Chapter7 PER UNIT Analysis
Chapter7 PER UNIT Analysis
=
= =
S
S
V
V
Z old
B
New
B
New
B
old
B
old
pu
2
(
(
=
(5.32)
(5.33)
Example
PER UNIT ANALYSIS OF NORMAL
SYSTEM
If we have a normal system, we can
greatly simplify the solution of the
usual power system problem by using
an impedance diagram.
The rationale was described in Section
5.5 and the procedure is summarized
as follows.
Procedure for a per unit analysis
1. Pick a volt-ampere base for the whole
system.
2. Pick one base voltage arbitrarily. Relate all
the others by the ratio of the magnitudes of
the open-circuit line voltages of each
transformer bank.
3. Find the impedance bases in the different
sections and express all impedances in
consistent per unit terms.
desired.
4. Draw the impedance diagram for the
entire system, and solve for desired per
unit quantities.
5. Convert back to actual quantities if
desired.
In step 1 it is convenient to pick the
three-phase volt-ampere rating of one of
the generators or transformer banks.
In step 2 it is convenient to pick as a
base voltage the rated voltage of the unit
picked in step 1.
In this case in step 3, the manufacturer's
specification of impedance in per unit be
used directly.
If not, in step 3 use (5.33). In step 4
we note that the impedance diagram
will not have phase shifters or ideal
transformers.
Finally, we note that for a normal
system the procedure described in
step 2 is feasible; we get a consistent
set of base voltages.
The procedure is illustrated in the next
two examples.
Example 5.1
Consider a system with one-line diagram shown in
Figure E5.14(a).
The three phase transformer nameplate rating are
listed. The transformer reactance are given in
percent; 10% = 0.1p.u.
The transmission line and load impedances are in
actual ohms.
The generator terminal voltage (magnitude) is
13.2kV (line-line).
Find the generator current, the transmission-line
current, the load current, the load voltage, and the
power delivered to the load.
Solution
The system is normal, and we can ignore
transformation-induced phase shifts.
We wish to derive an impedance diagram.
In Figure E5.14(a), three sections (1, 2, and
3) are identified.
We will need to pick appropriate bases for
these three sections.
To do the circuit analysis it is convenient to
pick E
s
=0.96L0
o
p.u. but since this choice is
arbitrary, there is no significance to the
absolute phases of the quantities resulting
from the analysis.
Step 4: We are now able to draw the
impedance diagram [Figure E5.14(b)].
The points labeled KLMN correspond to the
points similarly labeled on the one line
diagram.
Note that the same I
pu
represents different
actual currents in sections 1,2, and 3
because the base values are different.
Calculating the load voltage,
The element values shown are expressed in
per unit.
We next find Ipu by circuit analysis.
Example 2
Consider the same basic system as in
Example 5.1 but with these changes. The
generator voltage and load impedance are
not specified. Instead we are given the
following information. The voltage
(magnitude) at the load is 63 kV and the
three-phase load power is 5.0MW at a PF of
0.9 lagging. Find the load current, the
generator voltage and the generator power.
Solution
Using the same choice of bases as in Example
5.1 we have
Thus we can solve for Ip.u We get I
pu
= 0.608.
Since PF = 0.9 lagging implies that the
current lags the voltage by 25.84,we have in
fact, I
pu
= 0.608 Altering the
impedance diagram in Example 5.1to fit the
present case we have the circuit shown in
Figure E5.15. It is now easy to find E
spu
o
84 . 25 Z
We now can calculate actual quantities by
multiplying the per unit values by the
appropriate bases. We get
Example 3
Prepare a per phase schematic of the system
shown in Figure E5.16 and show all
impedances in p.u. on a l00-MVA, 132-kV base
in the transmission-line circuit. The necessary
data for this problem are as follows:
Determine the p.u. impedance of the load for
the following cases:
a. Load modeled as a series combination of
resistance and inductance
b. Load modeled as a parallel combination
of resistance and inductance
Solution
This example illustrates the various steps in
deriving the p.u. representation of the system.
Note that the data presented are in p.u on a
base specified for each component.
This would be typically provided by the
manufacturer. In the following analysis, we will
convert all these quantities to a common
system base that has been specified in the
transmission circuit.
Note: Once the base voltage is specified in
the transmission-line circuit, the base
voltage in all other circuits is determined by
the ratio of the magnitudes of the open
circuit line voltages of the appropriate
transformer bank connecting the circuits.
This is step 2 in the procedure described
earlier.
We now proceed to convert all the
parameter values to p.u. on the common
base specified.
The p.u. impedance of the transmission
lines connecting the load bus to the
high voltage buses is given by
The base impedance in the load circuit is
the same as the base impedance in the
transmission-line circuit.