Shallow Foundation Design Report
Shallow Foundation Design Report
FOUNDATION DESIGN :
Design of Isolated Footing
SHALLOW FOUNDATION
Soil layer is suitable for supporting a structure at a relatively shallow depth.
If the soil conditions immediately below the structure are sufficiently strong and capable of
supporting the required load, then shallow spread footings can be used to transmit the load. On
the other hand, if the soil conditions are weak, then piles or piers are used to carry the loads
into deeper, more suitable soil.
Shallow foundations are foundations
where the depth of the footing is
generally less than the width (B) of
the footing. Deep foundations are
foundations where the depth of the
footing is greater than the width (B) of
the footing.
SHALLOW FOUNDATION
Design Considerations:
Must not settle excessively.
Must be placed at depth sufficient to prevent damage from surface environmental effects (frost,
swelling and shrinkage, erosion and scour).
Must not cause failure of supporting soil (Bearing Capacity criteria).
Advantages of using shallow foundation
Cost (affordable)
Construction Procedure (simple)
Materials (mostly concrete)
Labor (does not need expertise)
SHALLOW FOUNDATION
Disadvantages of using shallow foundation
Settlement
Irregular ground surface (slope, retaining wall)
Foundation subjected to pullout, torsion, moment.
DESIGN A SQUARE FOOTING
PROBLEM:
A reinforced concrete square column is supported by a square isolated footing (spread footing).
The footing is of plain concrete, and concentrically loaded. Design the footing in accordance
with the requirements of ACI 318M-08 and using the following available data:
Net allowable pressure, net = 150 kPa
Column loads (unfactored) : D = 150 kN ; L = 100 kN
Column diameter = 300mm
Column steel: 6-25mmØ bars with = 420 MPa ; = 200000 Mpa
Column concrete : = 28 MPa
Footing concrete : = 21 MPa
DESIGN A SQUARE FOOTING
SOLUTION:
Step 1: Find footing base dimensions (ACI Section 22.7.2).
The greatest combination of the given loads is
D + L = 150 kN + 100 kN = 250 kN
Footing base area = 1.67 sq.m.
The footing base area is square, hence B = L = = 1.29 m
Try square footing 1.30 m x 1.30 m, and check the net
DESIGN A SQUARE FOOTING
SOLUTION:
Net
Net 148 kPa < net (OK)
Use 1.30m x 1.30m square footing.
Step 2: Compute the design factored net load and factored net soil pressure
The set of factored load combinations are the following:
U = 1.4D = 1.4(150) = 210 kN
U = 1.4D + 1.6L = (1.2x150) + (1.6x100) = 340 kN
DESIGN A SQUARE FOOTING
SOLUTION:
The designed factored net load is the greater of the two values.
Use: D = 340 kN
Design factored net soil pressure = net
=201.2 kPa
Let Ø Vn = Vu
Therefore, vertical compression reinforcement or dowels through the supporting surface at the
interface is theoretically not required.
DESIGN A SQUARE FOOTING
(b) Base of the column. The allowable bearing strength of the column base at the interface is
Therefore, dowels through the column base at the interface are theoretically not required.
Step 5. Design dowels to satisfy the minimum area of reinforcement across interface
Using 75 mm minimum concrete cover (ACI Section 7.7.1) at each side, center to center bar
spacing will be 283 mm. Check concrete cover provided at each side:
DESIGN A SQUARE FOOTING
The center to center bar spacing of 283 mm also satisfies the maximum spacing requirement of
ACI Section 7.12.2.2.
Use five No. 16 bars @ 283 mm c.c. both ways, distributed near the top of the footing.
Step 8. Decide whether the footing should be sloped or stepped so that some economy may
be achieved.
With L = 2.8 m and B = 2.65 m, we get the maximum and minimum pressures as
1620(1.15)/(2.85)(2.70) 170(6)/(2.7)(2.85)(2.85) = 242.105 ± 46.51 = 288.615 kN/m 2 and
195.595 kN/m2, respectively (see figure).
Both the values are less than 300 kN/m2. Hence, o.k.
RECTANGULAR FOOTING
Step 2: Thickness of footing slab based on
one-way shear
The average soil pressure in the figure at the right is
{288.615 – (288.615 – 195.595)(1200 – d)/2850}
= 249.449 + 0.0326d.
The one-way shear force is
(2.7)(1.2 – 0.001d((249.449 + 0.0326d) kN.
RECTANGULAR FOOTING
Assuming 0.15 per cent reinforcement in the footing slab, the shear strength of M 25 concrete =
0.29 N/mm2. Hence, the shear strength of the section = 2700(d)(0.29)(103) kN. From the
condition that shear strength has to be shear force, we have
2700(d)(0.29)(10-3) = (2.7)(1.2 – 0.001d)(249.449 + 0.0326d)
Solving, we get d = 576.6198.
Let us assume d = 600 mm
Step 3: Checking for two-way shear
At the critical section of the figure, the shear resistance is obtained
τ = (0.5 + 450/300)(0.25)(25)1/2
RECTANGULAR FOOTING
But the multiplying factor (0.5 + 450/300) 1.0, so we have τ = 0.25(25) 1/2 = 1.25 N/mm2. Hence,
the shear resistance = (1.25)(2){(300 + 600) + (450 + 600)}(600) = 2925 kN.
Actual shear force is determined on the basis of average soil pressure at the center line of the
cross-section which is (195.595 + 288.615)/2 = 242.105 kN/m 2
The actual shear force = = (242.105){(2.7)(2.85) – (0.3 + 0.6)(0.45 + 0.6)}
=1634.209 kN < shear resistance (= 2925 kN).
Hence, the depth of the footing With effective depth = 600 mm, the total
is governed by one-way shear. depth of footing = 600 + 50 (cover) + 16
(bar dia) + 8 (half bar dia) = 674 mm.
RECTANGULAR FOOTING
Step 4: Gross bearing capacity
(i) Due to = 1620 kN: pressure = 1620/(2.7)(2.85) = 210.53 kN/m 2
(ii) Due to = 170 kNm: pressure = ± 170(6)/(2.7)(2.85)(2.85) = ±46.51 kN/m 2
(iii) Self weight of footing of depth 674 mm and soil of (1000 – 674) = 326 mm:
pressure = 0.674(25) + 0.326(18) = 22.718 kN/m2
Thus, the maximum and minimum pressures are = 210.53 + 22.718 ± 46.51
= 279.758 kN/m2 and 186.738 kN/m2 < 300 kN/m2. Hence, o.k.
RECTANGULAR FOOTING
Step 5: Bending moment
(i) In the long direction (along the length = 2850 mm)
Bending moment = 249.45(2.7)(1.2)(0.6) + (288.615 – 249.45)(2.7)(1.2)(2)/(2)(3) = 527.23 kNm.
M/Bd2 = 527.23(106)/(2700)(616)(616) = 0.515 N/mm2 < 3.45 N/mm2 for M 25 concrete.
Thus, Ast = 0.15(2700)(616)/100 = 2494.8 mm2.
Provide 13 bars of 16 mm diameter (area = 2613 mm2)
spacing = (2700 – 100 – 16)/12 = 215.33 mm, say 210 mm c/c.
RECTANGULAR FOOTING
(ii) In the short direction (B = 2700 mm)
The average pressure on soil between the edge and center of the footing = (288.615 + 242.105)/2 =
265.36 kN/m2.
Bending moment = (265.36)(1.2)(0.6)(2.85) kNm = 544.519 kNm
M/Ld2 = 544.519(106)/(2850)(600)(600) = 0.531
Area of steel = 0.15068(2850)(600)/100 = 2576.628 mm2.
Provide 13 bars of 16 mm diameter (area = 2613 mm2) @ 210 mm c/c
Step 6: Development length
Development length of 16 mm diameter bars (M 25 concrete) = 0.87(415)(16)/4(1.6)(1.4) = 644.73 mm.
Length available = 1200 – 50 – 8 = 1142 mm > 644.73 mm. Hence, o.k.
RECTANGULAR FOOTING
Step 7: Transfer of force at the base of the column
The required development length of 20 mm bars = 0.87(415)/4(1.4)(1.6) = 805.92 mm.
Length available = 600 mm < 805.92 mm.
The bars shall be given 90o bend and then shall be extended by 200 mm horizontally to give a
total length of 600 + 8(20) (bend value) + 200 = 960 mm > 805.92 mm
REFERENCES
318, A. C. (2014). Building Code Requirements. Farmington Hills, MI 48331: American Concrete
Institute.
Baban, T. M. (2016). Shallow Foundations Discussions and Problem Solving. West Sussex, P019
8SQ, United Kingdom: John Wiley and Sons, Ltd.