Fire Fighting - REF T
Fire Fighting - REF T
FIRE EXTINGUISHERS -
- A fire extinguisher should never be used to prop open a
door. It should always be fixed to the wall, and it should be
checked monthly by a service technician.
- Most modern fire extinguishers are developed to deal with
many different fire scenarios. Fire extinguishers can be filled
with powder, water additive, foam, or carbon dioxide
- When choosing a fire extinguisher, be sure to pick one that
will fight the fires that are most likely to develop in your
business or home.
Extinguisher Common
Features
- Locking pin
- Carrying handle/operating lever
- Pressure guage
- Label :
Type(Water,CO2,Dry Chemical)
Classification (A,B,C..)
NFPA Capacity Rating
Instructions
5. Basement :
● The access to the basement shall be either from the main or alternate
staircase providing access and exit from higher floors. Where the staircase is
continue the same shall be enclosed type serving as a fire separation from the
basement floor and higher floors.
● In case of basement for office, sufficient number of exit ways and access
ways shall be provided with a travel distance of maximum 15 m. The travel
distance in case of dead end shall be 7.5 m
● The basement shall be partitioned and in no case compartment shall be
more than 500. Sq.m. area except parking.
● The first basement can be used for services/ parking or other permissible
services. Lower basement, if provided, shall exclusively be used for car
parking only.
● Each basement shall be separately ventilated. Vents with cross sectional
area not less than 2.5 percent of the floor area spread evenly around the
perimeter of the basement shall be provided in the form of grills or
breakable starboard lights or by the way of shaft.
● The staircase of basement shall be of enclosed type having fire resistance of
minimum 2 hours and shall be situated at the periphery of the basement to
be entered at ground level.
● In multi-storeyed basements, intake duct may serve all basements levels,
but each basement and basement compartment shall have separate smoke
outlet ducts.
● Mechanical extractors for smoke venting system from lower basements
levels shall also be provided.
● Mechanical extractors shall have and internal locking arrangement so that
extractors shall continue to operate and supply fan shall stop automatically
with the actuation of fire detectors.
● Mechanical extractors shall be designed to permit 30 air changes per hour in
case of fire or distress call.
● Mechanical extractors shall have an alternate source of power supply
● Ventilating ducts shall be integrated with the structure and made out of
brick masonry or RCC as far as possible.
● Kitchens working on gas fuel shall not be permitted in basement.
● If cutouts are provided from basement to the upper floors or to the
atmosphere, all side cutout openings in the basement shall be protected
by sprinkler heads at closed spacing so as to form a water curtain in the
event of a fire.
● Dewatering pump shall be provided in all basements.
6. Service Ducts / Refuge Chute
● Service duct shall be enclosed by walls and door, if any, of 2 hours fire rating.
● If ducts are larger than 10 sq.m. the floor should seal them, but provide suitable
opening for the pipes to pass through, with the gaps sealed.
● A vent opening at the top of the service shaft shall be provided between one-
fourth and one-half of the area of the shaft.
● Refuge chute shall have an outlet at least of wall of non-combustible material
with fire resistance of not less than two hours. They shall not be located within
the staircase enclosure or service shafts or air-conditioning shafts.
● Refuge chutes shall not be provided in staircase walls and A/C shafts etc.
7. Air Conditioning
● Air-conditioning system should be installed and maintained so as to minimise
the danger of spread fire, smoke or fumes thereby from one floor of fire area to
another or from outside to any occupied building.
● Air-conditioning systems circulating air to more than one floor area should be
provided with dampers designed to close automatically in case of fire and
thereby prevent spread of fire or smoke.
● Air-conditioning system serving large place of assembly, large departmental
stores, or hostels with over 100 rooms in a single block should be provided with
effective means for preventing circulation of smoke through the system in case
of fire in air filters or from other sources drawn into the system even though
there is insufficient heat to actuate heat smoke sensitive devices controlling fans
or dampers.
7.1 Air Conditioning should confirm to the following
● Escape routes like staircase, common corridors, lift lobbies, etc. should not be
used as return air passage.
● The ducting should be constructed of metal.
● Wherever the ducts pass through fire walls or floor, the opening around the
ducts should be sealed with fire resisting material of same rating as of walls,
floors.
● Metallic ducts should be used even for the return air instead of space above
the false ceiling.
● The material used for insulating the duct system should be of flame resistant
and non conductor of heat.
● Area more than 750 sq.m. on individual floor should be segregated by a
firewall and automatic fire dampers for isolation should be provided.