Autroprime102 Eng
Autroprime102 Eng
ID:Autroprime102_Eng
BSA-200
Connections
maritime version with 4 loops
ID:Autroprime102_Eng
BSA-200 J1:1 til J1:32
Loop 1: 25 – 28
Loop 2: 29 – 32
Relay 1: 19 – 21
Relay 2: 22 – 24
Note! 18 is +24V (for OC outputs)
Charger: 3 and 4
Batteries: 1 and 2
ID:Autroprime102_Eng
BSA-200 J4:1 to J4:23
Serial port: 1 – 7
Operator panel 24 V 1: 8 and 9
Operator panel comm. 1: 10 and
11
Operator panel 24V 2: 12 and 13
Operator panel comm. 2: 14 and
15
Panel bus comm. out: 16 and 17
Panel bus comm. in: 18 and 19
ID:Autroprime102_Eng
BSA-200 fuses
F4 F3 F2 F1
24V2 24V1 Charg Batt
1A 1A 5A 5A
ID:Autroprime102_Eng
Autroprime – BSA-200 J3
Vcon
-V
PSF
ID:Autroprime102_Eng
Autroprime – capacity
Serial ports 1
Ethernet RJ45 1
Languages supported 15
ID:Autroprime102_Eng
Autroprime – system capacity I/O
Monitored inputs 2
Non-monitored inputs 2
ID:Autroprime102_Eng
Autroprime – configurable inputs
ID:Autroprime102_Eng
Autroprime – configurable outputs
ID:Autroprime102_Eng
Autroprime – I/O capacity on the panel bus
ID:Autroprime102_Eng
Autroprime –
connection of panel bus
ID:Autroprime102_Eng
Autroprime –
connection of panel bus
Operator panel
Other panels
ID:Autroprime102_Eng
Autroprime – connection of panel bus
Signal
ID:Autroprime102_Eng
Interconnection, BS-200 and BU/BV- panels
1
Panel BU/BV/BUR
Data BU/BV-B2
Data BU/BV-B1
Data BU/BV-A2
Data BU/BV-A1
J14 J13
24V Inn-2
24V Inn-1
24V Inn-2
24V Inn-1
BS-200
Termineringskort BSA-200
Termination board BSA-200
GND
A1
B1
A2
B2
0V
0V
0V
0V
+24V
+24V
+24V
24V
GND
1 2 3 4 5 6 71 2 3 4 5 6 7
Power-1
Power-2
Data
Data
Data
J4
Power
19 B2
Data Data
J1 BU/BV 18
A2
_
8
24V UT-2 Power-2
+ 7
Data 17 B1
A1 Data
BU/BV 16
_
6
24V UT-1 Power-1
+ 5
ID:Autroprime102_Eng
Interconnection, BS-200 and BU/BV- panels
1 2
Panel BU/BV/BUR Panel BU/BV/BUR
Data BU/BV-B2
Data BU/BV-B1
Data BU/BV-A2
Data BU/BV-A1
Data BU/BV-B2
J13
Data BU/BV-B1
Data BU/BV-A2
Data BU/BV-A1
J14 J13 J14
24V Inn-2
24V Inn-1
24V Inn-2
24V Inn-1
24V Inn-2
24V Inn-1
24V Inn-2
24V Inn-1
GND
A1
B1
A2
B2
0V
0V
0V
0V
+24V
+24V
+24V
24V
GND
GND
A1
B1
A2
B2
0V
0V
0V
0V
+24V
+24V
+24V
24V
GND
BS-200 1 2 3 4 5 6 71 2 3 4 5 6 7 1 2 3 4 5 6 71 2 3 4 5 6 7
Termineringskort BSA-200
Termination board BSA-200 Data
Data Power-1
J4
Power-2
Power
19 B2
Data Data
J1 BU/BV 18
A2
_
8
24V UT-2 Power-2
+ 7
Data 17 B1
A1 Data
BU/BV 16
_
6
24V UT-1 Power-1
+ 5
ID:Autroprime102_Eng
Autroprime – detection loops
ID:Autroprime102_Eng
Autroprime – default settings
ID:Autroprime102_Eng
Autroprime – default settings
ID:Autroprime102_Eng
Autroprime – default settings
ID:Autroprime102_Eng
Autroprime – default settings
The alarm will activate all sounders in the Default Alarm Zone
(relay #1)
ID:Autroprime102_Eng
Autroprime – standard alarm
Alarm
First detection zone in alarm
Default detection zone
A2004
ID:Autroprime102_Eng
Autroprime – changes in the configuration
Points can be moved to new detection zones, alarm units to new alarm
zones
Outputs and inputs can be given special functions (from the drop down
list), and a flexible “cause and effect” functionality is available.
This is easily done from the panel. To make changes just choose:
Save configuration and restart the system
A copy of the configuration can easily be saved on a USB memory
stick
ID:Autroprime102_Eng
Bring simplicity to life
ID:Autroprime102_Eng
ID: autroprime_technical_ eng. 2007-11-13