Lecture 18 Cooling Load
Lecture 18 Cooling Load
(ME 439)
Chapter 8
Cooling Load calculations
total cooling load on any building consists of both sensible as well as latent load components.
The sensible load affects dry bulb temperature, while the latent load affects the moisture
content of the conditioned space
1. Estimation of external loads:
All of the load calculations are based on the ASHRAE Handbook: Fundamentals
1. ROOF Since the ASHRAE tables provide hourly CLTD values for one
typical set of conditions i.e. outdoor maximum temperature of
The basic conduction equation for heat gain is q = U A ΔT 95°F with mean temperature of 85°F and daily range of 21°F,
q = Heat gain in Btu/hr the equation is further adjusted to apply correction factors for
U = Thermal Transmittance for roof in Btu/hr.ft².°F conditions other than the mentioned base case
A = area of roof in ft2
Q Roof = U * A * CLTD Roof Corrected
ΔT = Temperature difference in °F
Due to transient heat transfer, and thermal capacity of roof
material, there is decrement factor and time lag. The heat
gain is converted to cooling load using the cooling load
temperature difference
Q = U * A * (CLTD)
Example:
The wall has a 4" brick exterior, a 1" air gap, and 8" concrete
block wall. Calculate the overall U value of the walls
(Btu/hr/ft2/°F) based on the materials used and the standards
set forth in ASHRAE.
3. FENESTRATION
3. FENESTRATION
For the glass types used, select from ASHRAE tables the overall
heat transfer coefficient (U). Pay attention to effect of shading,
Solar load through glass has two components: reflective films, curtains, drapes etc
1) Conductive and 2) Solar Transmission
Select CLTD Glass for time of interest, typically on an hourly basis
The absorbed and then conductive portion of the (Chapter 28 ASHRAE Table 34)
radiation through the windows is treated like the
roof & walls where CLTD values for standard glazing Determine shading coefficient (SC) from ASHRAE 1997 Chapter 29,
are tabulated in ASHARE fundamentals handbook Table 11
The exfiltration rate is obtained by using either the air change method or the crack method
Q latent = N (QL)
1. Fluorescent lights
2. Incandescent lights
The ballast factor takes into account the load imposed by ballasts used in
fluorescent lights. A typical ballast factor value of 1.25 is taken for fluorescent
lights, while it is equal to 1.0 for incandescent lamps
3. POWER LOADS 4. APPLIANCES
In a cooling load estimate, heat gain from all appliances-
The industrial and commercial applications use various
electrical, gas, or steam-should be taken into account.
equipment such as fans, pumps, machine tools, elevators,
Because of the variety of appliances, applications,
escalators and other machinery, which add significantly to the
schedules, use, and installations, estimates can be very
heat gain.
subjective
3. Estimation of load on system:
cooling load on the coil due to sensible heat transfer of the
Ventilation ventilated air is given by:
Duct Loss and leakage
Supply fan heat load
1. VENTILATION
The latent heat load on the coil due to ventilation is given by:
One can also calculate the sensible heat factor for the coil (CSHF) and draw
the process line on the Psychrometric chart and find the required coil
Apparatus Dew Point Temperature (coil ADP) from the above data
Example 2. Zone Division
Estimate the cooling load of an office building located at 40° N latitude. Due to solar exposure and sun movement, the heat
The following data of building is gathered: gain through exterior walls (in perimetric areas) will
Number of floors: 1 be much higher than the interior zones. The central
Floor area: 64 ft x 80 ft = 5120 ft2 zone heat gain conduction through the walls are
Floor-to-floor Height: 15 ft zero due to ΔT=0
Window area: 20 % of the wall area
Windows: Double glazed
Wall: Wall number 13 [U= 0.2 Btu/h.ft2.F, as per table 33A*, pg 28.46
Roof: Roof number 13 [U= 0.2 Btu/h.ft2.F as per table 31, pg 28.42]
Windows: U= 0.55 Btu/h.ft2.F
Recommended ventilation: ½ air change per hour (min) or 20 cfm/person
Occupancy: 7 persons per 1000 sq-ft
Working: 8 hrs of working - 9.00 to 17.00 hrs
1. Design Conditions
Outdoor design dry-bulb: 90 °F
Outdoor design wet-bulb: 75 °F
Indoor design Dry-bulb: 78 °F
Daily Range: 20 °F
Relative humidity: 50%
Wind velocity: 7½ mph
ASSUMPTIONS
a. ROOF
b. Walls
Zone 5 is an internal
zone with NO solar
exposure. Therefore
heat load due to
conduction through the
walls for zone 5 is Zero.
b. Windows
VENTILATION
Ventilation load has two components
1) Sensible load and 2) Latent load
Sensible Heat
ZONE LOAD SUMMARY
The maximum load of the
building is found at 17.00
hours. The maximum space
loads which required for the
building are 224987 Btu/hr
sensible, 11080 Btu/hr latent.
Also the maximum total loads for the
building (included space and fresh air
loads) are 235067 Btu/hr “sensible”,
28880 Btu/hr “latent”.
End of Chapter 6 & 8
Assignment # 4
• Cooling load calculations
Upload on MS Team before Monday 8:00 am,
For each minute late submissions, 1% marks will be deducted