The document provides an overview of the BCI-C BACnet Communication Interface for chillers, including: - The BCI-C allows chillers to communicate over the BACnet protocol via its hardware and firmware. - It supports common BACnet objects, functions on the MS/TP network topology, and has default configuration settings. - Tools like the Tracer TU and BACnet Setup Tool are used to install and configure the BCI-C, including setting the MAC address, device ID, and other parameters. - Resources and documentation and available to support BCI-C installation, configuration, troubleshooting and use.

Uploaded by

crackerthief
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
79 views22 pages

BCI-C Tech Preso Oct1 2010

The document provides an overview of the BCI-C BACnet Communication Interface for chillers, including: - The BCI-C allows chillers to communicate over the BACnet protocol via its hardware and firmware. - It supports common BACnet objects, functions on the MS/TP network topology, and has default configuration settings. - Tools like the Tracer TU and BACnet Setup Tool are used to install and configure the BCI-C, including setting the MAC address, device ID, and other parameters. - Resources and documentation and available to support BCI-C installation, configuration, troubleshooting and use.

Uploaded by

crackerthief
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 22

BCI-C

Technology Transfer

02/15/24 © Trane.
Session - Agenda

• BCI-C Overview
• BACnet Overview
• Installing the BCI-C
• Resources Available
• FAQs

02/15/24
2 © Trane
What is the BCI-C?
• Hardware – UC400
• Software – BCI-C Firmware
• Service Tools – KestrelView, Tracer TU, BACnet Setup
Tool
– Tracer TU Available fromTracer TU page
– BACnet Setup Tool will be available at Technician’s page
UC400 (1 hardware platform, several applications)
- Programmable Applications
- VAV
- Communication Interface (BACnet)

02/15/24
3 © Trane
What is the BCI-C?

• BACnet Communication Interface for Chillers


– RTWD/RTUD release date: October 20th
– CGAM release date: October 20th
– RTHD release date: November 20th
– RTAC release date: November 20th
• Other CH530 based chillers
in the future

02/15/24
4 © Trane
BACnet Overview

• Open Protocol regulated by ASHRAE standard 135


• Typically communicated over IP or MSTP
– BCI-C uses BACnet MSTP
• Common Objects
– *Inputs (Analog/Binary/Multi-state)
– *Outputs (Analog/Binary/Multi-state)
– Values (Analog/Binary/Multi-state)

*Objects in BCI-C

02/15/24
5 © Trane
BACnet Addressing Terms
MAC Address vs. Device ID

MAC – Media Access Control


MAC Address Device ID
The controller’s address The controller’s address
on the MS/TP link on the BACnet network
• Set using the 3 rotary • Must be unique across
switches the entire BACnet
• Valid range: 1-120 network
• Rule: unique per link • Valid range: 1-4194302
• Best practice: start at
1, be sequential and
no gaps

02/15/24
6 © Trane
Set the BACnet MS/TP Address
of a Tracer UC400

• Set rotary switches to a valid address (1 - 120)


– Rule: Rotary address must be unique per BACnet MSTP link

MAC
Address

02/15/24
7 © Trane
Tools for Installation/Replacement

• 3.5 mm (1/8 inch) Flat Blade Screwdriver


• Tracer TU (Version 3.0 or higher) or BACnet Setup
Tool
• TechView (Version 12.1 SP2 or higher)
• CH530 MP Software (available with TV 12.1 SP2)
– RTWD/RTUD 6.30 or higher
– RTHD 12.0 or higher
– RTAC 37.0 or higher
– CGAM 2.00 or higher

02/15/24
8 © Trane
Installing the BCI-C
• Factory Installed
– Connect BACnet link to port labeled Link
– Connect Tracer TU or BACnet Setup Tool
– Set the following parameters by getting information
from your customer/integrator
 Controller name
 Baud rate
 Engineering units
 Device ID

02/15/24
9 © Trane
BCI-C replacement
1. Remove the old BCI-C
2. Snap the BCI-C on the DIN Rail
3. Connect the chiller bus to the IMC port
4. Connect the comm. link to port labeled “Link”
5. Set rotary addresses to the same as old controller
6. Connect Tracer TU or BACnet Setup Tool and set
 Controller name
 Baud rate
 Engineering units
 Device ID
7. Connect KestrelView
8. Bind BCI-C into CH530
9. Navigate to “Unit View”
10. Verify communication with BAS

02/15/24
10 © Trane
Tracer TU/BACnet Setup Tool
Configuration

• Connect
• Navigate to Controller Settings
• Set:
– Date/Time*
– Controller Name
– Units of Measure (VERY IMPORTANT)
– BAUD Rate
– BACnet Device ID

* Only available in Tracer TU

02/15/24
11 © Trane
Tracer TU

02/15/24
12 © Trane
BACnet Setup Tool

02/15/24
13 © Trane
TechView/KestrelView Configuration

• Connect
• Navigate to Configuration View, Options Tab
• Choose BACnet for BAS Interface
• Navigate to Binding View
– Select BACnet BCI-C
– When prompted push the SERVICE button on BCI-C
– Click OK

02/15/24
14 © Trane
BACnet MS/TP Link Rules

Trane BACnet Trane BACnet


60 Devices Max per Link
Terminator (TBT) Terminator (TBT)
Not Including System Controller

4000 Feet (1219 M)

BACnet Wiring Guide: BAS-SVN03A-EN

02/15/24
15 © Trane
BACnet MS/TP Link Rules
Shield Drain Wire

Maintain Polarity in Daisy Chain Connection


Use 18 AWG Shielded Twisted Pair
Shield Terminated Only at System Controller
Same Baud Rate on Each Controller

02/15/24
16 © Trane
The Trane BACnet Terminator (TBT)

• Provides end of line termination resistance


• Provides network biasing (per BACnet)
• Install one at each end of the link
24 VAC/VDC
BACnet MS/TP Power
Link

Trane BACnet
Terminator

TBT Installation Guide: X39641151-01B


02/15/24
17 © Trane
BCI-C BACnet Objects
• When the BCI-C is installed it interrogates the CH530
and creates all objects associated with the chiller
configuration
– Does not create an object if the option is not installed
– Does not require any programming of objects
• Object list is described in BAS-SVP05
– Integration Guide BACnet™ Communication Interface
for Chiller (BCI-C)
– Literature available in litweb chiller directory

02/15/24
18 © Trane
Alarming with BCI-C

• BI23 Alarm Present


– Notification Class: HVAC-Information
• BI24 Shutdown Alarm Present
– Notification Class: HVAC-Critical
• BI25 Last Diagnostic
– Indicates the last diagnostic in the Active Text

These points are always present. To use BACnet services for


alarm notification the 3rd party must subscribe to the notification
classes of the BCI-C

02/15/24
19 © Trane
Available Resources
• Literature available in litweb chiller directory:
– Integration Guide (objects list, PICS, etc…)
 BAS-SVP05
– Field Kit Installation Guide (step by step directions for replacement)
 RF-SVN02

• The following literature is available on BCI-C page on Trane.com


– Product Data Sheet
 BAS-PRC038
– Overnight Expert
– PICS (also included in BAS-SVP05)
 BAS-PRG007
– Applications Guide, Air Systems for Tracer SC
 BAS-APG007-EN - pages 144 through 149

02/15/24
20 © Trane
What to expect

• Units Conversion
– BCI-C defaults to SI units. Use the BACnet Setup Tool
to change engineering units.
• IP vs. MSTP
– If an IP connection is required we recommend the
PolarSoft Free Range Router
• Data List
– Described in BAS-SVP05
• Standard Link Troubleshooting Questions

02/15/24
21 © Trane
FAQs
• Existing Waves:
– Wave #44869 – How do I integrate BCI-C?
– Wave #4399 – Do we have BTL listing?
– Wave #44711 – Alarming with BCI-C
– Wave #49123 – How to troubleshoot BACnet links

• Answers available in knowledge center :


– Please click on the knowledge center link in this
webpage:
 https://home.ingerrand.com/Our%20Businesses/
ClimateSolutions/Pages/index.aspx
– Just copy paste one of the questions above in the
request area.

02/15/24
22 © Trane