PSA - Lecture 6 - Symmetrical Fault Analysis (Part-1) - MAZS
PSA - Lecture 6 - Symmetrical Fault Analysis (Part-1) - MAZS
Lecture on
Symmetrical Fault Analysis (Part-1)
Lecture Outcomes
By the end of this lecture, the students should be able to:
All the phases are short-circuited to each other and often to earth.
Rarely occurred
Great
importance
The total
current is
called the
asymmetrical
current.
Synchronous Reactance
Obviousl
y
Fault Currents of SM (no load condition)
Symmetrical short-
circuit armature
current in SM
Envelope of SM
symmetrical short
circuit current.
Different time constants of SM after fault
The duration of I″ is determined by time constant Td′′,
This Td′′ is called the direct-axis short-circuit sub-transient time constant.
When t> Td′′ but t < Td′ => direct-axis short-circuit transient time constant
the first exponential term of above equation has decayed almost zero, but the
second exponential has not decayed significantly.
Since the three-phase no-load voltages are displaced 120o from each
other, the three-phase ac fault currents are displaced 120o fro each
other. In addition to that ac fault current, each phase has a different
dc offset. The maximum dc offset in any phase, which occurs when
α=0 is
Tutorial:
Problem 3: [Ref. 3, p. 363] A 500 MVA, 20 kV, 60 Hz synchronous
generator with Xd′′=0.15, Xd′=0.24, Xd=1.1 pu and time constant Td′
′=0.035, Td′= 2.0, TA=0.2 s is connected to the circuit breaker.
At nominal voltage the Thevenin equivalent circuit looking back into the
system from the point of connection is an emf of 1.0∠0 pu in series with
the pu impedance Zth. Therefore, under short-circuit conditions,
Short Circuit Capacity (SCC)/ Fault Level of Bus
Pre-fault
Bus voltage = 1 pu
After-fault
The strength of a bus is the ability Bus voltage 0 pu
of the bus to maintain its voltage
when a fault takes place at other
bus:
Strength of a bus related to SCC.
Higher SCC => Higher Bus
Other bus voltages
changes
Strength
If XT =0 then SCC = ∞.
For this case the bus is known as
Tutorial:
Problem 6: A small generating station has a bus-bar divided into three
sections. Each section is through a reactor rated at 5MVA, 0.1 p.u. A
generator of 8MVA. 0.15p.u. is connected to each section of the bas bar.
Determine the SCC of the bus if a three-phase fault takes place on one of
the section of the sections of bus-bar.
Let the base: 8 MVA in the generator
circuit. Xg = 0.15 pu
Tutorial:
Problem 7: Two generating station having 1200 MVA and 800 MVA
respectively and operating at 11 kV are linked with an inter-connected
cable having reactance of 0.5Ω per phase. Determine the SCC of each
station. Xg1=Xg2= 0.1 pu
Tutorial:
Problem
7:
References
[1] Willaim D. Stevenson, Elements of Power System Analysis, Fouth Edition,
McGraw-Hill International Editions, Civil Engineering Series, McGraw-Hill Inc.
[2] John J. Grainger, William D. Steevnson, Jr., Power System Analysis,
McGraw-Hill Series in Electrical and Conputer Engineering, McGraw-Hill Inc.
[3] J. Duncan Glover, Mulukutla S. Sharma, Thomas J. Overbye, Power System
Analysis and Design, Fouth Edition (India Edition), Course Technology Cengage
Learning
[4] Hadi Saadat, Power System Analysis, Tata McGraw-Hill Publishing Company
Limited [5] I J Nagrath, D P Lothari, Modern Power System Analysis, Second
Edition, Tata McGraw-Hill Publishing Company Liited
[6] V. K. Mehta, Rohit Mehta, Principles of Power System, Multicolor Illustrative
Edition, S. Chand and Company Limited
[7] AIUB Lecture Notes
[8] Engineering notes
https://www.engineeringenotes.com/