
OFF
CANCEL
GV (FT(X)A)
Notes 1. A short beep and two consecutive beeps indicate non-corresponding codes.
2. To return to the normal mode.
GV : Press [Timer CANCEL] for 5 seconds
When the remote controller is left untouched for 60 seconds, it also returns to the normal mode.
Service Diagnosis 60
Troubleshooting DAMA-SM-20-002
4. Troubleshooting
4.1 Error Codes and Description
Error
Description Reference Page
Codes
System
00 Normal condition -
E6 Compressor lock 75
E7 DC fan lock 76
61 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Service Diagnosis 62
Troubleshooting DAMA-SM-20-002
Method of Error The system checks if the circuit works properly within the microcomputer of the indoor unit.
Detection
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Cautio n connectors, or parts may be damaged.
No
No
Remove the casing Is error repeat? Completed
Yes
Is the ON/OFF No
switch can be Replace the
pressed? indoor unit PCB.
(Display PCB) Turn on the power
supply
Yes
No Yes
Is error repeat? Completed
Replace the indoor unit PCB.
(Control PCB)
63 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Error Decision During cooling operation, the indoor heat exchange temperature is below 0°C.
Conditions High pressure control
During heating operations, the temperature detected by the indoor heat exchanger thermistor is
above 61°C.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
Is there any short circuit? Provide sufficient air passage.
NO
YES
Dirty? Clean the air filter.
NO
Check the dust accumulation on
the indoor heat exchanger.
YES
Dirty? Clean the indoor heat
exchanger.
NO
Check No. 01
Check the indoor heat exchanger
thermistor.
As
described in the NO
thermistor characteristic Replace the indoor heat
chart? exchanger thermistor.
YES
Replace the indoor unit PCB
(control PCB).
Note When replacing the defective thermistor(s), replace the thermistor as ASSY.
Refer to Appendix when using the transmission monitor to identify the error code.
Service Diagnosis 64
Troubleshooting DAMA-SM-20-002
Method of Error The rotation speed detected by the Hall IC during fan motor operation is used to determine
Detection abnormal fan motor operation.
Error Decision The detected rotation speed does not reach the demanded rotation speed of the target tap, and
Conditions is less than 50% of the maximum fan motor rotation speed.
Possible Root 1. Indoor fan motor winding short, or the motor lead wire broken.
Causes 2. Indoor PCB faulty.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
No
Does it rotate? Change fan motor.
Yes
Does it connect No
Connect correctly.
properly?
Yes
Replace the indoor unit PCB
(control PCB) and turn on power
No Complete.
Is error repeated?
Yes
Change Fan motor.
Note Refer to Appendix when using the transmission monitor to identify the error code.
65 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Method of Error The temperature detected by the thermistors determine thermistor errors.
Detection
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
Normal ? Correct the connection.
YES
Check No. 01
Check the thermistor resistance
value.
NO
Normal ? Replace the defective
thermistor.
YES
Replace the indoor unit PCB
(control PCB).
Note When replacing the defective thermistor(s), replace the thermistor as ASSY.
Refer to Appendix when using the transmission monitor to identify the error code.
Service Diagnosis 66
Troubleshooting DAMA-SM-20-002
Method of Error The temperature detected by the thermistors determine thermistor errors.
Detection
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
Normal ? Correct the connection.
YES
Check No. 01
Check the thermistor resistance
value.
NO
Normal ? Replace the defective
thermistor.
YES
Replace the indoor unit PCB
(control PCB).
Note When replacing the defective thermistor(s), replace the thermistor as ASSY.
Refer to Appendix when using the transmission monitor to identify the error code.
67 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Over-voltage detection:
An abnormal voltage rise is detected by the DC over-voltage detection circuit.
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes Power supply voltage out of specification Short circuit inside the fan motor winding
Defective DC voltage detection circuit Noise
Defective over-voltage detection circuit Momentary drop of voltage
Defective PAM control part Momentary power failure
Disconnection of compressor harness Defective outdoor unit PCB
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the
voltage fluctuation NO
within ±10% from the Correct the power supply.
rated value?
YES
Check the connection of the
compressor harness.
Loose or YES
disconnected? Reconnect the harness.
NO
Does the
NO
outdoor fan rotate Replace the outdoor fan motor
smoothly? and the outdoor unit PCB
(main PCB).
YES
(Precaution before turning on the power again)
Make sure the power has been off for at
least 30 seconds.
Turn on
the power. System YES Disturbance factors
restarted? (Repeat a few * Noise Check for such factors for a
times.) * Power supply distortion long term.
NO
1145d21h58m16s DEMO\DEMO052.TXT
2020/06/22 16:45:01 60Hz EN03
Note Refer to Appendix when using the transmission monitor to identify the error code.
Service Diagnosis 68
Troubleshooting DAMA-SM-20-002
Error Decision The data sent from the outdoor unit cannot be received normally, or the content of the data is
Conditions abnormal.
69 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Is the
voltage fluctuation NO
within ±10% from the Correct the power supply.
rated value?
YES
Check the connection wires
between the indoor unit and the
outdoor unit.
YES
Is there any wiring error? Correct the connection wires
between the indoor unit and
the outdoor unit.
NO
NO
Properly insulated? Replace the connection wires
between the indoor unit and
outdoor unit.
YES
Continuously ON or OFF
Is LED A blinking? Replace the outdoor unit PCB
(main PCB).
Blink
Rotate the
outdoor fan manually. NO
Does the outdoor fan rotate Replace the outdoor fan motor
smoothly? and the outdoor unit PCB
(main PCB).
YES
Check No.11
Check the power supply
waveform.
NO
Is there any disturbance? Replace the indoor unit PCB
(control PCB).
YES
Locate and eliminate the
cause of the disturbance of
the power supply waveform.
Service Diagnosis 70
Troubleshooting DAMA-SM-20-002
Error Decision The pair type and multi type are interconnected.
Conditions
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
OK? Match the compatible models.
YES
Are the
connecting wires NO
Correct the connection.
connected properly?
YES
Check the part numbers of the
indoor and outdoor unit PCB
with the Parts List.
If not matched, change for the
correct PCB.
71 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
Error again? Replace the outdoor unit PCB
(main PCB).
NO
NO
Grounded? Ground the system.
YES
The cause can be external
factors other than malfunction.
Investigate the cause of noise.
Service Diagnosis 72
Troubleshooting DAMA-SM-20-002
73 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Discharge
pipe thermistor YES
Insert the thermistor in
disconnected? position.
NO
OK
YES
Check Resistance
the resistance ∞ Disconnect the 2 terminals
between the 2 terminals on of the OL (Q1L).
connector S40.
Nearly 0 Ω
Check the
Resistance
resistance
∞
between the 2 Replace the OL (Q1L)
terminals of the OL
(Q1L).
Nearly 0 Ω
Replace the OL harness.
Check the electronic NG Replace the electronic expansion
expansion valve. valve or the coil
OK
NG
Check the refrigerant Refer to the refrigerant line
line. • Refrigerant shortage check procedure.
• Water mixed
• Stop valve
OK
Replace the outdoor unit PCB
(main PCB).
Note When replacing the defective thermistor(s), replace the thermistor as ASSY.
Service Diagnosis 74
Troubleshooting DAMA-SM-20-002
Method of Error A compressor lock is detected by checking the compressor running condition through the
Detection position detection circuit.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
YES
Stop valve closed? Open the stop valve.
NO
Emergency
YES
stop without compressor Replace the compressor. /
running? outdoor unit PCB (main PCB)
NO
System shut NO
down after errors repeated Check the electronic expansion
several times? valve coil. Go to Check No. 12.
YES
Replace the compressor. /
outdoor unit PCB (main PCB)
75 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Error Decision The fan does not start in about 30 ~ 60 seconds (depending on the model) even when the
Conditions fan motor is running.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Fan rotates NO
smoothly? Replace the outdoor fan
motor.
YES
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB (main PCB).
NO
Pulse signal generated? Replace the outdoor fan
motor.
YES
Replace the outdoor unit
PCB (main PCB).
Service Diagnosis 76
Troubleshooting DAMA-SM-20-002
Method of Error An input overcurrent is detected by checking the input current value with the compressor
Detection running.
Error Decision The current exceeds 10 ~ 15 A (depending on the model) for 2.5 seconds with the compressor running.
Conditions The upper limit of the current decreases when the outdoor temperature exceeds a certain level.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No. 17
Check the installation condition.
YES
Check No. 18
Check the discharge pressure.
Cautions: Be sure to turn off the power switch before connecting or disconnecting connectors, or parts
may be damaged.
An input overcurrent may result from wrong internal wiring. If the system is interrupted by an
input overcurrent after the wires have been disconnected and reconnected for part
displacement, check the wiring again.
Note Refer to Appendix when using the transmission monitor to identify the error code.
77 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Error Decision If the temperature detected by the discharge pipe thermistor rises above A°C, the
Conditions compressor stops.
The error is cleared when the discharge pipe temperature has dropped below B°C.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Model RXC20/25/35
A (°C) B (°C)
(1) above 45 Hz 110 85
(2) 20 ~ 45 Hz 95 70
(3) below 20 Hz 90 65
Model RXC50/60/71
A (°C) B (°C)
(1) above 50 Hz (rising), 45 Hz (dropping) 113 80
(2) 21 ~ 50 Hz (rising), 16 ~ 45 Hz (dropping) 101 68
(3) below 21 Hz (rising), 16 Hz (dropping) 93 60
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No. 01 NG
Check the thermistors. Replace the defective
∗ Discharge pipe thermistor thermistor(s).
∗ Outdoor heat exchanger thermistor
OK ∗ Outdoor temperature thermistor
Check No. 12 NG
Check the electronic Replace the electronic
expansion valve. expansion valve or the coil.
OK
Check No. 14 NG
Check the refrigerant Refer to the refrigerant line
line. ∗ Refrigerant shortage check procedure.
∗ Water mixed
OK ∗ Stop valve
Service Diagnosis 78
Troubleshooting DAMA-SM-20-002
Note When replacing the defective thermistor(s), replace the thermistor as ASSY.
Refer to Appendix when using the transmission monitor to identify the error code.
79 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Error Decision The temperature sensed by the outdoor heat exchanger thermistor rises above A°C.
Conditions The error is cleared when the temperature drops below B°C.
A (°C) B (°C)
RXC20/25/35 61 55
RXC35 61 53
RXC50 61 55
RXC60 61 54
RXC71 61 55
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No. 17
Check the installation NG
Change the installation
condition. location or direction.
Clean the outdoor heat
OK exchanger.
Check No. 19 NG
Check the outdoor fan. Replace the outdoor fan
motor.
Reconnect the connector or
OK fan motor lead wires.
Check No. 18 NG
Check the discharge Replace the stop valve.
pressure.
OK
Check No. 12
Check the electronic NG
Replace the electronic
expansion valve. expansion valve or the coil.
Replace the outdoor unit
OK PCB (main PCB).
Check No. 01
Check the outdoor heat NG
exchanger thermistor. Replace the outdoor heat
exchanger thermistor.
OK
Service Diagnosis 80
Troubleshooting DAMA-SM-20-002
Note When replacing the defective thermistor(s), replace the thermistor as ASSY.
Refer to Appendix when using the transmission monitor to identify the error code.
81 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Error Decision The voltage converted from the DC current before compressor start-up is out of the range
Conditions 0.5 ~ 4.5 V.
The DC voltage before compressor start-up is below 50 V.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check the relay harness for the
compressor.
YES
Is the harness broken? Replace the harness.
NO
Restart operation NO
and error displayed Not a malfunction.
again? Keep observing.
YES
Replace the outdoor unit
PCB (main PCB).
Service Diagnosis 82
Troubleshooting DAMA-SM-20-002
Method of Error A compressor start-up failure is detected by checking the compressor running condition through
Detection the position detection circuit.
Error Decision The compressor fails to start in about 15 seconds after the compressor run command signal
Conditions is sent.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
Voltage as rated? Correct the power supply.
YES
Check No. 18
Check the discharge pressure.
NO
OK? Replace the stop valve.
YES
Check No. 20
Check the short circuit of the
diode bridge.
NO
Normal? Replace the outdoor
unit PCB (main PCB).
YES
Electrical
components or
NO
compressor harnesses Reconnect the electrical
connected as components or compressor
specified? harnesses as specified.
YES
Replace the outdoor unit
PCB (main PCB) / compressor
83 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Method of Error This fault is identified based on the thermistor input voltage to the microcomputer.
Detection A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision The voltage between both ends of the thermistor is either 4.96 V or more, or 0.04 V or less
Conditions with the power on.
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Troubleshooting In case of H9
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts
may be damaged.
Caution
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Yes
Check the thermistor resistance value.
Indoor heat
No Replace the indoor heat
exchanger thermistor
functioning? exchanger thermistor.
Yes
Replace the outdoor unit PCB.
Service Diagnosis 84
Troubleshooting DAMA-SM-20-002
Note When replacing the defective thermistor(s), replace the thermistor as ASSY.
Refer to Appendix when using the transmission monitor to identify the error code.
85 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Method of Error This fault is identified based on the thermistor input voltage to the microcomputer.
Detection A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision The voltage between both ends of the thermistor is either 4.96 V or more, or 0.04 V or less
Conditions with the power on.
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Troubleshooting In case of J3
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts
may be damaged.
Caution
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Yes
Check the thermistor resistance value.
Indoor heat
No Replace the indoor heat
exchanger thermistor
functioning? exchanger thermistor.
Yes
Replace the outdoor unit PCB.
Service Diagnosis 86
Troubleshooting DAMA-SM-20-002
Note When replacing the defective thermistor(s), replace the thermistor as ASSY.
Refer to Appendix when using the transmission monitor to identify the error code.
87 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Method of Error This fault is identified based on the thermistor input voltage to the microcomputer.
Detection A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision The voltage between both ends of the thermistor is either 4.96 V or more, or 0.04 V or less
Conditions with the power on.
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Troubleshooting In case of J6
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts
may be damaged.
Caution
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Yes
Check the thermistor resistance value.
Indoor heat
No Replace the indoor heat
exchanger thermistor
functioning? exchanger thermistor.
Yes
Replace the outdoor unit PCB.
Service Diagnosis 88
Troubleshooting DAMA-SM-20-002
Note When replacing the defective thermistor(s), replace the thermistor as ASSY.
Refer to Appendix when using the transmission monitor to identify the error code.
89 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Method of Error This fault is identified based on the thermistor input voltage to the microcomputer.
Detection A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision The voltage between both ends of the thermistor is either 4.96 V or more, or 0.04 V or less
Conditions with the power on.
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Troubleshooting In case of P4
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts
may be damaged.
Caution
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Yes
Check the thermistor resistance value.
Indoor heat
No Replace the indoor heat
exchanger thermistor
functioning? exchanger thermistor.
Yes
Replace the outdoor unit PCB.
Service Diagnosis 90
Troubleshooting DAMA-SM-20-002
Note When replacing the defective thermistor(s), replace the thermistor as ASSY.
Refer to Appendix when using the transmission monitor to identify the error code.
91 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Error Decision With the compressor off, the radiation fin temperature is above A °C.
Conditions The error is cleared when the radiation fin temperature drops below B °C.
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
rises above C °C and stops when the radiation fin temperature drops below B °C.
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Turn off the power. Then, turn on WARNING
the power to restart the system. To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above C °C. The outdoor fan stops
when the radiation fin temperature
Error again or outdoor YES drops below B °C.
fan activated?
NO
Above A°C? Replace the outdoor unit
PCB (main PCB).
YES
Check No. 19 NG
Check the outdoor fan. Replace the outdoor fan
motor.
Correct the connectors
OK and fan motor lead wire.
Replace the outdoor unit
PCB (main PCB).
NO
Radiation fin dirty? Check the installation
condition.
Go to Check No. 17.
YES
Clean up the radiation fin.
Service Diagnosis 92
Troubleshooting DAMA-SM-20-002
Error Decision The radiation fin temperature with the compressor on is above A °C.
Conditions The error is cleared when the radiation fin temperature drops below B °C.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
Above A °C? Replace the outdoor unit
PCB (main PCB).
YES
Check No. 19 NG
Check the outdoor fan. Replace the outdoor fan
motor.
Correct the connectors and
OK fan motor leads.
Replace the outdoor unit
PCB (main PCB).
NO
Radiation fin dirty? Check the installation
condition.
Go to Check No. 17.
YES
Clean up the radiation fin.
Reference Refer to Silicone Grease on Power Transistor/Diode Bridge on page 108 for details.
93 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Method of Error An output overcurrent is detected by checking the current that flows in the inverter DC section.
Detection
Error Decision A position signal error occurs while the compressor is running.
Conditions A rotation speed error occurs while the compressor is running.
An output overcurrent is fed from the output overcurrent detection circuit to the
microcomputer.
If error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error.
Service Diagnosis 94
Troubleshooting DAMA-SM-20-002
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
Check No. 17
Check the installation condition.
YES
Normal? NO
Replace the outdoor unit
PCB (main PCB).
YES
Check the power supply voltage.
NO
Voltage as rated? Correct the power supply.
YES
Short circuit of
wire breakage between NO
Check the discharge pressure.
compressor’s coil Go to Check No. 18
phases?
YES
Replace the compressor.
95 Service Diagnosis
DAMA-SM-20-002 Troubleshooting
Method of The indoor air temperature thermistor, the indoor unit heat exchanger thermistor, the outdoor
Malfunction temperature thermistor and the outdoor unit heat exchanger thermistor are checked to see if the
Detection function within their normal ranges in the operating mode.
Service Diagnosis 96
Troubleshooting DAMA-SM-20-002
Troubleshooting
Be sure to turn off the power switch before connecting or disconnecting
Caution connectors, or parts may be damaged.
NO
NO
Resistance
between NO
Replace the four way
harnesses about valve coil.
500-2300Ω
YES
Check No. 13 NG
Check the four way valve Replace the outdoor
switching output. unit PCB (main PCB).
OK
NO
Check No. 01 NG
Check the thermistors. Replace the defective
thermistor(s).
OK
Check No. 14 NG
Check the refrigerant Refer to the refrigerant
line. *) Refrigerant shortage line check procedure.
*) Water mixed
*) Stop valve
OK
97 Service Diagnosis
DAMA-SM-20-002 Actuator Check
5. Actuator Check
5.1 Thermistor Resistance Check
Check No.01 Measure the resistance of each thermistor using multimeter.
The resistance values are defined by below table.
If the measured resistance value does not match the listed value, the thermistor must be
replaced.
Disconnect the connector of thermistor ASSY from the PCB to measure the resistance
between the pins using multimeter.
To check the thermistor soldered on a PCB, disconnect the PCB from other PCB/parts, and
measure the resistance between the both ends of soldered thermistor.
Thermistor ASSY Soldered thermistor
Multimeter
Resistance range
Multimeter
Service Diagnosis 98
Actuator Check DAMA-SM-20-002
Harness 5P Harness 6P
5-1 6-1
5-2 6-2
S20 Check Check
5P Connector 5-3 6P Connector 6-3
5-4 6-4
1 2 3 4 5 1 2 3 4 5 6 6-5
RXC*BV1B
Class 20/25/35 50/60/71
EV connector P/N R04059047977 3P540612-1
Coil Model Name DPFX07-116 PQM10175
5P 5wires 6P 6wires
99 Service Diagnosis
DAMA-SM-20-002 Actuator Check
S80
voltage at 208 - 230 NO Replace the outdoor
VAC with compressor unit PCB (main PCB).
onΩ (Fig.1)
YES
Four way
valve coil resistance at NO Replace the four way valve
500-2300Ω coil.
YES
Replace the four way valve.
(Fig.1)
Voltage at S80
Time
Compressor
ON
NO
Check for refrigerant leakage.
See the section on refrigerant
shortage detection.
When the fuse is melted, check the outdoor fan motor for proper function.
If NG in step 2 → Defective PCB → Replace the outdoor unit PCB (main PCB).
If NG in step 4 → Defective Hall IC → Replace the outdoor fan motor.
If OK in both steps 2 and 4 → Replace the outdoor unit PCB (main PCB).
PCB
S71
1 Actual rotation pulse input (0 ~ 15 VDC)
4 Rotation command voltage (0 ~ 6.5 VDC)
7 Control voltage 15 VDC
10
11
12
13 320 VDC
OK
NO
NO
Is the stop valve open? Open the stop valve.
YES
YES
Clean the dirty air filter or
indoor/outdoor heat
exchanger.
YES YES
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Follow the procedure below to measure resistance between the (+) or (–) terminal of the
power module and the U, V, or W terminal of the compressor with a multimeter. Evaluate the
measurement results referring to the following table.
Positive terminal (+) of Power module UVW Power module UVW
digital multimeter (+) (–)
Negative terminal (–) of UVW Power module UVW Power module
digital multimeter (+) (–)
Resistance is OK. several kΩ ~ several MΩ
Resistance is NG. 0 Ω or ∞
Part 6
Trial Operation and
Field Settings
1. Pump Down Operation........................................................................106
2. Forced Cooling Operation ...................................................................107
3. Silicone Grease on Power Transistor/Diode Bridge............................108
Details 1. Remove the valve caps from the liquid stop valve and the gas stop valve.
2. Carry out forced cooling operation.
3. After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4. After 2 to 3 minutes, close the gas stop valve and stop the forced cooling operation.
Hexagonal
wrench
Close
ON/OFF
switch
Note: Smoke emission may be caused by bad heat radiation when the silicone grease is not
appropriately applied.
PCB
Radiation
fin
Silicone grease
Foreign matter
Part 7
Appendix
1. Piping Diagrams..................................................................................110
1.1 Indoor Unit............................................................................................110
1.2 Outdoor Unit .........................................................................................112
2. Wiring Diagrams..................................................................................114
2.1 Indoor Unit............................................................................................114
2.2 Outdoor Unit .........................................................................................115
2.3 Printed Circuit Board Connector Wiring Diagram.................................116
2.4 Printed Circuit Board Connector Wiring Diagram.................................117
3. Operation Limit....................................................................................119
4. Transmission Monitor [TM2016-1] Operation Instructions ..................120
4.1 Names and Functions of Parts .............................................................120
4.2 Basic Operations and Display ..............................................................121
1. Piping Diagrams
1.1 Indoor Unit
Model: FTXC/ATXC20/25B
INDOOR UNIT
THERMISTOR
ON HEAT EXCH.
REFRIGERANT FLOW
COOLING
HEATING
Note: Dimension in mm
Model: FTXC/ATXC35B
INDOOR UNIT
HEAT EXCHANGER
6. 4CuT
REFRIGERANT FLOW
COOLING
HEATING
Note: Dimension in mm
Appendix 110
Piping Diagrams DAMA-SM-20-002
Model: FTXC/ATXC50B
INDOOR UNIT
HEAT EXCHANGER
6. 4CuT
REFRIGERANT FLOW
COOLING
HEATING
Note: Dimension in mm
Model: FTXC/ATXC60/71B
INDOOR UNIT
6. 4CuT
DISTRIBUTOR
HEAT EXCHANGER
THERMISTOR
CROSS FLOW FAN ON HEAT EXCH.
FIELD PIPING
6. 4CuT M
FAN MOTOR
HEADER
FIELD PIPING
12. 7CuT 12. 7CuT
REFRIGERANT FLOW
COOLING
HEATING
Note: Dimension in mm
111 Appendix
DAMA-SM-20-002 Piping Diagrams
OUTDOOR UNIT
HEAT EXCHANGER
7. 0CuT OUTDOOR AIR TEMPERATURE THERMISTOR
9. 5CuT
7. 0CuT
7.0CuT STRAINER
M
PROPELLER FAN
9. 5CuT
9. 5CuT
STRAINER
6. 4CuT
4-WAY VALVE
ON: HEATING
MUFFLER
DISCHARGE PIPE
THERMISTOR
6.4CuT
9. 5CuT 9. 5CuT
COMPRESSOR (9.5CuT)
ACCUMULATOR MUFFLER GAS STOP VALVE REFRIGERANT FLOW
COOLING
HEATING
Note: Dimension in mm
Model: RXC/ARXC50/60B
OUTDOOR UNIT
7.0CuT
ELECTRONIC
EXPANSION
HEAT EXCHANGER THERMISTOR VALVE
STRAINER
M
6. 4CuT
PROPELLER FAN
12.7CuT
STRAINER
6. 4Cut
FOUR WAY
12.7CuT
FIELD PIPING
9. 52CuT
VALVE
HEATING: ON (6. 4CuT)
LIQUID STOP
VALVE
DISCHARGE PIPE
THERMISTOR
MUFFLER
12.7CuT 12.7CuT FIELD PIPING
9.52Cut
COMPRESSOR (12.7CuT)
ACCUMULATOR MUFFLER MUFFLER GAS STOP
VALVE REFRIGERANT FLOW
COOLING
HEATING
Note: Dimension in mm
Appendix 112
Piping Diagrams DAMA-SM-20-002
Model: RXC/ARXC71B
OUTDOOR UNIT
7. 0CuT
ELECTRONIC
EXPANSION
HEAT EXCHANGER THERMISTOR VALVE
EV
6. 4CuT 9.52CuT 6. 4CuT
STRAINER
6. 4CuT
M
PROPELLER FAN
STRAINER
12.7CuT
CAPILLARY TUBE
LIQUID RECEIVER
6. 4CuT
FOUR WAY
12.7CuT
VALVE
9. 52CuT
HEATING: ON
FIELD PIPING
DISCHARGE PIPE (6. 4CuT)
LIQUID STOP
THERMISTOR VALVE
MUFFLER
12.7CuT 12.7CuT FIELD PIPING
9.5Cut
COMPRESSOR (12.7CuT)
ACCUMULATOR MUFFLER MUFFLER MUFFLER GAS STOP
VALVE REFRIGERANT FLOW
COOLING
HEATING
Note: Dimension in mm
113 Appendix
DAMA-SM-20-002 Wiring Diagrams
2. Wiring Diagrams
2.1 Indoor Unit
Model: FTXC/ATXC20/25/35B
TH1
DISPLAY BOARD
MF
250VAC T3.15A
EARTH
250VAC T3.15A
CN_DCFM
LIVE
TH2
CN_SW_LR
CN_DSP
NEUTRAL
CN_COIL
SIG CN_SW_UD MS1
CN_S21 CN_NS
G/Y
Z1C
C1 N=3
ORANGE
G/Y
BROWN
ADAPTER
(OPTIONAL) WIRED
3 2 1 ACCESSORY
(OPTIONAL)
(OD UNIT)
NOTATION:
MF: FAN MOTOR
MS1: AIR SWING MOTOR (UP DOWN)
TH1: INDOOR COIL THERMISTOR
TH2: ROOM THERMISTOR
OD: OUTDOOR
----: FIELD WIRING
Z1C: FERRITE CORE
C1: CAPACITOR
Note: Dimension in mm
Model: FTXC/ATXC50/60/71B
TH1
DISPLAY BOARD
MF
250VAC T3.15A
EARTH
CN_DCFM
250VAC T3.15A
LIVE
TH2
CN_SW_LR
CN_DSP
NEUTRAL
CN_COIL
SIG CN_SW_UD MS1
CN_S21 CN_NS
G/Y
ORANGE
G/Y
BROWN
WIFI
BLUE
ADAPTER
(OPTIONAL) WIRED
3 2 1 ACCESSORY
(OPTIONAL)
(OD UNIT)
NOTATION:
MF: FAN MOTOR
MS1: AIR SWING MOTOR (UP DOWN)
TH1: INDOOR COIL THERMISTOR
TH2: ROOM THERMISTOR
OD: OUTDOOR
----: FIELD WIRING
Note: Dimension in mm
Appendix 114
Wiring Diagrams DAMA-SM-20-002
Note: Dimension in mm
Model: RXC/ARXC50/60/71B
HN1 E1
HL1
EXV
S
4WV
X12A
Z3C
S78 MF
E2
BLACK
WHITE
RED
U S79
V
W
1 2 3 S40 S90
TB L N
S80 S70 S20
REFER VIEW A
GREEN/YELLOW
BLUE (W)
(POWER SUPPLY) (TO INDOOR UNIT)
VIEW A
DISCHARGE SENSOR
NOTATION:
MC: COMPRESSOR MOTOR HEAT EXCHANGER SENSOR
MF: FAN MOTOR
OLP: OVERLOAD PROTECTOR OUTDOOR AIR SENSOR
TB: TERMINAL BLOCK
EXV: ELECTRONIC EXPANSION VALVE COIL
X11A,X12A: CONNECTOR
Z1C,Z2C,Z3C: FERRITE CORE
4WV: FOUR WAY VALVE
-------: FIELD SUPPLY WIRING
Note: Dimension in mm
115 Appendix
DAMA-SM-20-002 Wiring Diagrams
Note The symbols in the parenthesis are the names on the appropriate wiring diagram.
Display/Signal
Receiver PCB 1) S27 Connector for control PCB (A1P)
(A2P) Indoor unit ON/OFF switch
2) SW1 (BS1) (Forced cooling operation ON/OFF switch)
* Refer to page 102 for detail of forced cooling operating.
3) LED1 (H1P) LED for operating (green)
4) LED2 (H2P) LED for timer (yellow)
5 RTH1 (R1T) Room temperature thermistor
Note The symbols in the parenthesis are the names on the appropriate wiring diagram.
Appendix 116
Wiring Diagrams DAMA-SM-20-002
Note The symbols in the parenthesis are the names on the appropriate wiring diagram.
117 Appendix
DAMA-SM-20-002 Wiring Diagrams
2.4.2 50 Class
Main PCB (A1P)
1) S20 Connector for electronic expansion valve coil
2) S40 Connector for overload protector
3) S70 Connector for DC fan motor
Connector for thermistors
4) S90 (outdoor temperature, outdoor heat exchanger,
discharge pipe temperature)
5 HL1, HN1, S Connector for terminal strip
6) E1, E2 Terminals for earth wire
7) U, V, W Connector for compressor
8) FU1 (F1U), Fuse (3.15 A, 250 V)
FU2 (F2U)
9) FU3 (F3U) Fuse (30 A, 250 V)
10) LED A LED for service monitor (green)
11) V1 (R1V), Varistor
V2 (R2V),
V3 (R3V)
Note The symbols in the parenthesis are the names on the appropriate wiring diagram.
Appendix 118
Operation Limit DAMA-SM-20-002
3. Operation Limit
Model: RXC/ARXC20/25/35B
Model: RXC/ARXC50/60/71B
119 Appendix
DAMA-SM-20-002 Transmission Monitor [TM2016-1] Operation Instructions
Appendix 120
Transmission Monitor [TM2016-1] Operation Instructions DAMA-SM-20-002
121 Appendix
Warning z Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorized importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
z Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
z Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or