I & C Engineering & Basic Control System
I & C Engineering & Basic Control System
PRESENTED BY-
Mr. ASISH SAHA
DATE: 27-01-2014
The demand for use state of the art technological software is also
increasing. Hence emphasis on measurement, testing and control using
software to improve commercial, industrial, and service productivity
through automation is envisaged.
C. Data communication
Serial communication by RS-232C/422/485
Field Bus.
Ethernet TCP/IP
Wireless communication
Input Actuator/
Output
Controller
FCE
Process
r e
+ - Actuator/
Controller
Set Point FCE Process
Output
c
Sensor
Close loop System
Disadvantages:
Control action is taken after disturbances
have been felt.
FB control is incapable of correcting a
deviation from set point at the time of its
detection.
Theoretically not capable of achieving
“perfect control.”
For frequent and severe disturbances,
process may not settle out.
Block Diagram
D
Controller Process
Ysp U Y
FF Control
Attempts to eliminate the effects of
measurable disturbances.
FB Control
Corrects for unmeasured disturbances,
modeling errors, etc.
FB Controller
FF Controller
Heat Exchanger
FB Controller
Feedback Control
FF Controller
Heat Exchanger
Heat Exchanger
Feedback-feedforword Control
Feedforward Control
CONSULTING ENGINEERS LIMITED
Cont…Deaerator Level Control
X2
- Controller Process X1/X2 C
Set Point + X1
KX2
X2
+ K
- Controller Process
Set Point + C
X1
Method 1 Method 2
Primary Loop
Secondary Loop
d1 d2
Set Point +
Primary Secondary +
+ + Process II + Process I +
- Controller - Controller
Controlled
O/P
Measuring
Device
Measuring
Device
Philosophy:
One controller output is the set point of other controller to integrate
information.
CONSULTING ENGINEERS LIMITED
Example: Level Controller on a Tank
With and Without
Cascade Control
Advantage:
• Controller responds quickly to high frequency changes.
• Controller integrates multiple sensor readings together
• Secondary loop reduces the phase lag.
• Process gain variations in the secondary part are taken care of in this loop
itself.
Disadvantage:
• Cascade controller can be employed only when a suitable intermediate
variable can be measured.
• Cascade controller is effective only when the secondary time constant is
smaller than the primary time constant.
Inputs Output
Devices
PLC
(Programmable
Logic Controller)
PROGRAMMABLE CONTROLLER, PC
POWER
SUPPLY
I M O M
N O
P D U O
U U PROCESSOR T D
T L P U
From E U L
To
SENSORS T E
OUTPUT
Pushbuttons, Solenoids,
contacts, contactors,
limit switches, alarms
etc. etc.
PROGRAMMING
DEVICE
serial connections
redundant field
bus connection
inputs/outputs
Enterprise Network
Engineer Operator Supervisor
station station gateway
Station
Control Bus
(e.g. Ethernet)
PLC
Large Control Station
COM1
COM 2
PLC
COM1
COM1
COM 2
CPU
with Field Bus
CPU
CPU
I/O
PLCs gateway
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
direct I/O
Field Bus Field Bus
COM
COM
COM
COM
COM
CPU
CPU
CPU
directly connected
I/O
I/O
I/O
I/O
I/O
I/O
I/O
I/O
Field Stations FB
gateway Field Devices
small PLC
Data concentrators,
(not programmable,
but configurable)
Sensor Bus (e.g. ASI)
Features
DCS Architecture
•Redundancy RequirementsMapping
DCS Capability
•Interface Requirements • Client Server based Architecture
•Engineering capability • Server less Architecture
•Sequence of Events Recording
•Historization
•Graphics capability
•Alarm & Event monitoring
•Time synchronization
•Hardware features
•Software features
Geographically Distributed
Functionally Distributed
In this configuration , the OS are WS with access to Global Data Base and
have peer-to-peer communication with the controllers.
• Triple Redundant control systems which are used for very critical controls.
Human Machine
Interface – HMI
Operator
station
Access / authorization (Multiple levels)
Plant control display and plant schematics
Alarm notification and action
Alarm display function and alarm summaries
Individual point data
Trend plot features, X-Y Plots
Logs/ Reports
Performance calculations
• Specification of DCS –
• Architecture of DCS -
Example :
ID fan interlocks
FD fan interlocks
Boiler feed Pump Interlocks
Communication
Deterministic (IEEE 802.4 or IEEE 802.5)
[ Control Net, Device Net, V-net, Master Bus]
OPC
Wireless
Ethernet on TCP/IP
Graphic Capability
Plant Schematics : Plant level, Area level, group level and equipment level.
Plant operation through soft face plates.
Multiple window capability.
Time Synchronization
Uniform timing in all systems throughout the plant.
Master clock system synchronized to GPS satellite.
Slave clock at strategic locations.
QUERIES