0% found this document useful (0 votes)
49 views29 pages

LECTURE 2 - Key Components of Protection System - CB, VT Adn CT

A power protection system comprises current transformers, voltage transformers, protective relays, and circuit breakers. Circuit breakers are electrically operated switches that open or close based on relay outputs, while instrument transformers isolate and supply appropriate current and voltage levels for protection and measurement. Current transformers are categorized into metering and protection types, with specific accuracy classes and operational characteristics to ensure effective fault detection and system safety.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views29 pages

LECTURE 2 - Key Components of Protection System - CB, VT Adn CT

A power protection system comprises current transformers, voltage transformers, protective relays, and circuit breakers. Circuit breakers are electrically operated switches that open or close based on relay outputs, while instrument transformers isolate and supply appropriate current and voltage levels for protection and measurement. Current transformers are categorized into metering and protection types, with specific accuracy classes and operational characteristics to ensure effective fault detection and system safety.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 29

KEY COMPONENTS

OF A PROTECTION
SYSTEM
• A typical power protection system consists of the following components
Current transformer
Voltage transformer
Protective Relay
Circuit breaker
Circuit Breaker

The circuit breaker is an electrically operated switch, which is capable of


safely making, as well as breaking, short-circuit currents. The circuit breaker
is operated by the output of the associated relay.
 When the circuit breaker is in the closed condition, its contacts are held
closed by the tension of the closing spring. When the trip coil is energized,
it releases a latch, causing the stored energy in the closing spring to bring
about a quick opening operation.
Trip Circuit of a CB
Consider that the circuit breaker contacts are in a closed position by the force of
a spring. Energy is stored in the spring during the closing operation.
In order to trip the circuit breaker, it is necessary to release a latch either
manually or by energizing the trip-coil of the circuit breaker.
 The trip-battery supplies energy to the trip-coil for this operation. The relay
output contact is wired in series with the trip-battery and the trip-coil. Thus
when the relay operates, the trip-coil gets energized and the circuit breaker
quickly parts its contacts.
The figure below shows the typical layout of the circuit.
A typical trip circuit layout of
Circuit breaker
 When the CT secondary current exceeds
a specified ‘‘pickup’’ value, the relay
operating coil causes the
 normally open trip contacts to close.

 When the relay trip contacts close, the


trip coil of the circuit breaker is
energized, which then causes the circuit
breaker to open.

 Note that the circuit breaker does not


open until its operating coil is
energized, either manually or by relay
operation.

 Based on information from instrument


transformers, a decision is made and
‘‘relayed’’ to the trip coil of the breaker,
Instrument
transformers
(Current transformers and
Voltage transformers)
• Instrument transformers are necessary for

Isolating the protection, control & measurement


equipment from the high voltages of a power system
Supplying the equipment with the appropriate values
of current and voltage
Instrument
transformers
There are two basic types of instrument transformers: voltage transformers
(VTs), formerly called potential transformers (PTs), and current transformers CTs).
Figure below shows a schematic representation for the VT and CT.
Voltage Transformers
The voltage transformer steps down the high voltage of the line to a level safe
enough for the relaying system and personnel to handle.
The standard secondary voltage on line-to-line basis is 110 V. This helps in
standardizing the protective relaying equipment irrespective of the value of the
primary EHV adopted.
-A PT primary is connected in parallel at the point where a measurement is
desired, unlike a CT whose primary is in series with the line in which current is to
be measured.
Installed VT (Outdoor and
Indoor)
VTs cont’d
The transformer primary is connected to or into the power system and is
insulated for the power system voltage.

 The VT reduces the primary voltage to much lower, standardized levels suitable
for operation of relays

Ideally, the VT secondary is connected to a voltage-sensing device with infinite


impedance, such that the entire VT secondary voltage is across the sensing
device.

 In practice, the secondary voltage divides across the high impedance sensing
device and the VT series leakage impedances. VT leakage impedances are kept
low in order to minimize voltage drops and phase-angle differences from
primary to secondary
• Current Transformer
The current transformer has three jobs to do.
Firstly, it steps down the current to such levels that it can be easily handled by
the relay current coil. The standard secondary current ratings used in practice
are 5 A and 1 A.
 Secondly, it isolates the relay circuitry from the high voltage of the EHV
system.
Permit the use of standard current ratings for secondary equipment
Circuit diagram of CT
Installed CT’s in substation (Outdoor and
indoor)
Current Transformer Construction
Current Transformer Construction
Current Transformer
operation
• Like any other transformer, a current transformer has a primary winding, a
magnetic core and a secondary winding
• The primary winding of a current transformer is connected in series with the
power circuit The impedance is negligible compared with that of the power
circuit
• The alternating current flowing in the primary produces a magnetic field in
the core & induces a current in the secondary winding
• The CT's primary circuit consists of a single 'turn' of conductor, with a
secondary of many tens or hundreds of turns
• The primary winding may be a permanent part of the current transformer,
with a heavy copper bar to carry current through the magnetic core
CT Terminologies
• Rated transformation ratio. The rated transformation ratio is defined as
the ratio of the rated primary current to the rated secondary current.

• Current error (ratio error). The percentage error in the magnitude of


the secondary current is defined by the following formula:

• Ratio error = (KnIs - Ip)/ Ip x 100%

• Ip, Is = primary and secondary winding currents respectively,

• Kn = turns ratio
CT Terminologies cont’d

• Accuracy class. Accuracy class tells you how accurate the current transformer
is. Accuracy class shall be 0.2, 0.5, 1, 3 or 5.

• Phase displacement. The difference in phase between the primary and the
secondary current phasors, the direction of the phasors being chosen such
that the angle is zero for a perfect transformer.

• Rated secondary current. The value of rated secondary current shall be 5 A


or 1 A. In some cases, 2A may also be used .

• Rated burden. The product of current and voltage at the secondary side of
the CT is called the rated burden. It is measured in volt ampere (VA)
Current Transformer categories
Current transformers are categorized into two;
Metering CTs
Protection CTs

Metering CTs
A metering core is designed to work more accurately within the rated
current range designated.

When current flow exceeds that rating, the Metering core will become
saturated, thereby limiting the amount of current level within the device
Metering CTs
This protects connected metering devices from
overloading in the presence of fault level current flows.

Metering CTs need perform very accurately but only


over the normal range of load up to, say, 120% full load
current.
• Protection CTs

A protection core is designed to transform a distortion-free signal even well


into the overcurrent range.
This enables the protective relays to measure the fault current value
accurately, even in very high current conditions.

Relays are required to perform in fault current type situations


Moderate accuracy over a wider range
More core material is needed
CT Classes
Both Metering and Protection CTs Classes are defined differently .

In other words, the class of the CT dictates its accuracy (variation of calculated
secondary current from actual secondary current i.e accuracy “class”)

Protection CTs are usually defined as,


• The 10P10, 5P20, 5P10
• For “5P10”. Stands for;
5 is the accuracy or ratio error and is specified as a percentage
P stands for protection class type CT
10 is for Accuracy Limiting factor (ALF)
Accuracy Limiting Factor (ALF)
multiple of rated current (IN) up to which declared accuracy will be
maintained with rated burden connected
Example; for a CT whose ratio is 200/5A with ALF 20, means that CT
will maintain it’s accuracy certification up to 200*20= 4000A

In general, a protection CT specified as 5P10 means;


It indicates 5% accuracy (ratio error) at 10 times rated fault
current at rated burden. In other words, the CT will give
ratio error of only 5% even if the fault current reaches 10
times the nominal value (IN) after which the CT will start to
saturate
CT Saturation and Knee Voltage
• CΤ errors result from excitation current, so much so that, in order to
check if a CT is functioning correctly, it is essential to measure or
calculate the excitation curve.
• The magnetization current of a CT depends on the cross section and
length of the magnetic circuit, the number of turns in the windings,
and the magnetic characteristics of the material.
• for a given CT, the voltage across the magnetization impedance is
directly proportional to the secondary current.
• when the primary current and therefore the secondary current is
increased, these currents reach a point where the core commences
to saturate and the magnetization current becomes sufficiently high
to produce an excessive error.
CT Excitation Curve
The excitation curve is a curve of the CT secondary voltage against the
excitation current.
The CT saturation begins at the point when the Knee point is reached
at which point we can determine the Knee voltage and Knee current.

The Knee Point is defined as the point at which an increase in the


voltage of 10% produces an increase in the excitation current of 50%

The ‘Knee Point Voltage’ (Vkp) is defined as the secondary voltage at


which an increase of 10% produces an increase in magnetizing current
of 50%. It is the secondary voltage above which the CT is near
magnetic saturation.
Safety Precaution
The secondary of a current transformer should never be disconnected
from its load while current is flowing in the primary

The transformer secondary will attempt to continue driving current


across the effectively infinite impedance.
 This will produce a high voltage across the open secondary
 This high peaks of voltage may not be measured by conventional
voltmeter. But these high peaks of induced voltage may breakdown the
CT insulation, and may case accident to personnel

You might also like