Busbar Protection Areva Compress
Busbar Protection Areva Compress
Alan Wixon
Senior Applications Engineer
F1 F2
There are fewer faults on busbars than on other parts of the power system.
▶ No dislocation of system due to accidental operation of busbar
protection.
▶ Slow fault clearance.
Busbar faults at F1 and F2 are cleared by remote time delayed
protection on circuits feeding the faults:
Time Delayed Overcurrent or Time
Delayed Distance Protection
> Busbar Protection – January 2004 3
Without Busbar Protection (2)
BUSBAR
ZONE
F1 F2
CAUSES :
▶ Insulation failures
▶ Circuit breaker failures
▶ Falling debris
▶ Isolators operated outside their ratings
▶ Safety earths left connected
▶ Current transformer failures
THEREFORE :
Circuit breakers should be tripped and locked
out by busbar protection
▶ RELIABLE
Failure could cause widespread damage to the
substation
▶ STABLE
False tripping can cause widespread interruption
of supplies to customers
▶ DISCRIMINATING
Should trip the minimum number of breakers to
clear the fault
▶ FAST
To limit damage and possible power system
instability
Syste
Earth m
earthin
bar g
resisto
r
I1 +
I2
I1 I2
Frame I1
Earthing
resistance to
insulation electrode
earth (> 10) resistance (<
1)
> Busbar Protection – January 2004 10
High Impedance Protection
CT requirements:
Equal ratios
RST
METROSIL Class ‘X’
8
7 May require stabilising
resistors, RST.
Zone
A
87 87 Zone
A A B
Check
zone
87A
I1
CT1 I2 I3 I4
RST
V R
ZM2 ZM3 ZM4
Supe
r RR
visio
n
relay I1
95
X Bus wire short
95 contacts
X
95 9 Supervisio
X 5 n relay
Metrosi Stabilisin
l g
resistor v v v resistors
s 8 8 8
7 7 7
Typical route is :-
CT’s to marshalling kiosk
Marshalling kiosk to isolator auxiliaries
Loop between marshalling kiosks
Conductor size :-
Normally 2.5mm2
Interlocke
Circuit d
protectio overcurre
n nt relay
Circuit Circuit
protectio protectio
n n
Busbar Busbar
protectio protectio
n n
Busbar
protectio Interlocke
n d
overcurre
nt relay
Overlapping All C.T.s on line All C.T.s on Busbar
side of circuit side of circuit
C.T.s breaker breaker
60MW
Generators
75MVA
132/13.8kV
Transformer
s
132k
V
Zone
Zone G H
BS
BC BC
Zone
J
Typical Feeder
Circuits
> Busbar Protection – January 2004 26
Isolator Auxiliary Switches
M
Auxiliary switches should :
A B C D
1) Close before the isolator
closes
2) Open after the isolator
a c opens
b d
In order to maintain stability
on switching.
r
m
Buswires
+ -
In M1 M2R 87CH -
87M1 -
Out 96D 1
1 1
CSS - 96D
M1 87M2 - a 2
1 1 96E
CSS - c
M2 87R -
1
1
CSS - R 96F
1
96F
b1 2
96
G
c2
96H
1
9
6
H
2
D.C. Buswires
80T
> Busbar Protection – January 2004 29
Double Busbar with Transfer Facilities
Mai
n
Reserve /
Transfer
By- By-
pass pass
Isolato Isolato
r r
Mai
n
Reserv
e
Transfe Transfe
r CB r CB
Transfe
r
8
7
8
7
T T
1 3
T T
4 2
F4 F2
F1 F3
87 87
R1 R3
T T
1 3
T T
4 2
87 87
R4 R2
F4 F2
Z Z
1 2
F1 F2 BS F3 F4
F F BSM F F
M M M M
1 2 3 4
Z1 Z2
ZCK ZCK
Z1 ZCK Z2
BS
Z Z
1
Z 2
Z
3 4
BC1 F2 F3 F4 BC2
F1
Z1 Z
Z3 Z
2
ZCK ZCK
4
Z Z ZCK Z Z
1 3 2 4
Incomer
BLOCK
O/C Relay
IF2
IF1
OC OC OC OC
F3 F4 F5 F6