Profinet HW Config1 v1
Profinet HW Config1 v1
PROFInet
IE/PB Link
PROFINET IO DEVICES
University of Ruse 1
Configuration of a PROFINET IO System
PROFINET IO Communication Model
PROFINET IO SUPERVISORS Network
Visualization and Engineering Management
Parameterization Web Application
Commissioning,
Diagnostics
Diagnosis,
TCP/IP on Upload/Download
Ethernet PROFINET I/O Controller
Application program with access to
process signals via process image Parameterization,
Ethernet Configuration, Diagnosis
Cyclic data Production
Exchande IR data,
T Alarms
PROXY
PROFIBUS
PROFINET IO DEVICES
Read and write
IO data
University of Ruse 2
Configuration of a PROFINET IO System
PROFINET IO Device Model
SUBSLOT 1 = Channel 1
SUBSLOT 1 = Channel 1
SUBSLOT 1 = Channel 1
SUBSLOT 1 = Channel 1
sub slot.
Bus-Interface
Each sub slot can contain I/O data
(DAP)
or alarms.
Ethernet
3
PROFINET IO
DEVICE
1 GSD import net configuration in the Engineering Tool
2 The configuration is carried out in the engineering system (for example STEP 7).
The configuration and the user program are then transferred to the IO controller.
Once you have assigned device names to the IO devices, the data is exchanged
3 between the IO controller and assigned to IO devices automatically .
University of Ruse 4
Configuration of a PROFINET IO System
Addressing of a PROFINET IO DEVICE
University of Ruse 5
Configuration of a PROFINET IO System
Structure of IP addresses
Length = 6 bytes
Representation = hexadecimal
Example: 00-0E-8C-XX-XX-
XX Siemens Serial No
University of Ruse 7
Configuration of a PROFINET IO System
Address Assignment with DCP (Discovery and Configuration Protocol)
PROFINET IO
CONTROLER 2
3 Ethernet
MAC Addr 2
Start up
IO Controller
assigns IP-Address MAC Addr 1
to the device
University of Ruse 8
Configuration of a PROFINET IO System
Address assignment
C-PLUG
contain the
Device name
transfer the device data
from the PC/PC directly
192.168.100.3 to the MMC
University of Ruse 9
Configuration of a PROFINET IO System
Basic steps from planning to operating a plant
University of Ruse 10
Configuration of a PROFINET IO System
Configuring the system with STEP 7 - SCENARIO
From Creating the Project to Starting Hardware configuration Tool
Hardware Catalog and Insert new GSD File
Configuring PROFINET IO Controller
Integrating the Industrial switch (SCALANCE X208) into the PROFINET IO system
Integrating the ET200S into the PROFINET IO system
Integrating Non SIEMENS PROFINET IO Devices
Network transition: IE/PB - Link PN IO
Hardware configuration
•Rack, Slots, Electronic Modules • Insert GSD files in Hardware catalog
•Addressing S7-300™ Modules • Insert the IO Devices from: PROFINET IO ->
Configuring the PROFINET interface Additional Field Devices and Insert the necessary
•Assign parameter to PN Interface components in the configuration table
• components in the configuration table
•Assigning Device name and IP • Adjust the IP address and the device name.
Address • Set IO Cycle parameters
•Configuring Alarms • Adjust Parameter tab
•Configuring Media redundancy •Insert Device from Hardware catalog
tab •Properties of PROFIBUS DP Interface
•Prioritizing startup •Properties of PROFINET IO
•Hardware
Configuring the topology Rack, Slots, Electronic
configuration Interface
Modules •Integration of DP slaves
Assigning a device name to the IO device ET 200S PN
Configuring the PROFINET interface
•Synchronization tab
•IO Cycle Tab
•Prioritized startup
•Setting up the communication ports 11
University of Ruse Configuration of a PROFINET IO System
From Creating the Project to Starting Hardware Configuration Tool
1 generate a new project
2 Insert Station
project name
storage location
University of Ruse 12
Configuration of a PROFINET IO System
Hardware Catalog and Insert new GSD File
Hardware
Catalog Window
University of Ruse 13
Configuration of a PROFINET IO System
Configuring the PROFINET IO Controller
1. Rack, Slots, Electronic Modules
Hardware catalog
plain list
Slot 1 Power Supply
Slot 3 Reserved
detailed view
University of Ruse 14
Configuration of a PROFINET IO System
Configuring the PROFINET IO Controller
2. Addressing S7-300™ Modules
Slot No. 1 2 4 5 6 7 8 9 10 11
Modules PS CPU SM SM SM SM SM SM SM SM
Address 0.0
Address 0.7
Address 1.0
Address 1.7
University of Ruse 15
Configuration of a PROFINET IO System
Configuring the PROFINET IO Controller
3. Configuration of the PROFINET interface
1
2
University of Ruse 16
Configuration of a PROFINET IO System
Configuring the PROFINET IO Controller
4. Assign parameter to PN Interface
University of Ruse 17
Configuration of a PROFINET IO System
Integrating the SCALANCE X208 into the PROFINET IO system
1. Insert Device from Hardware catalog
University of Ruse 18
Configuration of a PROFINET IO System
Integrating the SCALANCE X208 into the PROFINET IO system
2. Assign Device name and IP Address
University of Ruse 19
Configuration of a PROFINET IO System
Integrating the SCALANCE X208 into the PROFINET IO system
3. Configuring Alarms
System default
University of Ruse 20
Configuration of a PROFINET IO System
Integrating the SCALANCE X208 into the PROFINET IO system
4. Configuring Media redundancy tab
1
mrpdomain-1
Open dialog box
3 default-mrpdomain
University of Ruse 21
Configuration of a PROFINET IO System
Integrating the SCALANCE X208 into the PROFINET IO system
4. Configuring Media redundancy tab - Continued
1
mrpdomain-1
Open dialog box
3 default-mrpdomain
To ensure problem-free operation when using a third-party device as the redundancy manager in the ring , make
sure that you assign the fixed role of "Redundancy client" to all other devices in the ring, before you close the ring.
Otherwise, there may be circulating data frames that will cause a failure in the network.
If you reset to the factory settings, the ring port settings are also reset. With the appropriate attachment, a ring node
that was previously correctly configured can cause circulating frames and loss of the data traffic.
If you reset to the factory settings, the MRP role of the device is also reset. If you are operating a third-party device
as the redundancy manager in the ring, this may cause loss of the data traffic.
University of Ruse 22
Configuration of a PROFINET IO System
Integrating the SCALANCE X208 into the PROFINET IO system
5. Prioritized startup
1
Open dialog box
University of Ruse 23
Configuration of a PROFINET IO System
Integrating the SCALANCE X208 into the PROFINET IO system
5. Configuring the topology
1
Open dialog box
Only for fiber-optic cable
University of Ruse 24
Configuration of a PROFINET IO System
Integrating the SCALANCE X208 into the PROFINET IO system
5. Configuring the topology - Continued
2 3
1
Open dialog box
Ensure that the setting for the local port and the partner port are identical.
University of Ruse 25
Configuration of a PROFINET IO System
Integrating the ET200S into the PROFINET IO system
1. Insert Device from Hardware catalog. Rack, Slots, Electronic Modules
Select IO
Device
1
Power Module
Output addresses,
band model
Input addresses,
band model Select IO
Modules
2
University of Ruse 26
Configuration of a PROFINET IO System
Integrating the ET200S into the PROFINET IO system
2. Assigning a device name to the IO device ET 200S PN (Offline).
Double Click
University of Ruse 27
Configuration of a PROFINET IO System
Integrating the ET200S into the PROFINET IO system
3. Assigning properties to PROFINET Interface.
University of Ruse 28
Configuration of a PROFINET IO System
Integrating the ET200S into the PROFINET IO system
1 2
University of Ruse 29
Configuration of a PROFINET IO System
Integrating the ET200S into the PROFINET IO system
Double Click
1 2
Maximum watchdog
time: 1.92 seconds.
University of Ruse 30
Configuration of a PROFINET IO System
Integrating the ET200S into the PROFINET IO system
Double Click
1
2 3
University of Ruse 31
Configuration of a PROFINET IO System
Integrating the ET200S into the PROFINET IO system
3.4. Setting up the communication ports
This section
shows the
name of the
local port.
University of Ruse 32
Configuration of a PROFINET IO System
Integrating the ET200S into the PROFINET IO system
3.5. Setting up the communication ports/ Disable autonegotation
Autonegotiation - operating
parameters of the connected
network are detected and the
data transmission speed and
transmission mode are
optimally set.
University of Ruse 33
Configuration of a PROFINET IO System
Integrating Non SIEMENS PROFINET IO Devices
Insert GSD files in Hardware catalog (slide 12)
Insert the IO Devices form PROFINET IO -> Additional Field Devices (slide 25)
Insert the necessary components in the configuration table (slide 25)
Adjust the IP address and the device name. (slide 26)
Set IO Cycle parameters (see slide 29)
Adjust Parameter tab
University of Ruse 34
Configuration of a PROFINET IO System
Integrating Non SIEMENS PROFINET IO Devices
Insert GSD files in Hardware catalog (slide 12)
Insert the IO Devices form PROFINET IO -> Additional Field Devices See (slide 25)
Insert the necessary components in the configuration table (slide 25)
Adjusting the IP address and the device name. (slide 26)
Set IO Cycle parameters (slide 29)
Adjust Parameter tab
Example refers to
WAGO System
750/753
University of Ruse 35
Configuration of a PROFINET IO System
Integrating Non SIEMENS PROFINET IO Devices
Insert GSD files in Hardware catalog (slide 12)
Insert the IO Devices form PROFINET IO -> Additional Field Devices See (slide 25)
Insert the necessary components in the configuration table (slide 25)
Adjust the IP address and the device name. (slide 26)
Set IO Cycle parameters (slide 29)
Adjust Parameter tab
Example refers to
WAGO System
750/753
University of Ruse 36
Configuration of a PROFINET IO System
Network transition: IE/PB - Link PN IO
The C-PLUG may
only be inserted or
removed when the
power is off. A
screwdriver can be
used as an aid.
University of Ruse 37
Configuration of a PROFINET IO System
Integration of IE/PB Link PN IO
1. Insert Device from Hardware catalog
University of Ruse 38
Configuration of a PROFINET IO System
Integration of IE/PB Link PN IO
2. Properties of PROFIBUS DP
University of Ruse 39
Configuration of a PROFINET IO System
Integration of IE/PB Link PN IO
2. Properties of PROFONET IO Interface
the highest
unassigned
number
University of Ruse 40
Configuration of a PROFINET IO System
Integration of IE/PB Link PN IO
3. Integration of DP slaves. Rack, Slots, Electronic Modules
University of Ruse 41
Configuration of a PROFINET IO System
PROFINET IO COMMISSIONING
University of Ruse 42
Configuration of a PROFINET IO System
Switching the PG interface on the network card from the "Ethernet" type
University of Ruse 43
Configuration of a PROFINET IO System
Assigning an IP address for PG/PC
3
4
2
University of Ruse 44
Configuration of a PROFINET IO System
Assigning an IP address for PG/PC - Test for real connections
Accessible
Nodes Button
University of Ruse 45
Configuration of a PROFINET IO System
Assign IP address to the IO controller
Select the IO
Controller CPU
University of Ruse 46
Configuration of a PROFINET IO System
Assign IP address to the IO controller
Result: IO controller is
Insert IP assigned a name and
Address and IP address
Subnet mask
Confirm
address
Insert IP
Controller name
and Confirm with
button
University of Ruse 47
Configuration of a PROFINET IO System
Assign Device Name
2
3
University of Ruse 48
Configuration of a PROFINET IO System
Download Project into PROFINET IO Controller
University of Ruse 49
Configuration of a PROFINET IO System
Switch the IO controller from STOP to RUN
There are two types of LED displays on SIMATIC S7 PROFINET IO devices:
• General status and error displays
• Status displays for the communication interfaces
PHOENIX CONTACT
FL-IL-BK-PAC
Please see the manufacturer
SF UL documentation for the detailed
BF UM
COL US functions of the PROFINET
XMT node displays.
RCV
LNC
University of Ruse 50
Configuration of a PROFINET IO System
Exercise
Task: Create PROFINET IO project with the configuration shown
Industrial Ethernet: Ethernet(1) contains
the following network connections:
University of Ruse 51
Configuration of a PROFINET IO System
Exercise
Task: Use the built-in electronic module models for the individual
configuration of PROFINET devices.
University of Ruse 53
Configuration of a PROFINET IO System
Reference
1. Mackay S., Edwin Wright, Deon Reynders, John Park, Practical Industrial Data Networks:
Design, Installation and Troubleshooting, Elsevier 2004, ISBN 07506 5807X
2. Pigan Raimond, Mark Metter, Automating with PROFINET. Industrial Communication based on
Industrial Ethernet, SIEMENS 2006, ISBN 3-89578-256-4
3. Configuration and Diagnostics of a PROFINET IO System, PROFINET IO Configuration
Example, Application Description, SIEMENS 01/2010
4. FL IL 24 BK-PN-PAC PROFINET IO/Inline Bus Coupler, Data Sheet, PHOENIX CONTACT
07/2005.
5. Hardware and Firmware User Manual for the FL IL 24 BK / FL IL 24 BK-PAC Ethernet/Inline Bus
Coupler, Revision: 05, Order No.:90 14 20 5 PHOENIX CONTACT, 09/2004.
6. SIMATIC PROFINET System Description, System Manual, A5E00298288-04, 06/2008
7. SIMATIC Configuring Hardware and Communication Connections with STEP 7, Manual,
A5E00706939-01, SIEMENS Edition 03/2006.
8. SIMATIC NET Industrial Ethernet Switches SCALANCE X-200 / XF-200. Operating Instructions,
A5E00349864-14, SIEMENS, 03/2009.
9. SIMATIC ET 200S distributed I/O Interface module IM151-3 PN HIGH FEATURE (6ES7151-
3BA23-0AB0), Manual, A5E01584258-04, SIEMENS 08/2010
10. WAGO IO SYSTEM 750, Using the WAGO 750 -340 PROFINET Coupler as Remote I/O with a
Siemens S7 PLC, Application note A115400
11. PROFINET Technology and Application – System description
http://www.profibus.com/nc/download/technical-descriptions-books/
University of Ruse 54
Configuration of a PROFINET IO System