High Frequency Generator and Transformer For HVDC-connected Wind Turbine Farms
High Frequency Generator and Transformer For HVDC-connected Wind Turbine Farms
High Frequency Generator and Transformer For HVDC-connected Wind Turbine Farms
I. I NTRODUCTION
energy sources are attracting a continuously
rising amount of interest, due to increasing
environmental concerns. Wind power systems are currently
considered to be one of the most applicable Rectifier
natural energy
sources. State of the art wind turbines use different generator
topologies to take into account the variations in shaft speeds.
This is done either by the use of full scale converters or
by utilizing classic doubly fed induction generators along
with smaller converters. When applying doubly fed induction
generators a speed change of approximately 30 % can be
achieved [2]. This allows an increased utilization compared
to stall regulated wind turbines. The use of converters offers
an advantage because it allows full control of the output
power. Unfortunately full scale active converters has a major
drawback due to their high cost, thus a configuration without
them would be a great improvement.
Wind turbines are often placed in farms far away from
the customers, including off shore. This introduces new
challenges in transportation of energy from wind farms
into mainland. HVDC-lines from wind turbine farms to
mainland are currently being tested and it seems to be a good
solution for several reasons; for instance lower transmission
losses and easy control of the wind turbine park since the
individual wind turbine is decoupled from the common grid.
A new way of designing wind turbines is by use of direct
drive generators. This eliminates the use of gearboxes and
Rasmus . Nielsen
Christian F. Jensen
ATURAL
Rectifier
irec
Generator
In this article
another approachRectifier
for choosing a generator for
+
vgen Z is considered. The idea proposed
a direct drive wind turbine
is to use a high frequency synchronous generator. The output
from this generator will be controlled by controlling the field
current for the generator. This means that only the field
winding needs to be fed by a converter. Thus the converter
only needs to handle a fraction of the total power delivered
by the wind turbine. A power transformer is used in order to
Synchronous
Generatorlevel. Because of the high
transform the voltage
to a higher
frequency output from the generator, the transformer size can
be reduced and thereby
its cost.
All wind turbines
Statorreducing
winding
Rectifier
Output
in a farm needs to be coupled together. This is done by using
HVDC, and a simple diode rectifier is proposed. Because of
Field coilall generators are decoupled from their common
the rectifier
Field winding
Converter
grid. With a DC voltage as output, the wind turbine can change
shaft speed independent of the speed of the other wind turbines
in the farm. A block diagram of the system is shown onRegulator
Figure
1.
Wind turbine
Synchronous
Generator
Transformer
Wind turbine
Synchronous
Generator
Transformer
Wind turbine
Synchronous
Generator
Transformer
DC AC
Converter
Windturbine
Synchronous
Generator
P-80
P-84
Transformer
HVDC
P-79
Windturbine
Synchronous
Generator
Windturbine
Synchronous
Generator
P-89
Buck
Converter
P-82
P-87
Transformer
P-88
Transformer
P-78
Main
Converter
HVAC
Buc
Conve
Synchronous
Generator
ynchronous
Generator
ynchronous
Generator
P-83
ynchronous
Generator
P-81
ynchronous
Generator
P-79
ynchronous
Generator
P-89
ynchronous
Generator
Windmill
Windmill
Windmill
Windmill
Transformer
Transformer
Buck
Converter
PWM
kW
P-42
Windmill
Synchronous
Generator
Windmill
Synchronous
Generator
Windmill
Synchronous
Generator
Synchronous
Generator
Regulator
Vref
ynchronous
Generator
1120
Field winding
P-41
Load
DC Voltage
VDC
PI
Compensator
Field
supply
P-31
DC AC
Synchronous
Generator
Converter
Figure 2. Parts
in a single wind turbine system.
Transformer
The system
Buck
Converter
P-86
B. P-85
System description
Transformer
Voltage
The generator DCrotor
comprise of two pieces, molded as
in Figure 3. Around the middle of one of the pieces
the field winding is placed. Thereafter the two halves are
joint together forming the rotor. When applying a current to
the rotor winding,
magnetic north and south poles will be
Synchronous
Generator
present
DC
Voltage at the top and bottom claws depending on the current
direction. The stator is constructed ofDClaminated
steel. The
Voltage
PI windings are sinusoidal distributed with 12 poles per phase.
Field
shown
supply
Regulator
Buck
Converter
PWM
v rqd
Generator
qd model
i rqd
P-78
P-88
Transformer
P-42
Synchronous
Generator
P-41
Table I
R ATED DATA FOR THE GENERATOR
Parameter
Value
Power P-32 1.12
Transformer
Voltage
11.4
Current
56.7
Speed
6000
Frequency
600
P-43
PI
Regulator
Ksr
vabc
Load
Unit
P-40
kW
V Rectifier
A
RPM
Hz
P-33
HVDC
preparations
In Figure 4 the superscript
P-36
P-35
Synchronous
In order to convert the
three phase AC voltage
delivered by HVDC
The model calculates the qd currents from the field coil
Transformer
Rectifier
Generator
preparations
the generator into DC, a six pulse rectifier will be modeled voltage and input mechanical speed. The iqdHVAC
currents are
Main
and verified by means of tests in the laboratory. The rectifier transformed to the abcHVDC
system and the
load determines the abc
must be able to handle a three phase voltage with a line-line currents. These currents are used Converter
to calculate the abc voltage.
P-31
Synchronous
Generator
P-29
Synchronous
Generator
P-37
Transformer
P-34
Rectifier
P-39
HVDC
preparations
P-28
Transformer
P-30
Rectifier
P-38
HVDC
preparations
P-29
Synchronous
Generator
= vabc iabc
3
=
(vq iq + vd id )
[W]
(12)
2
The model machine parameters are determined according to
IEEE 115 [4] and IEC 34-4 [3], where all values are referred
to the stator side.
(1)
where
f qd0s = [ fq
fd
f0 ]T
(2)
f abcs = [ fa
fb
fc ]T
(3)
Table II
M ODEL PARAMETERS EXPRESSED AS INDUCTANCES AND RESISTANCES .
and
cos( + 2
3 )
sin( + 2
3 )
cos( 2
3 )
sin( 2
3 )
cos()
2
sin()
Ks =
3
1
1
2
(4)
1
2
(5)
fqs
fas
vfrd
drqs
dt
drds
r
r
= rs ids + r ds +
dt
0
r
d
0 0
fd
= rr ifrd +
dt
= rs irqs r rds +
[V]
(6)
[V]
(7)
[V]
(8)
rds
frd
Llf d ifrd
Lmd (irds
Table III
R ESULTS FROM THE FIELD SHORT CIRCUIT TEST CONDUCTED AT 3000
RPM WITH AT RESISTIVE LOAD OF 0.175 AT RATED VOLTAGE .
(9)
0
fds
r
vds
0.003
r
vqs
Rf d
fcs
Unit
H
H
H
H
A. Model implementation
()d + (0)
fbs
Value
0.0709
25.06
248.5
135
441
is defined as:
=
Parameter
Rs
Lls
Lmd
Lmq
0
Lf d
ifrd )
(10)
(11)
Vpeak
Remenance
Output power
Simulated
17 V
155 ms
1 Vp
824 W
Measured
16.5 V
155 ms
1 Vp
812 W
Error
2.9 %
0%
0%
1.5 %
20
10
5
0
5
40
10
30
15
15
20
0.1
0.1
0.2
0.3
0.4
0.5
0.6
Time [s]
Figure 6. Simulation of field short circuit test at 3000 RPM with at resistive
load of 0.175 at rated voltage.
20
10
0
10
20
30
40
20
15
Measured
Simulated
10
15
20
Time [ms]
10
0
5
10
15
20
0.1
0.1
0.2
0.3
0.4
0.5
0.6
40
Time [s]
30
Figure 7. Measurement of field short circuit test at 3000 RPM with at resistive
load of 0.175 at rated voltage.
In the test the shaft speed changes from 3000 rpm to 3244
rpm.
The largest deviations from all the tests conducted are
shown in Table IV.
20
10
0
10
20
30
40
Table IV
0
Vpeak
Remanence (peak)
Output power
Load
315 W
736 W
315 W
315 W
Simulated
17.1 V
135 ms
2.4 V
351 W
Measured
15.9 V
146 ms
2.1 V
315 W
0.1
0.2
0.3
0.4
0.5
Time [s]
Error
7%
8.1 %
12.5 %
10.3 %
Figure 9. Simulated short circuit test at 3000 RPM and rated voltage.
2) Three phase short circuit test: For the three phase short
circuit test, the generator is driven at 3000 RPM and loaded
with a resistive load of 5 before the short circuit is applied.
At an arbitrary chosen moment a three phase short circuit
is applied to the stator terminals. As the frequency is high
4
As can be seen from the figure there are two stages, either
the current in the inductor is zero or larger than zero. If the
current through the inductor is larger than zero a pair of
diodes will always be conducting. If the current through the
inductor is zero no diodes will be conducting. When it has
been evaluated whether the current through the inductor is
larger than zero and this is true, the input voltage to the load
(Vrec ) will be the largest line-line voltage with two forward
voltage drops subtracted. If the current through the inductor
is zero, it is necessary to check whether the largest line-line
voltage is larger than the output voltage plus two forward
voltage drops before the diodes can start to conduct.
40
30
20
10
0
10
20
30
40
0
0.1
0.2
0.3
0.4
0.5
Time [s]
Figure 10. Measured short circuit test at 3000 RPM and rated voltage.
III. R ECTIFIER
In this section the modeling of the rectifier and the verification of this will be discussed. The model should be able
to predict which currents that are drawn from each phase at
a given three phase input voltage. The load will be modeled
using an inductor, capacitor and resistor. The rectifier and load
model is shown in Figure 11:
iL
va
D1
D2
vL
vrec
vc
iC
C
iR
R
D4
D5
iL
vL
vo
vb
iR
D3
iC
Vo
-
vf
vf
iL > 0
no
(13)
[A]
(14)
[A]
(15)
[V]
(16)
[V]
(17)
= v0 + Rd id
[V]
= 0.28 + 0.0027 id [V]
(18)
(19)
iL
yes
[A]
D6
Find Largest
vLL
= iL iR
vo
=
RZ
1
vL ( ) d
=
L
= vrec vo
Z
1
=
iC ( ) d
C
the
the
the
the
17
no
vrec = Vo
Calculate iL
5
Find Largest V
Vb
Vc
Calculate VLL
Find largest
(Va >Vb & Va>Vc)=1
(Vb >Vc & Vb>Va)=2
(Vc >Vb & Vc>Va)=3
Find smallest
(Va <Vb & Va<Vc)=1
(Vb <Vc & Vb<Va)=2
(Vc <Vb & Vc<Va)=3
15
Simulated
Measured
2
10
10
10
5
0
10
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
10
Figure 16. Phase a current, measured and simulated with the rectifier model.
20
30
Simulink simulation
LTspice simulation
25
15
14
16
10
5
0
5
12
10
8
6
10
15
2
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
Simulated
Measured
18
20
20
0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05
Time [s]
0.1
0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05
Time [s]
Time [s]
Figure 17. Rectifier output voltage, measured and simulated with unbalanced
supply .
Figure 14. Phase a current, simulated in LTspice and simulated with the
rectifier model.
20
Simulink simulation
LTspice simulation
18
16
Synchronous
Generator
IV. M ERGING
OF THE GENERATOR AND RECTIFIER
Windmill
Transformer
14
MODELS
12
10
8
6
4
2
0
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.1
Time [s]
P-69
Rectifier
Figure 15. Output voltage, simulated in LTspice and simulated with the
rectifier model.
igen
Generator
vgen
-
irec
Rectifier
Z
Figure 18. Block diagram for the merging strategy for the generator and
rectifier model.
6
Synchronous Generator
Stator winding
Field coil
Rectifier
Output
(20)
vabc iabc
0
-20
20
10
-10
-20
20
ifabc iabc
Filter
1
=
+1
1
j
236k
+1
v
= 0.124A
Xc
15
10
0.5
1.5
2.5
3.5
4.5
Time [ms]
Figure 20. Verification at 3000 RPM with a load resistor of 0.5 .
(21)
20
Rectifier
Generator
H(j) =
40
-40
vabc iabc
Simulated
Measured
60
(22)
Parameter
Phase a current (rms)
Line-line voltage (rms)
Output voltage (avg)
Error
6.89 %
5.2 %
4.1 %
V. S YSTEM VERIFICATION
2) Verification with LCR load: The test was conducted at
3000 RPM with a inductor of 0.6 mH, capacitor of 5.1 mF
and a load resistor of 0.5 . The results are shown in Figure
21. From Figure 21 it is seen that both the simulated and
measured phase a currents and output voltages share the same
tendencies. The simulated line-line voltage becomes unstable
when the diodes are switching.
Measured
Simulated
18
Simulated
Measured
40
16
20
14
60
0
-20
-40
40
12
10
8
6
30
2
20
10
-20
-30
20
0.2
0.4
0.6
0.8
1.2
-10
15
10
VI. C ONCLUSION
As stated in the introduction, the main goal of the article was to develop a complete model capable of predicting
both voltages and currents in the system under normal and
short circuit fault conditions. The models developed for the
synchronous generator and rectifier are capable of modeling
their individual output voltages and currents with an acceptable
degree of accuracy. Unfortunately the model for the complete
unregulated system is only capable of modeling output voltages and currents at resistive loads. With a LCR load the model
fails to modeling the line-line voltage. It is concluded that this
is due to numerical problems in the simulator.
The PI compensator can control the output voltage with an
LCR load as expected. This works, in spite of the problems
with the model merging. The reason why the PI compensator
works, is because, only a part of the synchronous generator
model and not the rectifier model is used in the designing of
the regulated system.
Conclusively, it seems to be necessary to improve the strategy for combining the models for the synchronous generator
and rectifier in order to achieve a complete model which
is capable of modeling the output voltages and current at
different loads.
Time [s]
0.5
1.5
2.5
3.5
4.5
Time [ms]
Figure 21. Verification at 3000 RPM with a inductor of 0.6 mH, capacitor of
5.1 mF and a load resistor of 0.5 .
R EFERENCES
[1] Anders Berner. Abb melder sig ud af vindmlle-racet. Internet, Written:
15/03 2002. Shown: 05/10 2008, http://ing.dk/artikel/45650.
[2] Anca D. Hansen and Lars H. Hansen. Market penetration of wind
turbine concepts over the years.
Internet, Shown: 17/05 2008.
http://www.risoe.dk/rispubl/art/2007 136 paper.pdf.
[3] IEC34-4. Rotating electrical machines IEC 34-4. IEC, 1985. ISBN -.
[4] IEEE. IEEE guide: Test Procedures for Synchronous Machines. IEEE,
1995. ISBN - 1-55937-710-0.
[5] Infolytica. Claw-pole alternator. Internet, Written: 2008. Shown: 05/12
2008, http://www.infolytica.com/en/coolstuff/ex0070/.
Table VI
K EY
Parameter
Rise time
Settling time (max)
Overshoot
Steady state error
Demand
500 ms
1000 ms
0%
0%
Measured
480 ms
900 ms
0%
0%
Simulated
420 ms
640 ms
0%
0%
[6] IXYS. Power schottky rectifier. Internet, Written: 2002. Shown: 10/12
2008, http://ixdev.ixys.com/DataSheet/L227.pdf.
[7] Paule C. Krause, Oleg Wasynczuk, and Scott D. Sundhoff. Analysis of
electric machinery and drive systems. Wiley Interscience, 2002. ISBN
0-471-14326-X.
[8] Sanne Wittrup.
Afventende modtagelse af abbs nye
vindmllegenerator. Internet, Written: 16/06 2000. Shown: 05/10
2008, http://ing.dk/artikel/29471.