Chapter 5, Economic Dispatch
Chapter 5, Economic Dispatch
04/22/2025 1
INTRODUCTION
04/22/2025 2
INPUT-OUTPUT CHARACTERISTIC
OF GENERATOR UNITS
04/22/2025 5
The minimal power output is determined by technical conditions or
other factors of the boiler or turbine. Generally, the minimum load
at which a unit can operate is influenced more by the steam
generator and the regenerative cycle than by the turbine. The only
critical parameters for the turbine are shell and rotor metal
differential temperatures, exhaust hood temperature, and rotor and
shell expansion. Minimum load limitations of the boiler are gener-
ally caused by fuel combustion stability, and the values, which will
differ with different types of boiler and fuel, are about 25 – 70% of
design capacity. Minimum load limitations of the turbine - generator
unit are caused by inherent steam generator design constraints,
which are generally about 10 – 15%. The maximal power output of
the generating unit is determined by the design capacity or rate
capacity of the boiler, turbine, or generator.
04/22/2025 6
Generally, the input - output characteristic of the
generating unit is non-linear. The widely used input -
output characteristic of the generating unit is a
quadratic function,
04/22/2025 7
Calculation of Input - Output
Characteristic Parameters
The parameters of the input - output characteristic of the
generating unit may be determined by the following approaches :
(1) Based on the experiments of the generating unit efficiency
(2) Based on the historic records of the generating unit operation
(3) Based on the design data of the generating unit provided by
manufacturer
04/22/2025 8
THERMAL SYSTEM ECONOMIC DISPATCH
NEGLECTING NETWORK LOSSES
Principle of Equal Incremental Rate
Given a system that consists of two generators connected to a
single bus serving a received electrical load PD . The input - output
characteristics of two generating units are F1 ( PG1 ) and F2 ( PG2 ),
respectively. The total fuel consumption of the system F is the sum
of the fuel consumptions of the two generating units. Assuming
there is no power output limitation for both generators, the
essential constraint on the operation of this system is that the sum
of the output powers must equal the load demand. The economic
power dispatch problem of the system, which is to minimize F
under the above - mentioned constraint, can be expressed as:
04/22/2025 9
04/22/2025 10
04/22/2025 11
04/22/2025 12
04/22/2025 13
04/22/2025 14
04/22/2025 15
04/22/2025 16
04/22/2025 17
04/22/2025 18
04/22/2025 19
04/22/2025 20
04/22/2025 21
04/22/2025 22
04/22/2025 23
04/22/2025 24
04/22/2025 25
04/22/2025 26