We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 15
Polarity Test of Transformer
• Polarity means the direction of the induced voltages in the primary
and the secondary winding of the transformer. If the two transformers are connected in parallel, then the polarity should be known for the proper connection of the transformer. • There are two types of polarity Additive Polarity: In additive polarity, the same terminals of the primary and the secondary windings of the transformer are connected.
Subtractive Polarity: In subtractive polarity, different terminals of the
primary and secondary side of the transformer is connected. Explanation With Connection Diagram • Each of the terminals of the primary, as well as the secondary winding of a transformer, is alternatively positive and negative with respect to each other as shown in the figure below. Let A1 and A2 be the positive and negative terminal, respectively of the primary side of the transformer and a1, a2 are the positive and negative terminal of the secondary side of the transformer. • If A1 is connected to a1 and A2 is connected to a2 that means similar terminals of the transformer are connected, then the polarity is said to be additive. If A1 is connected to a2 and A2 to a1, that means the opposite terminals are connected to each other, and thus the voltmeter will read the subtractive polarity. • It is essential to know the relative polarities at any instant of the primary and the secondary terminals for making the correct connections if the transformers are to be connected in parallel or they are used in a three-phase circuit. • In the primary side, the terminals are marked as A1 and A2 and from the secondary side, the terminals are named as a1 and a2. The terminal A1 is connected to one end of the secondary winding, and a voltmeter is connected between A2 and the other end of the secondary winding. • When the voltmeter reads the difference that is (V1 – V2), the transformer is said to be connected with opposite polarity know as subtractive polarity and when the voltmeter reads (V1 + V2), the transformer is said to have additive polarity. Insulation Resistance Test of Transformer
• This test is performed at or above rated voltage to determine if there
are low resistance paths to the ground or between winding to winding as a result of winding insulation deterioration. • The test measurement values are affected by variables such as temperature, humidity, test voltage, and size of the transformer. • The general rule of thumb that is used for acceptable values for safe energization is 1 MΩ per 1000 V of applied test voltage plus 1 MΩ. CONTINUUTY TEST • A continuity test verifies that current will flow in an electrical circuit (i.e. that the circuit is continuous). The test is performed by placing a small voltage between 2 or more endpoints of the circuit. The flow of current can be verified qualitatively, by observing a light or buzzer in series with the circuit actuates or quantitatively, using a multimeter to measure the resistance between the endpoint.
• Transformer continuity test is a standard procedure conducted to
check the integrity of windings in a transformer. It helps to identify any faults or breaks in the windings, which can affect the performance and efficiency of the transformer. • During the continuity test, a low-voltage direct current (DC) source is connected to one winding of the transformer, while the other winding is connected to a voltmeter or an ohmmeter. The DC current creates a magnetic field in the primary winding, which induces a voltage in the secondary winding. By measuring the voltage or resistance, the continuity of the windings can be determined. • If the windings are continuous and intact, the voltmeter or ohmmeter will register a reading indicating a complete circuit. However, if there is a break or fault in the windings, the reading will be zero or significantly lower than expected. • The continuity test is essential during transformer maintenance, repair, or troubleshooting processes. It helps to identify potential issues such as short circuits, open circuits, or damaged windings, allowing for timely repairs and ensuring the transformer's optimal performance and safety. transformer breakdown voltage test • The transformer breakdown voltage test, also known as the dielectric strength test, is a crucial procedure conducted to determine the insulation capability of a transformer. This test helps to ensure that the transformer can withstand the rated voltage without any insulation failure or breakdown. • During the test, a high voltage source is connected to the transformer's windings, applying a voltage that exceeds the rated voltage. The voltage is gradually increased until a breakdown occurs in the insulation. Breakdown can manifest as a spark or a sudden jump in current. The voltage at which breakdown occurs is known as the breakdown voltage • During the test, a high voltage source is connected to the transformer's windings, applying a voltage that exceeds the rated voltage. The voltage is gradually increased until a breakdown occurs in the insulation. Breakdown can manifest as a spark or a sudden jump in current. The voltage at which breakdown occurs is known as the breakdown voltage • The breakdown voltage test is performed to verify the insulation quality and integrity of the transformer's windings and insulation materials. It helps to identify weak spots, manufacturing defects, or deteriorated insulation that could compromise the transformer's performance or pose safety hazards.
• By conducting the breakdown voltage test, engineers can determine if
the transformer's insulation is suitable for the specified operating conditions and ensure its reliability in real-world scenarios. It is a vital part of transformer testing and maintenance to prevent insulation failures and potential damage to the transformer or connected equipment. The open circuit test and short circuit test • The open circuit test, also known as the no-load test, is conducted by applying a rated voltage to the primary winding of the transformer while the secondary winding is left open (not connected to any load). The purpose of this test is to determine the core losses of the transformer, including iron losses and a small amount of copper losses. By measuring the input power and current, the core losses can be determined, allowing for the calculation of parameters such as core loss resistance and magnetizing current. • On the other hand, the short circuit test, also known as the impedance test, involves applying a low voltage to the secondary winding of the transformer while the primary winding is short- circuited. This test is performed to determine the parameters related to the transformer's impedance and copper losses. By measuring the input power, voltage, and current, the short circuit impedance and copper losses can be calculated. The short circuit test also helps in assessing the ability of the transformer to handle high currents and withstand short circuit conditions. • Both the open circuit test and short circuit test provide valuable information about the transformer's performance, efficiency, and its ability to handle different load conditions. These tests are conducted during the manufacturing process, as well as during maintenance and troubleshooting to ensure the transformer is operating within its specified parameters and to identify any potential issues or faults.