We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 13
CHAPTER 8 -
COMMUNICATION SYSTEMS COMMUNICATION CIRCUITS
Wires and Cables Outside of the Building (Clearance):
On Poles and In-Span - Supply service drops of 0-750 volts
running above and parallel to communications service drops shall have a minimum separation of 300 mm at any point in the span, including the point of and at their attachment to the building. Above Roofs - Shall have a vertical clearance of not less than 2500 mm from all points of the roof which they pass. Lighting Conductors - A separation of at least 1800 mm shall be between communications wires and cables on buildings and lightning conductors. RADIO AND TELEVISION EQUIPMENT
Clearances - Receiving Stations
a) Outside of Buildings - Lead-in conductors attached to buildings shall be installed so that they cannot swing closer than 600 mm to the conductors of circuits of 250V or less between conductors, or 3000 mm to the conductors of circuits of over 250V between conductors, except that in the case of circuits not over 150V between conductors, where all conductors involved are supported so as to ensure permanent separation, the clearance shall be permitted to be reduced but shall not be less than 100 mm. b) From Lighting Rod Systems - The clearance shall not be less than 1800 mm c) Underground Conductors - Shall be separated at least 300 mm from conductors of any light or power circuits or Class 1 circuits. d) Antennas and Lead-ins (Indoors) - Shall not be run nearer than 50 mm to conductors of other wiring systems in the premises. OPTICAL FIBER CABLES AND RACEWAYS
that is not terminated at equipment other than a connector and not identified for future use with a tag. Cable Sheath. A covering over the optical fiber assembly that includes one or more jackets and may include one or more metallic members or strength members. Exposed (to Accidental Contact). A conductive optical fiber cable in such a position that, in case of failure of supports or insulation, contact between the cable's noncurrent-carrying conductive members and an electrical circuit may result to short circuits. 7.70.2 Cables Outside and Entering Buildings
7.70.2.1 Overhead (Aerial) Optical Fiber Cables.
Overhead optical fiber cables containing a non current-carrying metallic member entering buildings shall comply with 8.40.2. 1(A) and (B).
(A) On Poles and In-Span.
Where outside plant optical fiber cables and electric light or power conductors are supported by the same pole or are run parallel to each other in-span, the conditions described in 7.70.2.1(A) (1) through (A)(4) shall be met. (1) Relative Location. Where practicable, the outside plant optical fiber cables shall be located below the electric light or power conductors. (2) Attachment to Cross-Arms. Attachment of outside plant optical fiber cables to a cross-arm that carries electric light or power conductors shall not be permitted. (3) Climbing Space. The climbing space through outside plant optical fiber cables shall comply with the requirements of 2.25.1.14(D). (4) Clearance. Supply service drops and sets of overhead service conductors of 0 to 750 volts running above and parallel to optical fiber cable service drops shall have a minimum separation of 300 mm at any point in the span, including the point of their attachment to the building. Clearance of not less than 1000 mm shall be maintained (B) Above Roofs. Outside plant optical fiber cables shall have a vertical clearance of not less than 2500 mm from all points of roofs above which they pass. Exception No. 1: The requirement of 7.70.2.1 (B) shall not apply to auxiliary buildings such as garages and the like. Exception No. 2: 4 reduction in clearance above onlv the overhanging portion of the roof to not less than 450 mm shall be permitted if (a) not more than 1200 mm of optical fiber cable service drop cable passes above the roof overhang, and (b) the cable is terminated at a through- or above-the-roof raceway or approved support. Exception No. 3: Where the roof has a slope of not less than 100 mm in 300 mm, a reduction in clearance to not less than 900 mm shall be permitted. 7.70.2.4 Underground Optical Fiber Cables Entering Buildings. Underground optical fiber cables entering buildings shall comply with 7.70.2.4(A) and (B).
(A) Underground Systems with Electric Light, Power, Class 1,
or Non-Power-Limited Fire Alarm Circuit Conductors. Underground conductive optical fiber cables entering buildings with electric light, power, Class 1, or non- power-limited fire alarm circuit conductors in a raceway, handhole enclosure, or manhole shall be located in a section separated from such conductors by means of brick, concrete, or tile partitions or by means of a suitable barrier. (B) Direct-Buried Cables and Raceways. Direct-buried conductive optical fiber cables shall be separated by at least 300 mm from conductors of any electric light, power, or non power-limited fire alarm circuit conductors or Class 1 circuit. NETWORK-POWERED BROADBAND COMMUNICATIONS SYSTEMS
Abandoned Network-Powered Broadband
Communications Cable. Installed network-powered broadband communications cable that is not terminated at equipment other than a connector and not identified for future use with a tag. Block. A square or portion of a city, town, or village enclosed by streets, including the alleys so enclosed but not any street. Exposed (to Accidental Contact).A circuit in such a position that, in case of failure ofsupports or insulation, contact with another circuit may result. Fault Protection Device. An electronic device that is intended for the protection of personnel and functions under fault conditions, such as network-powered broadband communications cable short or open circuit, to limit the current or voltage, or both, for a low-power network-powered broadband communications circuit and provide acceptable protection from electric shock. Network Interface Unit (NIU).A device that converts a broadband signal into component voice, audio, video, data, and interactive services signals and provides isolation between the network power and the premises signal circuits. These devices contain primary and secondary protectors. Network-Powered Broadband Communications Circuit. The circuit extending from the communications utility's serving terminal or tap up to and including the NIU. PREMISES-POWERED BROADBAND COMMUNICATIONS SYSTEMS
Network Terminal. A device that converts network provided
signals (optical, electrical, or wireless) into component signals, including voice, audio, video, data, wireless, optical, and interactive services, and considered a network device on the premises that is connected to a communications service provided and is powered at the premises. Premises Communications Circuit. The circuit that extends voice, audio, video, data, interactive services, telegraph (except radio), and outside wiring for fire alarm and burglar alarm from the service provider's network terminal lo the customer's communications equipment up to and including terminal equipment, such as a telephone, a fax machine, or an answering machine.
Premises Community Antenna Television (CATV) Circuit.
The circuit that extends community antenna television (CATV) systems for audio, video, data, and interactive services from the service provider’s onto the appropriate customer equipment.