2022 NEE 4103 - 1EE Service Entrance Conductor & Service Equipment

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 19

University of the East

Department of Electrical Engineering

NEE 4103 4EE – 1A


Service Entrance Conductor &
Service Equipment Calculations
for Dwelling Unit
Example 1 – One Family Dwelling
Feeder Calculation for Single Family Dwelling
Unit up to 150m² more than 6 circuits, 230V,
60hz, Single Phase Service
Given : 145m² (habitable area excluding
terrace, balcony & porches), 2 – Small
Appliance Circuit, 1 - Laundry Circuit, 1 –
8kW Electric Range, 3 – 1hp Room ACU, 2 –
2.5kW Shower Heater, 1 – Water Pump 1.5hp
Determine the Service Entrance Conductor &
Service Equipment
Solution :
a) General Lighting Load (GLL) :
= 145m² x 24 VA/m² = 3,480VA

b) Small Appliance Load (SA) :


= 2 x 1,500 = 3,000VA
C) Laundry Circuit = 1,500VA

SUB – TOTAL======== 7,980VA


Application of Demand Factors
See Table 2.20.3.3
1st 3000VA @ 100% D.F. = 3,000VA
Remainder @ 35% D.F.
(7,980 – 3,000) x 0.35 = 1,743VA
------------
TOTAL = 4,743VA
d) Other Loads
1 – 8kW Electric Range @ 80% D.F. = 6,400VA
See Table 2.20.3.16
3 – Room ACU 1hp 8A x 230 x 3 = 5,520VA
See Table Table 4.30.14.2
2 – Shower Heater @ 2.5kW each = 5,000VA
1 – Water Pump 1.5hp 10A x 230 = 2,300VA
See Table Table 4.30.14.2
SUB – TOTAL ======= 19,220VA
Total Net Computed Load
Net Total GLL, SA & Laundry = 4,743VA
Other Loads = 19,220VA
----------------
23,963 VA
Service Entrance Conductor(SEC) :
= [4,743+6,400+5,520+5,000+1.25(2300)]/230
= 106.68A
Alternate Method :
= [23,963 + 0.25(2300)] / 230
= 106.68A
Use THW Copper 38mm² (115A)
See Table 3.10.2.6(B)(16)
Service Equipment (SE) :
= [4,743+6,400+5,520+5,000+2.5(2,300)]/230
= 27,413 / 230
= 119.18 A
Alternate Method :
= [23,963 + 1.5(2,300)]/230
= 119.18 A
Use 100AT, 100AF, 2P, MCCB
Example 2 – One Family
Dwelling
Single Family Dwelling Unit, more than 150m²
Floor Area, 230V, 60Hz, Single Phase Service
Given : 250m² Floor Area, 6 – Room ACU
1.5hp, 4 – Small Appliance, 1 – Laundry Circuit,
2 – WMO @ 4kW each, 1 – Electric Range 8kW,
1 – 12kW Electric Range, 1 – MWO 1.5kW, 1 –
Clothes Dryer @ 5kW, 4 – Shower Heater @
2.5kW each, 1 – Water Pump 1.5hp
Determine the Service Entrance Conductor &
Service Equipment
Solution :
a) Room ACU Load :
6 - 1.5hp (FLC = 10A)
= 10 x 230 x 6 = 13,800VA
b) General Lighting Load (GLL) :
= 250m² x 24VA/m² = 6,000VA
c) Cooking Appliances Load :
2 – Wall Mounted Oven (WMO) @ 4kW each
4,000 x 2 = 8,000VA
1 – Electric Range @ 8kW = 8,000VA
-------------
16,000VA
Net Load : 16,000 x 55% D.F. = 8,800VA
See Table 2.20.3.16 (Column B)
1 – Microwave Oven (MWO) @1.5kW
= 1,500VA x 80% D.F. = 1,200VA
See Table 2.20.3.16 (Column A)
1 – Electric Range @ 12kW = 8,000VA
See Table 2.20.3.16 (Column C)
Total Net Cooking Appliances Load = 18,000VA
d) Other Loads :
4 – Small Appliance @ 1,500VA each = 6,000VA
1 – Laundry Circuit @ 1,500VA = 1,500VA
1 – Clothes Dryer @ 5kW = 5,000VA
4 – Shower Heater @2.5kW each =
10,000VA
1 – Water Pump @ 1.5hp (FLC = 10A)
= 10 X 230 (See Table 4.30.14.2) = 2,300VA
---------------
24,800VA
Apply Demand Factor See Section 2.20.3.23
= 24,800 x 0.40 ======= 9,920VA
Total Net Computed Load
= ACU load + GLL + Net Cooking Load + Net
Other Loads
= 13,800 + 6,000 + 18,000 + 9,920
= 47,720 VA
Service Entrance Conductor(SEC)
SEC = [1.25(2300) + 11,500 + 6,000 + 18,000 +
9,920] / 230 = 209.98A
Alternate Method :
SEC = [47,720 + .25(2300)]/230 = 209.98A
Use 100mm² THW Copper (220A)
Service Equipment (SE) :
SE = [2.50(2300) + 11,500 + 6,000 + 18,000
+ 9,920] / 230 = 222.48A
Alternate Method :
SE = [47,720 + 1.50(2300)]/230 = 222.48A
Use 200AT, 225AF, 2P, MCCB
Example 3 – One Family
Dwelling
Given : 240m² Floor Area, 5 – Room ACU 1.5hp,
3 – Small Appliance, 1 – Laundry Circuit, 2 –
WMO @ 4kW each, 1 – Electric Range 6kW, 1 –
12kW Electric Range, 2 – MWO 1.5kW, 1 –
Clothes Dryer @ 5kW, 3 – Shower Heater @
2.5kW each, 1 – Water Pump 1.0hp
Determine the Service Entrance Conductor &
Service Equipment
Solution :
a) ACU Load : ____11,500 VA____
b) GLL : ____ 5760 VA ___
c) Net Cooking Load : __17,950 VA___
d) Net Other Loads : ___8,136 VA____
e) Total Net Computed Load : _43,346 VA___
f) SEC calculated & THW Copper __190.96 A___
Use 100mm² THW Copper (220A)
g) SE calculated & Rating of the Main C. B.:
SE = 203.46 A
h) Size of RMC: 53 mm
End of the