Tss Layout AND Protection
Tss Layout AND Protection
AND
PROTECTION
01/27/2025 1
TSS Schematic diagram
&
Protection
TSS Schematic Diagram
Incoming Supply 220 / 132 /110 kV
Traction Transformer
DP
ISOLATOR
CT
CIRCUIT BREAKER
LIGHTNING
ARRESTER
TRACTION
TRANSFORMER
25 kv
42 kv LIGHTNING
CT
ARRESTER
TO BURIED RAIL &
NEAREST RUNNING 25 kv CIRCUIT BREAKER
TRACK 25 kv CT
25 KV SP ISOLATOR 25 kv SP ISOLATOR
NORMALLY CLOSED 100 kva, 25 kv/240 VLT SUPPLY
25 kv SP ISOLATOR TRANSFORMER
25 kv CT
25 KV/110V PT
25 kv FEEDER CIRCUIT BREAKER
(PROTECTION)
25 kv SP ISOLATOR
25 kv BUS COUPLER
INTERRUPTOR
(NORMAL OPEN)
25 kv INTERRUPTOR
25 kv SP ISOLATOR
25 kv PT
SUB SECTIONING &
PARALLELING STATION (SSP)
42 KV LA STATION TYPE:
HEAVY DUTY
SECTOR
R
HT SUPPLY
Y Incoming Supply
220 / 132 /110 kV
B
DPI
For Cross
Connection
DPI
Incoming CT
Incoming CB
Bushing CT
Incoming LA198/120/96 kV
TRACTION
01/27/2025 TRANSFORMER 5
Incoming ac BUS Incoming ac BUS
DPI DPI
CT CT
HV CB HV CB
LA LA
TRACTION TRACTION
TRANSFORMER TRANSFORMER
Bushing CTs
01/27/2025 6
25 KV FEEDING
ARRANGEMENT TRACTION
TRANSFORMER
Bushing CTs
42 kV LA
CT 25kV CB
SP Isolator
AT 10 kVA AT 100 kVA
PT
CT
Bus Coupler
Interrupter 25kV Feeder CB
DP Isolator SP Isolator
25 kV
Interrupter
DP Isolators
PT PT
LA
DN line
IOL
01/27/2025 7
Up line
Sectioning Arrangement
TSS
FP
SSP SP
01/27/2025 Sector 8
Concept Of Sector And Subsector
TSS -1 TSS -2
FP SP SSP FP
SSP
FP FP
SSP SP SSP
LA 42 kV LA 42 kV
IOL
DPI
Paralleling INTR
IOL
LA 42 kV LA 42 kV
PT AT
Sectioning
Interrupter
01/27/2025 10
SP
LA 42 kV LA 42 kV
BPI
Paralleling Intr
Neutral
Section
LA 42 kV LA 42 kV
AT
PT
Bridging
Interrupter
01/27/2025 11
Protection Scheme
Incoming feeder
protection
25kV CB protection
outgoing
feeder
protection
01/27/2025 12
Incoming HV Supply Side protection
• LA - 198 KV LA For 220 KV
System
- 120 KV LA For 132 KV
System
- 96 KV LA For 110 KV
System
•01/27/2025
REF - 10% of IFL 13
HV Side Protection
CT CT
Stabilizing
Resistance
OCR
01/27/2025 14
Differential protection
• Bias setting - 30%
• Differential setting - 40%
• HF setting - 10 N
01/27/2025 15
Differential protection
Restraining
Coil Opt Coil
01/27/2025 16
25 KV Side Protection
• LA - 42 KV LA
01/27/2025 17
25 kV/LV Side
Protection TFR
42kV LA
RESISTANCE
STABILIZING
CT
• Delta I relay
01/27/2025 19
Outgoing Feeder Protection
From TFR
PT
Inst CT
WPC DPR
OCR
Integrated feeder
Delta I Relay
01/27/2025 protection Relay 20
TO OHE
TRANSFORMER IN BUILT
PROTECTION
1. Arcing horn gap
2. PRD / Diaphragm
3. Buchhloz relay----
--- Stage 1 - alarm
(200CC)
--- stage 2 -
tripping(300CC)
4. OTI------
--- Stage 1 - alarm (75°c)
01/27/2025 --- stage 2 - tripping (85°c)21
TRANSFORMER IN BUILT PROTECTION
5. WTI ---------
--Stage 1 - Alarm (85°c)
--Stage 2 - Tripping (95°C)
6. Low Oil Level Alarm
7. Tripping of CB’s
If Changing tap, On Load / CKT