Lectures 3 6
Lectures 3 6
2
Introduction
The simplified diagram is called the single-line diagram
or one-line diagram.
The one-line diagram summarizes the relevant
information about the system for the particular problem
studied.
For example, relays and circuit breakers are not
important when dealing with a normal state problem.
However, when fault conditions are considered, the
location of relays and circuit breakers is important and
is thus included in the single-line diagram.
3
Introduction
The International Electrotechnical Commission
(IEC), the American National Standards Institute
(ANSI), and the Institute of Electrical and
Electronics Engineers (IEEE) have published a
set of standard symbols for electrical diagrams.
The main component of a one-line (or single line)
diagram are : Buses, Branches, Loads, Machines,
2 winding Transformers, Switched Shunts, Reactor
and Capacitor Banks.
4
One Line Diagram -
Symbols two-winding
transformer
current transformer
two-winding
voltage transformer
transformer
generator capacitor
G1 T1 T2
G3
G2 Load B
Load A
6
Impedance and Reactance Diagrams
The impedance (Z = R + jX) diagram is converted
from one-line diagram showing the equivalent
circuit of each component of the system.
It is needed in order to calculate the performance of
a system under load conditions (Load flow studies)
or upon the occurrence of a short circuit (fault
analysis studies).
7
Impedance and Reactance Diagrams
1 T1 T2 3
2 Load B
Load A
E1 E2 E3
9
Impedance and Reactance Diagrams
Reactance (jX) diagram is further simplified
from impedance diagram by omitting
🞑 all static loads,
🞑 all resistances,
🞑 the magnetizing current of each transformer, and
🞑 the capacitance of the transmission line.
E1 E2 E3
and 2 T1 Line T2
3
11
Impedance and Reactance Diagrams
Y Y
Y
Y Y
12
Impedance and Reactance Diagrams
Q2, Convert the one line diagram s h o w n b e l o w into
the impedance diagram?
Impedance diagram
14
Impedance and Reactance Diagrams
Reactance diagram
15
Per Unit
System
In power systems large amounts of power being
transmitted in the range of kilowatts to
megawatts, at different voltage levels.
As a result, in analysis, it is useful to scale, or
normalize quantities with large physical values
and this is commonly called per unit system in
power system analysis.
16
Per Unit
System
The per unit system is widely used in the power
system industry to express values of voltages,
currents, powers, and impedances of various
power equipment.
It is mainly used for transformers and AC
machines
Per unit system used extensively along with one-
line diagram to further simplify the process.
17
Advantages of P.U.
system
Transformer equivalent circuit can be simplified
by properly specifying base quantities.
🞑 Give a clear idea of relative magnitudes of various
quantities such as voltage, current, power and
impedance.
🞑 Avoid possibility of making serious calculation error
when referring quantities from one side of
transformer to the other.
18
Advantages of P.U. system
Per-unit impedances of electrical equipment of similar type
usually lie within a narrow numerical range when the
equipment ratings are used as base values.
🞑 Manufacturers usually specify the impedances of
machines and transformers in per-unit or percent in
nameplate rating.
The circuit laws are valid in per unit systems, and the power
and voltage equation are simplified since the factor √3 and 3
are eliminates in the per-unit systems.
Ideal for the computerized analysis and simulation of
complex power system problems.
19
Advantages
Why Use the Per Unit System Instead of
the Standard SI Units?
Here are the main reasons for using the per unit
system:
When values are expressed in pu, the comparison of
electrical quantities with their "normal" values is
straightforward.
For example, a transient voltage reaching a
maximum of 1.42 pu indicates immediately that
this voltage exceeds the nominal value by 42%.
20
Advantages
The values of impedances expressed in pu stay fairly
constant whatever the power and voltage ratings.
For example, for all transformers in the 3 kVA to 300
kVA power range, the leakage reactance varies
approximately between 0.01 pu and 0.03 pu, whereas
the winding resistances vary between 0.01 pu and
0.005 pu, whatever the nominal voltage. For
transformers in the 300 kVA to 300 MVA range, the
leakage reactance varies approximately between 0.03 pu
and 0.12 pu, whereas the winding resistances vary
between 0.005 pu and 0.002 pu.
21
Advantages
Similarly, for salient pole synchronous machines,
the synchronous reactance Xd is generally
between
0.60 and 1.50 pu, whereas the subtransient
reactance X'd is generally between 0.20 and 0.50
pu.
It means that if you do not know the parameters
for a 10 kVA transformer, you are not making a
major error by assuming an average value of 0.02
pu for leakage reactances and 0.0075 pu for
winding resistances.
22
Advantages
The calculations using the per unit system are
simplified. When all impedances in a multivoltage
power system are expressed on a common power
base and on the nominal voltages of the different
subnetworks, the total impedance in pu seen at one
bus is obtained by simply adding all impedances in
pu, without taking into consideration the transformer
ratios.
23
Per Unit Calculations
All base values are only magnitude. They are not associated
with any angle.
The per unit values, however, are phasors.
The phase angles of the currents and voltages and the power factor
of the circuit are not affected by the conversion to per unit values.
In general, the per unit value is the ratio of the actual value and
the base value of the same quantity.
actual value
per unit value base value
The per unit system values can also be expressed as per cent values.
24
Procedure for Per Unit
Analysis
1. Pick SBase for the system.
2. Pick VBase according to line-to-line
3. Calculate voltage.
Z for different zones.
Base
25
Base value
26
Base values
27
Base values
Usually, the nominal apparent power (S) and
nominal voltage (V) are taken as the base values
for power (Sbase) and voltage (Vbase).
28
Per-unit System for 1- Circuits
I B SB,1
V
B,LN V2
VB,LN
Z B RB X B B,LN
IB S B,1
29
Base
value
For single phase system
30
Per-Unit
System
V p.u. Vactual I p.u. Iactual
VB IB
100% 31
Per-unit System for 1-
Circuits
For actual quantity that has complex
Z
number, Per unit can be expressed as: Z pu Z
B
Q
displayed.
Q pu S pu
b
V 32
exercise
A generator has an impedance of 2.65 ohms. What
is its impedance in per-unit, using bases 500MVA
and 22kV
33
Per Unit system for 3- Circuits
In a balanced 3-Φ system, the magnitude of voltages and currents
in every phase, is the same and is displaced by 120o.
Have the same per unit values for line to line and line to neutral
quantities.
Make everything look like a single phase circuit.
Balanced three phase circuits can be solved in per unit on a per
phase basis after converting delta load impedance to equivalent Y
impedance.
Base value can be selected on a per phase basis or on a three
phase basis.
To simplify further we can remove the neutral connection, thus
leaving only the live connection as a single line.
This kind of diagram is called, the single line diagram. 34
Three phase
system
35
Per Unit system for 3- φ Circuits (Voltage)
V pu V pu
LL LN
So
V pu V pu
VLL V
V LN
: LL LN VB,LL B,LN
VB,LL 3VB,LN
36
Per Unit system for 3- φ Circuits (Power)
S3 3S1
We know:
S pu S pu
S 3 S 1
SB,3 SB,1
3
1
So
:
SB,3 3SB,1
37
Per Unit system for 3- φ Circuits (Current)
S3 3VLN I LN
* 3VLL I LL
We know:
So:
S pu V pu I pu
S
S pu
V pu
I pu
VLL ILL
IB
SB,3 VB,LL
IB SB,3
3VB,LL 38
Per Unit system for 3- Circuits
(Impedance)
39
Example 1
Given base kVA for 3 phase systems is 30 000kVA and voltage base
line to line 120kV. Find:
Solution:
Base kVA3Φ = 30,000 kVA
and Base kVLL = 120 kVA
therefore Base kVA 1Φ = 30,000 / 3 = 10,000
kVA
41
Example 2
Determine the per-unit values of the following single-line diagram and draw the impedance
diagram.
5 MVA 100 MVA 50 MVA
275 kV/132 kV Transmission line 132 kV/66 kV
Xg = 16%
j 3.48
Solution:
Chosen base: Always choose the largest rating, therefore Sbase = 100 MVA, V = 66 kV, 132 kV and 275 kV
Per-unit calculations:
100
X g ( pu ) 0.16 0.32 p.u.
50
42
Example 2
Transmission line TL: Transformer T2:
Z base
kV base 2
Z pu
Z actual X T 2 ( pu ) 0.04
100
0.08 p.u.
50
MVA base Z base
3.4 100
X TL ( pu ) 0.0195 p.u.
132 2
Inductive load:
66 10 3
3
Z actual 6
87 .1236 .87 o
40 10
3 66 10 3 0.8
87.1236.87 o 100
Z L ( pu ) 2
236.87 o or (1.6 j1.2) p.u.
66
43
Example 2
Now, we have all the impedance values in per-unit with a common base and we can now combine all the
impedances and determine the overall impedance.
5 MVA 100 MVA 50 MVA
275 kV/132 kV Transmission line 132 kV/66 kV
Xg = 16%
j 3.48
Generator Load
G j 1.2 p.u.
44
Change of Base
45
Change of Base
In other word, since all impedances in any one part of the a system
must be expressed on the same impedance base when making
computations, it is necessary to have a means of converting per-
unit impedances from one based to another.
Z Z pu
Z Z pu
Z
actual new B,new old
B,old
npeuw o lpdu Z
Z Z Z BB,,noelwd
2
V
But we always have : Z B
B
SB
S V B,old
2
Z npeuw Z o l dp u B,new
S B,old V B , n e w
46
Change of Base
If VB, new
= VB,old
So
npeuw o pl du
SB,new
Z Z S B,old
47
Example 3
48
Example 3
49
Exercise 1
Generator rated at 10MVA, 20kV
XS = 0.9pu on the basis of the generator rating
Given SB,new =100MVA and VB,new =20kV
new
Find: X
S
Solution:
50
Exercise 2
Transformer rated at 10MVA, 33/11kV
Z = 10% and R = 1%
Given SB,new=200MVA and VB,new =22kV (HV side
transformer)
Find: i. Zbase(HV and LV sides)
ii. actual Z and R referred to primary and secondary
iii.Transformer losses in kW, if 0.033 p.u (selected base) of
current flow through R
Solution:
51
Source
52
Transformer Voltage Base
53
How to Choose Base
Values
?
Divide circuit into zones by
transformers.
Specify two base values out of IB ,VB , ZB , SB ;
for
example, S
Base and VBase
Specify voltage base in the ratio of zone line to line
voltage.
V1 :V2 V2 :V3 V3 :V4
Source
54
Example 4
Given a one line diagram,
Vg 13.2kV
Ig Zline 10 j100
~ Zload 300
5 MVA 10 MVA
13.2 Δ – 132 Y kV 138 Y - 69 Δ kV
X 1 0.1p.u. X 2 0.08p.u.
56
Step 1, 2, and 3: Base Values
57
Step 4: All in Per Unit
g
Quantities
V 13.2kV T1 T2
Ig Zline 10 j100
~ Zload 300
5 MVA 10 MVA
13.2 Δ – 132 Y kV 138 Y - 69 Δ kV
X 1 0.1p.u. X 2 0.08p.u.
+
-
Calculate Vg in per unit
Calculate the new reactance for X1 and X2 in per unit
Calculate the impedance in per unit
Draw the impedance diagram 58
Step 4: All in Per Unit
Quantities
59
Step 5: One Phase Diagram & Solve
+ Vg,p.u. 0.960
- Zload,p.u. 0.63
0.960
I load,p.u. Vg,p.u. 1.35
Z total,p.u. 0.70926.4
26.4
Vload,p.u. Iload,p.u.Zload,p.u. 0.8505 26.4
S load,p.u. *
load,p.u. I load,p.u.
V 1.148
Ig,p.u. I t-line,p.u. Iload,p.u. 1.35 26.4
60
Step 6: Convert back to actual quantities
Vg 13.2kV
Ig Zline 10 j100
~ Zload 300
I g Ig,p.u. I B 1
I t-line I t-line,p.u. I B 2 Iload Iload,p.u. I B 3
Vload Vload,p.u.VB 3
Sload Sload,p.u.SB 61
1. Per Unit Exam Practice Problem
Using the Per Unit system and taking into account the transformer percent
impedances, solve for the current in each part of the three-phase system
shown below. Assume both transformers are either delta – delta or wye – wye
connected and that there is no phase shift between primary and secondary
current and voltage.
62
Step 1: Separate by Voltage Zones
The usefulness of the per unit system is in converting all system impedances to per
unit impedances and re-drawing the circuit without having to worry about the
different voltage levels from each transformer.
In this example, there are two transformers that divide the system into three
different voltage zones that are created by the stepping up or stepping down of
voltage by each transformer.
The first step is to illustrate this by drawing a straight line through each transformer:
63
Step 2: Assign Base Values
The next step is to choose the base values for power and voltage.
The base power will be the same in for each zone, but each zone will have a
different base voltage.
For base power, I’ve arbitrarily picked T1’s MVA rating for the system
and the voltage ratios of the transformers for the base voltage in each
zone:
64
Step 3: Calculate Base Impedance for Each Zone
We can solve for impedance using voltage and power, and if we use the base voltage
and base power in each zone, then the resulting impedance will be the base
impedance for each zone as shown below:
65
Step 4: Calculate the Per Unit Impedance for Each Zone
we can start calculating the per unit impedances of each system element using the
following formula:
We will start by
calculating the per unit
line impedance and per
unit load impedance first
before we tackle the
transformers.
The line per unit
impedance and load per
unit impedance are
calculated as shown
below:
66
Step 4: Calculate the Per Unit Impedance for Each Zone cont’d
Now that we know the per unit line and load impedances, let’s draw them on
the per unit circuit diagram:
67
Step 5: Calculate the Per Unit Impedance for Transformer T1
In order to complete the above diagram, we’ll need to calculate the per unit
impedances of both transformers T1 and T2.
The catch here is that we don’t know either of the transformer impedances
in ohms, we are instead given their percent impedances.
When you are given the percent impedance of a machine such as a
transformer, generator, or motor, the percent impedance is given in the base
ratings of the machine itself.
This means that in order to calculate the percent impedances of the
transformers, we actually need to
perform a per unit base change using the following formula:
68
Step 5: Calculate the Per Unit Impedance for Transformer T1
In this case, the old base will be the ratings of each transformer,
and the new base will be the new bases we have chosen.
Since we are working with impedances, we will need to plug in
the impedance formula that uses the square of the voltage
divided by power:
In the above formula, S BASE NEW and V BASE NEW will be the chosen
bases of our system and zone, and S BASE OLD and V BASE OLD will be
the transformer voltage and power rating.
69
Step 5: Calculate the Per Unit Impedance for Transformer T1
70
Step 5: Calculate the Per Unit Impedance for Transformer T1
71
Step 6: Calculate the Per Unit Impedance for Transformer T2
72
Step 7: Calculate the Per Unit Current and Per Unit Voltage
Now that we have both per unit impedances let’s fill in the
remaining values in our per unit impedance diagram.
Again, notice that both transformer per unit impedances are
reactive terms and we had to add the “j” multiplier:
73
Step 7: Calculate the Per Unit Current and Per Unit Voltage
Luckily for us, the voltage on our input bus is equal to the base voltage
selected in that zone which simplifies the math since both terms cancel:
74
Step 8: Use Ohm’s Law to Calculate the Per Unit Current
Since the input voltage is equal to the base voltage in zone 1, the per unit voltage
at the source of our per unit impedance diagram is equal to 1.
This greatly simplifies solving for the per unit current which will now equal the
inverse of the total series per unit impedance of the system:
The per unit current will be the same value for each voltage75zone.
Step 9: Calculate the Base Current in Each Zone
Now that we know the per unit current, we can finally calculate the actual
current in each voltage zone by multiplying by the per unit current by
each base current:
76
Step 9: Calculate the Base Current in Each Zone
However, this requires us to know what the base current in each voltage zone is equal
to.
We can calculate it using the chosen base power and the chosen base voltage in each
zone as shown below.
Notice the √3 multiplier since it is a three phase system:
77
Step 10: Calculate the Actual Current in Each Zone
78
Step 10: Calculate the Actual Current in Each Zone
79
Step 11: Check Your Work Using the Transformer Ratios
For a quick check of our work, we can use the transformer voltage ratios to verify our
currents are equal in each zone depending on voltage level.
If we did our work correctly we should get almost the exact same answer for each current
by starting with one and using the transformer ratios to solve for the rest
Let’s start with current I3 and work our way back to I2 and I1:
80
Step 12: The Completed Diagram
81
Exercise 3
82
If a transformer connected in the system
84
To simplify the analysis, assume that the resistance of
the transformer can be neglected.
85
The reactance referred to the primary side is
86
The final equivalent is circuit is as shown
below
87
If the impedance is referred to the secondary :
88
The final equivalent is circuit is as shown
below
89
with base voltage of 10 V and 20 V respectively at the
primary and secondary windings and base power of 100
VA, thus the base reactance at the primary side is
90
The reactance referred to the primary side in per unit is
91
And the reactance referred to the secondary side is
92
Thus the equivalent circuit in pu
is:
93
Example 5
94
Example 5
95
Example 6
Find the per unit value for each component and draw the
impedance diagram.
96
Example 6
The base parameters taken for the system, both at
the generator, are:
VL-base = 10 kV.
VA3Φ-base = 100 MVA.
97
Example 6
98
Example 6
99
Example 6
The impedance diagram :
100
Example 7
102
Example 7
The actual current value at each component
is
103
Example 7
The voltage drop at every componenr-tUinsit:
104
Example 7
The generated voltage is :
106
Example 7
107
Example 7
108
Example 7
109
Example 8
A three phase generator has the following voltage and
power ratings:
Vbase = 10 kV
VAbase = 50 MVA
110
Example 8
if the following new bases are used,
Vbase-new = 20 kV
VAbase-new = 10 MVA,
Then
111
Example 8
Given the old base values for voltage and power and the
impedance based on these values,
112
Example 8
113
Example 9
114
Example 9
115
Example 9
116
Example 9
Data :
118
Exercise 4
119
Example 10
A 3 phase Wye connected load consists of three
impedances, each with a value of 20∠30o Ω. The line
voltage at the load terminal is 4.4 kV. The line impedance
is 1.4 ∠ 75o Ω. Obtain the line voltage at the source end.
120
Example 10
121
Example 10
122
Example 10
123
Example 11
124
Example 11
125
Example 11
126
Example 11
127
Example 11
128
Example 11
129
Example 11
130
Example 11
131
Example 12
This figure shows a single line diagram of a network.
Select a common base of 100MVA and 13.8kV on the
generator side. Draw the per unit impedance diagram.
132
Example 12
133
Example 12
134
Example 12
135
Example 12
136
Example 12
137
Example 13
The figure shows a single line diagram of a single phase
circuit.
Using the base value of 3 kVA and 230V.
Draw the per unit circuit diagram.
Also calculate the load current both in per
unit and amperes.
138
Example 13
For generator
For Line
139
Example 13
For load
140
Example 13
141
Example 13
142
Fault
calculation
Per unit calculation is used extensively in fault
calculation. The idea is to convert all quantities to
per unit.
The normal circuit analysis is used to calculate
current and voltage under short-circuit condition.
143
As an example, consider the following
network
144
Changing impedances into pu with 100MVA base,
145
146
QUESTIONS?
147