Chapter 11 - Stability
Chapter 11 - Stability
• Generator failure
System State
x
© 2023 Daniel Kirschen
(state variable describing the system)
8
Stable System
Potential energy
Perturbation
Potential energy
Equilibrium state
x
© 2023 Daniel Kirschen 10
Unstable System
Potential energy
x
© 2023 Daniel Kirschen 11
Slow Evolution of a Stable System
Potential energy
New conditions
Original conditions
x
© 2023 Daniel Kirschen 12
Steady State Stability
Potential energy
Instability!
x
© 2023 Daniel Kirschen 13
Transient Stability
Potential energy
x
© 2023 Daniel Kirschen 14
Transient Stability
Potential energy How large a perturbation would be
Needed to make the system unstable?
Stability margin
Large
perturbation
x
© 2023 Daniel Kirschen 15
Steady state stability vs. transient stability
• Steady state stability is a function only • Transient stability depends not only
of the system and its state on the system and its state but also on
the size of the perturbation
• Any system is unstable if the
perturbation is sufficiently large…
• Must limit the analysis to “credible”
perturbations
𝑉𝐵
and
1
0.8
𝑉 𝐴 =𝑉 𝐴 ∠ 𝛿 𝑉 𝐵 =𝑉 𝐵 ∠ 0 °
0.6
𝐼
𝑃 + 𝑗𝑄
0.4
0.2
No solution for !
0
0 0.1 0.2 0.3 0.4 0.5 0.6
© 2023 Daniel Kirschen 𝑃 20
PV Curves – Lagging power factor load (
1.2
𝑉𝐵
and
1
pf = 1.0
0.8
𝑉 𝐴 =𝑉 𝐴 ∠ 𝛿 𝑉 𝐵 =𝑉 𝐵 ∠ 0 °
pf = 0.9 lag
0.6
𝐼
𝑃 + 𝑗𝑄
0.4
0.2
Voltage drops faster as
0
0 0.1 0.2 0.3 0.4 0.5 0.6
Maximum is smaller
© 2023 Daniel Kirschen 𝑃 21
PV Curves – Leading power factor load (
1.2
𝑉𝐵 pf = 0.9 lead
and
1
pf = 1.0
0.8
𝑉 𝐴 =𝑉 𝐴 ∠ 𝛿 𝑉 𝐵 =𝑉 𝐵 ∠ 0 °
pf = 0.9 lag
0.6
𝐼
𝑃 + 𝑗𝑄
0.4
• Maximum load that this system can deliver for load power factors of
1.0, 0.9 lag, and 0.9 lead?
Power factor
Unity 0 1.6667 0.7071
0.9 lag 1.0446 0.5901
0.9 lead 2.6591 0.9415
• of critical load
𝑉𝐵
Two lines
To avoid a system collapse if
One line one of the lines were to be
disconnected, the loading
must be less than the critical
value with only one line in
service
𝑉𝐵
A
Unity pf
100 MW
100 MW
A 100 MW
B
100 MW
100 MW
A 100 MW
B
150 MW
150 MW
A B
A B
• Will the disconnection of one of the lines overload the remaining ones?
• Need to perform a contingency analysis
• How does distributes itself among the remaining lines?
Source: UCTE
© Daniel Kirschen & University of Washington
Frequency in the three areas following the separation
Source: UCTE
© 2023 Daniel Kirschen 46
Electromechanical stability
• Commonly known as transient stability
• Interactions between the mechanical and electrical systems
• Mechanical system: rotating generators providing power
• Electrical system: export power from the generator to the loads
• These systems are coupled
• How does this electromechanical system respond to a fault?
𝑇𝑚 𝑇𝑒
Prime Mover Grid
𝜔𝑚
2
𝑑 𝜃𝑚
Newton’s law of motion : 𝐽 2
=𝑇 𝑚 − 𝑇 𝑒
𝑑𝑡
angular position of the rotor
moment of inertia of prime mover and generator
𝛿𝑚 ( 𝑡 )=𝜃𝑚 ( 𝑡 ) − 𝜃𝑚 , 𝑠𝑦𝑛 (𝑡 )
𝛿𝑚 ( 𝑡 )=𝜃𝑚 ( 𝑡 ) − 𝜔𝑚 , 𝑠𝑦𝑛 𝑡 − 𝜃 𝑚 ,0
𝑑 𝛿𝑚 𝑑 𝜃𝑚
= − 𝜔𝑚 , 𝑠𝑦𝑛
𝑑𝑡 𝑑𝑡
2 2
𝑑 𝛿𝑚 𝑑 𝜃𝑚
2
= 2
© 2023 Daniel Kirschen
𝑑𝑡 𝑑𝑡 51
Swing equation
~ ~
𝑃𝑚 𝑃𝑒
𝑇𝑚 𝑇𝑒
Prime Mover Grid
𝜔𝑚
2
𝑑 𝛿𝑚
𝐽 2
=𝑇𝑚 −𝑇 𝑒
𝑑𝑡
~
𝑃 𝑚 =𝜔 𝑚 𝑇 𝑚
~
𝑃 𝑒 = 𝜔𝑚 𝑇 𝑒
2
𝑑 𝛿𝑚 ~ ~
𝐽 𝜔𝑚 ( 𝑡 ) 2
=𝑃𝑚 − 𝑃𝑒
𝑑𝑡
© 2023 Daniel Kirschen 52
Swing equation
~ ~
𝑃𝑚 𝑃𝑒
𝑇𝑚 𝑇𝑒
Prime Mover Grid
𝜔𝑚
2
𝑑 𝛿𝑚 ~ ~
𝐽 𝜔𝑚 ( 𝑡 ) 2
=𝑃𝑚 − 𝑃𝑒
𝑑𝑡
2
𝐽 𝜔 𝑚 (𝑡 ) 𝑑 𝛿𝑚 : power in per unit
=𝑃 𝑚 − 𝑃 𝑒
𝑆𝑟𝑎𝑡𝑒𝑑 𝑑𝑡 2
: MVA rating of the generator
𝑃
𝜔 𝑠𝑦𝑛 = 𝜔𝑚 , 𝑠𝑦𝑛
2
𝑃
𝜔
Electrical ( 𝑡 )=
angles ( 𝑡 ) angles
𝜔 Mechanical
2 𝑚
𝑃
𝛿 ( 𝑡 )= 𝛿 (𝑡 )
2 𝑚
𝑃
𝛿 ( 𝑡 )= 𝛿 (𝑡 )
2 𝑚
2 𝐻 𝜔 ( 𝑡 ) 𝑑2 𝛿
2 2
=𝑃 𝑚 − 𝑃 𝑒
𝜔 𝑠𝑦𝑛 𝑑𝑡 2𝐻
2
𝑑 𝛿
𝜔 𝑝𝑢 ( 𝑡 ) 2 =𝑃 𝑚 − 𝑃 𝑒
𝜔 (𝑡 ) 𝜔 𝑠𝑦𝑛 𝑑𝑡
𝜔 𝑝𝑢 ( 𝑡 )=
𝜔 𝑠𝑦𝑛
𝑑𝛿
=𝜔 ( 𝑡 ) −𝜔 𝑠𝑦𝑛
2 𝑑𝑡
2𝐻 ( ) 𝑑 𝛿
𝜔 𝑝𝑢 𝑡 =𝑃 𝑚 − 𝑃 𝑒
𝜔 𝑠𝑦𝑛 𝑑𝑡
2
𝜔𝑠𝑦𝑛
𝑑𝜔
= ( 𝑃 𝑚− 𝑃 𝑒 )
𝑑𝑡 2 𝐻 𝜔 𝑝𝑢 ( 𝑡 )
𝑑𝜔 𝜔 𝑠𝑦𝑛
= 𝑃𝑚 with the initial condition
𝑑𝑡 2𝐻
𝜔 𝑠𝑦𝑛
𝜔 ( 𝑡 )= 𝑃𝑚 𝑡 + 𝜔 𝑠𝑦𝑛
2 𝐻 𝑑𝛿 𝜔 𝑠𝑦𝑛 𝜔 𝑠𝑦𝑛 2
=𝑃 𝑚 𝑡 𝛿 ( 𝑡 )= 𝑃 𝑚 𝑡 + 𝛿 ( 0)
𝑑𝛿 𝑑𝑡 2𝐻 4𝐻
=𝜔 ( 𝑡 ) −𝜔 𝑠𝑦𝑛
𝑑𝑡
is determined by the pre-fault
© 2023 Daniel Kirschen
loading of the generator 60
Example 11.6
How much would it require for a 60 Hz generator with an inertia constant operating at
rated power and a rotor angle to reach following such a fault?
60 Hz generator
Rated power
2
𝛿 ( 𝑡 )=31.42 𝑡 + 0.262𝑟𝑎𝑑 for
′ ′ ′
𝑋 < 𝑋 < 𝑋 𝑆
© 2023 Daniel Kirschen 64
Subtransient, transient and steady periods
2
2𝐻 𝑑 𝛿
𝜔 𝑝𝑢 ( 𝑡 ) =𝑃 𝑚 − 𝑃 𝑒
𝜔 𝑠𝑦𝑛 𝑑𝑡
2
Electrical power
𝑋
′
𝐼 𝑋
′
𝐸 =𝐸 ∠ 𝛿
′
𝑉𝑡 𝑉 ∞ =𝑉 ∞ ∠0°
©©2023
Daniel Kirschen
Daniel & University of Washington
Kirschen 70
Electric power in the one-machine vs. infinite bus model
𝑋
′
𝐼 𝑋
′
𝐸 =𝐸 ∠ 𝛿
′
𝑉𝑡 𝑉 ∞ =𝑉 ∞ ∠0°
′
𝐸 𝑉 ∞
𝑃𝑒 (𝛿)= ′
sin 𝛿
𝑋 +𝑋
©©2023
Daniel Kirschen
Daniel & University of Washington
Kirschen 71
Stable and unstable operating points
𝑃
𝑃 𝑒 (𝛿)
• Steady state:
S U
𝑃𝑚
• Operating point S at
0 𝛿0 90 𝛿𝑈 180
𝑃
𝑃 𝑒 (𝛿)
S1 U1
S 𝑃 𝑚 − 𝑃 𝑒 <0 𝑃 𝑚 − 𝑃 𝑒 <0 U
𝑃𝑚
𝑃 𝑚 − 𝑃 𝑒 >0 𝑃 𝑚 − 𝑃 𝑒 >0
S2 U2
0 𝛿0 90 𝛿𝑈 180
0 𝛿0 90 𝛿𝑈 180
0 90 180
𝑃
𝑃 𝑒 (𝛿)
𝑃𝑚 S U
0 𝛿0 90 𝛿𝑈 180
© 2023 Daniel Kirschen (degrees) 76
Example 11.7
A synchronous generator with a transient reactance delivers apparent power
at 0.95 pf lagging and nominal voltage.
Calculate the rotor angles corresponding to the stable and unstable operating points.
𝑃
𝑃 𝑒 (𝛿)
𝑃𝑚 S U Hence:
.
By symmetry:
0 𝛿0 90 𝛿𝑈 180
© 2023 Daniel Kirschen (degrees) 77
Simplest example of large disturbances
𝐺 ∞
𝐶𝐵 1 𝐶𝐵 2
• Generator injects power into the infinite bus through a single line of
reactance
• Bolted three-phase fault immediately to the right of
• Fault cleared by opening of
• Effect on the electromechanical dynamics of the generator?
• assumed constant
𝐶𝐵 1 𝐶𝐵 2
• Pre-fault conditions:
•
• Gives the initial value of for the differential equations
• Fault conditions:
• Post-fault conditions
A 𝑃 𝑒= 0 B
0 𝛿0 𝛿𝑐𝑙𝑒𝑎𝑟 90 𝛿𝑙𝑖𝑚 𝛿𝑈 180
𝑃 𝑒 (𝛿)
U Kinetic energy not exhausted before reaching
S
𝑃𝑚 the unstable operating point
Angle continues to increase instability
A 𝑃 𝑒= 0 B
0 𝛿0 𝛿𝑐𝑙𝑒𝑎𝑟 90 𝛿𝑈 180
• Marble is released
• Gravity causes the marble to accelerate
• Marble has exhausted its momentum before reaching top of the next hill
• Speed is zero
• Marble starts moving downwards because of gravity
• Marble still has some momentum when it reaches the top of the next hill
• Marble starts accelerating again
• Instability
A B
0 𝛿0 𝛿𝑐𝑙𝑒𝑎𝑟 90 𝛿𝑙𝑖𝑚 𝛿𝑈 180
(degrees)
© 2023 Daniel Kirschen 87
Equal area criterion
• Generator speeds up during the fault
It acquires kinetic energy during the fault
• Generator slows down after the fault is cleared
It injects this kinetic energy back into the system
• Can it return enough kinetic energy (i.e., slow down) before it reaches
the unstable equilibrium point?
• Develop a simple criteria
• Visualize the factors that influence stability
Kinetic energy
acquired during
the fault () 𝐴1
0 𝛿0 𝛿𝑐𝑙𝑒𝑎𝑟 90 𝛿𝑈 180
(degrees)
© 2023 Daniel Kirschen 92
System will remain stable if the generator
Stability criterion can return this kinetic energy to the grid
before reaching the unstable equilibrium
point U.
𝑃 Mathematically: .
𝑃 𝑒 (𝛿)
𝐴2
S U
𝑃𝑚
𝐴1
0 𝛿0 𝛿𝑐𝑙𝑒𝑎𝑟 90 𝛿𝑈 180
(degrees)
© 2023 Daniel Kirschen 93
Critical clearing angle
such that ?
𝑃
𝑃 𝑒 (𝛿)
𝐴2
S U
𝑃𝑚
𝐴1
0 𝛿0 𝛿 𝑐𝑟𝑖𝑡 90 𝛿𝑈 180
(degrees)
© 2023 Daniel Kirschen 94
Calculating the critical clearing angle
is such that:
𝑃
𝑃 𝑒 (𝛿)
𝐴2
S U
𝑃𝑚 Equivalent to:
𝐴1 𝐴3
0 𝛿0 𝛿 𝑐𝑟𝑖𝑡 90 𝛿𝑈
© 2023 Daniel Kirschen
(degrees) 180
95
Calculating the critical clearing angle
𝐶𝐵 1 𝐶𝐵 2
•
•
• for each line
•
𝐶𝐵 1 𝐶𝐵 2
• Before the fault, the generator injects power through one line of reactance
• During the fault, the generator injects no power at all
• After the fault, the generator injects power through the same line of reactance
• In other words, the system is back to its original state
• This is usually not the case
• Let us develop some more sophisticated examples
𝐺 ∞ ′
𝑝𝑜𝑠𝑡 𝐸 𝑉∞
Post-fault
𝑃 𝑒 ( 𝛿 )= ′
sin 𝛿
𝑋 +𝑋
𝐶𝐵 1 𝐶𝐵 2
𝑝𝑜𝑠𝑡
𝑃𝑒 ( 𝛿)
D E
𝐴2
A F U
𝑃𝑚
𝐴1
B C
0 𝛿0 𝛿1 𝛿𝑐𝑙𝑒𝑎𝑟 90 𝛿𝑙𝑖𝑚 𝛿𝑈 180
© 2023 Daniel Kirschen
(degrees) 100
Example 11.9
𝐺 ∞
𝐶𝐵 1 𝐶𝐵 2
•
•
• for each line
and
•
𝐶𝐵 1 𝐶𝐵 2
𝑋 𝑋
2 2
•
•
• for each line
•
𝐺 Pre-fault ∞ ′
𝐸 =1.2∠ 𝛿 𝑝. 𝑢. 𝑉 ∞ =1.0 ∠0° 𝑝. 𝑢.
𝑗 0.4 𝑝. 𝑢.
𝐶𝐵 1 𝐶𝐵 2
′
𝐸 =1.2∠ 𝛿 𝑝. 𝑢. 𝑗 0.2 𝑝 .𝑢. 𝑗 0.2 𝑝 .𝑢.
𝑉 ∞ =1.0 ∠0° 𝑝. 𝑢.
′
𝐸 =1.2∠ 𝛿 𝑝. 𝑢. 𝑉 𝑇𝐻 =0.333 ∠ 0°𝑝. 𝑢.
𝐺 Pre-fault ∞ ′
𝐸 =1.2∠ 𝛿 𝑝. 𝑢. 𝑉 ∞ =1.0 ∠0° 𝑝. 𝑢.
𝑗 0.4 𝑝. 𝑢.
𝐶𝐵 1 𝐶𝐵 2
𝑗 0.3 𝑝 .𝑢. 𝑗𝑋 𝑇𝐻 = 𝑗 0.133 𝑝 .𝑢 .
𝐺 Fault ∞ ′
𝐸 =1.2∠ 𝛿 𝑝. 𝑢. 𝑉 𝑇𝐻 =0.333 ∠ 0°𝑝. 𝑢.
𝐶𝐵 1 𝐶𝐵 2
𝑝𝑜𝑠𝑡
E 𝑃𝑒 ( 𝛿)
D
𝐴2
A F U
𝑃𝑚
𝐴1 C
𝑓𝑎𝑢𝑙𝑡
𝑃𝑒 ( 𝛿)
𝑝𝑜𝑠𝑡
E 𝑃𝑒 ( 𝛿)
D
𝐴2
A F U
𝑃𝑚
𝐴1 C
𝑓𝑎𝑢𝑙𝑡
𝑃𝑒 ( 𝛿)
Series compensation
𝑥 (𝑡 )?
• We want to calculate
𝑥0
0 𝑡
𝑥0
0 ∆𝑡 𝑡
𝑥2
𝑥1
𝑥0
•…
0 ∆ 𝑡 2∆𝑡 3 ∆𝑡 𝑡
𝑝𝑟𝑒 𝐸𝑉
Initial conditions: 𝜔 0 =𝜔 𝑠𝑦𝑛 𝑃 𝑒 = sin 𝛿0 =𝑃 𝑚
𝑋𝑆
© 2023 Daniel Kirschen 129
Numerical integration: pre-fault
Pre-fault conditions:
2
𝜔
𝜔 𝑘+1 =𝜔 𝑘 + [
𝑠𝑦𝑛
𝑃 𝑚 − 𝑃 𝑒 ( 𝛿𝑘 ) ] × ∆ 𝑡 𝜔 𝑘+1 =𝜔 𝑘=𝜔0 =𝜔 𝑠𝑦𝑛
2 𝐻 𝜔𝑘
¿0
𝛿𝑘+1=𝛿𝑘 + ( 𝜔 𝑘 − 𝜔 𝑠𝑦𝑛 ) × ∆ 𝑡 𝛿𝑘+1=𝛿𝑘=𝛿0
¿0
𝛿𝑘+1=𝛿𝑘 + ( 𝜔 𝑘 − 𝜔 𝑠𝑦𝑛 ) × ∆ 𝑡 Angle increases
¿0
𝛿𝑘+1=𝛿𝑘 + ( 𝜔 𝑘 − 𝜔 𝑠𝑦𝑛 ) × ∆ 𝑡 Angle increases until
and then decreases unless
exceeds
160
(degrees) Unstable
140 Re-acceleration beyond the
unstable operating point
120
Marginally stable
100 Fault cleared for the
marginally stable and
80
unstable cases
60
160
(degrees)
140 Unstable
120
100
Marginally stable
80
Fault
60 cleared
40
Onset of
20
the fault Stable
0
1
𝑗 𝑋1
• System with generators
′
𝐼1 • Each generator represented
𝐸 ∠ 𝛿1
1
by the classical model:
𝑗 𝑋2
′
• Constant voltage behind
2 transient reactance
′ 𝐼2 Transmission Network
𝐸 ∠ 𝛿2
2 and Loads
⋯
′
𝑗 𝑋𝑛
𝑛
′
𝐼𝑛
𝐸 ∠ 𝛿𝑛
𝑛
1
𝑗 𝑋1
• For each generator :
′
𝐼1 •
𝐸 ∠ 𝛿1
1
′
𝑗 𝑋2
2 first order differential
′ 𝐼2 Transmission Network equations
𝐸 ∠ 𝛿2
2 and Loads
• is a function not only of but of
⋯ the state of the entire system
′
𝑗 𝑋𝑛
𝑛
′
𝐼𝑛
𝐸 ∠ 𝛿𝑛
𝑛
′
𝑗 𝑋𝑖 𝑘
𝑖
′ 𝐼𝑖
𝐸 ∠ 𝛿𝑖
𝑖
1
𝑗 𝑋1
• Internal buses of generators
𝐼1 numbered to
′
𝐸 ∠ 𝛿1
1
• Other buses numbered to
2
𝑗 𝑋2
′
• Injected current only at internal
generator buses
′ 𝐼2 Transmission Network
𝐸 ∠ 𝛿2
2 and Loads
⋯
′
𝑗 𝑋𝑛
𝑛
′
𝐼𝑛
𝐸 ∠ 𝛿𝑛
𝑛
1
𝑗 𝑋1
Only interested in angles
′
𝐼1
𝐸 ∠ 𝛿1
1
′
𝑗 𝑋2
2
′ 𝐼2 Transmission Network
𝐸 ∠ 𝛿2
2 and Loads
⋯
′
𝑗 𝑋𝑛
𝑛
′
𝐼𝑛
𝐸 ∠ 𝛿𝑛
𝑛
1
𝑗 𝑋1
Only interested in angles
𝒀
′
𝐼1
𝐸 ∠ 𝛿1
1
′
𝑗 𝑋2
2
′ 𝐼2
𝐸 ∠ 𝛿2
2
⋯
′
𝑗 𝑋𝑛
𝑛
′
𝐼𝑛
𝐸 ∠ 𝛿𝑛
𝑛
• With:
•
𝐸′1 ∠ 𝛿1 𝐺1
′
𝑗 𝑋2 5
2 7
𝐸′2 ∠ 𝛿2 𝐺2 8 𝐿7
𝐿8
′
𝑗 𝑋3 6
3
𝐸′3 ∠ 𝛿3 𝐺3
80
𝛿3 − 𝛿1
60
40
𝛿2 − 𝛿1
20
-20
-40
0 0.5 1 1.5 2 2.5
𝛿3 − 𝛿1
120
80
40
𝛿2 − 𝛿1
-40
0 0.5 1 1.5 2 2.5
(degrees)
80
𝛿3 − 𝛿1
60
40
20
𝛿2 − 𝛿1
0
-20
-40
0 0.5 1 1.5 2 2.5
© 2023 Daniel Kirschen Time (s) 154
Detailed dynamic models
• We have used the classical generator model
• Constant emf behind transient reactance
• This model is simple but does not accurately reflect the dynamic
electrical behavior of generators
• Include differential equations to reflect the electrical dynamics of
generators
• Very large system of coupled differential equations