Autroprime102 Eng

This document provides information about connections and capacity for the Autroprime BSA-200 fire detection system. It includes details about loop and I/O connections on the main circuit board and panel bus. The system can support up to 2 detection loops with 127 devices each, as well as 8 repeater panels. Programmable inputs and outputs are listed, and the document describes how to interconnect the BSA-200 termination board with BU/BV operator panels via the panel bus.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views24 pages

Autroprime102 Eng

This document provides information about connections and capacity for the Autroprime BSA-200 fire detection system. It includes details about loop and I/O connections on the main circuit board and panel bus. The system can support up to 2 detection loops with 127 devices each, as well as 8 repeater panels. Programmable inputs and outputs are listed, and the document describes how to interconnect the BSA-200 termination board with BU/BV operator panels via the panel bus.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 24

Bring simplicity to life

Autroprime interactive fire detection system

ID:Autroprime102_Eng
BSA-200

Connections
 maritime version with 4 loops

ID:Autroprime102_Eng
BSA-200 J1:1 til J1:32
Loop 1: 25 – 28
Loop 2: 29 – 32
Relay 1: 19 – 21
Relay 2: 22 – 24
Note! 18 is +24V (for OC outputs)

2 open collector outputs: 16 and 17


2 monitored output. (24V): 12 – 15
2 monitored input: 9 - 11
2 supply voltage 24V: 5 – 8
(Note! Not 2 control outputs 24V!)

Charger: 3 and 4
Batteries: 1 and 2
ID:Autroprime102_Eng
BSA-200 J4:1 to J4:23
Serial port: 1 – 7
Operator panel 24 V 1: 8 and 9
Operator panel comm. 1: 10 and
11
Operator panel 24V 2: 12 and 13
Operator panel comm. 2: 14 and
15
Panel bus comm. out: 16 and 17
Panel bus comm. in: 18 and 19

2 non monitored inputs.: 20 - 23

ID:Autroprime102_Eng
BSA-200 fuses

F4 F3 F2 F1
24V2 24V1 Charg Batt
1A 1A 5A 5A

ID:Autroprime102_Eng
Autroprime – BSA-200 J3

Vcon
-V
PSF

ID:Autroprime102_Eng
Autroprime – capacity

Maximum numbers of;

Detection loops per fire alarm control panel (maritme) 2 (4)

Loop units per detection loop 127

Loop units per branch each detection loop 32

Alarm units per detection loop 40

Fire brigade-/information-/repeater panel per fire alarm control panel 8

Serial ports 1

Service port (connection to PC) 1

USB host ports 2

Ethernet RJ45 1

Languages supported 15

ID:Autroprime102_Eng
Autroprime – system capacity I/O

Main circuit board outputs

Monitored 24V DC 0,5 A outputs (standard* FAD1, FAD2) 2

Relay outputs (NC or NO) (standard alarm and fault relay) 2

Non-monitored collector outputs 2

Main circuit board outputs (programmable) 6


Main circuit board inputs

Monitored inputs 2

Non-monitored inputs 2

Main circuit board inputs (programmable) 4


* Default settings

Identical I/O-units as those used in the AutroSafe-system (in example BN-units)

ID:Autroprime102_Eng
Autroprime – configurable inputs

 Input for day/night mode


 Configurable inputs
 Input for “Morse signal”
 Input for muting of alarm bells and loop sounders
 Input for reset panel
 Input for silence bells
 Input for feedback for alarm/fault output
 Input for activating all fire alarm devices
 Input for monitoring FWRE (Fault warning routing equipment)

ID:Autroprime102_Eng
Autroprime – configurable outputs

 Configurable output (or General Output)


 Output for reset
 Output for silence bells
 Output for disablements
 Output for silence alarm
 Output for small alarm
 Output for alarm bells
 Output for external alarm signal (FARE)
 Output for external fault signal (FWRE)

ID:Autroprime102_Eng
Autroprime – I/O capacity on the panel bus

 Mimic driver BUR-200


 capable of driving 32 LEDs
 8 standard monitored inputs
 A maximum of 7 slave drivers
can be connected to 1 master
driver providing a total of 256
outputs and 64 monitored
inputs

ID:Autroprime102_Eng
Autroprime –
connection of panel bus

 Operator panel only

ID:Autroprime102_Eng
Autroprime –
connection of panel bus

 Operator panel

 Other panels

ID:Autroprime102_Eng
Autroprime – connection of panel bus

Power (Aux 2) Power (Aux 1)

Signal

ID:Autroprime102_Eng
Interconnection, BS-200 and BU/BV- panels

1
Panel BU/BV/BUR

Data BU/BV-B2
Data BU/BV-B1

Data BU/BV-A2
Data BU/BV-A1
J14 J13

24V Inn-2

24V Inn-1

24V Inn-2
24V Inn-1
BS-200
Termineringskort BSA-200
Termination board BSA-200

GND
A1
B1

A2
B2
0V

0V

0V

0V
+24V

+24V

+24V

24V
GND
1 2 3 4 5 6 71 2 3 4 5 6 7

Power-1

Power-2
Data

Data
Data
J4
Power
19 B2
Data Data
J1 BU/BV 18
A2

_
8
24V UT-2 Power-2
+ 7
Data 17 B1
A1 Data
BU/BV 16
_
6
24V UT-1 Power-1
+ 5

ID:Autroprime102_Eng
Interconnection, BS-200 and BU/BV- panels

1 2
Panel BU/BV/BUR Panel BU/BV/BUR

Data BU/BV-B2
Data BU/BV-B1

Data BU/BV-A2
Data BU/BV-A1
Data BU/BV-B2
J13

Data BU/BV-B1

Data BU/BV-A2
Data BU/BV-A1
J14 J13 J14

24V Inn-2

24V Inn-1

24V Inn-2
24V Inn-1
24V Inn-2

24V Inn-1

24V Inn-2
24V Inn-1

GND
A1
B1

A2
B2
0V

0V

0V

0V
+24V

+24V

+24V

24V
GND

GND
A1
B1

A2
B2
0V

0V

0V

0V
+24V

+24V

+24V

24V
GND
BS-200 1 2 3 4 5 6 71 2 3 4 5 6 7 1 2 3 4 5 6 71 2 3 4 5 6 7
Termineringskort BSA-200
Termination board BSA-200 Data

Data Power-1

J4
Power-2
Power
19 B2
Data Data
J1 BU/BV 18
A2

_
8
24V UT-2 Power-2
+ 7
Data 17 B1
A1 Data
BU/BV 16
_
6
24V UT-1 Power-1
+ 5

ID:Autroprime102_Eng
Autroprime – detection loops

 Adjustable loop current..  ..adapted to max loop cable resistance


 100 mA  50 Ω
 150 mA  31 Ω
 200 mA  20 Ω
 250 mA  11 Ω

ID:Autroprime102_Eng
Autroprime – default settings

 All loop units are recognized as alarm units (points),


 detectors
 manual call points
 fire alarm interfaces,
are placed in the detection zone; Default Detection Zone

ID:Autroprime102_Eng
Autroprime – default settings

 All outputs, recognized as ”Fire Alarm Devices”,


 FAD1, FAD2 (standard functionality)
 all BBR-200 units on the loop
 all BBR-110 units on the loop,
are placed in the alarm zone; Default Alarm Zone

ID:Autroprime102_Eng
Autroprime – default settings

 External Fire Alarm Routing Equipment (FARE):


Relay output # 1

 External Fault Warning Routing Equipment (FWRE):


Relay output # 2

ID:Autroprime102_Eng
Autroprime – default settings

 After the default configuration is saved, and a restart, an alarm


will be indicated as Default Detection Zone together with the
default name of the loop unit

The alarm will activate all sounders in the Default Alarm Zone
(relay #1)

ID:Autroprime102_Eng
Autroprime – standard alarm

Alarm
First detection zone in alarm
Default detection zone
A2004

ID:Autroprime102_Eng
Autroprime – changes in the configuration

 Points can be moved to new detection zones, alarm units to new alarm
zones
 Outputs and inputs can be given special functions (from the drop down
list), and a flexible “cause and effect” functionality is available.

This is easily done from the panel. To make changes just choose:
 Save configuration and restart the system
 A copy of the configuration can easily be saved on a USB memory
stick

ID:Autroprime102_Eng
Bring simplicity to life

ID:Autroprime102_Eng
ID: autroprime_technical_ eng. 2007-11-13