Topics 5
Topics 5
PRESSURE
CONTROL
SYSTEMS
ME160P-2
Pressure Control
Systems
CONTINUE
Ingoude Company
On and Off
Example
on and off
In the example shown, an on/off pressure control system controls the solenoid
operated outlet valve. When the pressure exceeds the upper limit (150 kPa), the
valve will fully open. This allows fluid through the valve and decreases the fluid
pressure in the pipe When the pressure goes below the lower limit (130 kPa), the
valve will close. This will prevent any fluid from going hrough the valve as fluid
pressure in the pipe increases
www.reallygreatsite.com
On and Off
Advantages and Disadvantages
Continuous
Control
Controller Process
Controller Pressure
Valve Sensor
Ingoude Company
Valve Position
Oscillation
An on/off control system hat compares the desired pressure with
actual pressure can reach a state where the alve position rapidly
transitions between fully open and fully closed The figure shown
displays the rapid switching of a valve's position as the actual
pressure goes above and below the desired pressure. This rapid
switching can cause damage to a control valve.
DEAD BAND
To prevent he rapid switching
between on and off control valve
states, the controller compares the
actual pressure with an upper limit
value and a lower limit value as
illustrated in the figure. The difference
between the upper and lower limit is
called the dead band.
The dead band interval must be wide
enough to prevent rapid control valve
switching but still control the process
variable within acceptable limits.
The control valve fully open and fully
closed states are shown in the table.
Operation
Connections
Configuration
Configuration
Configuration
Configuration
Configuration
Configuration
Configuration
THE END.