VLF Training
VLF Training
VLF Training
USING
VERY LOW FREQUENCY (VLF)
AC TECHNOLOGY
Michael T. Peschel
High Voltage, Inc.
Copake, NY. USA
www.hvinc.com
06/28/24 1
This Can Be Prevented
06/28/24 4
VLF Explained
Xc = 1
2 x pi x f x C
The lower the frequency, the higher Xc (capacitive reactance).
The higher Xc (or resistance across the power supply output),
the lower the current/power needed to apply a desired voltage.
At 0.1 Hz, it takes 600 times less power to test a cable, or any other high
capacitance load, than at 60 Hz. At 0.01 Hz, 6000 times higher
capacitive loads can be tested than at 60 Hz.
06/28/24 5
60 Hz vs. 0.1 Hz
06/28/24 9
Won’t There Be Near Fault
Defects Left After Testing?
Very few if test is performed correctly.
Far less than when DC testing
Far less than if no testing is performed
At 3Vo for 30 minutes, >95% of defects will
clear. At 60 minutes nearly 100%
No better odds from any other method
06/28/24 10
XLPE Tree Growth Rate
Per IEEE 400-2001
06/28/24 12
North American Standards For
VLF Testing Of Cable
• IEEE 433-1974 covers VLF testing for rotating machinery.
• IEEE 400-2001 overall cable testing standard sanctions
VLF testing of cables.
• IEEE 400.2 sub-standard specific to VLF cable testing
06/28/24 13
IEEE P400.2/D3
Guide for Field Testing of
Shielded Power Cable Systems
Using Very Low Frequency (VLF)
Prepared by WG C18 of the
Insulated Conductors Committee of the
IEEE Power Engineering Society
06/28/24 14
IEEE VLF Std 400.2/D3 (11/03)
Recommends test voltage of 3V0
(V0 equals line-to-ground voltage).
Test duration is 15 – 60 minutes.
Recommendation is for 30 minutes. Most
defects are exposed in first 10 minutes, longer
testing is optional to expose minor cable faults.
06/28/24 15
Suggested IEEE Field Test Voltages
For Shielded Power Cable Systems
Using Sine Wave Output VLF
---------------------- 0.1 Hz Test Voltage --------------------
System Voltage Installation Acceptance Maintenance
phase to phase phase to ground phase to ground phase to ground
kVrms kVrms/kVpeak kVrms/kVpeak kVrms/kVpeak
Weight: 69 lbs/30 kg
06/28/24 18
VLF AC Hipot
Model VLF-4022CM
0 - 40 kV Peak
0.1 Hz @ 1.1 μf Load
0.05 Hz @ 2.2 μf Load
0.02 Hz @ 5.5 μf Load
Controls: 50 lbs/22 kg
HV Tank: 72 lbs/31 kg
06/28/24 19
VLF AC Hipot
Model VLF-6022CM
0 - 60 kV Peak
0.1 Hz @ 1.1 μf Load
0.05 Hz @ 2.2 μf Load
0.02 Hz @ 5.5 μf Load
Controls: 55 lbs/25 kg
HV Tank: 100 lbs/45 kg
06/28/24 20
VLF AC Hipot
Model VLF-12011CM
0 - 120 kV Peak
0.1 Hz @ .55 μf Load
0.05 Hz @ 1.1 μf Load
0.02 Hz @ 2.75 μf Load
0.01 Hz @ 5.5 μf Load
Weight: 565 lbs/257 kg
06/28/24 21
Other VLF Models
VLF-50CM 0 – 50 kV @ 50 μF @ 0.01Hz 0.1 – 0.01 Hz
Tests up to 50 kilometers of cable.
06/28/24 22
Cables Included
HV output
from tank 2 test leads for
Cable connectors capacitance
measurement
hook or clamp
06/28/24
Phase jumpers Interconnect Scope bnc 23
with grounds
VLF Hand Truck
06/28/24 24
VLF-4022CM
VLF-4022CM
06/28/24 25
06/28/24 26
How to VLF Test
VLF testing is easier than DC testing.
Isolate cable ends like with DC testing, although no
cleaning and bagging is necessary.
Connect VLF HV lead to conductor – ground to shield.
Apply HV to cable.
There are no leakage currents to read. Test is go/no-go
Wait the desired test time.
If cable holds, test is over. De-energize.
If cable fails, make repairs and repeat test, or replace.
Most models can test all three phases at once, saving time.
06/28/24 27
Operating
Instructions
1. Select Frequency
3. Rotate to zero
6. Rotate to
raise voltage
5. Press HV On
06/28/24 28
What is Cable Failure Indication?
06/28/24 29
Questions?
06/28/24 30
Thank You
Mike Peschel - High Voltage, Inc.
www.hvinc.com
06/28/24 31