0% found this document useful (0 votes)
40 views10 pages

Parallel Operation of Transformer

The document discusses the concept of circulating current in parallel transformers, specifically when a load switch is open and closed. It provides an example with two 100 kVA transformers, detailing their impedances and how to calculate the circulating current, its percentage of rated current, and the voltage difference causing it. The calculations show that the circulating current is 30.2% of the rated current in transformer A, with a 2.2% voltage difference between the transformers.

Uploaded by

Telayhun Addis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views10 pages

Parallel Operation of Transformer

The document discusses the concept of circulating current in parallel transformers, specifically when a load switch is open and closed. It provides an example with two 100 kVA transformers, detailing their impedances and how to calculate the circulating current, its percentage of rated current, and the voltage difference causing it. The calculations show that the circulating current is 30.2% of the rated current in transformer A, with a 2.2% voltage difference between the transformers.

Uploaded by

Telayhun Addis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 10

Circulating Current – load switch open

E A  EB
I circulating 
Z A  ZB
Circulating Current load switch closed
Icirculating adds to the load current in one
transformer and subtracts from the load current
in the other transformer. At rated load, the
transformer with the higher secondary voltage
will be overloaded!
Example 3.4

• Two 100 kVA single-phase transformers A


and B are to be operated in parallel. The
respective no-load voltage ratios and
respective impedances are obtained from
the nameplates as
– Transformer A
• 2300 – 460 V%R = 1.36 %X = 3.50
– Transformer B
• 2300 – 450 %R = 1.40 %X = 3.32
Example 3.4 continued

• Determine
– the circulating current in the paralleled
secondaries
– the circulating current as a percent of the
rated current in transformer A
– the percent difference in secondary voltage
that caused the circulating current.
The rated low-side currents are

100kVA
IA  217.39 A
460V
100kVA
IB  222.22 A
450V
The equivalent resistance and reactance of each transformer
referred to the low side
I rated Req
RPU 
Vrated
217.39 RAeq
0.0136   RAeq 0.0288
460
222.22 RBeq
0.0140   RBeq 0.0284
450
I rated X eq
X PU 
Vrated
217.39 X Aeq
0.0350   X Aeq 0.0741
460
222.22 X Beq
0.0332   X Beq 0.0672
450
The impedance of the closed loop formed by the two secondaries

Z loop Z A  Z B
Z loop 0.0288  j 0.0741  0.0284  j 0.0672
Z loop 0.0572  j 0.1413
Z loop 0.152467.97 

The circulating current

E A  EB
I circulatin g 
Z A  ZB
4600  4500
I circulatin g 
0.15467.97
I circulatin g 65.6  68 A
The circulating current as a percent of the rated current in transformer A

I circulating 65.62
 0.302  30.2%
I Arated 217.39

The percent difference in secondary voltage that caused the circulating current

VA  VB 460  450
 0.022  2.2%
VB 450

You might also like