Airbus A319 A321 DLH Training Manual Ata 29 Hydraulic Power Line Amp Base Maintenance Level 3
Airbus A319 A321 DLH Training Manual Ata 29 Hydraulic Power Line Amp Base Maintenance Level 3
Airbus A319 A321 DLH Training Manual Ata 29 Hydraulic Power Line Amp Base Maintenance Level 3
ATA 29
Hydraulic Power
Line & Base Maintenance
Level 3
90
RAT GROUND TEST (CONFIG 2) . . . . . . . . . . . . . . . . . . .
92
TABLE OF CONTENTS
RAT AUTOMATIC DEPLOYMENT 94
29-24 TEST . . . . . . . . . . . . .
YELLOW AUXILIARY HYDRAULIC POWER . . . . . . . . . . . 96
POWER TRANSFER UNIT . . . . . . . . . . . . . . . . . . . . . . . . . 96
PTU INHIBITION ON GROUND . . . . . . . . . . . . . . . . . . . . . 98
PTU POWER SUPPLY & MONITORING . . . . . . . . . . . . . .
100 YELLOW ELECTRIC PUMP . . . . . . . . . . . . . . . . . . . . . . . .
102
YELLOW HAND PUMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
PHASE UNBALANCE DETECTOR . . . . . . . . . . . . . . . . . . .
104 YELLOW ELECTRICAL PUMP POWER SUPPLY . . . . . .
106 GROUND INTERNAL LEAK TEST SYSTEM . . . . . . . . . .
29-00 108 GROUND INTERNAL LEAK TEST SYSTEM . . . . . . . . . .
110 SEAL DRAIN SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
112
SYS. MONITORING & INDICATION . . . . . . . . . . . . . . . . . . . .
114
SYSTEM PRESSURE MONITOR . . . . . . . . . . . . . . . . . . . . 114
SYSTEM PRESSURE INDICATION . . . . . . . . . . . . . . . . . . 114
PUMP OUTPUT MONITOR . . . . . . . . . . . . . . . . . . . . . . . . . 116
QTY MONITORING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
LOW LEVEL MONITORING . . . . . . . . . . . . . . . . . . . . . . . . .
118 FLUID HIGH TEMPERATURE WARNING . . . . . . . . . . . . .
120 RESERVOIR AIR PRESSURE INDICATION . . . . . . . . . .
122 RESERVOIR AIR PRESSURE INDICATION . . . . . . . . . .
124 FAULT MONITORING THROUGH CFDS . . . . . . . . . . . . .
126 SELF EXAMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
133
Page: ii
TABLE OF FIGURES
Figure 1 Hydraulic System Presentation . . . . . . . . . . . . . . . . . . . . . 3 Figure 36 Blue System Ground Service Panel . . . . . . . . . . . . . . . . . 69
.
Figure 2 Hydraulic Panel 5 Figure 37 Hydraulic Systems Pressurization . . . . . . . . . . . . . . . . . . 71
40VU . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3 Hydraulic System Control . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 38 RAT Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
. .
Figure 4 Hydraulic ECAM 9 Figure 39 Ram Air Turbine Config 1 . . . . . . . . . . . . . . . . . . . . . . . . . 75
Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 5 Hydraulic ECAM 11 Figure 40 RAT 77
Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 6 ECAM Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Figure 41 RAT Retraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
.. .
Figure 7 Identifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 42 RAT Safety 81
.. Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 8 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Figure 43 RAT Protective Equipment . . . . . . . . . . . . . . . . . . . . . . . . 83
..
Figure 9 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Figure 44 Ram Air Turbine Config 2 . . . . . . . . . . . . . . . . . . . . . . . . . 85
..
Figure 10 Component Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 45 RAT Retraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
.
Figure 11 Green System Basic Schematic . . . . . . . . . . . . . . . . . . . . 21 Figure 46 RAT Safety 89
Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 12 Green System Component Location . . . . . . . . . . . . . . . . 23 Figure 47 RAT Flow Control Test Kit . . . . . . . . . . . . . . . . . . . . . . . . . 91
Figure 13 Green Hydraulic System Reservoir . . . . . . . . . . . . . . . . . 25 Figure 48 RAT Auto Deloyment Test . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 14 Engine Fire Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Figure 49 PTU / Manifold Installation . . . . . . . . . . . . . . . . . . . . . . . . . 95
.
Figure 15 Engine Driven 29 Figure 50 PTU Inhibition ( Ground ) . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 16 EDP Electrical 31 Figure 51 PTU Power Supply & Monitoring . . . . . . . . . . . . . . . . . . . 99
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 17 System Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Figure 52 Yellow Electrical Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
.
Figure 18 Manifold Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Figure 53 Phase Unbalance Detector ( Blue & Yellow ) . . . . . . . . . 103
Figure 19 System 37 Figure 54 Yellow Electric Pump Control . . . . . . . . . . . . . . . . . . . . . . 105
Accumulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 20 Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Figure 55 Internal Leak Test Components . . . . . . . . . . . . . . . . . . . . 107
..
Figure 21 Green System Ground Service Panel . . . . . . . . . . . . . . . 41 Figure 56 Internal Leak Test System . . . . . . . . . . . . . . . . . . . . . . . . . 109
Figure 22 Service Panel Components . . . . . . . . . . . . . . . . . . . . . . . . 43 Figure 57 Seal Drain 111
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page: iii
Figure 23 Reservoir Filling 45 Figure 58 Sys. Pressure / Low Press. Warning . . . . . . . . . . . . . . . . 113
System . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 24 Pressurization Components . . . . . . . . . . . . . . . . . . . . . . . 47 Figure 59 Pump Low Pressure Warning . . . . . . . . . . . . . . . . . . . . . . 115
Figure 25 Reservoir Pressurization System (cofig 1 ) . . . . . . . . . . . 48 Figure 60 QTY Monitoring & Low QTY Warning . . . . . . . . . . . . . . . 117
Figure 26 Reservoir Pressurization System ( config 2 ) . . . . . . . . . 49 Figure 61 High Temperature Warning . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 27 Yellow System Basic Schematic . . . . . . . . . . . . . . . . . . . . 51 Figure 62 Reservoir Low Air Pressure Warning . . . . . . . . . . . . . . . . 121
Figure 28 Yellow System Component Location . . . . . . . . . . . . . . . . 53 Figure 63 Blue Reservoir Low Air Pressure Warning . . . . . . . . . . . 123
Figure 29 Yellow Hydraulic System Components . . . . . . . . . . . . . . 55 Figure 64 Fault Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
.
Figure 30 Yellow Hydraulic System Components . . . . . . . . . . . . . . 57 Figure 65 Safety 126
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 31 Yellow System Ground Service Panel . . . . . . . . . . . . . . . 59 Figure 66 Safety 127
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 32 Blue System Basic Schematic . . . . . . . . . . . . . . . . . . . . . 61 Figure 67 External Leakage Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Figure 33 Blue System Component Location . . . . . . . . . . . . . . . . . . 63 Figure 68 External Leakage Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Figure 34 Blue System Components . . . . . . . . . . . . . . . . . . . . . . . . . 65 Figure 69 Hydraulic System Symbols . . . . . . . . . . . . . . . . . . . . . . . . 130
Figure 35 Blue SYstem Components . . . . . . . . . . . . . . . . . . . . . . . . 67 Figure A Basic Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
..
HYDRAULIC POWER A319 / 320 / 321
Lufthansa Technical Training
GENERAL
29-00
ATA 29
HYDRAULIC
POWER
For Training Purposes Only
General
29-00
• Case drain filters on engine and blue electric pumps permit the monitoring
of wear by detection of particles in the filters.
General
29-00
S S
LEAK MEASUREMENT S LEAK MEASUREMENT S PTU S LEAK MEASUREMENT
VALVE VALVE VALVE
TO ELAC & SEC TO ELAC & SEC TO ELAC & SEC
TO ELAC
TO FAC, SEC, ELAC SEC
FWC & BSCU L&R L&R FAC &
TO FWC,SEC & ELAC LAF FWC
LAF
ACCU ACCU
L & R AILERON L & R AILERON ( A320 L & R SPOILER 2
( A320
only ) only )
L & R SPOILER 5 TO FCDC TO FCDC L & R SPOILER 4
L & R SPOILER 3
RUDDER RUDDER RUDDER
SLATS
FLAPS R WTB
General
29-00
System Presentation ( Cont )
Reservoirs SOME HYDRAULIC SYSTEM USERS:
Each system is supplied by its own hydraulic reservoir. The reservoirs are pres-
Green Users
surized using HPC-air of engine no 1 or bleed air from the pneumatic system
(Engine or APU) or from a ground connection. The Green main hydraulic system supplies:
- the landing gear and doors (including nosewheel steering),
Fire Valve - the normal braking system,
On the green and yellow systems, a fire valve is positioned upstream of the - the left (No. 1) engine thrust reverser,
engine driven pump to isolate the system.
- some of the flight controls,
Ram Air Turbine - the power transfer unit (PTU).
A Ram Air Turbine, wich extends automatically in the event of both engines
and APU generator failure, allows the blue hydraulic system to be pressurized. Blue Users
NOTE: RAT delivered pressure is 2500 psi (172 bar). The Blue hydraulic system supplies:
Automatic deployment is inhibited on ground. Manual operation from the cock- - some of the flight controls,
pit is always possible. - the CSM/G
NOTE: RAT stowage is possible on ground only.
Yellow Users
ACCUMULATORS
The Yellow hydraulic system supplies:
• System Accumulators
- the cargo doors,
- An accumulator in each circuit helps to maintain a constant pressure dur-
- the alternate and parking brake systems,
ing normal operation by covering transient demands.
• LAF Accumulators (A320 only) - the right-hand (No. 2) engine thrust reverser,
- The Load Allevation Function ( LAF ) relieves wing structure load in tur- - some of the flight controls,
bulence by moving the ailerons and spoiler 4 and 5 symetrically, in addi- - the Power Transfer Unit (PTU).
tion to giving roll orders.
Leak Measurement Valves
A leak measurement valve is positioned in each circuit upstream of the primary
For Training Purposes Only
flight controls.They are used for the leakage measurement of each circuit and
are closed by operation of the leak measurement valves Pb switches on the
maintenance panel.
Priority Valves
In the event of low hydraulic pressure, the priority valves maintain the operation
of essential systems by cutting off hydraulic power to heavy load users.
General
29-00
S S
LEAK MEASUREMENT S LEAK MEASUREMENT S PTU S LEAK MEASUREMENT
VALVE VALVE VALVE
TO ELAC & SEC TO ELAC & SEC TO ELAC & SEC
TO ELAC
TO FAC, SEC, ELAC SEC
FWC & BSCU L&R L&R FAC &
TO FWC,SEC & ELAC LAF FWC
LAF
ACCU ACCU
L & R AILERON L & R AILERON ( A320 L & R SPOILER 2
( A320
only ) only )
L & R SPOILER 5 TO FCDC TO FCDC L & R SPOILER 4
L & R SPOILER 3
RUDDER RUDDER RUDDER
SLATS
FLAPS R WTB
System Controls
29-00
”OFF”
2 RAT MAN ON pb-switch ( guarded )
• the electrical pump is deenergized,
• The RAT MAN ON guarded pushbutton permits Ram Air Turbine deploy-
NOTE: The electrical pump is automatically energized,when the cargo
ment at any time. doors are opened or closed.
• RAT deployment is automatic in case of failure of main generators
- If electrical power is removed the pump will remain deenergized at the
( ENG and APU ) in flight. next electrical power application.
• deactivates the FAULT LT except at overheat-condition.
System Controls
29-00
PANEL LOCATION
PTU
RAT MAN ON A
FAULT
U
ELEC PUMP
OFF T
H H
ENG 1 PUMP ELEC PUMP ENG 2 PUMP
Y FAULT Y
A O
D FAULT FAULT U FAULT ON D
OFF OFF T OFF
For Training Purposes Only
1 2 3 4 5 6
System Controls
29-00
CONTINUE.
”FAULT” illuminates amber in case of: pressing the BLUE PUMP OVRD puschbutton on the maintenance overhead
- pump low pressure panel.
- reservoir low level ”ON”
- reservoir low air press. • On ground, the electric pump operates if the ELEC PUMP pushbutton is set
- pump elec. motor overheat 1) to AUTO.
- reservoir overheat 1)
7 LEAK MEASUREMENT VALVE pb switch ( Blue )
4 PTU pb switch
8 LEAK MEASUREMENT VALVE pb switch ( Green )
”AUTO”( pb switch in )
• The bidirectional Power Transfer Unit is armed, 9 LEAK MEASUREMENT VALVE pb switch ( Yellow )
- yellow and green PTU solenoid valves are deenergized open. Panel 5OVU has the pushbutton switches which control the thre leakage mea-
- PTU operates automatically when the differential pressure between the surement selectors. These are used for servicing only.
green and yellow system is more than 500 psi. ”ON”( pb switch out )
NOTE:The PTU is inhibited during cargo door operation and first eingine • ON illuminates white
start and is automatically tested during the second engine start. • the respective solenoid valve is energized closed and the hydraulic supply
to the primary flight controls is shut off.
”OFF”( pb switch out ) illuminates white
• the PTU is off
EMERGENCY ELECRIC POWER PANEL 21VU
- yellow and green PTU solenoid valves are energized closed.
11 MAN ON pb-switch ( guarded )
• deactivates the FAULT LT except at overheat-condition.
• The MAN ON guarded pushbutton permits Ram Air Turbine deployment at
any time.
”FAULT” illuminates amber in case of:
• RAT deployment is automatic in case of failure of main generators (ENG
- green or yellow reservoir low level
and APU) in flight.
- green or yellow reservoir overheat 1)
FIRE PANEL 45VU
For Training Purposes Only
System Controls
29-00
PANEL LOCATION
AGENT 1 AGENT 2
SQUIB SQUIB
F F
DISCH DISCH
I I
ENG 1 FIRE ENG 2 FIRE
R R
E TEST TEST E
PUSH PUSH
12 12
GEN
OFF
11
10 7 8 9
refer to ATA 24
ECAM
29-00
Resevoir Pressure LO AIR PRESS ELEC PUMP pushbutton is on and hydraulic pressure
2 is normal ( green )
Reservoir LO AIR PRESS indication appears amber if the corresponding reser- ELEC PUMP pushbutton is OFF ( amber )
voir air pressure drops below normal.
LO ELEC PUMP pushbutton is on and hydraulic pressure
3 Resevoir Overheat is low ( amber )
ELEC Elec pump normal operation ( green )
Reservoir OVHT indication appears amber if the return hydraulic fluid tempera-
ture is above normal. ELEC associated power supply failure ( amber )
OVHT appears in case of pump overheat ( amber )
4 Fire Valve Indication
8 Yellow Electric Pump
For Training Purposes Only
ECAM
29-00
B System Display
B A
RELATED WARNINGS
HYD BLUE RSVR LO AIR PRESS
AND NECESSARY
BLUE ELEC PUMP ...........OFF
ACTIONS
ECAM
29-00
ECAM
29-00
B System Display
B A
RELATED WARNINGS
HYD BLUE RSVR LO AIR PRESS
AND NECESSARY
BLUE ELEC PUMP ...........OFF
ACTIONS
ECAM
29-00
ECAM WARNINGS
Possible ECAM Warnings
The possible ECAM Warnings of the hydraulic system and the related FLIGHT
PHASE INHIBITIONS are shown on the page below.
For Training Purposes Only
ECAM
29-00
TOUCH DOWN
1500 Ft
800 Ft
5 MN AFTER
ELEC PWR
LIFT OFF
80 Kts
80 Kts
1 2 3 4 5 6 7 8 9 10
For Training Purposes Only
Identifications
29-00
COMPONENT IDENTIFICATION
All Hydraulic components are marked with a label which contains the FIN and
the name.
• FIN number 1000 = Green System
• FIN number 2000 = Blue System
• FIN number 3000 = Yellow System
PIPELINE IDENTIFICATION
All Hydraulic pipelines are marked with a coulor code and a number for system
identification.
For Training Purposes Only
Maintenance Practices
29-00
For Training Purposes Only
Maintenance Practices
29-00
For Training Purposes Only
Component Locations
29-00
COMPONENT LOCATIONS
Hydraulic System Components
The page below shows locations of the main components of the three
hydraulic systems.
For Training Purposes Only
Component Locations
29-00
For Training Purposes Only
Green System
29-11
29-11
GREEN
HYDRAULIC
It pressurizes the Green system to approximately the same pressure as the
SYSTEM Yellow system (the pressure is less because the PTU is not 100 % efficient).
29-11
22
Seite: Page: 23
LAF ACCUS
YAW DAMPER MAIN
( IF INSTALLED )
LANDING GEAR
PITCH TRIM LH SLAT WTB RH SLAT WTB MLG DOORS
RUDDER LH AILERON RH AILERON NOSE LANDIND
GEAR
LH ELEVATOR LH SPOILER 5 RH SPOILER 5 NLG DOORS
RH FLAP WTB NOSE
LH WHEEL
THRUST STEERING
REVERSE RH SLAT
R LH SPOILER 1 RH SPOILER 1 MOTOR
LH FLAP
MOTOR
NORMA
L
BRAKES
A
GREEN BLUE YELLOW
PTU
A
RAT MAN ON
H FAULT
U
ELEC PUMP
OFF T
ENG 1 PUMP ELEC PUMP
O ENG 2 PUMP H
Y FAULT
Figure 12
HP MANIFOLD PTU MANIFOLD
SDAC
FROM
CONSUMER
S
SDAC
SDAC
ENG 1 FIRE ENG 2 FIRE
PUSH PUSH
Main Hydraulic Power
SDAC
GREEN GRD SEVICE PANEL
Lufthansa Technical Training For Training Purposes Only
Main Hydraulic Power A319 / A320 / A321
Lufthansa Technical Training
Green System
29-11
Identifications
29-00
Component Identification
3002GM
FILTER RSVR
RETURN, Y
IDENTIFICATION LABEL ON
NEARBY STRUCTURE
Pipeline Identification
HYDRAULIC SYSTEM IDENTIFICATION
1 GREEN GREEN
2 BLUE BLUE
3 YELLOW YELLOW
For Training Purposes Only
PRESSURE 1
1
PRESSURE
FUNCTION AND
HYDRAULIC FLOW ARROWS
SYMBOL
Figure 8 Identifications
FRA US-T gs 1.7.98 Seite: Page: 17
Main Hydraulic Power A319 / A320 / A321
Lufthansa Technical Training
Green System
29-11
G PTU MANIFOLD
SYSTEM MANIFOLD
PRESSURE FILTER
For Training Purposes Only
RETURN FILTER
SYSTEM ACCUMULATOR
GREEN RESERVOIR
Green System
29-11
QUANTITY INDICATOR
GREEN HYDRAULIC SYSTEM RESERVOIR
General Description
General Description
Each reservoir has a gage-transmitter which gives a visual indication and
The reservoir is made of two molded light alloy sections which are welded to- sends electrical signals to show the fluid contents. The unit is a float assembly
gether to make a cylindrical shape. The top of the reservoir has a manifold for connected mechanically to a synchro transmitter. The pointer of the mechanical
the components of the air pressurization system . The bottom of the reservoir contents gage is connected to the synchro transmitter. When the float moves,
has three ports for the hydraulic connections. A drain valve is installed on one the synchro transmitter and the pointer turn together. The synchro transmitter
of the ports, the other two are for the suction and return line connections. The sends signals to the ECAM system and to the reservoir quantity indicator on
reservoir also has flanges to attach the quantity indicator/transmitter and the the Green ground-service panel.
low level switch .
The inside of the reservoir includes baffles which give a supply (for 20s) of fluid LOW LEVEL SWITCH
under negative ’g’ conditions. The baffles also form an anti-emulsion device
which limits the emulsion of the fluid when there is a large return flow. General Description
The hydraulic fluid capacities of the reservoir are: The low level switch is installed in the reservoir and gives a signal when the
- the normal fill level 14 l (3.6983 USgal), fluid level is too low. It is a float-operated switch which includes a relay. The
- the maximum gageable level 18 l (4.7550 USgal) float assembly includes a magnet which keeps the contacts of a reed switch
- the low level warning level 3.0 + 0.4 - 0.4 l (0.8 + 0.1 - 0.1 USgal) open when the float is high. When the level of the fluid decreases, the float falls
and the reed switch closes. Discrete signals are sent to the SDAC and to the
The reservoir is pressurized to 50 psi (3.5 bar) and is sealed to hold thepres- overhead panel.
sure if there is no supply of air (for example, when the aircraft is parked). It is
possible to pressurize the reservoir from a ground supply .The reservoir is filled
with hydraulic fluid through the reservoir filling system .
For Training Purposes Only
Green System
29-11
AIR MANIFOLD
QUANTITY INDICATOR
FLOAT ARM
DRAIN VALVE
Green System
29-11
Purpose
The FIRE pushbutton in the flight compartment control the supply of electrical
power to the motor. When the valve closes it stops the supply of fluid to the
EDP.
Valve Description
The fire valve ( Ball type valve ) is made up of two main parts;
- the valve assembly, and
- the actuator assembly.
The two parts are connected together with screws. It is not necessary to dis-
connect or empty the hydraulic pipes to remove the actuator assembly from the
valve assembly.
The body of the valve assembly has arrows which show the direction of flow
through the valve. The valve ball has a connection for the output shaft of the
actuator. The ball turns thru 90 degrees each time it operates. The ball always
turns in the same direction.The electric motor is a 28 V DC type.
VISUELL POSITION INDICATION: Two types of valves can be installed.
- a visual indicator is attached to the gearbox output shaft. It is visible
through a window in the housing. The indicator shows red when the
valve is open or green when it is closed.
- a visual indicator is attached to the gearbox output shaft. It is visible on
For Training Purposes Only
Green System
29-11
INDICATOR
WINDOW
A
VALVE ASSY
COMPENSATOR
SLIDE ASSY
OPEN
SHUT
VALVE ASSY
LINE END
FITTING
Green System
29-11
General Description
PUMP PRESSURE SWITCH
There are two different types of EDP which are permitted. ABEX make one
type, VICKERS the other. The two types are completely interchangeable. They
give equivalent supplies of hydraulic power and their mechanical and electrical
connections are the same.
The engine-driven pump ( EDP ) is attached to the accessory gearbox on the
bottom of the engine. A splined quill drive connects the gearbox to the input
shaft of the pump. The quill drive is made to shear if the pump can not turn.
The attachment flange of the pump has keyhole slots where the installation
bolts are.
The suction line connection has a quick-release self-sealing coupling. Together,
CASE DRAIN FILTER
they make it possible to replace the pump quickly.
The pump is of the variable-displacement type. The rotating assembly turns all
of the time that the engine operates.
A solenoid valve ( controlled from the flight compartment ) makes it possible to
change the operation of the pump so that it does not supply pressure to the
system (depressurized mode ). The EDP includes a blocking valve which iso-
lates the pump from the hydraulic system when the pump operates in the de-
pressurized mode.
In the depressurized mode the outlet of the pump is connected internally di-
rectly to the inlet of the pump. The pump then operates with an internal pres-
sure of approximately 1000 psi ( 70 bar ), with zero flow. This is the pressure
necessary on the actuator piston to reduce the angle of the yoke to near zero
when the outlet and control pressures are balanced.
General
The pressure switche (1074GK ) downstream of the engine pump monitors the
output of the pump. When the pressure falls below 1740 + 72.5-72.5 psi (120
+ 5-5 bar ) the switch contacts close . INLET
At the same time a signal is sent to the overhead panel 40VU and the applica-
ble FAULT legends come on.
OUTLET
Green System
29-11
SEEPAGE DRAIN
DRIVE SHAFT
INLET
AUXILIARY PISTON
BLOCKING VALVE
( OPEN )
SOLENOID VALVE
( DE-ENERGIZED ) INLET PRESSURE CONTROL PRESSURE
Green System
29-11
Green System
29-11
1158VD SCH01
A
103VU A
30 15 P
UNSD B
C 1158VD
103VU
1384GH PRESS SW
G RSVR AIR
29-23SCH01 UNSD 1 A 29-23SCH01 147 29-34
11 9 UNSD 23
4 B
44 41 X
Z
1078GK RELAY
SCH05 G RSVR OVHT FAULT
2LP RELAY- 103VU220
33-14 8 7 BOARD-ANN LT
SCH05 9 FAULT TEST & INTFC 28
5 4 70VU 33-14 13
OFF 29-
1158VD
33SCH01
UNSD6 D2
D3 D1 33-14 103VU A
101PP SCH05 1
28V DC C2 3
C3 C1
BUS 1 UNSD 2
24-68- B2 UNSD
01 1701GK C/B- B3 B1 31-54SCH01 A
HYDRAULIC 31-54
G HYD/PUMP A2
31-54 SCH02 1030GK PUMP
ENG 1/MONG SCH02 A3 G ENG 1
A1 UNSD SDAC
121VU212 SDAC 430
SCH09
73-25
For Training Purposes Only
Green System
29-11
MANIFOLDS
There are three manifolds in the system, they are:
• the HP manifold,
• the PTU manifold,
• the LP manifold.
General
All of the manifolds are aluminum alloy castings. They are machined to make it
possible to install different components on them. Some of the hydraulic con-
nections between the manifolds and components are of the bobbin type .
Thus, replacement of components is possible with minimum effect on other
components or pipes. The manifolds are drilled to make the internal connec-
tions between components.
The following are the components installed on their related manifolds:
HP Manifold
- the solenoid valve 1150GP ,
- the pressure relief valve 1063GM,
- the HP filter 1048GM,
- the check valves 1022GM and 1059GM,
- the sampling valve 1187GM,
- the pressure transmitter 1065GN ,
- the pressure switch 1151GN ,
- the pressure switch 10-CE-2 .
PTU Manifold
- the priority valve 1064GM,
For Training Purposes Only
LP Manifold 1003GM
The LP manifold is the connection point for return lines from different parts of
the LP system. It is connected directly to the LP filter (1002GM). Check valve
1024GM is installed in one of the ports of the LP manifold.
Green System
29-11
For Training Purposes Only
Green System
29-11
PRIORITY VALVE
The priority valve is installed on the PTU manifold. It makes sure that all avail-
able hydraulic pressure is sent to the primary flight controls if pressure in the
system is reduced. The hydraulic connections between the valve and the man-
ifold are of the bobbin type .
Green System
29-11
MANIFOLD
FLUID
END CAP REMOVED OUTLET
AND USED AS TOOL TO
OPEN THE VALVE
OUTLET
For Training Purposes Only
INLET
Green System
29-11
SYSTEM ACCUMULATORS
The system accumulator is a cylindrical type with an internal bladder.
The metal body of the accumulator has an outer layer of kevlar to make it
stronger. The bladder is made of rubber and isolates the gas ( nitrogen ) from
the hydraulic fluid. A gas port is on one end of the body of the accumulator. It is
the connection for the gas charging valve and for the gas pressure gage. A hy-
draulic connection which includes an oi l valve is at the other end of the accu-
mulator. It is the connection between the accumulator and the aircraft system.
The oil valve stops overpressurization of the bladder. ·
The accumulator has a total volume of 1 l ( 0.26 USgal ) and the gas precharge
pressure is 130 bar ( 1885 psi ).
Green System
29-11
GAS CONNECTION
GAS SPACE
STEEL CASING
KEFLAR REINFORCEMENT
RUBBER BLADDER
For Training Purposes Only
FLUID SPACE
OIL VALVE
Green System
29-11
FILTERS
HP-Filter The by-pass device operates when the pressure differential across the
The HP filter has three main parts: filter element is more than 4.0 +0.4 - 0.4 bar (58 +6 -6 psi). It allows
• the filter head fluid to go from the inlet to the outlet without filtration.
• the filter bowl
• the filter element
The filter head includes the hydraulic connections and the mounting for the at-
tachment of the filter to the structure.
The filter head also includes the filter clogging indicator.
The clogging indicator is a red pin which comes out to show that the filter ele-
ment is too dirty. The indicator operates when the pressure differential accross
the filter reaches a certain amount. When the red pin is pushed back in, the
clogging indicator resets itself. The clogging indicator is latched magnetically. It
does not operate if the temperature of the fluid is lower than 0 deg.C (32
deg.F).
An anti-spill device in the filter head operates when the filter element and bowl
are removed. It stops fluid coming out of the system or air going in to it when
the filter element is changed.
The filter does not have a by-pass device to let fluid through if the element is
clogged.The filter bowl holds the filter element. It has a thread to attach it to the
filter head. It is not necessary to use tools to tighten the filter bowl in the filter
head.The filter element is of the replaceable type. It can not be cleaned. The
filtration rating of the element is 15 microns.
Case Drain Filter 1084GM
The case drain filter (1084GM) is functionally the same as the HP filter
(1048GM). The only differences are in its size and the configuration of
the filter head.
For Training Purposes Only
Green System
29-11
FILTER HEAD A
ANTI SPILL
DEVICE
CLOGGIN
G
INDICATO ANTI SPILL DEVICE
R
CHECK VALVE
FILTER BOWL FILTER ASSEMBLY
ELEMENT
FILTER BOWL
FILTER
ELEMENT
Case Drain Filter 1084GM
CLOGGING
INDICATOR
FILTER
ELEMENT
FILTER BOWL
CLOGGING INDICATOR
Figure 21 Filters
FRA US-T gs 2.7.98 Seite: Page: 41
26
Main Hydraulic Power A319 / A320 / A321
Lufthansa Technical Training
Green System
29-11
Green System
29-11
LOCATION
Green System
29-11
The hand pump provides the flow of fluid to fill the reservoirs if a ground supply
low hydraulic system.
is not available. The hand pump is the same as the hand pump installed on the
Electrical Switch Unit ground service panel of the Yellow system. The pump has a HP pressure relief
The electrical switch unit is attached to the bottom of the hydraulic selector. valve which opens at between 234 and 237.5 bar (3400 and 3445 psi).
The same shaft which operates the hydraulic selector also operates the hy-
draulic switch unit. The switch assembly is made up of a double wafer and a
double rotor. Together they make it possible to switch the five circuits to the
four possible selections (N,Y,B,G). Seals are installed between the hydraulic
and electrical parts of the selector valve assembly. They make sure that no
fluid goes into the electrical switch mechanism, but goes out as external leak-
age.
FRA US-T gs 3.7.98 Seite: Page: 44
42
Main Hydraulic Power A319 / A320 / A321
Lufthansa Technical Training
Green System
29-11
Reservoir Filling Selector Valve 1134GQ Hand Pump 1009GM & Fill Valve 1698GM
HYDRAULIC
CONNECTION
RING SEALS
REDUCTION
ELECTRICAL
GEARS CONNECTION
SWITCH
ASSEMBLY
FILL VALVE
CLOGGING
INDICATOR
Servicing
29-10
29-10
HYDRAULIC Reservoir fluid filling procedure ( with container ) :
FLUID - Remove the handpump handle from the yellow system service panel.
- Connect the handpump handle to the reservoir filling handpump at the
SERVICING green system service panel.
- Remove the filling hose, kept in position at the green system service
HYDRAULIC FLUID
panel and connect it to the fill valve-
FILLING SYSTEM - Put the other end of the fill hose into the hydraulic fluid container.
It is possible to fill any of the three hydraulic reservoirs from one place. - Turn the selector to the position of the system you want to fill.
Most of the components of the reservoir filling system are installed on the
ground service panel of the Green system. Operate the pump and monitor the increase of the fluid level on the quantity
indicator.
The system can be serviced useing a container or a ground hydraulic Stop the flow of hydraulic fluid when the pointer of the quantity indicator is at
supply . the end of the coloured line of the system you have selected.
If the source is a container, a flexible pipe makes the connection between the If a reservoir is overfilled it can be drained by operating a drain valve at the bot-
container and the hand pump. You must connect it to the fill valve. tom of the green and yellow reservoirs.
The fill valve is installed in the suction port of the hand pump. It includes a filter To drain the blue reservoir a drain valve is located at the blue system service
and a check valve. The hand pump is the same as the pump in the Yellow hy- panel.
draulic system, but a different suction port is used. Note:
The self-sealing coupling socket is the connection for a pressurized ground If a ground hydraulic supply is used fit a adapter to the fill valve . The use of
hydraulic supply. There is a restrictor between the coupling socket and the se- the handpump and the flexible hose from the hydraulic service panel is not nes-
lector valve. The restrictor protects the system against overpressure. sessary.
A high-pressure (HP) filter is installed upstream of the selector valve. The se-
lector valve is a 4 port/4 way valve which gets fluid from the supply and sends
it to the applicable reservoir. The selector valve also controls the power supply
to the electrical contents indicator
The check valves isolate the low-pressure (LP) circuits of the main hydraulic
systems from the reservoir filling system when it is not in use.
For Training Purposes Only
Servicing
29-10
A320 only
G Y B
RESERVOIR
FILLING
SELECTOR
VALVE
For Training Purposes Only
HAND PUMP
Servicing
29-10
29-10
RESERVOIR
AIR Pressurization of Hydraulic Reservoirs
PRESSURIZATI The three reservoirs are pressurized at the same time.
The ground connector is installed on the reservoir pressurization manifold.The
ON connector is a plunger type valve.It is opened and closed manually.Rotation of
the nut moves the plunger in or out to open or close the valve. A cap fitted to
GENERAL the connector prevents external contamination.
The aircraft has a pressurization system for the hydraulic reservoirs . Each res-
ervoir gets pressurized air to 50 psi (3.5 bar) (usual operation), which prevents Operation
cavitation of the pumps. The system also remains airtight in the event of failure • Make sure that the reservoir depressurization valves are closed.
of the pressurization system or after an engine shutdown. • Fill the reservoirs with air until 50 PSI is shown on the reservoir pressure
Air for the reservoir pressurization is supplied by: gages.
• Engine 1 high pressure compressor Note:
Air Pressurization Manifold If the system pressure gets higher than 5.3 bar (76.85 PSI ) relative the pres-
• Low pressure bleed air from the pneumatic manifold.
The reservoir pressurization manifold has three inlet ports,one from each sup- sure relief valve opens to relieve the high pressure.
• Ground supply through the air charging ground connector on the reservoir
ply source.
pressurization manifold. Depressurization of Hydraulic Reservoirs
Outlet of the airflow is through the fluid separator which is fitted to the manifold.
Also fitted to the manifold is the pressure reducing valve. • Turn the cap of the reservoir depressurization valve clockwise through 90
PRESSURIZATION COMPONENTS deg. .This allows the air pressure through the valve to the atmosphere.
Two filters are installed in the manifold assembly. Indicators are fitted to the
filters to show when the filters are clogged. • Listen to hear if all air is released.
Reservoir Pessurization Unit Alternatively the air pressure can be released by the connection of a depressu-
rization coupling.
Purpose same as the Pressurization Manifold
Warning:
Depressurization Valve
When opening the manual depressurization valve of the reservoirs it is
Each hydraulic reservoir can be depressurized independently on the applicable possible that the gas is hot and contains hydraulic fluid.
For Training Purposes Only
Servicing
29-10
C
H
E
C
K
V
A
L
V
E
S
AIR CHARGING
GROUND CONNECTOR
PRESSURE SWITCH
FILTERTS
For Training Purposes Only
PRESSURE
RELIEF
VALVE
Servicing
29-10
FLUID
SEPARATOR
CHECK VALVE
( A320 Aircraft only with RAT config
PRESSURE SWITCH
1)
TO SDAC
TO SDAC TO SDAC
PRESSURE RELIEF VALVE
G Y B
For Training Purposes Only
DEPRESSURIZATION VALVE
Servicing
29-10
PRESSURE
REDUCING
VALVE
WATER
PRESSURE SEPERATOR
AIR CHARGING WATER REDUCING AIR FILTER
GROUND CONNECTOR SEPERATOR VALVE
MANUAL
DRAIN
VALVE AUTOMATIC DRAIN VALVE
CLOSED INDICATOR
AUTOMATIC DRAIN VALVE MANUAL DRAIN
VALVE
CHECK VALVE
PRESSURE SWITCH
PRESSURE RELIEF VALVE TO SDAC TO SDAC TO SDAC
G Y B
DEPRESSURIZATION VALVE
Yellow System
29-13
The Power Transfer Unit ( PTU ) 1088GM can also pressurize the Yellow HP
29-13 circuit. The PTU gets its power from the Green hydraulic system. It supplies
YELLOW power to the Yellow hydraulic system if the pressure in the system falls to
approximately 500 psi ( 34.48 bar ) below the pressure in the Green hydraulic
HYDRAULIC system. There is no hydraulic connection between the two hydraulic systems
so no fluid can get from one system to the other. The PTU pushbutton switch
SYSTEM 1802GL in the flight compartment controls the operation of the two solenoid
valves. When the pushbutton switch is operated, the two solenoid valves are
GENERAL energized and the supply of fluid to / from the PTU is stopped.
If the EDP fails, or for maintenance on the ground, it is possible to pressurize
Most of the components of the system are installed in the Yellow hydraulic the Yellow hydraulic system with the electric pump.
compartment in the RH belly fairing, forward of the main gear compartment.
The system is kept physically apart from the other two systems where pos- The system pressure inlet to the HP manifold has a filter 3048GM. A check
sible.The
- the system is hydraulically isolated from the other two systems. It is not- valve 3059GM is installed on the manifold. A sampling valve 3187GM makes it
engine-driven pump ( EDP ) 1030GK connected to the right
possible for fluid to go from one system to another. possible to take samples of fluid from the system for analysis. You can take the
( No 2 ) engine.
The-system operates at a nominal pressure of 3000 psi ( 206 bar ). It is pos- sample when the system is at full pressure.
the Power Transfer Unit ( PTU )1088GM, A pressure relief valve ( PRV ) 3063GM is installed on the HP manifold to pro-
sible to pressurize the high pressure ( HP ) system from three different
- the Yellow electric pump tect the system against overpressure.
sources:
- the hand pump for the operation of the cargo doors Two pressure switches 3151GN, 10CE-3 and a pressure transducer 3065GN
- the ground supply connections. are also installed on the HP manifold to monitor the pressure in the system The
supply to most of the consumers goes through the HP and Leakage Measure-
The Yellow hydraulic system has two sub-systems: ment System ( LMS ) manifolds. Thus it is possible to isolate some consumers
- a high-pressure ( HP ) circuit which supplies consumers, to measure the internal leakage of parts of the system. The supply to the alter-
- a low-pressure ( LP ) or return circuit through which the fluid returns to nate and parking brake systems goes from the HP manifold through the brake
the reservoir. parking brake systems goes from the HP manifold through the brake manifold.
A solenoid valve 3150GP on the HP manifold controls the flow of fluid to the
SYSTEM OPERATION LMS manifold. The solenoid valve is usually operated from the flight compart-
ment by the switch 1883GP on the maintenance panel 50VU but it also has an
The operation of the system is fully automatic.
automatic function. This function is related to the operation of the cargo doors.
The EDP starts to supply the system as soon as the No. 2 ( right ) engine is
When the cargo doors are set to open or close ( and the Yellow electric pump
started. The EDP supplies the system with fluid at 3000 psi ( 206 bar ) and
For Training Purposes Only
starts ), the solenoid valve is automatically closed. This stops the supply of fluid
changes its output to that which is necessary for the system. A pressure switch
to the flight controls.
3074GD and a check valve 3050GM are installed downstream of the EDP. The
pressure switch monitors the output pressure of the pump . The system accu-
The condition of the system is monitored continuously. Temperature and pres-
mulator 3070GM has direct hydraulic connections to the HP and brake man-
sure sensors send information to the flight compartment. The information is
ifolds and to the cargo door selector valve. The accumulator keeps the pres-
shown on the ECAM displays and as FAULT warnings on the overhead panel.
sure in the system free of small changes. It also makes a supply of fluid
The crew can stop the supply of fluid to the EDP ( if there is a fire in the
available to replace any temperary shortage. This can occur if there is a sud-
nacelle ) by operation of the fire valve 3046GD. The fire valve closes when the
den large demand and the pump has not had time to respond. The accumulator
ENG 2 FIRE pushbutton is operated. A symbol on the HYD page of the ECAM
is pre-charged with nitrogen at 1885 psi ( 130 bar ) and holds 0.18 l ( 0.0475
system display shows if the fire valve is open or closed.
USgal ) of the useable fluid when it is full.
29-13
Page: 53
GREEN BLUE
PTU
YELLOW
LAF ACCUS 53
RAT MAN ON
A ( IF INSTALLED )
H FAULT U
ELEC PUMP
Y ENG 1 PUMP ELEC PUMP
OFF T
O ENG 2 PUMP H
D A
FAULT FAULT U FAULT
FAULT
Y
OFF
D
Page
OFF OFF T OFF
O
A 1 2 3 4 5 6
LH SPOILER 4 RH SPOILER 4
:
RUDDER LH FLAP WTB ALT PARK
BRAKE
RH FLAPMOTOR
RH THRUST
REVERSER
LEAK MEASUREMENT
MANIFOLD
ATA 27
S
Y BRAKE
FWC SDAC MANIFOLD
S
ELAC T
PTU E
M
Figure 28
PTU MANIFOLD HP MANIFOLD
SDAC
CARGO
DOOR
SELECTOR
VALVE
ENG 2 FIRE
Main Hydraulic Power
PUSH
SDAC
FRA US-T gs 6.7.98
FROM
CONSUMERS
SDAC
Yellow System
SDAC
Yellow System
29-13
Yellow System
29-13
YELLOW HYDRAULIC
COMPARTMENT
SYSTEM ACCU
For Training Purposes Only
RETURN FILTER
RESERVOIR
HP MANIFOLD
HP FILTER
Yellow System
29-13
Yellow System
29-13
ACTUATOR
AIR MANIFOLD
INDICATOR
WINDOW
QUANTITY INDICATOR
COMPENSATOR
SLIDE ASSY
For Training Purposes Only
VALVE
ASSY
DRAIN VALVE
OPEN
LINE END
FITTING
SHUT
Figure 30 Yellow Hydraulic System Components
FRA US-T gs 6.7.98 Seite: Page: 57
56
Main Hydraulic Power A319 / A320 / A321
Lufthansa Technical Training
Yellow System
29-13
Yellow System
29-13
Engine Driven Pump 3030GD HP Manifold 3011GM Case Drain Filter 3084GM
Yellow System
29-13
Yellow System
29-13
LOCATION
For Training Purposes Only
Blue System
29-12
tinue to operate if the supply of AC power comes from the APU. In this case,
29-12 compression of the nose landing gear stops the electric pump. A time delay
BLUE circuit keeps the electric pump in operation for two minutes after compression
GENERAL of the nose landing gear. This makes sure that the electric pump does not stop
HYDRAULIC immediately when the aircraft lands.
Most of the components of the system are installed in the Blue hydraulic
SYSTEMThe compartment is in the left-hand belly fairing, forward of the
compartment. If there is a total failure of the AC power supply (which causes the electric
main landing-gear compartment. The reservoir and the Low Pressure (LP) filter pump to stop), the RAT automatically operates and pressurizes the system. It
are not in the hydraulic compartment. They are in the left-hand belly fairing aft is also possible to operate the RAT from the flight compartment .
of the main landing-gear compartment. The case drain fluid from the electric pump assembly goes to the LP circuit
The system operates at a nominal pressure of 3000 psi (206 bar). It can through a check valve 2041GM and a filter 2084GM.
provide 32 l/min (8.45 USgal) from the electric pump.
It is possible to pressurize the High Pressure (HP) system from any of three The system has a pulsation dampener 2092GM installed immediately down-
different sources: stream of the electric pump. It smoothes the output of the electric pump. Also
- the electric pump, installed downstream of the electric pump are a pressure switch 2074GJ and a
- the Ram Air Turbine (RAT) check valve 2050GM. The pressure switch monitors the output pressure of the
electric pump. The check valve stops the flow of fluid toward the electric pump
- the ground supply connections.
if the system is pressurized from another source.
Operation of the system is usually automatic, but the crew can control parts of
the system from the flight compartment if required. The supply to all of the consumers goes through the HP manifold 2011GM. The
The Blue hydraulic system is made up of two main parts; supply to all of the consumers other than the slat motor and CSM/G also goes
- a HP circuit which supplies the consumers, through the Leakage Measurement System (LMS) manifold.
- a LP or return circuit through which fluid returns to the reservoir. A solenoid valve 2150GP on the HP manifold controls the flow of fluid to the
LMS manifold. The solenoid valve is operated from the maintenance panel
SYSTEM OPERATION 50VU. A HP filter 2048GM is installed on the system pressure inlet of the HP
manifold. A pressure relief valve 2063GM installed on the HP manifold protects
The electric pump 2075GJ usually pressurizes the HP circuit. the system from overpressure.
The electric pump starts automatically when one of the engines is started. It
then operates continuously until the two engines are stopped.The system accu- Two pressure switches 2151GN and 10CE-1 on the HP manifold monitor the
mulator makes allowance for any temporary decrease in pressure because of pressure in the system. The pressure switch 2151GN sends information to the
For Training Purposes Only
the response time of the electric pump. Two pushbutton switches (P/BSW) in ECAM and warning systems. The pressure switch 10CE-1 sends information
the flight compartment control the operation of the electric pump. The BLUE to the flight control system only. A pressure transmitter 2065GN also sends
ELEC PUMP P/BSW 2704GJ is on the overhead panel 40VU. The crew mem- pressure information to the ECAM and warning system.
bers use it to stop the pump when there is a fault. It is usually set to AUTO and
has the legends FAULT and OFF which come on as necessary. The BLUE The sampling valve 2187GM is installed on the HP manifold. It makes it pos-
PUMP OVRD P/BSW 2703GJ is on the maintenance panel 50VU. The legend sible to get samples of the system fluid for analysis.
ON on the P/BSW comes on when applicable. The P/BSW makes it possible to The priority valve 2064GM is also installed on the HP manifold. It stops the
start the electric pump on the ground when the engines are not in operation. supply of fluid to non-essential consumers (slats and CSM/G) if the pressure
in the system is too low.
If the two engines stop in flight, the electric pump of the blue system will con-
29-12
Page: 63
63
LH FLAP WTB EMER
RUDDER RH FLAP WTB GENERATOR
LH SLAT WTB
Page
RH ELEVATOR RH SLAT WTB LH SLAT MOTOR
LH AILERON RH AILERON
Sete
i
BLUE PUMP
OVRD
HYD
LEAK MEASUREMENT VALVES :
B G Y
10 7 8 9
SMOKE
OFF
SYSTEM
ACCU
ATA 27
SDAC
FWC ELAC
Figure 33
11
2
RAT
AUTO
FROM
CONSUMERS 3
SDAC 10
AUT
O
SDAC
CFDS
Main Hydraulic Power
SDAC
RAT
Blue System
SDAC
Blue System
29-12
Blue System
29-12
STA2296/FR50
LP FILTER
GROUND LEAK MEASURMENT
MANIFOLD
STA 2243/FR49
ELECTRIC PUMP FR 42
SYSTEM ACCU
HP MANIFOLD
For Training Purposes Only
HP FILTER
RESERVOIR
PULSATION DAMPER
Blue System
29-12
( P/B ) switch in the flight compartment makes it possible for the crew to stop
the electric pump.
It is also possible to pressurize the system with the electric pump when the en-
gines are stopped. A P/B switch on the maintenance panel 5OVU in the flight
compartment stops the automatic function and starts the electric pump. The
case drain fluid from the electric pump assembly goes to the LP circuit through
a check val ve 2041GM and a filter 2O84GM.
Blue System
29-12
Blue System
29-12
Blue System
29-12
Current Transformer 2770GM Case Drain Filter 2084GM LP Filter 2002GM HP Filter 2048GM
For Training Purposes Only
Blue System
29-12
The ground service panel for the Blue hydraulic system is in the left-hand
belly fairing, aft of the main landing-gear compartment.
The components and connections which are necessary to service the Blue hy-
draulic system (not including the pressurization connection for the reservoir)
are installed together in a group on it.On the ground, it is possible to pressurize
the system from a ground supply.
The system has self-sealing connections for a ground supply. They are
installed on the ground service panel of the Blue hydraulic system.
The ground service panel has these components on it:
• the ground test pressure and suction self-sealing connectors 2006GM and
2008GM,
• the Blue reservoir depressurization valve 2087GM ,
• the depressurization valve 2087GM of the reservoir,
• the drain valve 2264GM of the reservoir,
• the RAT control panel 2815GE.
For Training Purposes Only
Blue System
29-12
RESERVOIR
DEPRESSURIZITATION
VALVE 2087GM
RAT CONTROL PANEL (
RAT config 1 )
2
8
1
5
G
E
GROUND CONNECTION
SUCTION 2006GM
For Training Purposes Only
GROUND CONNECTION
DELIVERY 2008GM
RESERVOIR DRAIN
VALVE 2264GM
Maintenance Operations
29-00
Yellow and Green Hydraulic Pressurization
PRESSURIZATUON OF THE HYD. SYSTEMS
• Make sure that the ECAM hydraulic system page does not show any of
Blue Hydraulic System Pressurization these warnings:
- Low air pressure in the yellow or green reservoirs.
The BLUE hydraulic system is pressurized by an electric pump.
- Low fluid level in the yellow or green reservoirs.
In flight: automatically
On ground: automatically ,provided one engine is running
or when the BLUE PUMP OVRD pb sw has been pressed on the • On the overhead HYDR.panel 40VU push and release the yellow ELEC
maintenance panel. PUMP pb sw.
• Make sure that the ECAM hydraulic system page does not show any of - The ON legend illuminates.
these warnings: • Refer to the ECAM indication of the yellow system pressure and make sure
- Low air pressure in the blue reservoir. it is approximatly 3000 PSI.
- Low fluid level in the blue reservoir. • If the power transfer unit ( PTU ) pb sw on the overhead hydraulic panel
- OVHT ( Fluid Overheat ) 40VU is in AUTO the PTU automatically pressurizes the greeen hydraulic
• On the overhead HYDR panel ( 40VU ) make sure that BLUE ELEC PUMP system together with the yellow system.
pb sw is set to AUTO. • Green system pressure on the ECAM indication should be between 2400
- The OFF legend not illuminates. and 3100 PSI.
• On the maintenance panel 50VU lift the guard and push the BLUE PUMP
OVRD pb sw.
- The ON legend comes on.
• Refer to the ECAM indication of the BLUE system pressure and make sure
that it shows approximately 3000 PSI.
For Training Purposes Only
Maintenance Operations
29-00
Maintenance Panel 50 VU
HYD
BLUE PUMP LEAK MEASUREMENT
OVRD VALVES
B G
Y
RAT MAN ON A
FAULT U
ELEC PUMP
H OFF T H
ENG 1 PUMP ELEC PUMP O ENG 2 PUMP
Y FAULT Y
A
D FAULT FAULT U FAULT ON D
OFF OFF T OFF
O
29-22
AUXILIARY
HYDRAULIC
Power Supply:
POWER The RAT system gets electrical power from the DC system of the aircraft.
Hot Battery Bus 1 ( 701PP ) supplies 28 V DC to solenoid 1 on the RAT actua-
RAM AIR TURBINE tor through the automatic deployment logic. It also supplies solenoid 1 directly
GENERAL when the HYD OVRD switch ( 2805GE ) is operated. Battery No. 2 supplies 28
V DC directly to solenoid 2 when the ELEC OVRD switch ( 24XE ) is operated.
NOTE:
The Ram Air Turbine is available W A R N I N G:
in two different configurations IF YOU PUSH THE OVRD HYD PB ON 40VU OR THE OVRD
( Config 1 & 2 ). ELEC PB ON PANEL 21VU IN THE COCKPIT WHEN THE
• Configuration 1 is used on AIRCRAFT ELECTRICAL CIRCUITS ARE DEENERGIZED
early manufactured A320 ( BATTERIE 1 & 2 CONNECTED TO HOT BUS ) THE RAT WILL
aircraft DEPLOY !
• Configuration 2 is used on
A319 / A320 / A321 aircraft Monitoring:
When the RAT is in its stowed position, the system is monitored for faults. If
Purpose: a fault is found, the lower display unit ( DU ) of the ECAM shows the RAT
The RAT supplies the Blue main hydraulic system with hydraulic power in fault warning.
emergency conditions.When necessary an actuator extends the RAT automati- These faults
- the RAT williscause
not in a
itsRAT faultposition
stowed warning:( and no manual or automatic selec-
cally into the airflow.The flight and maintenance crews can also extend the RAT tion has been made to extend it ),
from the flight compartment. - the change-over valve in the ground check module is in the ”ground
check” position ( there is an unwanted electrical supply to the change-
Location: over valve ),
The RAT is installed in the left belly fairing FWD of the main landing gear.The - there is hydraulic pressure in the ”retract” side of the RAT jack ( the jack
For Training Purposes Only
RAT does not operate when in its stow position, but is on stand-by during the control module is in the wrong configuration ).
entire flight.
Only RAT Config 1 ( A320 ) :
Deployment Conditions: • To make sure that sufficient inlet pressure for the RAT is available, the air
Deployment of the RAT can be achieved with: pressure in the Blue system reservoir is monitored. A pressure transmitter is
installed on the air manifold of the reservoir. The pressure transmittersends
• manual operation of the pushbutton switch OVRD HYD 2805GE on the
information to the SDAC/FWC. If the air pressure during flight decreases to
HYD section of the overhead panel 40VU, or
less than 3.1 bar absolute ( 45 psi A ) a class 1 warning is given when the
• manual operation of the pushbutton switch OVRD ELEC 24XE on the aircraft lands.
overhead panel 21VU, or
• automatic into the airflow when there is a total loss of AC power ( when the
aircraft speed is greater than 100 kts ).The Blue auxiliary system then also
FRA US-T the
supplies gs aircraft
1.9.98 with electrical power through the constant speed motor/ Seite: Page: 74
generator ( CSM/G ) 8XE.
RAT Retraction:
It is only possible to retract the RAT from the RAT control panel when the air-
craft is on the ground.The RAT control panel is part of the Blue ground-service
panel, and the selector switches are in the flight compartment.
Auxiliary Hydraulic Power A319 / A320 / A321
Lufthansa Technical Training
1 XP
2 XP AUTOMATIC
DEPLOYMENT
703 PP
AIRCRAFT SPEED
> 100
kts
2805GE TO SOLENOID
24XE
For Training Purposes Only
NOTE:
RAT CONFIG 1 Shown !
RAT ACTUATOR
RAT RETRACTION
MODULE
GROUND CHECK
MODULE
RAT FRAME
LEG ASSEMBLY
For Training Purposes Only
RAT DOOR
engaged. The lower end of the leg assembly between the turbine and pump
contains a gerotor ( gear-type ) pump and a frequency wheel / pulse generator.
The gerotor pump supplies the pitch change mechanism with servo pressure.
The frequency wheel / pulse generator supplies turbine speed data during
ground test. The data is sent to the ground test connection in the RAT control
panel. The RAT ground test box uses the data during test of the RAT.
The pivot includes two microswitches. One microswitch monitors the turbine
index position and will stop the retraction of the RAT if the turbine blades are
not in the correct position ( this switch only operates until the leg assembly is
RAT Control Panel RAT Actuator & Leg Assembly RAT Ground Check Module
DEPLOY SOLENOIDS
SOLENOID
VALVE
NOTE:
If the stow switch is released during retraction the electrical power supply is
stopped and the RAT extends again !
If the turbine is not correctly lined up,and the stow selection is made,the RAT
will start to retract.When the leg gets to approx. 8 degrees from full extension
the turbine index switch operates and the RAT returns to the extended position.
• When the RAT is retracted set the ARM switch to the OFF position.
• Make sure the red warning light goes OFF.
For Training Purposes Only
NOTE:
The red warning light indicates that the RAT ground retraction module is still in
retract mode ( hydraulic pressurized )
”ARM” SWITCH
STOW SELECTED
301PP
5 LEG POS.
( >10° )
2
STOW POSITION
SWITCH
INDEX LOCK
MECHANISM
EJECTION JACK
For Training Purposes Only
5
MICRO SWITCH 4 MICRO SWITCH
SAFETY DEVICE
For Training Purposes Only
SCREW
SIGNAL FLAG
TO GROUND SOURCE
For Training Purposes Only
The de-icing device does not use external power sources. The heat is pro-
duced by the eddy current heating device. The heating device has two basic
components, an electrically conductive aluminium plate and an even number of
samarium cobalt magnets. The magnets are cicumferrentially mounted on a
stationary magnetic plate. When relative rotation take place, the flux field, when
it passes through the aluminium plate, produces a current. As aluminium has
an electrical resistance, power is generated which is than dissipated in the form
of heat.
RAT Installation
INLET PORT
( LOW PRESS )
DISCHARGE PORT
( HIGH PRESS. )
PIVOT
EJECTION JACK RAT FRAME
ATTACHMENT
EJECTION
DOOR LINK JACK 1GE
ATTACHMENT POINT LEG ASSEMBLY
DRAIN
CLOGGING INDICATOR TANK
AND FILTER
INDEX LOCKING
SHAFT PUMP HOUSING
LEAKAGE DRAIN
LINE
GEARBOX COVER
PLATE
FLUID LEVEL
SIGHT GLASS
FILL PORT
GEARBOX HOUSING
For Training Purposes Only
LEAKAGE DRAIN
LINE
RAT DOOR
TURBINE HUB
TURBINE BLADE
RAM AIR TURBINE 2GE
is pressurized, Before you do the retraction again, you must do the subsequent:
• the high pressure supply releases the ejection jack extend lock and retracts • press the warm up flow indicator in,
the RAT into the stow compartment, • align the index marks of the hub with the index marks on the leg so that the
• the return fluid from the ejection jack goes directly into the low-pressure index is in the correct position,
system of the aircraft. • put the STOW/RESET switch to the RESET position to reset the interlock
logic in the stow panel.
”ARM” SWITCH
STOW SELECTED
301PP
INTERLOCK INDICATION
LEG POS. > 10
INDEX LOCK
MECHANISM WARM FLOW
INDICATOR
For Training Purposes Only
2 COVER PLATE
SCREW
For Training Purposes Only
HYDRAULIC MOTOR
TO / FROM GROUND
SOURCE
2006GM
BLUE HYDRAULIC
GROUND SERVICE PANEL
2008GM
RAT GROUND
CHECKOUT UNIT
Note:
For further information refer to AMM Task 29-22-00-710-004 ( Config. 2 ) or
AMM Task 29-22-00-710-001 ( Config 1 )
Yellow System
29-24
29-24
YELLOW
POWER TRANSFER UNIT It also has a ratchet lock to keep it connected.When the isolation coupling is
AUXILIARY disconnected ( during ground maintenance operations only ), there is no
transfer of power.
Purpose:
HYDRAULIC
The aircraft has a power transfer system to transfer hydraulic power between
Operation
POWER
the Green and Yellow systems.
This is necessary if one of the engine pumps fails. It also makes it possible to The usual flight condition is the PTU system ”armed” ( the P/BSW set to AUTO
pressurize the Green system from the Yellow system for maintenance (with the and both solenoid valves deenergized open ) and the Green and Yellow hy-
Yellow system electric pump). draulic systems at the same pressure. Because the pressures of the two hy-
The power transfer system is always armed when the hydraulic systems are draulic systems are within 500 psi of each other the PTU does not turn.
pressurized. However, the crew can switch it off if necessary. The PTU automatically starts to operate when the pressure in one of the two
The connection between the two systems is mechanical. It is impossible for hydraulic systems is approximately 500 psi more than the pressure in the other
fluid to get from one system to the other. system.
A difference of pressure between the two systems moves the PTU servo valve
Location: and the variable cam. This causes a change in the stroke of the variable dis-
All components are installed in the main landing gear compartment. placement motor. When the pressure difference is approximately 500 psi the
change is enough to make the PTU start. Depending on the direction of move-
Electrical Power Supply ment of the servo valve, the variable displacement unit operates as a pump or
The power transfer system gets electrical power from the DC System of the as a motor.If the Green system has less pressure than the Yellow system, the
aircraft. The service bus 602PP supplies 28 V DC to the solenoid valves stroke increases to its maximum. The variable displacement ( Yellow ) unit op-
through the PTU switch. erates as a motor and the fixed displacement (Green) unit operates as a pump.
If the Yellow system has less pressure than the Green system the stroke de-
PTU Component Description creases to its minimum. The variable and fixed displacement units then operate
The main components in the power transfer system are: as a pump and a motor respectively.
- the PTU,
When the Yellow electric pump starts because of operation of the cargo doors,
- the solenoid valve (Green system),
movement of the flight controls is prevented. Electrical power is supplied to the
- the solenoid valve (Yellow system),
two solenoid valves 1012GL and 3012GL and the solenoid valve of the Yellow
- the isolation coupling,
leakage measurement system 3150GP. Thus no hydraulic power is supplied to
- the PTU switch.
For Training Purposes Only
Yellow System
29-24
Location
PTU Schematic
For Training Purposes Only
Yellow System
29-24
To prevent unwanted operation of the PTU when the aircraft is on the ground,
different switches and relays are installed in the aircraft. They operate together
to supply power to the two solenoid valves ( 1012GL and 3012GL ) under cer-
tain conditions.
The PTU will not operate if:
• the Yellow electric pump is in operation to close the cargo doors, or
• the aircraft is on the ground, only one engine is in operation and the parking
brake is ON, or
• the aircraft is on the ground, only one engine is in operation, the parking
brake is OFF and the nose wheel steering is deactivated,
• the PTU P/BSW on panel 40VU is set to OFF.
Because the solenoid valves are energized to close them, a 28 VDC supply is
necessary to automatically prevent operation of the PTU.
If no supply is available, the isolation coupling prevents operation of the PTU
during maintenance.
NOTE:
In addition the Flight Warning Computer ( FWC ) does a check of the PTU dur-
ing the start of the engines.
If the master switch of the engine 1 ( 2 ) is ON and the master switch of the
engine 2 ( 1 ) is OFF, the PTU is inhibited.
As soon as the master switches of engine 1 and engine 2 are in the ON posi-
tion, the PTU is no longer inhibited.
If there is now a difference in the Green and Yellow hydraulic system of more
For Training Purposes Only
than 650 psi during at least 4 s, the ECAM shows a PTU FAULT indication.
Yellow System
29-24
1802GL
1012GL
PTU P/B SW
602PP CLOSED WHEN
SET TO OFF
1801GL
28V DC
3811GX
GREEN PTU SOLENOID
VALVE ( ,ENERGIZED CLOSED )
ENERGIZED WHEN
CARGO DOORS/
ELECTRICAL
PUMP OPERATE
1804GL
11QG 12QG
1805GL
ENRGIZED WHEN
PARK. BRK. ON
For Training Purposes Only
1806GL
3112GL
YELLOW PTU SOLENOID
ENRGIZED WHEN
NLG COMPRESSED VALVE ( ,ENERGIZED CLOSED )
Yellow System
29-24
In addition the Flight Warning Computer ( FWC ) does a check of the PTU dur-
ing the start of the engines. If the master switch of the engine 1 ( 2 ) is ON and
the master switch of the engine 2 ( 1 ) is OFF, the PTU is inhibited.
As soon as the master switches of engine 1 and engine 2 are in the ON posi-
tion, the PTU is no longer inhibited.
If there is now a difference in the Green and Yellow hydraulic system of more
than 650 psi during at least 4 s, the ECAM shows a PTU FAULT indication.
For Training Purposes Only
< LAST LEG REPORT < LAST LEG REPORT CLASS 3 >
< LAST LEG ECAM REPORT < PREVIOUS LEG SYS TEST > ADR 1
REPORT INTERFACE TEST
GRD
< PREVIOUS LEGS REPORT < LRU REPORT >
IDENTIFICATION MAKE SURE THAT SEQUENCE
< AVIONICS STATUS < GRD SCAN OUTPUT TEST SHOWN ON THE NEXT PAGE
> IS DONE AFTER PUSHING
< SYSTEM REPORT/TEST THE START TEST KEY
< TROUBLE SHOOT DATA CURRENT >
POST STATUS
* SEND FLT REP PRINT *
< RETURN PRINT *
NEXT
PAGE
SYSTEM REPORT / TEST SYSTEM REPORT / TEST
NAV
< AIR COND
< ADR 1 IR 3 >
F / CTL >
Yellow System
29-24
For Training Purposes Only
Yellow System
29-24
sends signals to the ECAM and overhead panel. The message ”ELEC OVHT”
appears on the ECAM lower DU and the YELLOW ELEC PUMP/FAULT light
comes on.
The applicable messages appear on the STATUS page of the ECAM upper
DU.
If the temperature decreases, the warnings stop and a message on the STA-
TUS page gives the information that the electric pump is available.
Yellow System
29-24
A
YELLOW BLUE
3807GX 2706GJ
YELLOW
3808GX
BLUE
2707GJ
T
E
S
T
B
U
T
T
O 54
Figure Phase Unbalance Detector ( Blue & Yellow )
N
FRA US-T gs 4.9.98 Seite: Page: 102
105
I
N
D
I
C
A
T
O
R
L
I
G
H
T
Auxiliary Hydraulic Power A320
Lufthansa Technical Training
Yellow System
29-24
Yellow System
29-24
EXT PWR
GRD SERVICE ON
PTU
SFCC
LEAK
MEAS
URE
MENT
VALV
E(Y)
FWD / AFT CARGO
DOOR SELECTOR TD 10 sec
TD ON DROPOUT
A / C ON GROUND
For Training Purposes Only
EXT POWER ON
DC BUS 2
fied as B ) and three outlet ports ( identified as C, D and E ). Only one inlet port
from each pair is used, the ports which are not used are sealed.
In the manifold there are three check valves and three 2/2 - way valves. All of ON OFF OFF OFF
the valves are spring loaded poppet type valves. The 2/2 - way valves are
manually operated. They are only selected to open for ground maintenance
tasks.
HP MANIFOLD ( TYPICAL )
LEAK MEAS.
B SOLENOID VALVE
GROUND INTERNAL LEAK TEST SYSTEM It then goes through the valve which has been opened to supply the applicable
part of the aircraft.
System Description The pushbutton switch controls the solenoid valve. When the solenoid valve is
The ground leakage - measurement manifold and the solenoid valve are energized the supply of fluid goes only to the manual valves of the manifold.
installed in the high pressure ( HP ) circuit of the applicable system. The sole- Thus it is possible to control the supply of fluid to different parts of the aircraft.
noid valve controls the flow of the hydraulic fluid between the HP manifold and Thus no hydraulic power is supplied to the power transfer unit ( PTU )and the
the ground leakage - measurement manifold. flight controls.
When the Yellow electric pump starts because of the operation of the cargo
doors, the movement of the flight controls is prevented. Electrical power is sup-
plied to the solenoid valve 3150GP and the two solenoid valves l0l2GL and
3012GL.
6.0peration
The operation of the ground internal leak test system in each system is the
same.
A. During Flight
During flight, the solenoid valve is open ( de-energized ) and the 2/2-way
valves in the ground leakage-measurement manifold are closed. Inlet port A of
the ground leakage-measurement manifold gets HP fluid through the solenoid
valve.
The fluid divides into three flows. Each flow goes through the applicable check
valve to the outlet port of the applicable 2/2-way valve ( closed ). It then leaves
the ground leakage-measurement manifold through the applicable outlet port
(C, D or E) to supply the related systems.
Fluid also goes into the ground leakage-measurement through inlet port B. The
fluid divides into three flows. Each flow goes to the -nlet port of the applicable
2/2-way valve. The valve is closed and the flow of fluid stops.
B. During Ground Maintenance Tasks
For Training Purposes Only
During ground operation of the system, the applicable pushbutton switch on the
maintenance panel ( 50VU ) is set to close the related solenoid valve. This
means that the HP inlet port is closed and the HP supply port is connected to
LP return. No HP fluid goes to inlet port A of the ground leakagemeasurement
manifold.
A ground test rig and flow meter, connected to the applicable ground service
panel supply HP fluid to the system. The HP fluid goes through the HP man-
ifold to inlet port B of the ground leakage-measurement manifold. The HP fluid
divides into three flows and goes to the inlet ports of the three 2/2-way valves.
A B C
2/2 WAY VALVE
SELECTOR ( MANUALLY
LEKAGE OPERATED ) C
MEASUREMENT
MANIFOLD B
1146GM
2146GM A
3146GM
B HP - SUPPLY A HP - SUPPLY
SOLENOID FROM
VALVE
2150GP
3150GP
HP MANIFOLD
1011
2011
3011
PRESSURE RETURN
COLLECTOR TANK
OVERFLOW PIPE
PTU
CONSTANT SPEED
MOTOR / GENERATOR
For Training Purposes Only
System Monitoring
29-30
System Monitoring
29-30
For Training Purposes Only
System Monitoring
29-30
System Monitoring
29-30
For Training Purposes Only
System Monitoring
29-30
ting diodes (LED) and filament lamps which use the same supply. The DC bus
valve is set to.
l03PP supplies 28 V DC through circuit breaker l832GQ to the three low level
switches in the reservoirs. The indicator has a cylindrical case which contains a synchro. on one end of
the case there is the electrical receptacle. The indicator face is on the other
Gage-T ransmitter end. The indicator has three colored scales ( one for each reservoir ) and three
The gage-transmitter has four primary assemblies. They are lights which show which system the indicator is set to. Lighting of the indicator
face is given by three lights installed in the indicator. The Green and Yellow
• a float and arm assembly, together with a mechanism to change the move-
system indicators are LED; all of the other lights ( including the Blue system
ment of the arm so that it turns the synchron indicator ) are filament lamps.
• a synchro transmitter
System Monitoring
29-30
For Training Purposes Only
System Monitoring
29-30
System Monitoring
29-30
For Training Purposes Only
System Monitoring
29-30
Operation
ECAM ( Flight ) Warnings
The pressure switches ( 1384GH ), ( 2384GH ) and ( 3384GH ) monitor the air
pressure in each reservoir. Usually the reservoirs are pressurized to 3.5 bar
relative ( 50 psig ) ( 4.5 bar absolute ( 65 psia ). If the pressure decreases to
less than 2.5 + /- 0.1 bar absolute ( 37 + /- 1.45 psia ) ( l.5 + /- 0.1 bar relative
(22 + /- 1.45 psig ), the contacts of the pressure switch close. A discrete signal
is sent to the two SDAC which causes the ECAM system to show the applica-
ble warnings. A discrete signal which causes the applicable FAULT lights to
come on, is also sent to the overhead panel. The following warnings occur:
• the single-chime audio warning operates,
For Training Purposes Only
System Monitoring
29-30
For Training Purposes Only
29-30
Page: 125
12
5
SYSTEM DISPLAY
ENG / WARNING DISPLAY
HYD
GREEN BLUE YELLOW
Page
RAT ELEC
ELEC Sete
i
:
LOW AIR
PRESS
HYD B RSVR LO AIR PRESS
” LO AIR PRESS ”
LEGEND COMES
ON AMBER
SC
SDAC 1 / 2
28V DC
2386GH
2388GH
Figure 64
COMPRESSED
LGCIU 1
PTU
A
RAT MAN ON FAULT
H U
T ELEC PUMP
OFF
Y ENG 1 PUMP ELEC PUMP
O
ENG 2 PUMP H
D A
FAULT
Y
FAULT FAULT FAULT OFF
U D
OFF OFF T OFF
Main Hydraulic Power
O
FRA US-T gs 27.10.98
CFDS
29-30
CFDS
29-30
CFDS MENU
ECAM 1
GROUND SCANNING
Maintenance Practices
29-00
For Training Purposes Only
Maintenance Practices
29-00
For Training Purposes Only
Inspection Check
29-00
For Training Purposes Only
Inspection Check
29-00
For Training Purposes Only
General
29-00
For Training Purposes Only
SELF EXAMINATION
1 Which hydraulic systems are pressurized by an 6 What happens if the ”RAT MAN ON” pb switch is
EDP ? pressed ?
Answer: Answer:
4 Can the RAT be extended automatically on 9 What is the purpose of the Priority
ground ? Valves ?
Answer: Answer:
system ?
Answer:
Answer:
LEGENDE
LAF ACCUMULATORS LAF ACCUMULATORS PRESSURE
YAW DAMPER ( IF SYSTEM INSTALLED ) ( IF SYSTEM INSTALLED )
RETURN
A319 / A320 / A321
29 - 00
SUPPLY
PITCH TRIM
LANDING GEARS RUDDER CASE DRAIN
LH SLAT WTB RH SLAT WTB LH SPOILER 4 RH SPOILER 4
RUDDER LANDING GEAR
DOORS ALT PARK
LH AILERON RH FLAP WTB YAW DAMPER LH FLAP WTB
NOSE WHEEL BRAKE
LH ELEVATOR STEERING
LH SPOILER 5 RH AILERON PITCH TRIM FWD RUDDER LH FLAP WTB CSM / G
CARGO DOOR RH FLAP WTB
S
LH THRUST RH SPOILER 5 AFT LH SLAT
REVERSER RH ELEVATOR RH ELEVATOR LH SLAT WTB RH SLAT WTB
CARGO DOOR MOTOR
RH SLAT
MOTOR
LH ELEVATOR LH SPOILER 3 RH SPOILER 3
LH FLAP RH FLAP
LH SPOILER 1 RH SPOILER 1 MOTOR LH SPOILER 2 RH SPOILER 2
MOTOR
LH AILERON RH AILERON
RH THRUST
REVERSER
NORMAL HYD
LEAK MEASUREMENT VALVES
BRAKES BLUE PUMP
OVRD B G Y
10 7 8 9
A
RAT
&
GEN 1 LINE EMER GEN
RAT MAN ON A
FAULT U
H ELEC PUMP
Y ENG 1 PUMP ELEC PUMP
OFF T
O ENG 2 PUMP H
D A Y
11
FAULT
FAULT FAULT FAULT OFF D
U
OFF OFF
OFF T
O
1 2 3 4 5 6
LEAK LEAK LEAK
MEASUREMENT MEASUREMENT MEASUREMENT
MANIFOLD MANIFOLD MANIFOLD
SYSTEM ACCU
BRAKE
SEC SELECTOR
FAC VALVE SEC
ELAC FAC SDAC S ELAC
SDAC ELAC ELAC BRAKE
BSCU ELAC SEC SDAC
FWC
Y MANIFOLD ELAC P
FWC S
T FWC
S PTU
8 S 9 E
S M 7 S
P P
SYSTEM ACCU
4 4
1 5 11
SDAC SDAC
S S RAT
A A AUTO 2
FROM CONSUMERS
M M 6
M
CARGO DOOR
SDAC SELECTOR
VALVES 3
SDAC
M 10
A A
AUTO
FROM CONSUMERS
SDAC
SDAC A
SDAC SDAC
RAT CONFIG 1
ENG 1 FIRE ENG 1 FIRE
A ONLY
S
PUSH PUSH
SDAC
Basic Schematic
Hydraulic Power
M
SDAC