K007 Mk7 Manual Rev4

Download as pdf or txt
Download as pdf or txt
You are on page 1of 91

Ocean Automation Solutions [email protected] http://www.ocean-automation.

com

Mk 7 OIL MIST DETECTOR

INSTALLATION,
OPERATION AND
MAINTENANCE
MANUAL
59812-K007

PROPRIETY RIGHTS NOTICE

The information contained in this manual is the property of Kidde Products Limited and may not be reproduced or
transmitted in any form or by any means, electronic, mechanical, photocopying, recording or otherwise, nor stored
in any retrieval system or any nature without the express written authority of Kidde Products Limited.

© Copyright 2011 Kidde Products Ltd

May 2012 Page i of viii 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

TABLE OF CONTENTS
Chapter Page

OIL MIST DETECTOR WARRANTIES .................................................................................. 7

1 DESCRIPTION AND OPERATION ................................................................................ 9


1.1 INTRODUCTION 9
1.2 DESCRIPTION 10
1.3 TECHNICAL SPECIFICATION 12
1.4 SYSTEM OVERVIEW 14
1.5 SYSTEM CONTROLS AND DISPLAYS 15

2 INSTALLATION AND COMMISSIONING .....................................................................16


2.1 CONTROL UNIT MOUNTING 16
2.2 DETECTOR MOUNTING 17
2.3 DETECTOR CABLES 20
2.4 REMOTE DISPLAY UNIT 23
2.5 CONTROL UNIT 26
2.6 REMOTE DISPLAY UNIT 29
2.7 CONNECTING THE SYSTEM 32
2.8 SYSTEM CHECKS PRIOR TO SWITCHING ON 34
2.9 SYSTEM SETUP / CONFIGURATION – WITH A REMOTE DISPLAY UNIT 35
2.10 ISOLATION – USING THE REMOTE DISPLAY UNIT 47
2.11 TEST MENU & EVENT LOG 55

3 MAINTENANCE ...........................................................................................................62
3.1 ROUTINE MAINTENANCE 62
3.2 DETECTOR HEAD REPLACEMENT 63
3.3 DETECTOR HEAD REFURBISHMENT 64
3.4 FAN REPLACEMENT 67
3.5 CABLE REPLACEMENT 67
3.6 CONTROL UNIT MEMBRANE 68
3.7 CONTROL UNIT PCB REPLACEMENT 68
3.8 DECOMMISSIONING 68

4 FAULT FINDING ..........................................................................................................69


4.1 GENERAL 69

5 SPARE PARTS ............................................................................................................84


5.1 COMPLETE SPARE PARTS LIST 89

May 2012 Page ii of viii 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

LIST OF ILLUSTRATIONS
Figure Title Page

Figure 1 Areas of Failure – 2 Stroke Engine ...................................................................... 9


Figure 2 Areas of Failure – 4 Stroke Engine ...................................................................... 9
Figure 3 Graviner Mk7 OMD Components ........................................................................10
Figure 4 Typical System Configuration .............................................................................11
Figure 5 Relay Function Modes ........................................................................................15
Figure 6 Control Unit 53836-K270 ....................................................................................16
Figure 7 Ideal Mounting Position.......................................................................................17
Figure 8 Detector Head Installation...................................................................................18
Figure 9 Detector Head Installation (Short Sample Pipe) ..................................................19
Figure 10 Detector Cable ................................................................................................20
Figure 11 Detector Cable Assembly (Straight Connector) ...............................................21
Figure 12 Detector Cable Assembly (Right Angle Connector) .........................................22
Figure 13 Flush Mounting Cut-out for Remote Display Unit .............................................23
Figure 14 Flush Mounting for Remote Display Unit .........................................................24
Figure 15 Bulk Head Mounting for Remote Display Unit ..................................................25
Figure 16 Control Unit PCB .............................................................................................27
Figure 17 Wiring Drawing ................................................................................................28
Figure 18 24v DC Socket Wiring Drawing .......................................................................29
Figure 19 Modbus Connector Wiring Drawing .................................................................30
Figure 20 Remote Display Unit 53836-K271 ...................................................................30
Figure 21 Intentionally Left Blank ....................................................................................31
Figure 22 Power cable ....................................................................................................32
Figure 23 Power cable through EMC gland .....................................................................32
Figure 24 Control unit relay cable assembly ....................................................................33
Figure 25 Detector cable assembly .................................................................................33
Figure 26 Control unit - Detector cable assembly ............................................................34
Figure 27 Screen Shot 1 .................................................................................................35
Figure 28 Screen Shot 2 .................................................................................................35
Figure 29 Screen Shot 3 .................................................................................................35
Figure 30 Screen Shot 4 .................................................................................................36
Figure 31 Screen Shot 5 .................................................................................................36
Figure 32 Screen Shot 6 .................................................................................................36
Figure 33 Screen Shot 7 .................................................................................................36
Engine Selection List ............................................................................................................37
Figure 34 Screen Shot 8 .................................................................................................37
Figure 35 Screen Shot 9 .................................................................................................37
Figure 36 Screen Shot 10 ...............................................................................................37
Figure 37 Screen Shot 11 ...............................................................................................38
Figure 38 Screen Shot 12 ...............................................................................................38
Figure 39 Screen Shot 13 ...............................................................................................38
Figure 40 Screen Shot 14 ...............................................................................................38
Figure 41 Screen Shot 15 ...............................................................................................39
Figure 42 Screen Shot 16 ...............................................................................................39
Figure 43 Screen Shot 17 ...............................................................................................39
Figure 44 Screen Shot 18 ...............................................................................................39
Figure 45 Screen Shot 19 ...............................................................................................40
Detector Selection List..........................................................................................................40
Figure 46 Screen Shot 20 ...............................................................................................40
Figure 47 Screen Shot 21 ...............................................................................................41
Figure 48 Screen Shot 22 ...............................................................................................41
Figure 49 Screen Shot 23 ...............................................................................................41

May 2012 Page iii of viii 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 50 Screen Shot 24 ...............................................................................................41


Figure 51 Control Unit – USB Connector.........................................................................42
Figure 52 Computer Connection – USB Connector .........................................................42
Figure 53 USB Screen Shot 1 .........................................................................................43
Figure 54 USB Screen Shot 2 .........................................................................................43
Figure 55 USB Screen Shot 3 .........................................................................................43
Figure 56 Smoke Tester ..................................................................................................44
Figure 57 Smoke Test .....................................................................................................45
Figure 58 Screen Shot 25 ...............................................................................................47
Figure 59 Screen Shot 26 ...............................................................................................47
Figure 60 Screen Shot 27 ...............................................................................................47
Figure 61 Screen Shot 28 ...............................................................................................48
Figure 62 Screen Shot 29 ...............................................................................................48
Figure 63 Screen Shot 30 ...............................................................................................48
Figure 64 Screen Shot 31 ...............................................................................................48
Figure 65 Screen Shot 32 ...............................................................................................49
Figure 66 Screen Shot 33 ...............................................................................................49
Figure 67 Screen Shot 34 ...............................................................................................49
Figure 68 Screen Shot 35 ...............................................................................................49
Figure 69 Screen Shot 36 ...............................................................................................50
Figure 70 Screen Shot 37 ...............................................................................................50
Figure 71 Screen Shot 38 ...............................................................................................50
Figure 72 Screen Shot 39 ...............................................................................................50
Figure 73 Screen Shot 40 ...............................................................................................51
Figure 74 Screen Shot 41 ...............................................................................................51
Figure 75 Screen Shot 42 ...............................................................................................51
Figure 76 Screen Shot 43 ...............................................................................................51
Figure 77 Screen Shot 44 ...............................................................................................52
Figure 78 Screen Shot 45 ...............................................................................................52
Figure 79 Screen Shot 46 ...............................................................................................52
Figure 80 Screen Shot 47 ...............................................................................................52
Figure 81 Screen Shot 48 ...............................................................................................53
Figure 82 Screen Shot 49 ...............................................................................................53
Figure 83 Screen Shot 50 ...............................................................................................53
Figure 84 Screen Shot 51 ...............................................................................................53
Figure 85 Control Unit Membrane ...................................................................................54
Figure 86 Screen Shot 52 ...............................................................................................55
Figure 87 Screen Shot 53 ...............................................................................................55
Figure 88 Screen Shot 54 ...............................................................................................55
Figure 89 Screen Shot 55 ...............................................................................................56
Figure 90 Screen Shot 56 ...............................................................................................56
Figure 91 Screen Shot 57 ...............................................................................................56
Figure 92 Screen Shot 58 ...............................................................................................56
Figure 93 Screen Shot 59 ...............................................................................................57
Figure 94 Screen Shot 60 ...............................................................................................57
Figure 95 Screen Shot 61 ...............................................................................................57
Figure 96 Screen Shot 62 ...............................................................................................57
Figure 97 Screen Shot 63 ...............................................................................................58
Figure 98 Screen Shot 64 ...............................................................................................58
Figure 99 Screen Shot 65 ...............................................................................................58
Figure 100 Screen Shot 66 ...............................................................................................58
Figure 101 Screen Shot 67 ...............................................................................................59
Figure 102 Screen Shot 68 ...............................................................................................59
Figure 103 Screen Shot 70 ...............................................................................................60
Figure 104 Screen Shot 71 ...............................................................................................60

May 2012 Page iv of viii 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 105 Screen Shot 72 ...............................................................................................60


Figure 106 Screen Shot 73 ...............................................................................................61
Figure 107 Screen Shot 74 ...............................................................................................61
Figure 108 Screen Shot 75 ...............................................................................................61
Figure 110 Base Fixing Screw Removal............................................................................63
Figure 111 Cable Disconnect ............................................................................................64
Figure 112 Base Moulding Seal ........................................................................................64
Figure 113 Pulling Tool .....................................................................................................65
Figure 114 Fan Removal ...................................................................................................65
Figure 115 Cleaning Light Guide .......................................................................................66
Figure 116 Control Unit Spares .........................................................................................84
Figure 117 Detector Spares ..............................................................................................87

May 2012 Page v of viii 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

REVISION HISTORY

Issue Date Of Issue Revision History Amended by Approved by

1 Oct 2011 Draft – For Approval


M Daley A Willis

2 Nov 2011 Approved for Distribution


M Daley A Willis
Changes to Back Alarm
3 Jan 2012 operating philosophy and
Smoke Test procedure. M Daley A Willis
Changes to Warranty section,
4 May 2012
addition of default values.
M Daley A Willis

May 2012 Page vi of viii 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Oil Mist Detector Warranties


1. Kidde Products Ltd (KPL) warrants, for a period of 3 years from the handover of the new vessel
which is installed with KPL Oil Mist Detector (OMD) system to the system owner, and for a period
(*)
of 2 years from the commissioning date of a retro fitted Mk7 Oil Mist Detector (OMD) system, that
any component forming part of the original OMD system manufactured by or supplied by KPL shall
be free from defects in workmanship or materials during normal usage (the “OMD System
Warranty”). If any such component does not conform to this warranty KPL will, at its sole
discretion and its cost, either repair or replace such component. Installation of the repaired /
replacement parts is not covered under the OMD System Warranty. Components replaced or
repaired under the terms of the OMD System Warranty shall continue to have the benefit of the
unexpired portion of the OMD System Warranty, unless that unexpired portion is less than 12
months, in which case the repaired / replacement parts shall have the benefit of a 12 month
warranty against defects in workmanship or materials during normal usage starting on the date of
delivery. OMD‟s supplied as spares shall be warranted in accordance with paragraph 2 below
only.

2. KPL warrants for a period of 12 months from delivery that individual OMD‟s supplied as spares
shall be free from defects in workmanship or materials during normal usage.

3. Performance of KPL‟s repair or replacement obligations shall constitute an entire discharge of


KPL's liability under the warranties set out in paragraphs 1 and 2 above (“Warranties”).

4. The Warranties shall not apply to the following:


a. defects reasonably judged by KPL as being caused by the improper installation of the
OMD‟s and/or OMD system;
b. defects reasonably judged by KPL as being caused by the failure to follow the
recommendations contained in KPL‟s product manuals and/or other documentation
regarding the frequency of routine maintenance and testing of the OMD‟s and/or OMD
system and/or the failure to have such routine maintenance performed;
c. defects which are attributable to careless handling or storage, accident, improper use of
the OMD‟s and/or OMD system, or incorrectly completed repairs or routine maintenance
services;
d. damages or losses occurring as a result of any act or omission which is wilfully unlawful or
negligent;
e. defects arising from the use of non-genuine KPL parts or accessories, or the use of
materials not approved for use by KPL;

f. any modifications to or installations performed on the OMD‟s and/or OMD system outside
the scope of normal routine maintenance or running repairs without the express prior
written approval of KPL;
g. deterioration, staining or corrosion of parts which will occur due to normal exposure and
usage;
h. alleged defects not materially affecting the quality or proper functioning of the OMD
system.

5. In addition the Warranties shall be limited as follows:


a. KPL shall be under no liability in respect of any defect in the OMD‟s and/or OMD System
arising from any drawing, design or specification supplied by or at the request of the buyer
or system owner (not being a drawing, design or specification of KPL);

May 2012 Page vii of viii 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

b. KPL shall be under no liability in respect of any defect or failure of the OMD‟s and/or OMD
System to operate in accordance with specifications, illustrations, descriptions or other
particulars due to their combination or use with any incompatible equipment or product.
6. The Warranties are conditional upon:
a. the buyer or OMD system owner giving written notice to KPL of the alleged defect, such
notice to be given immediately when the buyer or OMD system owner discovers or ought
to have discovered the defect;
b. the buyer or OMD system owner affording KPL a reasonable opportunity to inspect the
OMD‟s and/or OMD system;
c. the buyer or OMD system owner not altering or attempting to repair the OMD‟s and/or
OMD system without the written consent of KPL.

7. The Warranties can be transferred to any new owner of the OMD system provided KPL is
informed in writing within 30 days of the transfer. The OMD System Warranty cannot be
transferred to another KPL OMD system.
8. Save to the extent amended by the provisions set out above, KPL‟s standard terms and conditions
of sale shall apply.

* Commissioning is to be performed by a KPL approved service agent.

OMD Service Life


Oil Mist Detectors (OMD‟s) are an integral part of critical safety systems designed to detect
certain conditions that could lead to crankcase explosions on large Diesel engines. They are
typically installed in harsh operating conditions - particularly with respect to temperature and
vibration - and are expected to provide continuous service over extended periods. They are
therefore subject to considerable wear and tear.
In order to ensure reliable performance, it is particularly important that OMD‟s are properly
installed, operated and maintained in accordance with the manufacturer‟s instructions and
guidelines. Given that they are components within key safety systems, as precautionary advice
the manufacturer recommends replacing or refurbishing OMD‟s which are more than 10 years
old, even if they are functioning correctly at that time.

May 2012 Page viii of viii 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

1 DESCRIPTION AND OPERATION

1.1 INTRODUCTION
High temperatures, in excess of 200ºC that occur on bearing surfaces under initial failure
conditions, can lead to a rapid generation of oil vapour When the hot vapour contacts the
relatively cooler atmosphere of the crankcase it condenses into a fine mist, with typical particle
sizes of around 0.5 to 5 microns in diameter. When the density of these particles reaches
between 30 to 50 mg/I (Milligrams per litre), depending upon the type of oil, an explosive
condition exists.

Piston Rod Seal

Cross Head Slides

Top End Bearing

Cross Head Bearing


Main Bearing

Bottom End Bearing

Figure 1 Areas of Failure – 2 Stroke Engine

Piston Seizure Top End Bearing

Cam Shaft Bearings Piston Blow By

Main Bearing
Bottom End
Bearing

Figure 2 Areas of Failure – 4 Stroke Engine


A fire or explosion needs three constituents: fuel, oxygen and an ignition source. Remove one of
these and no explosion will occur. Similarly, within the crankcase, the three constituents which
could cause an explosion are air, oil mist and an ignition source, the “hot spot‟. Using optical
measuring techniques, oil mist density can be measured at levels as low as 0.05 mg/I and give
early warning of a rise in oil mist density.
Oil Mist Detection (OMD) techniques have been used to monitor diesel engine crankcases for
potential explosive conditions and early detection of bearing failures. The systems available rely
mainly on analysing the optical density of oil mist samples drawn from the crankcase
compartments, through pipes to the detector. While these systems proved successful in the past,
engine design has improved significantly over the years and oil mist detection techniques have
improved substantially to maintain adequate protection.

May 2012 Page 9 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

The Graviner Mk 7 OMD provides the following benefits:


Auto addressed system monitoring up to 10 detector heads per control unit
Up to 10 control units per single system.
Suitable for both 2 stroke and 4 stroke engines.
Elimination of sample pipes - reduced installation costs.
Engine mounted Control Unit.
Optional Remote Display Unit mounted in a safe area, typically the Engine Control Room
(ECR).

Detector

Detector
Cable
Remote Display
Unit

Control Unit

Figure 3 Graviner Mk7 OMD Components

1.2 DESCRIPTION
The system comprises three main components (refer to Figure 3):
Detectors 53836-K269 (with base) / 53836-K272 (replacement head)
53836-269-01 (Short sample pipe)
Control Unit 53836-K270 (With Membrane)
53836-K276 (Without Membrane)
Remote Display Unit 53836-K271
And connecting cables
Control Unit to Detector cable (Straight) 43682-K286-XX
Control Unit to Detector cable (Right Angle) 43682-K285-XX
The Graviner Mk 7 OMD system can comprise up to 100 detectors directly mounted on the
crankcases of up to 10 engines, allowing both main propulsion and auxiliary generators to be
monitored at the same time.
Each detector communicates electronically over a serial data link via the engine mounted
Control Unit with the optional Remote Display Unit designed to be mounted within the Engine
Control Room. This eliminates the need to enter the machinery space in alarm conditions.

May 2012 Page 10 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 4 Typical System Configuration

May 2012 Page 11 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

1.3 TECHNICAL SPECIFICATION


Detector
Mounting ¾ inch BSP
Enclosure Rating IP65
Indicators Green Detector On
Red Alarm
Amber Detector Fault
Power Consumption 1.5W
o
Temperature Rating 0 – 70 C
Height 153mm
Width 90mm
Length 205mm
Weight 0.5kg

Control Unit
Enclosure Rating IP65
Max detector inputs 10
Output Relays Volt-free change over contacts rated at 30Vdc 1A
Back-up Alarm 1 set (de-energised during normal operation)
Pre Alarm 1 set (de-energised during normal operation)
Fault Alarm 1 set (energised during normal operation)
Engine Slowdown / Shutdown 1 set (de-energised during normal operation)
Alarm Ranges Pre Alarm 0.5mg/l to 1.2mg/l (adjustable)
Alarm 1.3mg/l to 2.4mg/l (adjustable)
Backup 3.0mg/l (fixed)
Power Consumption 3.9W
o
Temperature Rating 0 – 70 C
Dimensions
Height 186mm (110mm mounting centres)
Width 318mm (240mm mounting centres)
Depth 90mm
Weight 2.8kg

May 2012 Page 12 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Remote Display Unit


Enclosure Rating IP32
Max No. of detectors 100
Max No. of engines monitored 10
Power Supply 24Vdc (+30% -25%)
Power Consumption 6.0W
o
Temp Rating 0 – 70 C
Humidity level 95%
Dimensions
Bulkhead Mounted: Height 225mm (202mm mounting centres)
Width 240mm (217mm mounting centres)
Depth 58mm
Panel Mounted: Height 225mm (202mm mounting centres)
Width 240mm (217mm mounting centres)
Depth 55mm
Weight 1.0kg

May 2012 Page 13 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

1.4 SYSTEM OVERVIEW


The Graviner Mk7 OMD is an auto addressed oil mist detection system capable of monitoring
up to 10 Control Units per system with each Control Unit having up to 10 detectors connected
to it. This is achieved without external sample pipes and with minimum cabling. Each detector
head monitors a single crank space and is a stand-alone device. On power up the detectors
gather oil mist density data and convert it to a digital signal for transmission via the data lines
in the detector cable to the Control Unit which is also mounted on the side of the engine.
Alarm levels and Alarm output requirements are all set from either the optional Remote
Indicator Display or a PC connected directly to the control unit.
The Remote Display Unit houses a 7.5” LCD Touch Screen display that shows, on demand,
the signal from each detector and indicates the oil mist level for each engine and when
required each detector as well as the status of the system. In the event of an alarm, the display
immediately shows the oil mist levels for the relevant engine. It also enables the individual
readings of each detector on the engine to be displayed on demand and automatically under
alarm conditions.
In the event of a detector fault, that detector can be isolated without affecting the function of
the other detectors on the engine. The system will continue to operate while the faulty detector
is replaced, repaired or maintenance is carried out.
The Mk7 detectors still use optical sensing; (light scatter) as it‟s detection method and
continually monitors the oil mist density in the crank space to which it is connected. In addition,
it self checks for any internal faults. The Control Unit interrogates each detector in turn,
identifies the position connected at the Control Unit, the oil mist density value and determines
the status of the detector.
Each detector is fitted with 3 LED indicator lights:
Green - Power on
Red - Alarm
Amber - Fault
As all detectors operate independently, the loss of one detector through a fault does not affect
the operation of the rest of the system. Individual detectors, or engine groups, can be isolated
from the rest of the system for maintenance while the rest of the system remains in operation.
The Control Unit can be supplied with or without a control membrane. The control membrane
has LED indication for detectors connected, push buttons for isolation and de-isolation of
detectors, as well as pushbuttons for Accepting and Resetting Alarms.

Alarm Philosophy
The system has 3 separate alarm levels as detailed below
1. Pre Alarm - This indicates that the oil mist levels are increasing in a particular
crank space and that investigation should be undertaken. This alarm will not operate
the slowdown or shutdown relays.
2. High Alarm - When any detector reaches this threshold then the slowdown or
shutdown relays will be operated if they are connected.
3. Back Up Alarm - In the event of a failure of either the Pre Alarm or High Alarm, then
the Back Up Alarm will operate, but it will not operate the slowdown or shutdown relay.
This is an additional functional precaution added by Kidde Products Ltd which can be
connected in any way the customer requires. This is usually connected to a warning
beacon or siren; however the customer may choose to connect the relay to another
device or the engine slow down circuitry.
On receipt of either a Pre Alarm or High Alarm the engine should, unless connected to a
slowdown / shutdown relay, be stopped if safe to do so and allowed to cool down so that the
background oil mist levels reduce before entering the engine room.
When the oil mist levels have returned to normal then the Accept and Reset buttons can be
operated from the Control Unit membrane if fitted or alternatively form the Remote Display Unit
and the system will then return to normal operation.

May 2012 Page 14 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Fault Diagnosis
When a system fault is received, the information on the display should be noted and then the
appropriate Fault Finding procedure in Chapter 4 of the manual should be checked to enable
the fault to be rectified.
When the faults have been rectified the Accept and Reset buttons can be operated and the
system will return to normal

Event Log
All alarms, faults and events are recorded in an Event Log which is date and time stamped and
will indicate the type of event which enables analysis of the events at a later time. The Event
Log has a capacity of 1024 events and is a rolling buffer.

1.5 SYSTEM CONTROLS AND DISPLAYS


The Remote Display Unit and PC software is menu driven and provides a logical route to all
functions. It has three operating levels:
User
Engineer
Service
The User level is essentially for read only interrogation and does not allow any adjustments to
be made to alarm settings or system configuration.
The Engineer level is password protected and allows access to most functions and the full
range of programmable settings
When selected, a prompt for a password will appear, Enter 012345, when programming is
completed the Password should be changed by an authorised person to prevent unauthorised
access in the future. This process can be followed in Chapter 2.9 of this manual
The Service level is also password protected (different from the Engineer Menu) and allows
access to all functions. This is only available to authorised Kidde Fire Protection personnel and
authorised service agents.

Relay Backup
Unit off Unit on Pre-Alarm Slowdown Fault
Description Alarm

Pre-Alarm

Alarm

Backup-alarm

Fault

Figure 5 Relay Function Modes

May 2012 Page 15 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2 INSTALLATION AND COMMISSIONING

OMD Mk7 Installation

2.1 CONTROL UNIT MOUNTING

The Control Unit 53836-K270 or 53836-K276 is designed for on-engine mounting and it is
recommended that the Control Unit is installed as near to the centre of the engine as possible
to minimise detector cable lengths.
Mounting is via the four M6 locating holes in the box. Sufficient space must be left around the
Control Unit to allow access to the cable glands and the routing of the cables and to facilitate
easy access to all aspects of the Control Unit.

Figure 6 Control Unit 53836-K270

May 2012 Page 16 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.2 DETECTOR MOUNTING

Each detector is mounted to an individual crankcase via a ¾ inch BSP threaded hole.
Ensure all detectors fitted to the engine are locked tightly in place by means of the lock nut
supplied.
It is recommended that the detector be located at the upper part of the crankcase wall not in
the direct line of the oil throw. On smaller engines it is permissible to mount the detector on the
crankcase door if desired or as installation dictates, subject to vibration levels.

Figure 7 Ideal Mounting Position

The detector must be fitted at a maximum of plus or minus 20 degrees from the vertical.
Horizontally the detector must be mounted level or with the detector body inclined towards the
engine to ensure oil drainage. Refer to Figure 8, and Figure 9.
Please ensure that Detector 1 is connected to position 1 on the Control Unit, Detector 2 to
position 2. Repeat for all Detectors fitted.

May 2012 Page 17 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 8 Detector Head Installation

May 2012 Page 18 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 9 Detector Head Installation (Short Sample Pipe)

May 2012 Page 19 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.3 DETECTOR CABLES

Each detector must be connected to the Control Unit by way of a supplied detector cable.
Refer Figure 10.
Ensure that the cables are run in a suitable cable tray and clipped at regular intervals to
ensure they cannot be subjected to mechanical damage caused by vibration.

o
Cable Length 90 Connector Straight Connector
m Part No. Part No.
1.0 43682-K285-1.0 43682-K286-1.0
1.5 43682-K285-1.5 43682-K286-1.5
2.0 43682-K285-2.0 43682-K286-2.0
2.5 43682-K285-2.5 43682-K286-2.5
3.0 43682-K285-3.0 43682-K286-3.0
3.5 43682-K285-3.5 43682-K286-3.5
4.0 43682-K285-4.0 43682-K286-4.0
4.5 43682-K285-4.5 43682-K286-4.5
5.0 43682-K285-5.0 43682-K286-5.0
5.5 43682-K285-5.5 43682-K286-5.5
6.0 43682-K285-6.0 43682-K286-6.0
6.5 43682-K285-6.5 43682-K286-6.5
7.0 43682-K285-7.0 43682-K286-7.0
7.5 43682-K285-7.5 43682-K286-7.5
8.0 43682-K285-8.0 43682-K286-8.0
8.5 43682-K285-8.5 43682-K286-8.5
9.0 43682-K285-9.0 43682-K286-9.0
9.5 43682-K285-9.5 43682-K286-9.5
10.0 43682-K285-10.0 43682-K286-10.0
10.5 43682-K285-10.5 43682-K286-10.5
11.0 43682-K285-11.0 43682-K286-11.0
11.5 43682-K285-11.5 43682-K286-11.5
12.0 43682-K285-12.0 43682-K286-12.0
12.5 43682-K285-12.5 43682-K286-12.5
15.0 43682-K285-15.0 43682-K286-15.0
17.5 43682-K285-17.5 43682-K286-17.5
20.0 43682-K285-20.0 43682-K286-20.0
22.5 43682-K285-22.5 43682-K286-22.5
25.0 43682-K285-25.0 43682-K286-25.0

Figure 10 Detector Cable

May 2012 Page 20 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 11 Detector Cable Assembly (Straight Connector)

May 2012 Page 21 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 12 Detector Cable Assembly (Right Angle Connector)

May 2012 Page 22 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.4 REMOTE DISPLAY UNIT


The Remote Display Unit part number 53836-K271 must be mounted in the Engine Control
Room (ECR) or similar safe environment, do not mount in an Engine Room as it is not
designed to be mounted in this type of environment. Additionally Class Society rules state that
any display must be mounted in a safe area away from the Engine Room.

For flush mounting details see below and Figure 13 and Figure 14.
For bulk head mounting details see Figure 15.

Figure 13 Flush Mounting Cut-out for Remote Display Unit

May 2012 Page 23 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 14 Flush Mounting for Remote Display Unit

May 2012 Page 24 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 15 Bulk Head Mounting for Remote Display Unit

May 2012 Page 25 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.5 CONTROL UNIT


24v DC Input supply
The supply should be 24v DC +30% -25% rated at 1.2 amps.

Cables should be segregated from high voltage cables and follow good installation
practice
2
Cable type-2 Cores + Earth, CSA 2.5mm (50/0.25mm), flexible stranded bare copper
conductors, low smoke halogen free insulation, cores laid up, braided screen, low smoke
halogen free sheath – grey, outside diameter 9.8mm, operating temperature 0ºC + 80ºC.
Suggested cables
2
Lapp Kabel CY cable 3 core 2.5mm
2
Prysmian LSM-HF 3 core 2.5mm
2
Helkama LKAM-HF 3 core 2.5mm

Refer Figure 16 for connector location.


Refer Figure 16 for wiring drawing.

Modbus
Cable type – Individually screened 2 pair data cable, 24AWG, low capacitance, low smoke
halogen free. Outer diameter 7mm (max)

Cables should be segregated from high voltage cables and follow good installation
practice

Suggested cables
FS Cables 2402PIFFH
Beldon 9729
Helkama RFE-HF(i) 2x2x0.75
Jinro 60V RCOP(IS)

The above cable should be used to connect between the Control Unit and either the ships
AMS system or the Remote Display Unit.

Refer Figure 16 for connector location.


Refer Figure 16 for wiring drawing.

Relay Outputs
The relay outputs are rated at 30v DC at 1amps.
2
2 Cores + Earth, CSA 2.5mm (50/0.25mm), flexible stranded bare copper conductors, low
smoke halogen free insulation, cores laid up, braided screen, low smoke halogen free sheath
– grey, outside diameter 9.8mm, operating temperature 0oC + 80oC.
Cables should be segregated from high voltage cables and follow good installation
practice

Approved cables
2
Lapp Kabel CY cable 3 core 2.5mm
2
Prysmian LSM-HF 3 core 2.5mm
2
Helkama LKAM-HF 3 core 2.5mm

Refer Figure 16 for connector location.


Refer Figure 16 for wiring drawing.

USB Connection
Refer Figure 16 for connection location.

May 2012 Page 26 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

End of Line
Jumper

Modbus
Connector

End of Line
Jumper

USB
Connection

Relay Output
Connectors

24v DC input
Connector

Figure 16 Control Unit PCB

All Detector connectors are prewired.

May 2012 Page 27 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 17 Wiring Drawing

May 2012 Page 28 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.6 REMOTE DISPLAY UNIT


24v DC Input supply
A 24v DC supply rated 1.5 amps should be connected via a Hirschmann GM216 NJ.
2
Cable type – 2 Cores + Earth, CSA 1.5mm , fine stranded bare copper wires, braided screen,
low smoke halogen free sheath, outside diameter 10mm (max), operating temperature 0ºC +
80ºC.

Cables should be segregated from high voltage cables and follow good installation
practice

Suggested cables
2
Lapp Kabel 1.5mm Ölflex Classic 110CH - 10035068
2
Prysmian LSM-HF 3 core 1.5mm
2
Helkama LKAM-HF 3 core 1.5mm

Refer Figure 18 for 24vDC Socket wiring drawing.


Refer Figure 20 for connection location.

Figure 18 24v DC Socket Wiring Drawing

May 2012 Page 29 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Modbus
Cable type – Individually screened 2 pair data cable, 24AWG, low capacitance, low smoke
halogen free. Outer diameter 7mm (max)

Cables should be segregated from high voltage cables and follow good installation
practice

Suggested cables
FS Cables 2402PIFFH
Beldon 9729
Helkama RFE-HF(i) 2x2x0.75
Jinro 60V RCOP(IS)

The above cable should be used to connect between the control unit and either the ships AMS
system or the Remote Display Unit

Refer Figure 19 for Modbus Connector Wiring Drawing.


Refer Figure 20 for connector location.

Figure 19 Modbus Connector Wiring Drawing

24v DC
Connector Modbus
Connector

Figure 20 Remote Display Unit 53836-K271

May 2012 Page 30 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Intentionally Left Blank


Figure 21 Intentionally Left Blank

May 2012 Page 31 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.7 CONNECTING THE SYSTEM


2.7.1 Input power
+24 V dc and 0 V dc power input cables for the Control Unit should be terminated onto Supply
Input (terminal block TB1).
Cables should be segregated from high voltage cables and follow good installation
practice

Note all terminations should be made using crimped wires.


For each of the power connections strip the power cable to the required length to connect to
the terminals in the control unit. Then remove approximately 1cm of the outer sheath to
expose the cable screen as shown below.

Exposed screen

Figure 22 Power cable

Feed the cable into the control unit via a metal IP65 EMC gland supplied, ensuring that the
metal prongs make contact with the exposed cable screen as shown below.

Cable gland

Earthing Prongs

Figure 23 Power cable through EMC gland

May 2012 Page 32 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.7.2 Relay Cables


The connection to the slowdown relay, pre-alarm relay, backup alarm relay and fault relay and
24Vdc supply cables at the Control Unit should be made using screened cable. For each of the
relay connection strip the cable to the required length to connect to the terminals in the control
unit. Then remove approximately 1cm of the outer sheath to expose the cable screen as
shown below see Figure 24.
Cables should be segregated from high voltage cables and follow good installation
practice

Figure 24 Control unit relay cable assembly


Feed the cable into the control unit via a metal IP65 EMC gland supplied, ensuring that the
metal prongs make contact with the exposed cable screen as shown.

2.7.3 Control Unit to Detector Connections


At the detector, screw the connector to the top of the detector.

Figure 25 Detector cable assembly

May 2012 Page 33 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

At the control unit, screw the connector to the input required.

Note: Numbering indicates


correct Detector installation
position.

Figure 26 Control unit - Detector cable assembly

2.8 SYSTEM CHECKS PRIOR TO SWITCHING ON


2.8.1 Ensure that the 24v DC input power supply cable is connected correctly at each Control Unit (if
more than one installed).
2.8.2 Ensure that the Modbus Communication (if required) is terminated correctly at each Control
Unit (if more than one installed and/or Remote Indication Display installed or connected to
AMS).
2.8.2.1 If more than one control unit is installed, please ensure the End of Line (EOL) jumpers are
removed from all Control Units (refer Figure 15) except for the highest Modbus addressed
Control Unit.
2.8.2.2 Make sure that the Modbus address‟s are set as required, refer section 2.9.1 for procedure.
2.8.3 Ensure that the Backup Alarm, Pre Alarm, Fault and Slowdown relays are connected correctly
at each Control Unit (if more than one installed).
2.8.4 Ensure the detectors are connected to each Control Unit in the correct number sequence.
2.8.5 Check the cable run of all Modbus Communication cables between all installed Control Units
to each other and to the Remote Indication Display (If Installed) or AMS to ensure that it is not
damaged.
2.8.6 Ensure all unused Glands are removed from all Control Units and replaced by Blanking Plugs.
2.8.7 Ensure that the Modbus Communication and power supply cables are connected correctly at
the Remote Display Unit (If installed).
2.8.8 Ensure that the input voltage at the Control Unit(s) and the Remote Display Unit (If installed) is
a clean 24 V dc +30%, - 25%
2.8.9 When all of the above have been checked and are satisfactory the system is ready to switch
on.
2.8.10 Allow the engine to reach its' normal operating temperature before continuing to System
Configuration and Commissioning.
Oil Mist alarm levels should be set to a level above the actual normal operating level
displayed,

May 2012 Page 34 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.9 SYSTEM SETUP / CONFIGURATION – WITH A REMOTE DISPLAY UNIT


When all of the connections have been completed and checked, power up the Control Unit and
Remote Display Unit, the following power up screen will show for a few seconds on the
Remote Display Unit.
If there is more than one Control Unit connected to the display the Modbus address needs to
be set up via the USB connection on the control unit before it can talk to the display unit.
Please refer to section 2.9.1.1 for the Modbus setup

Figure 27 Screen Shot 1

After a few seconds the following will


be seen on the Remote Display Unit,
this shows one engine connected but
may show up to ten.

Press „OK‟

Figure 28 Screen Shot 2

Press the „Engineer‟ button to log in


as an Engineer.

Note – To setup Engine and


Detectors and Save Logs, you
must be logged in as Engineer.

Figure 29 Screen Shot 3

May 2012 Page 35 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Enter password 012345.

Figure 30 Screen Shot 4

Press „Menu‟ Button to display the


Engineers menu.

Figure 31 Screen Shot 5

To set or change Engine Names


press „Engine Names‟.

Figure 32 Screen Shot 6

Press the up and down arrows to


cycle through possible Engine
Names, this figure shows one engine
connected but may show up to ten.
Please see below for the full list of
Engine Names.
Press „Save‟ once your desired name
is selected for Engines.

Figure 33 Screen Shot 7

May 2012 Page 36 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Engine Selection List


ME 1 – Main Engine 1 ME 2 – Main Engine 2 FSU – Fuel Supply Unit
G/E 1 – Generator 1 GEN 1 – Generator 1 AUX 1 – Auxiliary Engine 1
G/E 2 – Generator 2 GEN 2 – Generator 2 AUX 2 – Auxiliary Engine 2
G/E 3 – Generator 3 GEN 3 – Generator 3 AUX 3 – Auxiliary Engine 3
G/E 4 – Generator 4 GEN 4 – Generator 4 AUX 4 – Auxiliary Engine 4
G/E 5 – Generator 5 GEN 5 – Generator 5 AUX 5 – Auxiliary Engine 5
G/E 6 – Generator 6 GEN 6 – Generator 6 AUX 6 – Auxiliary Engine 6
G/E 7 – Generator 7 GEN 7 – Generator 7 AUX 7 – Auxiliary Engine 7
G/E 8 – Generator 8 GEN 8 – Generator 8 AUX 8 – Auxiliary Engine 8
G/E 9 – Generator 9 GEN 9 – Generator 9 AUX 9 – Auxiliary Engine 9

Press „OK‟.
Figure 32 will then be displayed.
To change the Time & Date press
„Set Time / Date

Figure 34 Screen Shot 8

Use numeric keys to set the Time


and Date. Press „OK‟ when complete
Note – Time and Date must be
entered even if the correct Time
and Date is displayed.

Figure 35 Screen Shot 9

Press „OK‟, Figure 32 will then be


displayed.
To change the Engineer PIN press
„Change Engineer PIN‟.

Figure 36 Screen Shot 10

May 2012 Page 37 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Use numeric keys to enter new pin of


6 digits and then store in a safe place
where only authorised users can
access it
If the PIN number is lost, please refer
to Kidde Fire Protection

Figure 37 Screen Shot 11

Use numeric keys to re enter new pin


of 6 digits.

Figure 38 Screen Shot 12

Press „OK‟.
Figure 32 will then be displayed.
To save the event Log press „Save
Logs‟

Figure 39 Screen Shot 13

Figure 40 Screen Shot 14

May 2012 Page 38 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Press „OK‟ to return to Figure 32.


Note – Once the Logs are saved,
only Kidde Authorised Service
Agents can download them.
Press „Exit‟ to return to Engines
Overview screen (Figure 31)

Figure 41 Screen Shot 15

To setup the Detectors on each


Engine, press the button under the
mg/l display for the Engine being
setup.

Figure 42 Screen Shot 16

Press „Menu‟ to display the Engine


Menu.

Figure 43 Screen Shot 17

To set or change Detector Names


press „Detector Names‟.

Figure 44 Screen Shot 18

May 2012 Page 39 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Press the up and down arrows to


scroll through possible Detector
Names, this figure shows one
detector connected but may show up
to ten detectors.
Please see below for the full list of
Detector Names.
Press „Save‟ once your desired name
is selected for Detectors.

Figure 45 Screen Shot 19


Detector Selection List
Detector 1 Cylinder 1 Fuel Supply Unit 1
Detector 2 Cylinder 2 Fuel Supply Unit 2
Detector 3 Cylinder 3 Fuel Supply Unit 3
Detector 4 Cylinder 4 Fuel Supply Unit 4
Detector 5 Cylinder 5 Fuel Supply Unit 5
Detector 6 Cylinder 6 Chain Case
Detector 7 Cylinder 7 Gear Box
Detector 8 Cylinder 8 Transfer Box
Detector 9 Cylinder 9 Thrust Bearing
Detector 10 Cylinder 10 Moment Compensator
Detector 11 Cylinder 11
Detector 12 Cylinder 12
Detector 13 Cylinder 13
Detector 14 Cylinder 14
Detector 15 Cylinder 15
Detector 16 Cylinder 16
Detector 17 Cylinder 17
Detector 18 Cylinder 18
Detector 19 Cylinder 19
Detector 20 Cylinder 20

Press „OK‟. Figure 44 will then be


displayed.
Press „Exit‟.

Figure 46 Screen Shot 20

May 2012 Page 40 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

To set the individual Detector


parameters, press the button under
the mg/l display for the required
detector.

Figure 47 Screen Shot 21

Press „Menu‟ to display the Detector


Menu.

Figure 48 Screen Shot 22

Press the up and down arrows to


select the desired Alarm and Pre
Alarm Levels.
Alarm Limits 1.3 – 2.4mg/l
Pre-Alarm Limits 0.5 – 1.2mg/l
Default Settings
Alarm – 1.8mg/l
Pre-Alarm – 0.9mg/l

Press „Save‟ once complete.

Figure 49 Screen Shot 23

Press „OK‟.
Figure 48 will then be displayed.
Press „Back‟ to return to Figure 47.
Repeat setting Detector settings for
the number of Detectors connected.

Figure 50 Screen Shot 24


Once Detectors on Engine 1 have been set, Press „Back‟ to return to Engine Overview screen.
Repeat setting Engine Names & Detector settings for the number of Engines connected.
The OMD Mk7 System should now be setup.

May 2012 Page 41 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.9.1 Control Unit Addressing


When more than one Control Unit is connected on 1 system, the Modbus address needs to be
set up via the USB connection on the PCB in each Control Unit (refer Figure 51) before the
system will work properly.
NOTE – For multiple Control Units per system, each Control Unit must have its own
Control Unit Address and they must be sequential, i.e. 01. 02. 03 …..10
st
All Control Units will come shipped as Modbus address 01 (1 Control Unit)
2.9.1.1 To change the Modbus address
a. Connect the 24Vdc power supply to the Control Unit to be changed.
b. Connect the USB-B end to the USB socket located on the PCB inside the Control Unit (refer
Figure 51)

USB
Connection

Figure 51 Control Unit – USB Connector


c. Connect the other end of the USB Lead to a USB socket on your computer (refer Figure 53)

Figure 52 Computer Connection – USB Connector

May 2012 Page 42 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.9.1.2 With the above cables connected, open the „Mk7 Oil Mist Engine Manger‟ software on the
computer.

Click „Login‟, then „Engineer‟

Figure 53 USB Screen Shot 1

Enter 012345 and press „Login‟

Figure 54 USB Screen Shot 2

Select the required Control Unit


Address (this is the Modbus address)

Figure 55 USB Screen Shot 3

Repeat the above for the number of Control Units installed per system.
After the address‟s have been changed, please ensure that the EOL jumpers are fitted to the last
Control Unit, all other Control Units need to have the EOL jumpers removed.
Refer Figure 16 for EOL jumper positions.

May 2012 Page 43 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.9.2 Detector Smoke Alarm Test


Commence the smoke alarm test as follows: with the detector(s) fitted, electrically connected,
functioning and configured as described in the instruction manual.

Note: Isolation of the output relays (Pre Alarm and Slow-Down Relays) is
required before commencing the smoke alarm test. If the Back-up Alarm Relay
is connected to the engine shut/slow down system this should be
disconnected.
Warning: Carrying out this test without isolation or disconnection of the output
relays will cause the engine shut/slow down system to operate if connected.

a. Cut a length of wick approximately 30 mm long. Assemble the smoke tester by pushing
the wick into the wick holder fitted with the pipette bulb. Press the nylon pipe into the pipe
connector (refer to Figure 56).

Pipette Bulb

Wick Holder
Wick

Pipe Connector

Nylon Pipe

Figure 56 Smoke Tester

b. Push the nylon pipe of the smoke tester into the connector on the side of the detector
base body (refer to Figure 57).

May 2012 Page 44 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 57 Smoke Test

c. Dip the wick into the bottle of smoke oil and reseal the bottle firmly
Note: Only a small quantity of oil is required.
d. Ignite the wick of the smoke tester and blow out the flame. Squeeze the pipette bulb to
keep the wick smoking.
Note: Care to be taken with this activity at all times.
e. While the wick is still smouldering, insert it into the pipe connector and squeeze the
pipette bulb.
f. Observe the wick is still smouldering, insert nylon pipe into the pipe connector of the
detector and squeeze the pipette bulb.
g. After tests are completed the Detector Peak Level readings should be erased. This can be
done via the Engine Menu using Clear Peak. (refer Figure 44)
h. To release the pipe from the connector, press in the metal collar on the end of the
connector at the same time as pulling the pipe out
i. Remove the nylon pipe from the pipe connector for stowage purposes.
j. The wick is reusable and can be left in the wick holder. Fully extinguish the wick after use
at all times.
k. Refer to the Material Safety Data Sheet in the event of health or safety issues.

May 2012 Page 45 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.9.3 Back Up Alarm


The backup alarm is a hard wired link from each Detector installed on the system. This facility
will allow any detector which is in a fault condition and sees an oil mist level of 3.0mg/I or
greater to produce a „Back Up Alarm. This will produce operation of the Backup Alarm Relay in
the Control Unit; the Backup Alarm will also override any detector or detectors that are
isolated.
Whilst any detectors are in a Backup Alarm condition the accept key is inoperative until
the oil mist level drops below 3.0mg/l.
It is possible for a healthy detector to produce a back up alarm if the level of oil rises very
rapidly.
NOTE - The Backup Alarm will not operate the Slow-Down Relay

May 2012 Page 46 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.10 ISOLATION – USING THE REMOTE DISPLAY UNIT


If required, it is possible to isolate any individual detector, a complete engine, engine Pre-
Alarm or Slow Down relays. This allows maintenance to be carried out without affecting the
remaining system. Isolation inhibits all alarms and faults for the isolated item except the
Backup Alarm, which is a fixed level.

To prevent the possible activation of the Back-up Alarm Relay disconnect the cable from the
top of the detector unit.

2.10.1 Engine Isolation

To Isolate Engine or detectors on the


engine, press the button under the
mg/l display for the Engine to be
isolated. You must be in the Engineer
level to carry out this function

Figure 58 Screen Shot 25

Press the „Menu‟ button.

Figure 59 Screen Shot 26

Press the „Isolate‟ button.

Figure 60 Screen Shot 27

May 2012 Page 47 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

To Isolate All Detectors, press the


„Isolate‟ button.

Figure 61 Screen Shot 28

Press „Yes‟ to Isolate All Detectors.

Figure 62 Screen Shot 29

Press „OK‟

Figure 63 Screen Shot 30

To De-Isolate All Detectors, press the


„De-Isolate‟ button.

Figure 64 Screen Shot 31

May 2012 Page 48 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Press „Yes‟ to De-Isolate All


Detectors.

Figure 65 Screen Shot 32

Press „OK‟
You will be returned to Figure 64.
To Isolate the Pre-Alarm Relay, press
„Isolate‟

Figure 66 Screen Shot 33

Press „Yes‟ to Isolate the Pre-Alarm


relay.

Figure 67 Screen Shot 34

Press „OK‟

Figure 68 Screen Shot 35

May 2012 Page 49 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

To De-Isolate the Pre-Alarm relay,


press the „De-Isolate‟ button.

Figure 69 Screen Shot 36

Press „Yes‟ to De-Isolate the Pre-


Alarm relay.

Figure 70 Screen Shot 37

Press „OK‟
You will be returned to Figure 69.
To Isolate the Slow Down Relay,
press „Isolate‟

Figure 71 Screen Shot 38

Press „Yes‟ to Isolate the Slow Down


relay.

Figure 72 Screen Shot 39

May 2012 Page 50 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Press „OK‟

Figure 73 Screen Shot 40

To De-Isolate the Slow Down relay,


press the „De-Isolate‟ button.

Figure 74 Screen Shot 41

Press „Yes‟ to De-Isolate the Slow


Down relay.

Figure 75 Screen Shot 42

Press „OK‟
You will be returned to Figure 74.
Press „Exit‟ to return to Figure 59.
Press „Exit‟ to return to Engine 1
overview.

Figure 76 Screen Shot 43

May 2012 Page 51 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.10.2 Detector Isolation

To Isolate single Detectors, press the


button under the mg/l display for the
required detector.

Figure 77 Screen Shot 44

Press „Menu‟

Figure 78 Screen Shot 45

Press „Isolate‟

Figure 79 Screen Shot 46

Press „Yes‟ to Isolate the Detector.

Figure 80 Screen Shot 47

May 2012 Page 52 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Press „OK‟

Figure 81 Screen Shot 48

To De-Isolate the selected Detector,


press „De-Isolate‟

Figure 82 Screen Shot 49

Press „Yes‟ to De-Isolate the


Detector.

Figure 83 Screen Shot 50

Press „OK‟
You will be returned to Figure 82.
Press „Back‟ button to return to Figure 78.
Press „Back‟ button to return to Engine 1
overview screen (Figure 77).
Press „Back‟ button to return to Engines
overview screen.

Figure 84 Screen Shot 51

May 2012 Page 53 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.10.3 Detector Isolation – Using the Membrane


To isolate a detector at the Control Unit fitted with a Membrane, press the detector number
button for 2 seconds until the amber LED is steady. (Refer Figure 85)

Note: with the detector isolated the Back-up Alarm Relay may be activated if the oil mist level
increases above 3mg/l or light is introduced in to the detector. To prevent the possible
activation of the Back-up Alarm Relay disconnect the cable from the top of the detector unit.

Figure 85 Control Unit Membrane

Repeat the above to de-isolate a detector.

May 2012 Page 54 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.11 TEST MENU & EVENT LOG


This section will show how to Test the components in the OMD Mk7 system, and how to view
the Event Log. The Test and Event Log instructions are the same for User Level and Engineer
Level with the exception that the User Level cannot Test the Slow Down Relay.

2.11.1 Test Menu.


Warning: Carrying out this test with the engine operating will cause the engine shut/slow down
system to operate if connected.

Select the desired Engine for testing.

Figure 86 Screen Shot 52

Press the „Test‟ button.

Figure 87 Screen Shot 53

To test the Slow Down Relay, press


the „1‟ button.

Figure 88 Screen Shot 54

May 2012 Page 55 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Press „OK‟
You will be returned to Figure 88
To Test the Pre-Alarm Relay, press
the „1‟ button.

Figure 89 Screen Shot 55

Press „OK‟
You will be returned to Figure 88.
To Test the Fault Relay, press the „0‟
button.

Figure 90 Screen Shot 56

Press „OK‟
You will be returned to Figure 88.
To Test the Backup Alarm, press the
„Test‟ button.
Note – This is a software test only.

Figure 91 Screen Shot 57

Press „OK‟
You will be returned to Figure 88.
To Test the Optics, press the „Test‟
button.

Figure 92 Screen Shot 58

May 2012 Page 56 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Press „OK‟
You will be returned to Figure 88.
To Test the Front Panel, press the
„Test‟ button.

Figure 93 Screen Shot 59

Press „OK‟
You will be returned to Figure 88.
Press „Exit‟ to return to Engine 1
overview.
Note - This will also reset all Tests.

Figure 94 Screen Shot 60


For Testing of detectors per engine,
press the button under the mg/l
display for the required detector.

Figure 95 Screen Shot 61

Press „Alarm Test‟

Figure 96 Screen Shot 62

May 2012 Page 57 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Press „Test‟

Figure 97 Screen Shot 63

Press the button under the mg/l


display for the required engine.

Note: The Control Unit and


Detector tested will show ‘Alarm’.

Figure 98 Screen Shot 64

Press „Accept‟

Figure 99 Screen Shot 65

Press „OK‟

Figure 100 Screen Shot 66

May 2012 Page 58 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Press „Reset‟

Figure 101 Screen Shot 67

Press „OK‟
You will now return to Figure 87.
Press the „Back‟ button to return to
Engine Overview, Figure 86.

Figure 102 Screen Shot 68

May 2012 Page 59 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

2.11.2 Event Log.

The Event Log enables the user to interrogate the past 1024 events and can be accessed via
the menus below. The Event Log is a rolling buffer and when the events exceed 1024 then the
oldest event is dropped off the Event Log.

To access the Event Log from Figure 87, press „Event Log‟ button.

Use the Up and Down arrows to


scroll through the events in this
screen.
Press „By Date‟ tab to view event log
by date.

Figure 103 Screen Shot 70

Use the number buttons to select the


date to view events.
Press „Search‟ once the correct date
is entered.

Figure 104 Screen Shot 71

Use the Up and Down arrows to


scroll through the events in this
screen.
Press „By Event‟ tab to view event log
by Event.

Figure 105 Screen Shot 72

Note - If there are no Events matching your search then this screen will be blank.

May 2012 Page 60 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Use the Up and Down arrows to


select the event to search.
Press „Search‟ to view event log by
selected event.

Figure 106 Screen Shot 73

Use the Up and Down arrows to


scroll through the events in this
screen.
Press „By Detector‟ tab to view event
log by Detector.

Figure 107 Screen Shot 74

Use the Up and Down arrows to


select the detector to search.
Press „Search‟ to view event log by
selected detector.

Figure 108 Screen Shot 75

Use the Up and Down arrows to


scroll through the events in this
screen.
Press „Exit‟ to return to Engine 1
overview, Figure 87.
Press „Back‟ to return to Engines
Overview screen.

Figure 109 Screen Shot 76

May 2012 Page 61 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

3 MAINTENANCE

3.1 ROUTINE MAINTENANCE


Warning: Do not work on the system unless the power is
switched off or isolated.

Caution: Ensure that anti static handling procedures are


observed applied when working on the system, i.e. Anti- Static
Wrist Straps
The following checks are recommended to be carried out every 6 months , with the
system switched off. The checks should be carried out by competent personnel with
suitable skill levels.
3.1.2 Control Unit
1. Ensure that all connectors are tight to prevent ingress of oil and moisture and the screws
on the Control Unit are correctly tightened
3.1.3 Cables
1. Ensure all connections on the Control Unit are tight.
2. Check all cables. Replace any that are found to be damaged.
3.1.4 Detectors
1. Ensure that the detector base is screwed tight into the crankcase,
2. Remove the cable connector from the detector and check for damage.

May 2012 Page 62 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

3.2 DETECTOR HEAD REPLACEMENT


Warning: Do not remove the detector base from the crankcase whilst the engine is in
operation. This operation should be carried out while the engine is stopped
to avoid the possibility of hot oil coming out of the base fixing hole.
If an in-service detector head is removed for any reason, the detector optics must be cleaned
before reassembling and replacing it.
3.2.1 To replace the detector:
1. Switch off the system (if safe to do so) or isolate the detector
2. Remove the cable connector fitted to the top of the detector
3. Using a 4mm hexagonal key, loosen the two fixing screws in the assembly base.

Figure 110 Base Fixing Screw Removal

4. Lift out the faulty detector head


5. Fit the new detector head onto its base and tighten up the fixing screws. Re-fit the cable to
the detector head.
6. If the system was switched off, switch back on and allow the system to initialise.
7. If isolated, then de-isolate, Press OK on the Remote Display Unit, display will then return
to normal

May 2012 Page 63 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

3.3 DETECTOR HEAD REFURBISHMENT


1. Isolate the detectors as described in section 2.10 of the instruction manual.
2. Disconnect the cable from the top of the detector unit and remove the unit from the engine
casing (refer to Figure 111).

Figure 111 Cable Disconnect

3. Using a 4mm hexagon key, unscrew 2 off screws from the underside of the detector head
(refer to Figure 110). The screws are self-retaining.
4. Remove and invert the top part of the detector head. Examine the base moulding seal and
replace if damaged or perished (refer to Figure 112).

Screw Removal Fan Socket Fixing


Screw

Base Moulding Seal

Fan Retaining Plug

Figure 112 Base Moulding Seal


Caution: Do not press the fan, only handle the outer housing.

May 2012 Page 64 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

5. Using the Pulling Tool (refer to Figure 113), remove the Fan Retaining Plug by capturing
the shoulder and pulling. Carefully remove the Fan from its mountings (refer to Figure
114).

Figure 113 Pulling Tool

Compression
Spring

Fan

Fan Retaining
Plug

Figure 114 Fan Removal

May 2012 Page 65 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

6. Examine the 4 off compression springs and the fan retainer plug; replace any bent or
damaged items from the spares.
7. Examine the fan for free running and clogging due to oil residues. If damaged, refer to
paragraph 3.4 in the instruction manual. Although not necessary for service cleaning,
spares of the M3 screw and the fan connector seal are included in the kit.
8. Using a foam bud with glass cleaner applied, wipe carefully around the inside of the
smoke detecting orifice (refer to Figure 115).

Figure 115 Cleaning Light Guide

9. Dry the inside of the unit.


10. Examine the base body cavity and sampling tube, and wipe clean where necessary.
11. Reassemble the fan to the detector using a fan retaining plug.
Caution: Do not press the fan, only handle the outer housing.
12. Reassemble the detector head and base body. Replace the detector and then de-isolate.
13. Repeat the procedure for all detectors to be cleaned.
Refer to the Materials Safety Data Sheet in the event of health or safety issues.

May 2012 Page 66 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

3.4 FAN REPLACEMENT


Warning: Do not remove the detector base from the crankcase
whilst the engine is in operation. This operation should
be carried out while the engine is stopped to avoid the
possibility of hot oil coming out of the base fixing hole.
3.4.1 To replace the fan:
1. Switch off the system (if safe to do so), or isolate the associated detector.
2. Remove the cable connector from the top of the detector.
3. Using a 4mm Allen key, loosen the detector fixing screws on the base.
4. Remove the detector from its base and turn it upside down to reveal the fan.
5. Remove the fixing screw holding the fan socket to the mounting plate.
6. Using a pulling tool (Part Number D9131-002 available with service kit Part No.D9221-
027), remove the fan retaining plug holding the fan onto its mounting legs.
7. Lift the fan off of its mounting legs, ensuring the springs under the fan are not lost.
8. Discard the failed fan and fit a replacement fan in reverse order of disassembly.

3.5 CABLE REPLACEMENT


If changing a detector cable, isolating that detector will be sufficient (see section 2.10)
3.5.1 Detector Cable
1. Isolate the detector with the damaged cable.
2. Remove the cable connector on top of the detector.
3. Identify the cable to be removed at the Control Unit
4. Unscrew the cable connector at the Detector and discard the damaged cable.
5. Connect the replacement cable to the connector on the Control Unit ensuring it is screwed
in place.
6. Connect the cable connector to the detector
7. De-isolate the detector
8. Press OK on The Remote Display Unit
3.5.2 Power Supply Cable Replacement (Supplied by Others)
1. Switch off the system.
2. Disconnect the damaged power supply cable from the Control Unit or Remote Display
Unit.
3. Connect the replacement power supply cable to the Control Unit or Remote Indictor Unit
ensuring wires and cable screen are correctly fitted in the terminals.
4. Switch the system on and allow the system to initialise.

May 2012 Page 67 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

3.5.3 Communications Cable Replacement (Supplied by Others)


1. Switch off the system.
2. Disconnect the damaged communications cable from the Control Unit.
3. Disconnect the damaged communications cable from the Remote Display Unit or AMS.
4. Connect the replacement communications cable to the Control Unit ensuring it is screwed
in place.
5. The replacement communications cable must be connected to the terminals in the Control
Unit and the Remote Display Unit or AMS.
6. Switch the system on and allow it to initialise.
3.5.4 Control Unit (Pre-Alarm, Slowdown/Shutdown and Back Up Alarm or Fault Relay Cable
Replacement (Supplied by Others)
1. Switch off the system.
2. Remove the Control Unit Lid by removing the 4 screws
3. Disconnect the damaged relay cable from the Control Unit.
4. Disconnect the damaged relay cable from the monitoring equipment.
5. Connect the replacement relay cable to the control unit ensuring it is screwed in place.
6. Connect the replacement relay cable to the monitoring equipment.
7. Switch the system on and allow it to initialise.

3.6 CONTROL UNIT MEMBRANE


A new Control Unit Lid will be supplied fitted with the Membrane.

1. Unscrew the 4 screws to remove the Control Unit Lid


2. Disconnect the 2 ribbon cables connecting the Control Unit Lid to the main PCB.
3. Fit new lid in reverse

3.7 CONTROL UNIT PCB REPLACEMENT


1. Power down the system
2. Remove the 4 screws from the lid
3. Disconnect the ribbon cables
4. Remove the top half of the terminal blocks for the Communications Cables, Pre Alarm and
High Alarm Cables and Fault Cables
5. Disconnect the detector connectors (1 through to 10) – Push sides to release.
6. Remove the 4 screws at the corners of the PCB
7. Remove PCB
8. Fit new PCB in reverse order to the above

3.8 DECOMMISSIONING
All the components of the Graviner Mk7 OMD system must be disposed of as
electrical/electronic equipment waste. i.e. using waste disposal methods in accordance with
current local waste disposal regulations.

May 2012 Page 68 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

4 FAULT FINDING

4.1 GENERAL
The table below lists a series of failure modes and the likely faults that would be indicated
should that failure mode appear. Also listed are Actions, numbered 1 to 19, which should be
followed if the associated fault appears. On the following pages, Actions 1 to 19 are shown as
flow charts which will assist with fault finding on the Graviner Mk7 OMD system

Control Unit without a Remote Display

Failure Mode Fault Indication Fault Action

Supply Failure
Control Unit Power indicator is off All Control Unit LED‟s off 1.
Membrane failure

Control Unit fault Control Unit fault LED on. Control Unit fault 2.

No indication on the
detectors.
All detector Power On (Green) Control Unit fuse.
Control Unit fault LED on, all 3.
indicators are off. Detectors disconnected.
detector fault LED‟s flashing
1sec on 1sec off

Detector fault LED on Damaged detector cable


A detector indicating Control Unit fault LED on, all Detector failure. 4.
communications fault detector fault LED flashing
1sec on 1sec off Damaged Control Unit PCB

Detector fault LED on Fan fault


Detector fault other than Control Unit fault LED on, all LED contamination fault 5.
communications fault. detector fault LED flashing
0.5sec on 0.5sec off Detector failure

May 2012 Page 69 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Control Unit with Remote Display

Failure Mode Fault Indication Fault Action

All Control Unit LED‟s off

Control Unit Power indicator is off Communications fault with Supply Failure 6.
the engine indicated on the
Remote Display

Control Unit fault LED on.


Control Unit membrane
Control Unit membrane fault Front panel test failed fault 7.
indicated on the Remote
Control Unit PCB fault
Display

Control Unit fault LED on.


Control Unit memory fault External RAM indicated on Control Unit PCB fault 8.
the Remote Display

Control Unit fault LED on.


Control Unit watchdog fault Watchdog fault indicated on Control Unit PCB fault 8.
the Remote Display

No indication on the
detectors.
Control Unit fault LED on, all
All detector Power On (Green) detector fault LED‟s flashing Detectors disconnected.
3.
indicators are off. 1sec on 1sec off Power Supply failure
Remote Display indicates
communications fault on all
detectors for that engine.

Detector fault LED on


Control Unit fault LED on, all Damaged detector cable
detector fault LED flashing
A detector indicating
1sec on 1sec off Detector failure. 4.
communications fault
Remote Display indicates Damaged Control Unit PCB
communications fault on one
detector

Detector fault LED on


Control Unit fault LED on, all
detector fault LED flashing
Detector fan fault. Fan fault 9.
0.5sec on 0.5sec off
Remote Display indicates fan
fault on a detector

Detector fault LED on


Detector sample area
Control Unit fault LED on, all requires cleaning.
detector fault LED flashing
Detector LED fault. 10.
0.5sec on 0.5sec off An LED has failed.
Remote Display indicates an Detector failure.
LED fault on a detector

May 2012 Page 70 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Control Unit with Remote Display

Failure Mode Fault Indication Fault Action

Detector fault LED on


Control Unit fault LED on, all
detector fault LED flashing Detector sample area
Detector LED fault. 0.5sec on 0.5sec off requires cleaning. 10.
Remote Display indicates a Detector failure.
photodiode fault on a
detector

Detector fault LED on


Control Unit fault LED on, all
detector fault LED flashing
Detector watchdog fault. Detector software has reset 11
0.5sec on 0.5sec off
Remote Display indicates a
watchdog fault on a detector

Modbus communications
cable fault
Remote Display indicates a
Remote Display communications
communications fault on all End of line termination 12
with all engines fault.
engines incorrect.
Remote Display failure

May 2012 Page 71 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 1

No Is 24v present
at the supply
input terminals
(TB1)

Is the 24v input Yes


No power supply
cable connected
correctly

Yes

Correctly connect the 24v


Replace the Control
supply to the Control Unit
Unit

May 2012 Page 72 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 2

No Is 24v supply
between 18 –
31.2v

Reconnect the input Yes


supply to the correct
voltage
Cycle the power supply to
the Control Unit off then on.

No Do all of the
membrane LED‟s
operate correctly

Yes

Replace the Control


Unit lid and membrane Replace the Control Unit
PCB

May 2012 Page 73 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 3

Check the connections from the Control


Unit PCB to the Detector connectors.
Check all detector cables are connected
correctly.

No Are all
connections
made correctly

Yes

Remove the power from the


Correct the
Control Unit for a period of 15
connections
minutes

No On power up are
the detector
power LED‟s on

Yes

Replace the Control


Unit PCB
End

May 2012 Page 74 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 4

Swap the detector with an adjacent


working detector.

Yes Does the


communications
fault move with
the detector

No

Replace the faulty At the Control Unit swap the


detector. detector cable with an adjacent
working connection.

Does the
Yes communications
fault move with
the cable

No

Replace the faulty Replace the Control


detector cable Unit PCB

May 2012 Page 75 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 5

Remove the detector head and


check the operation of the fan.

No Is the fan
operating
correctly

Yes

Clean the detector sample


Replace the detector chamber and replace the
fan. detector head and reset the
Control Unit.

No Has the fault


been cleared

Yes

Replace the
detector End

May 2012 Page 76 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 6

No Is 24v present
at the supply
input terminals
(TB1)

Is the 24v
No Yes
input power
supply cable
connected
correctly

Yes

Correctly connect the


24v supply to the Replace the
Control Unit Control Unit

May 2012 Page 77 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 7

Switch the Control Unit power


off and on.
Observe the LED test
performed at power up

No Do all of the
LED‟s operate
correctly?

Yes

Replace the Control Unit Replace the Control


lid and membrane Unit PCB

May 2012 Page 78 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 8

Replace the
Control Unit
PCB

May 2012 Page 79 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 9

Replace the Detector fan

Reset the fault on the


Control Unit

Yes After 30 seconds


does the fan fault
remain cleared.

No

Replace the
End Detector

May 2012 Page 80 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 10

Remove the detector head


and clean the sample
chamber

Replace the detector head


and perform an optics test No
(Repeat once)

Yes
Optics test
passed?

No

Replace the
End Detector

May 2012 Page 81 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 11

Clear the fault on the


Control Unit

No Does the
watchdog fault
reoccur?

Yes

Replace the
End Detector

May 2012 Page 82 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Action 12

Check the Modbus connections from


the Remote Display Unit to each of the
Control Units.

No Are all
connections
made correctly

Correct the connections Yes

Are all of the


No Control Units
addressed
correctly?

Correctly set the


Control Unit Modbus Yes
addresses

Are the end of


No line jumpers set
correctly in each
Control Unit

Correct the jumper


links Yes

Replace the Remote


Display Unit

May 2012 Page 83 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

5 SPARE PARTS

Figure 116 Control Unit Spares

May 2012 Page 84 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Control Unit Spares


Item Description Part No.
Control Unit with Membrane 53836-K270
Control Unit without Membrane 53836-K276
1. Printed Circuit Board c/w Ribbon Cables 43782-K172-00
1. Printed Circuit Board w/out Ribbon Cables 43782-K172-01
2. 25mm Blanking Plug 22540-K029
3. Metal Gland 22540-K028
4. Detector Connection Cap 27400-K303

Detector Harness Kit 53569-K003


5. 6 Way Detector Connection – Qty 1
Wrench Tool – Qty 1

Control Unit Connector Kit 53569-K004


6. Relay & Power Plugs – Qty 3
7. Modbus Plug – Qty 1
8. EOL Jumpers – Qty 2

May 2012 Page 85 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Remote Display Unit Spares


Item Description Part No.
Remote Display Unit 53836-K271
1. 24VDC Power Socket (no Cable) 27400-K304
2. Modbus Connector (no Cable) 27400-K305
3. Modbus Connector c/w 5m Cable 43682-K297
4. 24VDC Power Socket c/w 5m Cable 43682-K296

May 2012 Page 86 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Figure 117 Detector Spares

Detector Spares
Item Description Part No.
Detector Complete 53836-K269
Detector Complete (Short Sample Pipe) 53836-K269-01
1 Detector Head Assembly 53836-K272
2 Fan Assembly D5622-005-02
3 Base Unit sub-Assembly D5622-101
4 Connector Push In B5465-307
5 Base moulding O Ring C1513-802

May 2012 Page 87 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Commissioning Kit D9221-026 consists of:


Description Part No. Qty Category
Wipes, Wet & Dry A7311-001 2 Consumables
Smoke Test Oil -30 ml D9221-028 1 Bottle Consumables
Wick - 150 mm 17100-H06 3 Consumables

Smoke Tester D9221-029 1 Tools

Materials Safety Data Sheet - 2 Information

Service Kit D9221-027


Description Part No Qty Category
Fan Retainer B3741-902 5 Spares
Compression Spring B3721-006 5 Spares
Base Moulding Seal C1513-802 5 Spares
Fan Connector Seal C1413-801 5 Spares
M3 Screw 21833-H01 5 Spares

Glass Cleaner 500ml A7311-002 1 Consumables


Foam Buds Pkts B6910-217 2 Consumables

4mm Hexagon Key B691 0-219 2 Tools


Pulling Tool D9131-002 1 Tools

Materials Safety Data Sheet - 2 Information

Recommended Operational Spares


Description Part No. Qty
Commissioning Kit D9221-026 1
Service Kit D9221-027 1
For systems with more than 10 detectors, it is recommended that additional detector head
assemblies (53836-K272) are supplied.

May 2012 Page 88 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

5.1 COMPLETE SPARE PARTS LIST

Part No. Description

53836-K270 Control Unit with Membrane for 10 detectors


53836-K276 Control Unit without Membrane for 10 detectors
53836-K271 Touch Screen Display Unit
53836-K269 Detector Complete
53836-K269-01 Detector Complete (Short Sample pipe)

Cable Assemblies

90º Connector
43682-K285-1.0 1.0m Cable with 90° Connector 1.0 Metres
43682-K285-1.5 1.5m Cable with 90° Connector 1.5 Metres
43682-K285-2.0 2.0m Cable with 90° Connector 2.0 Metres
43682-K285-2.5 2.5m Cable with 90° Connector 2.5 Metres
43682-K285-3.0 3.0m Cable with 90° Connector 3.0 Metres
43682-K285-3.5 3.5m Cable with 90° Connector 3.5 Metres
43682-K285-4.0 4.0m Cable with 90° Connector 4.0 Metres
43682-K285-4.5 4.5m Cable with 90° Connector 4.5 Metres
43682-K285-5.0 5.0m Cable with 90° Connector 5.0 Metres
43682-K285-5.5 5.5m Cable with 90° Connector 5.5 Metres
43682-K285-6.0 6.0m Cable with 90° Connector 6.0 Metres
43682-K285-6.5 6.5m Cable with 90° Connector 6.5 Metres
43682-K285-7.0 7.0m Cable with 90° Connector 7.0 Metres
43682-K285-7.5 7.5m Cable with 90° Connector 7.5 Metres
43682-K285-8.0 8.0m Cable with 90° Connector 8.0 Metres
43682-K285-8.5 8.5m Cable with 90° Connector 8.5 Metres
43682-K285-9.0 9.0m Cable with 90° Connector 9.0 Metres
43682-K285-9.5 9.5m Cable with 90° Connector 9.5 Metres
43682-K285-10.0 10.0m Cable with 90° Connector 10.0 Metres
43682-K285-10.5 10.5m Cable with 90° Connector 10.5 Metres
43682-K285-11.0 11.0m Cable with 90° Connector 11.0 Metres
43682-K285-11.5 11.5m Cable with 90° Connector 11.5 Metres
43682-K285-12.0 12.0m Cable with 90° Connector 12.0 Metres
43682-K285-12.5 12.5m Cable with 90° Connector 12.5 Metres
43682-K285-15.0 15.0m Cable with 90° Connector 15.0 Metres
43682-K285-17.5 17.5m Cable with 90° Connector 17.5 Metres
43682-K285-20.0 20.0m Cable with 90° Connector 20.0 Metres
43682-K285-22.5 22.5m Cable with 90° Connector 22.5 Metres
43682-K285-25.0 25.0m Cable with 90° Connector 25.0 Metres
43682-K285-27.5 27.5m Cable with 90° Connector 27.5 Metres
43682-K285-30.0 30.0m Cable with 90° Connector 30.0 Metres
43682-K285-32.5 32.5m Cable with 90° Connector 32.5 Metres
43682-K285-35.0 35.0m Cable with 90° Connector 35.0 Metres

May 2012 Page 89 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Part No. Description


Straight Connector
43682-K286-1.0 1.0m Cable with Straight Connector 1.0 Metres
43682-K286-1.5 1.5m Cable with Straight Connector 1.5 Metres
43682-K286-2.0 2.0m Cable with Straight Connector 2.0 Metres
43682-K286-2.5 2.5m Cable with Straight Connector 2.5 Metres
43682-K286-3.0 3.0m Cable with Straight Connector 3.0 Metres
43682-K286-3.5 3.5m Cable with Straight Connector 3.5 Metres
43682-K286-4.0 4.0m Cable with Straight Connector 4.0 Metres
43682-K286-4.5 4.5m Cable with Straight Connector 4.5 Metres
43682-K286-5.0 5.0m Cable with Straight Connector 5.0 Metres
43682-K286-5.5 5.5m Cable with Straight Connector 5.5 Metres
43682-K286-6.0 6.0m Cable with Straight Connector 6.0 Metres
43682-K286-6.5 6.5m Cable with Straight Connector 6.5 Metres
43682-K286-7.0 7.0m Cable with Straight Connector 7.0 Metres
43682-K286-7.5 7.5m Cable with Straight Connector 7.5 Metres
43682-K286-8.0 8.0m Cable with Straight Connector 8.0 Metres
43682-K286-8.5 8.5m Cable with Straight Connector 8.5 Metres
43682-K286-9.0 9.0m Cable with Straight Connector 9.0 Metres
43682-K286-9.5 9.5m Cable with Straight Connector 9.5 Metres
43682-K286-10.0 10.0m Cable with Straight Connector 10.0 Metres
43682-K286-10.5 10.5m Cable with Straight Connector 10.5 Metres
43682-K286-11.0 11.0m Cable with Straight Connector 11.0 Metres
43682-K286-11.5 11.5m Cable with Straight Connector 11.5 Metres
43682-K286-12.0 12.0m Cable with Straight Connector 12.0 Metres
43682-K286-12.5 12.5m Cable with Straight Connector 12.5 Metres
43682-K286-15.0 15.0m Cable with Straight Connector 15.0 Metres
43682-K286-17.5 17.5m Cable with Straight Connector 17.5 Metres
43682-K286-20.0 20.0m Cable with Straight Connector 20.0 Metres
43682-K286-22.5 22.5m Cable with Straight Connector 22.5 Metres
43682-K286-25.0 25.0m Cable with Straight Connector 25.0 Metres
43682-K286-27.5 27.5m Cable with Straight Connector 27.5 Metres
43682-K286-30.0 30.0m Cable with Straight Connector 30.0 Metres
43682-K286-32.5 32.5m Cable with Straight Connector 32.5 Metres
43682-K286-35.0 35.0m Cable with Straight Connector 35.0 Metres

May 2012 Page 90 of 91 59812-K007 Rev 4


Ocean Automation Solutions [email protected] http://www.ocean-automation.com

Part No. Description


Spare Parts

17100-H06 Cotton Wick (1 hank = 10 meters)


21833-H01 M3 screw
22540-K028 Metal Gland
22540-K029 25mm Blanking Plug
27400-K303 Detector Connection Cap
27400-K304 24VDC Power Socket (no Cable)
27400-K305 Modbus Connector (no Cable)
35100-K274 Mk5 - Mk7 Retrofit Plate
43682-K296 24VDC Power Socket c/w 5m Cable
43682-K297 Modbus Connector c/w 5m Cable
43782-K172-00 Printed Circuit Board c/w Ribbon Cables
43782-K172-01 Printed Circuit Board w/out Ribbon Cables
53569-K003 Detector Harness Kit
Incl 1 x 6Way Detector Connection
Incl 1 x Wrench Tool
53569-K004 Control Unit Connector Kit
Incl 3 x Relay & Power Plugs
Incl 1 x Modbus Plug
Incl 2 x EOL Jumpers
53836-K272 Mk7 Detector Head Assembly
Incl 1 x D5622-005-02
Incl 1 x C1513-802
A7311-001 Wet Wipes
A7311-002 Glass Cleaner 500ml
B3721-006 Compression spring
B3741-902 Fan Retainer
B5465-307 Connector Push in
B6910-217 Foam Buds Pkts
B6910-219 4mm Hex Key
C1413-801 Fan Connector seal
C1513-802 Base moulding O ring
D5622-005-02 Fan, Micronel type F41LP-005KK-9
D5622-101 Base unit sub assy
Incl 1 x B5465-307
D9131-002 Pulling tool
D9221-026 Commissioning Kit
D9221-027 Service Kit
D9221-028 Smoke Oil
D9221-029 Smoke tester

May 2012 Page 91 of 91 59812-K007 Rev 4