Power System Protection - PPTX 1
Power System Protection - PPTX 1
RESEARCH BHOPAL
Current reactor allows free interchange of power under normal condition, but when the fault
occurs the disturbance is restricted by the current reactor to the faulty section. As the
resistance of the system is very small as compared to their reactance. Hence, the efficiency of
the system is not much affected.
2. It limits the fault current to flow into the healthy feeders or parts of the system,
thereby avoiding the fault from spreading. This increase the chances of continuity of
supply.
3. Current limiting reactor reduces the flow of short circuit current so as to protect the
• appliances
Drawbacks fromof
mechanical stress and reactor
current limiting overheating.
2. When the reactor is installed on the network, the total percentage reactance of the
circuit increases.
3. It decreases the power factor and thus the regulation becomes poorer.
• Location of Reactors
at different location in a power system for reducing the short circuit current. These reactors
may be coReactors are located nnected in series with the generators, feeders or in bus-bars as
explained below.
• Generators Reactors
Generator reactors are inserted between the generator and the generator bus. Such reactors
protect the machines individually. In power station generator, reactors are installed along
with the generators. The magnitude of reactors is approximately about 0.05 per unit. The
main disadvantages of such type of reactors are that if the fault occurs on one feeder, then
the whole of the system will be adversely affected by it.
• Feeders Reactors
Reactors, which is connected in series with the feeder is called feeders reactor. When the
fault occurs on any one feeder, then the voltage drops occur only in its reactors and the bus
bar is not affected much. Hence the machines continue to supply the load. The other
advantage is that the fault occurs on a feeder will not affect the others feeders, and thus the
effects of fault are localized.
The disadvantage of such type of reactors is that it does not provide any protection to the
generators against short circuit faults occurs across the bus bars. Also, there is a constant
voltage drop and constant power loss in reactors during normal operating conditions.
• Bus-Bar Reactor
When the reactors are inserted in the bus bar, then it is called bus-bar reactors. The constant
voltage drop and constant power loss in reactors may be avoided by inserting the reactors in
the bus bars. The bus bar reactor for ring system and the tie system are explained below.