Introduction
Introduction
POWER GENERATION
Sadullah Chandio
Assistant Professor Deptt Of Electrical Engg, QUEST Nawabshah
INTRODUCTION
Books Recommended
INTRODUCTION
Books Recommended
POWER ECONOMICS / INTRODUCTION
ECONOMICAL
ECONOMICAL
PROTECTION &
GENERATION
SERVICES
ECONOMICAL ECONOMICAL
DISTRIBUTION TRANSMISSION
POWER ECONOMICS / ECONOMICS OF
POWER GENERATION
.
POWER ECONOMICS
.
POWER ECONOMICS
B. HOT RESERVES : The boiler is ready consuming fuel but not coupled with
generator . In case of failure or short fall generator is required to coupled the
boiler due to maintain continuity of supply.
C. SPINNING RESERVES : It is generating capacity , boiler , turbine &
generator is mechanically coupled but generator is operating on no load.
Specially diesel generators are used as stand by generator because in case of
peak load demand it can be easily switched on.
POWER ECONOMICS
Reserve Capacity of the plant should be equal to largest generating unit of the
plant & greater than Present Maximum demand to meet the load demand in
future
PB # 01: A Power station has a maximum demand of 14000 kW. The annual load
factor is 60% and the plant capacity is 18750 kW. Determine the following
Plant capacity factor,
Reserve capacity, and
Plant use factor.
ECONOMICS OF POWER GENERATION
Maximum Demand:
The maximum demand of an installation, system or house is the maximum rate of
consumption expressed in amperes, watts, kW or kVA occurred during specified
period of time.
Lets see the connected load of house quoted from pervious slide was =2946watts.
If this customer switched on all apparatus at specified time for 2 hours in a day, than
its max demand can be said 2946 watts over that interval of time of the day
But in practical load is variable according to our living standard . In the night we
switched off all lights if we are sleeping in AC ROOM only AC may be working,
whereas freezer is also working all times but pumping motor is also switched off
So we can say the Max Demand of this customer in the night only AC & freezer that
will be 1600 watts only. Max Demand is variable of all customers , it depend upon
directly to our living standard
ECONOMICS OF POWER GENERATION
DEMAND FACTOR:
Demand factor is always less than one or equal to one if all apparatus of system are
switched on
From above QUOTED example , the connected load of house was 2946 watts but at
night his max demand was 1600 watts , lets calculate his demand factor
LOAD FACTOR:
LOAD FACTOR:
The load factor can be daily load factor, monthly load factor or
annual load factor if the time period (T) considered is a day or a
month or a year respectively. The load factor of a power station is
always less than 1. It is because the average load on the power
station is smaller than the maximum demand. The load factor is
very important because it is used to determine the overall cost per
unit generated, i.e., if the load factor of the power station is
higher, then the cost per unit generated will be lesser.
ECONOMICS OF POWER GENERATION
DIVERSITY FACTOR:
DIVERSITY FACTOR:
Example-: A sub-station has three outgoing feeders:
feeder 1 has maximum demand 10 MW at 10:00 am,
feeder 2 has maximum demand 12 MW at 7:00 pm and
feeder 3 has maximum demand 15 MW at 9:00 pm,
While the maximum demand of all three feeders is 33 MW at
8:00 pm.
Here, the sum of the maximum demand of the individual sub-
systems (feeders) is 10 + 12 + 15 = 37 MW, while the system
maximum demand is 33 MW. The diversity factor is 37/33 = 1.12.
The diversity factor is usually greater than 1.
ECONOMICS OF POWER GENERATION
DIVERSITY FACTOR:
Example-:
A Nawabshah Substation has supplies the following loads to various consumers
1. Domestic light = 500 kW
2. Domestic power = 100 kW
3. University consumers = 2000 kW
4. Airport establishments = 700 kW
5. If the maximum demand on the power station is 3000 kW. Determine the
diversity factor of the Substation
Solution
ECONOMICS OF POWER GENERATION
DIVERSITY FACTOR:
In real individual customers do not have peak demand same because according
to job, trade business , living standard & load demand they will consume
electricity so the load will be diversified. Due to diversified load on feeders
caused diversification of substations & transmission lines.
If the value of the diversity factor is greater than 1, then it is a good diversity
factor, and 1.0 represents a poor diversity factor. A high diversity factor has
the effect of reducing the maximum demand. It is obtained by using electrical
energy at night load or light load periods.
The maximum demands of the individual consumers of a group do not occur
simultaneously. Thus, there is a diversity in the occurrence of the load. Due to
this diverse nature of the load, full load power supply to all the consumers at the
same time is not required.
Greater the diversity factor, lesser is the cost of generation of power.
ECONOMICS OF POWER GENERATION
LOAD DIVERSITY
Load diversity is the difference between the sum of the peaks of two or more
individual loads and the peak of the combined load.’
Since load diversity is the difference between two quantities of similar units
(rather than a ratio), it is expressed in the units of the two demands being
compare
1. Feeder kW
2. 1 10
3. 2 9
4. 3 10
5. 4 14
load diversity = 10+9+10+14-14=29kW
ECONOMICS OF POWER GENERATION
CO INCIDENT FACTOR (CF)
• Engineers prefer to have a factor which describes the characteristics of loads
that have a value equal to or less than unity. The reciprocal of the diversity
factor is known as the coincident factor: CF helps in planning new substations
and extension of power industry.
The coincident factor is dependent upon the type of loads connected to the
system. Typically,
Loads CF
Distribution transformers 0.74—0.83
Primary feeders 0.83—0.92
Substations 0.80—0.96
ECONOMICS OF POWER GENERATION
BASE LOAD :
The base load is the load below which the demand never falls and is
supplied 100% of the time. It is constant load throughout day, month or
year that power stations has to supply without rest.
PEAK LOAD:
The peak load occurs for about 15% of the time. It is variable load and
followed by our living standard . In Pakistan peak load may occur from
3 p.m to 9 .pm, because all shops, factories, hotels, & domestic
apparatus are consuming electrical energy.
INTERMEDIATE LOAD:
The intermediate load represents the remaining load region in the load
curve. These types of loads are shown in the next figure.
Load Characteristics & Types
.
Load Characteristics & Types
.
Load Characteristics & Types
.
Load characteristics & Types
Intermediate load
BASE LOAD
BASE LOAD
TYPES OF LOADS
b. Commercial Loads:
Commercial loads occur for longer period compare to residential loads. This types of loads
are mainly electrical energy utilize for commercial shops, school, colleges, advertising,
hoardings, malls, elevator, cinema halls etc. Commercial load fluctuations are mainly due
to switching of air-conditioning equipment. These loads vary more depending upon the
season.
c. Industrial Loads:
Industrial loads have constant demand and consider as base loads. Commercial loads are
little affected by seasonal variations and weather conditions. This loads mainly include
industrial appliances like motor, furnaces, cranes, industrial lighting, computers, elevators,
pumps. Industrial loads utilize more electrical energy supplied by the utility. This load
does not vary with seasonal change having constant demand throughout the day. Industry
loads further divided into section according to power required.
Small scale industries
Medium scale industries
Large scale industries
Heavy industries
TYPES OF LOADS
d. Agricultural loads :
Agricultural types of loads use electrical energy for doing agriculture activities.
Agricultural loads mainly include irrigation pumps, lights, water pumps.
e. Municipal Loads :
Municipal loads consist of street lights, electricity required for water supply
pumps and drainage system. for water supply water is pumped to the overhead
tank using electric pump, overhead water tank pumping is carried out during off-
peak time. like during night time. its improve load factor of power system.
f. Traction Loads :
This types of loads mainly include trains ,Metros, suburban railways & main
railway system.
g. Government load:
This may includes public sector offices, This types of loads mainly include
trains, ,colleges, schools ,all courts , defense factories & public sector
understandings.
TYPES OF LOADS
Considering above points the best choice in Pakistan to accommodate base load
listed as below.
ALL TYPES OF RENEWABLE POWER PLANTS
HYDEL POWER PLANT
COAL POWER PLANT
GAS POWER PLANT
COMBINED CYCLE POWER PLANT
NUCLEAR POWER PLANT
Similary for peak load that occurred for specified interval of time, if possible
above power plants can accommodate otherwise
Reserve capacity need to start
Stand by diesel generator need to start
Hence the cost of per kWh for base load & peak load is charged
accordingly.
LOAD CURVES
There are two types of load curves used to study , analyze & prediction of base &
peak demand from distribution system on power generating stations.
LOAD CURVE ( LC) &
OR
The curve which shows the variation of load on the electrical power station with
respect to time is known as load variation curve or simply load curve.
It represents the load in its time sequence. As typical curve is obtained by
plotting the station load (KW or MW ) along Y-axis and the time( hours) when it
occurs along X-axis.
If plotted variable load supplied by generating stations for 24 hours of single
day, it is known as daily load curve. If it is drawn time against hours of month, it
is known as monthly load curve. Similarly if plotted variable load demand of
consumers against 8760 hours, than it is call annual load curve.
Daily load curves gives an idea of load demand of the day, whereas monthly
load curve followed by daily load curve used to fix cost of per kWh.
Annual load curves helps in annual energy requirements & and are use to
determine annual load factor.
Load characteristics & Types
Intermediate load
BASE LOAD
BASE LOAD
12/04/2024 50
Importance of load curve :
The daily load curve shows the variations of load on the power station
during different hours of the day
The area under the daily load curve gives the number of units generated in the
day. Units generated/day = Area (in kWh) under daily load curve.
The highest point on the daily load curve represents the maximum demand on
the station on that day.
The area under the daily load curve divided by the total number of hours gives
the average load on the station in the day.
Importance of load curve :
The size and the number of generating units can be determined from the load
curve
This Load Curve helps to determine the operation schedule of the station. In
that case when all the units or the less units needs to running is found
The size and the number of generating units can be determined from the load
curve
This Load Curve helps to determine the operation schedule of the
station. In that case when all the units or the less units needs to running
is found
LOAD CURVE DECIDES THE INSTALLED CAPACITY OF
GENERATING STATION.
LOAD DURATION CURVE (LDC) :
From the data available from the load curve determines the maximum load and the
Now take the next load and the total time during which this and the previous load occurs.
The load duration curves can be drawn for any duration of time, for example, a day or a
Time Load in MW
6.00 am to 8.00am 8
8.00 am to 1.00 noon 20
30 4 4/24×100=16.67%
20 4+5 9/24×100=37.5%
5 23+1 = 24 24/24×100=100%
BASE
LOAD DURATION CURVE (LDC) : LOAD
PEAK
LOAD
STARTS