CH 3
CH 3
(EMEg5171)
CHAPTER 3
CONTROLLER PRINCIPLES
Lidiya A.
2022 gc
OUTLINE
1. Process Characteristics
Process Equation, Process Load, Process Lag and Self-Regulation
3. Controller Mode
a) Discontinuous Controller Mode
Two-Position (ON/OFF) Mode, Multi-position Mode and Floating Control Mode
Example:
Liquid temperature control process in previous example has self-regulation, as shown by the following
argument:
Suppose we fix the steam valve at 50% and open the control loop so that no changes in valve position
are possible.
The liquid heats up until the energy carried away by the liquid equals that input energy from the steam
flow. Then the system stabilizes to the temperature where input and output energies are equal.
If a load change occur, a new temperature is adopted and the system stabilizes at that temperature.
Example of a process without self-regulation is a tank from which liquid is pumped at a fixed rate.
CONTROL SYSTEM PARAMETERS
We have just described the basic characteristics of the process that are related to
control.
Let us now examine the general properties of the controller shown below:
To review:
Inputs to the controller are a measured indication of both the controlled variable and a setpoint
representing the desired value of the variable, expressed in the same fashion as the measurement;
the controller output is a signal representing action to be taken when the measured value of the
controlled variable deviates from the setpoint.
The measured indication of a variable is denoted by b, and the actual variable is
denoted by c.
1. Error
Cont…
Example
The temperature in previous example
has a range of 300 to 440 K and a
setpoint of 384 K. Find the percent of
span error when the temperature is
379 K.
2. Control Lag
The control system also has a lag associated with its operation that must be compared
with process lag for appropriate control action.
When controlled variable experiences sudden change, the process control loop reacts
by giving command to final control element to adopt a new value to compensate for
the detected change and this event takes some time.
Control lag refers to the time for the process control loop to make necessary
adjustments to the final control element.
For example:
If a sudden change in liquid temperature occurs, it requires
some finite time for the control system to actuate the steam
control valve.
3. Dead Time
Another time variable associated with process control is a function of both the
process control system and the process.
Dead time is the elapsed time between the instant a deviation (error) occurs and
when the corrective action first occurs.
Example:
An example for dead time is the control of chemical reaction by varying reactant
flow through a long pipe.
oWhen a deviation is detected, a control system quickly changes a valve setting to adjust
flow rate.
oSince the pipe is particularly long, there is a period of time during which no effect is felt in
the reaction vessel.
oThis is the time required for the new flow rate to move down the length of the pipe.
4. Cycling
Cycling is defined as the oscillations of the error about zero value or nominal value.
This means that the variable will be cycling above and below the setpoint value.
Steady-state cycling is one in which oscillations will continue indefinitely.
In such conditions peak amplitude of error and
period of oscillations are important in understanding the nature of process variable.
Transient cycling is one in which oscillations will decay to zero after some time.
In such conditions initial error,
period of cyclic oscillations, and
decay time are important in understanding the nature of process variable.
CONTROLLER MODES
The controller was already defined by the statement that
Two-position controllers are purposely designed with neutral zone to prevent excessive
cycling.
Multi-position Mode
Continuous controller modes
Unlike the discontinuous mode the controller output changes smoothly in response to
the error or rate of change of error.
These modes are an extension of discontinuous controller modes.
In most of industrial processes one or combination of continuous controllers are
preferred.
Proportional Control Mode
Integral Control Mode
Derivative Control Mode
How much? Proportional Mode
How long? Integral Mode
How fast? Derivative Mode
Proportional Control mode
In this mode a smooth, linear relationship exists between the controller output and
the error magnitude.
Is a natural extension of ON/OFF control mode.
In ON/OFF control mode the controller output saturates at
either 0% or 100%
But in this mode there is a smooth relation between controller
output and error before the output saturates at 0% (OFF state)
or 100% (ON state). o
Between these saturation levels, there is a band of error, where every value of error has
a unique value of controller output.
There is a one-to-one correspondence exist between controller output and error.
The range of error to cover 0% to 100% of controller output is known as
Proportional Band (PB)
The one-to-one correspondence exist only for error in this range
Cont…
Applications
Whenever there is one-to-one correspondence of controller output is required with respect to error
change proportional mode will be ideal choice.
The offset error limits the use of proportional mode, but it can be used effectively wherever it is
possible to eliminate the offset by resetting the operating point.
Proportional control is generally used in processes where large load changes are unlikely or with
moderate to small process lag times.
Example
1. For a proportional controller, the controlled variable is a process temperature with a range of 50 to
130 oC and a setpoint of 73.5 oC. Under nominal conditions, the setpoint is maintained with an
output of 50%. Find the proportional offset resulting from a load change that requires a 55%
output if the proportional gain is (a) 0.1 (b) 0.7 (c) 2.0 and (d) 5.0.
Integral Control Mode
Cont…
Another way of observing this control mode is:
This equation shows that when an error occurs, the controller begins to increase (or
decrease) its output at a rate that depends upon the size of the error and the gain.
Characteristics of Integral Control Mode
1) If the error is zero, the output stays fixed at a value equal to what it was when the error
went to zero (i.e. p(0))
2) If the error is not zero, the output will begin to increase or decrease at a rate of KI %/sec
for every 1% of error.
Note That
This mode successfully eliminate offset, but in the process its response is sluggish.
If the process lag is too large, the error can oscillate about zero or even be cyclic.
Applications: In general, integral control mode is not used alone, but can be used for systems with small
process lags and correspondingly small capacities.
Example
An integral controller has a reset action of 2.2 minutes. Express the integral controller
constant in s-1. Find the output of this controller to a constant error of 2.2%.
Derivative Control Mode
Cont…
Derivative action is not used alone because it provides no output when the error is
constant.
Example
How would a derivative controller with KD = 4 s respond to an error that varies as
ep=2.2 Sin(0.04t)?
Composite control modes
Due to offset error, proportional mode is not used alone. Similarly, integral and
derivative modes are not used individually in practice.
Thus, to take the advantages of various modes together, the composite control modes
are used.
Composite modes of controller operation combine advantages of each pure mode.
1. Proportional-Integral Control Mode (PI Mode):
2. Proportional-Derivative Control Mode (PD Mode):
3. Proportional-Integral-Derivative Control Mode (PID or Three Mode):
Proportional-Integral Control mode