CH 2 (Part 1)
CH 2 (Part 1)
The modern electric power system consists of several elements. e.g. alternators, transformers,
station bus-bars, transmission lines and other equipment.
It is desirable and necessary to protect each element from a variety of fault conditions which
may occur sooner or later.
The most serious faults on alternators which require immediate attention are the stator winding
faults.
The major faults on transformers occur due to short-circuits in the transformers or their
connections.
The basic system used for protection against these faults is the differential relay scheme
because the differential nature of measurements makes this system much more sensitive than
other protective systems.
Protection of Alternators (Generators)
A generator is the heart of an electrical power system, as it converts mechanical energy into
its electrical equivalent, which is further distributed at various voltages.
Fig.2.1
The generating units, especially the larger ones, are relatively few in number and
higher in individual cost than most other equipments.
(a)The modern tendency is to design alternators with very high values of internal
impedance so that they will stand a complete short-circuit at their terminals for sufficient
time without serious overheating. On the occurrence of an overload, the alternators can
be disconnected manually.
b) The disadvantage of using overload protection for alternators is that such a protection
might disconnect the alternators from the power plant bus on account of some momentary
troubles outside the plant and, therefore, interfere with the continuity of electric service.
(iv) Overspeed.
The chief cause of Overspeed is the sudden loss of all or the major part of load on the
alternator.
Modern alternators are usually provided with mechanical centrifugal devices mounted on
their driving shafts to trip the main valve of the prime-mover when a dangerous overspeed
occurs.
(v) Over-voltage.
The field excitation system of modern alternators is so designed that overvoltage
conditions at normal running speeds cannot occur.
The over-voltage during this time may reach a value which would over-stress the stator
windings and insulation breakdown may occur.
The over-voltage relays are operated from a voltage supply derived from the generator
terminals.
The relays are so arranged that when the generated voltage rises 20% above the normal value,
they operate to:
(a) Trip the main circuit breaker to disconnect the faulty alternator from the system
Fig. 2.2 shows the schematic arrangement for the protection of alternator against unbalanced
Under normal operating conditions, equal currents flow through the
different phases of the alternator and their algebraic sum is zero.
Therefore, the sum of the currents flowing in the secondaries is also zero
and no current flows through the operating coil of the relay.
The operation of the relay will trip the circuit breaker to disconnect the
alternator from the system
(vii) Stator winding faults.
• These faults occur mainly due to the insulation failure of the stator windings.
Under normal operating conditions, these currents are equal but may become unequal on
the occurrence of a fault in the protected section.
The difference of the currents under fault conditions is arranged to pass through the
operating coil of the relay.
The relay then closes its contacts to isolate protected section from the system. This form
of protection is also known as Merz-Price circulating currents scheme.
Fig. 2.3 shows the schematic arrangement of current differential protection for a 3-phase
alternator.
Operation:
Under normal operating conditions, the current at both ends of each winding will be
equal and hence the currents in the secondaries of two CTs connected in any phase
will also be equal.
Therefore, there is balanced circulating current in the pilot wires and no current flows
through the operating coils (R1,R2 and R3)of the relays.
The circuit for alternator protection shown above has its own limitations.
It is a general practice to use neutral earthing resistance in order to limit the destructive
effects of earth-fault currents.
When an earth-fault occurs near the neutral point, there may be insufficient voltage
across the short-circuited portion to drive the necessary current round the fault circuit
to operate the relay. The magnitude of unprotected zone depends upon the value of
earthing resistance and relay setting.
Modified Differential Protection for Alternators
If the neutral point of a star-connected alternator is earthed through a high resistance,
protection schemes shown in Fig. 2.3 will not provide sufficient sensitivity for earth-
faults.
It is because the high earthing resistance will limit the earth-fault currents to a low
value, necessitating relays with low current settings if adequate portion of the generator
winding is to be protected.
However, too low a relay setting is undesirable for reliable stability on heavy through
phase-faults.
In order to overcome this difficulty, a modified form of differential protection is used in
which the setting of earth faults is reduced without impairing stability.
The modified arrangement is shown in Fig. 2.4. The modifications affect only the relay
connections and consist in connecting two relays for phase-fault protection and the third
for earth-fault protection only.
The two phase elements (PC and PA) and balancing resistance (BR) are connected in star
and the earth relay (ER) is connected between this star point and the fourth wire of
circulating current pilot-circuit.
Fig.2.4 Modified Deferential Protection Alternators
Operation.
Under normal operating conditions, currents at the two ends of each stator winding will
be equal. Therefore, there is a balanced circulating current in the phase pilot wires and no
current flows through the operating coils of the relays. Consequently, the relays remain
inoperative.
If an earth-fault occurs on any one phase, the out-of-balance secondary current in CTs in
that phase will flow through the earth relay ER and via pilot S or S to the neutral of the
1 2
current transformers. This will cause the operation of earth relay only.
If a fault occurs between two phases, the out of-balance current will circulate round the
two transformer secondaries via any two of the coils PA, BR, PC (the pair being decided
by the two phases that are faulty) without passing through the earth relay ER. Therefore,
only the phase-fault relays will operate.
Balanced Earth-fault Protection
In small-size alternators, the neutral ends of the three-phase windings are often
connected internally to a single terminal.
• Under normal operating conditions, the currents flowing in the alternator leads and hence the
currents flowing in secondaries of the line current transformers add to zero and no current
flows through the relay.
• Also under these conditions, the current in the neutral wire is zero and the secondary of neutral
current transformer supplies no current to the relay.
• If an earth-fault develops at F external to the protected zone, the sum of the currents at the
2
terminals of the alternator is exactly equal to the current in the neutral connection and hence no
current flows through the relay.
• When an earth-fault occurs at F or within the protected zone, these currents are no longer equal
1
and the differential current flows through the operating coil of the relay. The relay then closes
its contacts to disconnect the alternator from the system.
Stator Inter-turn Protection
It is because the current that this type of fault produces flows in a local circuit between the turns
involved and does not create a difference between the currents entering and leaving the winding
at its two ends where current transformers are applied.
However, it is usually considered unnecessary to provide protection for inter-turn faults because
they invariably develop into earth-faults.
In single turn generator (e.g. large steam-turbine generators), there is no necessity of protection
against inter-turn faults. However, inter-turn protection is provided for multi-turn generators such
as hydro-electric generators. These generators have double-winding armatures (i.e. each phase
winding is divided into two halves) owing to the very heavy currents which they have to carry.
The relays R provide protection against phase-to-ground
C