PSG Module II
PSG Module II
Electromagnetic Relays
Protective Relays
• It is an electrical device connected between the main circuit and the
circuit breaker that detects the fault and initiate the operation of
the circuit breaker to isolate the defective section from the rest of
the system.
• Operating time
It is the time between the moment the actuating quantity attains equal
value to the pick-up and the instant at which the relay operates its
contacts.
• Over Reach
A relay is said to over reach when it operates at a current which is lower
than its setting.
Terms Related to Relays
• Under Reach
A relay is said to under reach when it opens the trip coil at a current which is
higher than its setting.
• Plug Setting Multiplier (P.S.M)
Numerical
Application
relays
Relays
Digital Time of
relays operation
Static
relays
• Electromagnetic relays
Constr • Induction relays
uction • Electro thermal relays
& • Physico – electric relays
Princip •
le of
Electro – dynamic relays
Operat
ion
• Under voltage/current, Over voltage/current relays
• Directional relays
Appli • Differential relays
catio • Distance relays
n
• Instantaneous relays
• Definite time lag relays
Time
• Inverse time lag relays
of
oper • Inverse definite minimum time lag relays
ation
Non Directional Overcurrent Relay
Non Directional Overcurrent Relay
Inside of an Overcurrent Relay
Necessity of Directional Relays
• Consider a radial system fed at both ends.
• If only one relay is installed, then fault current may be supplied from
the other source.
• Hence, relays are also installed at other end of line to detect fault and
disconnect transmission line from the other end as well.
Necessity of Directional Relays
• Additional discrimination feature is to be provided to distinguish
between faults that it should respond to, and others that it should not
respond to.
• The relays in which the operation is based on the ratio of applied voltage to
the current in the protected circuit are called impedance relays.
• This type of relay operates whenever the impedance (V/I) of the protected
zone falls below a predetermined value.
Impedance Relays
Impedance Relays
• Torque produced by voltage element is α K1.V2
• Now the relay will operate when the torque T is positive. i.e. when,
Operating Characteristics of Mho relay
Reactance Relays
• A reactance relay is similar to an overcurrent relay. It does not have
directional feature in it.
• It measures the reactance of the line at the relay location.
• Hence the performance of the relay will not be affected by variations
in impedance of the line due to arcing ground.
• Whenever a fault occurs in the line, the measured reactance will be
less than that of the preset reactance and hence the relay operates.
Operation of Reactance Relays
• Torque produced on the relay,
• It is based on the fact that any internal fault in an electrical equipment would
cause the current entering it to be different from the current leaving it.
CTs may not have identical secondary currents due to their constructional
errors.
During heavy external fault, the fault current may saturate the CTs and
cause unequal secondary currents.
Percentage or Biased Differential Relay
• Ampere Turns on the left side of the
restraining coil
• For the operation of the relay, the differential current must be greater than
this fixed percentage of the restraining current. Hence this relay is called
percentage differential relay.
• Under normal condition or through fault condition, the restraining toque
will be more than the operating torque. Hence the relay is inoperative.
• During any internal fault condition, the operating torque will be more than
the restraining torque. Hence relay will operate.
Percentage or Biased Differential Relay
Balanced Voltage Differential protection
Normal condition & External Fault
Balanced Voltage Differential protection
Internal Fault
Negative Sequence Relays
• Negative sequence relays are generally used to give protection to
generators and motors against unbalanced currents.
𝐼𝑅
𝐼 𝑍 1=𝐼 𝑍 3=
√3
300
600 300
IZ3
• Currents from B phase divide into two equal components IZ2 and IZ4 at
point C. IZ2 leads IZ4 by 600.
Relay Operation for Positive sequence current
-IY
IB IZ4 IZ1 IR
300 300
300 300
IZ2 IZ3
IY
Relay Operation for Negative sequence current
IY
• From phasor diagram, it is clear that,
• Hence the relay will operate and trip the circuit breaker for the
flow of negative sequence current.
IZ4 IZ1
IB IZ2 IZ3 IR