KP STK 3 25 19a
KP STK 3 25 19a
KP STK 3 25 19a
Sign in sheet
Training site registration sheet
Quick Reference sheets
KP Manual KP
Strike Manual C
PRM Manual P
Feedback Form
Notepad
KP ?
Resources
• Local resources
• KP IS [email protected]
• Trussville Support [email protected]
• National Accounts [email protected]
• Training [email protected]
KP 2-1
2.75/ 3.75/ 4.75 Cylinder
Valve Assembly
PN12284
KP 2-1
275 / 375 / 475 Cylinder Brackets
KP 2-2
275 / 375 / 475 Cylinder Cover
•Lightweight
•Installs over existing bracket
•No need to alter existing
actuation or piping
•PN 25851
600 Cylinder & Valve Assembly
PN15196
KP 2-2
600 Cylinder Valve Assembly
PN15060
KP 2-3
Pneumatic Actuator for the
MODEL 600 Cylinder
PN 10147
KP 2-3
MODEL 600 Bracket
PN23184
KP 2-3
Mechanical Release Module (MRM)
PN18000
PN18001
KP 2-4
Mechanical Release Module (MRM)
KP 2-4
Amerex Gas Trip Assembly
PN12740
KP 2-4
Amerex Gas Trip Assembly
KP 2-4
Pneumatic Releasing Module (PRM)
KP 2-5, P
PRM
KP 2-5, P
Shown upside down
•Accumulator Block
•Connector Bridge
p/n 23540
New Piston Replacement,
completely encapsulated
Needs no maintenance
Like-Like replacement
PRM – Pneumatic Releasing Module
New Accumulator
backplate replacement
pn 25697
PRM
Second Generation
PRM End of Line Fitting
• This fitting is used as the
PN16506 termination point for the
detection tubing.
• Always check for leakage after
installation is complete.
• The sealing ball is required
for use with the end of line.
KP 2-5, P
PRM End of Line Fitting
KP 2-5, P
PRM DETECTOR TUBING
PN16557 - 25’ PN16579 - 100’
PN16551 - 50’ PN16552 - 150’
PN16556 - 75’ PN16554 - 300’
• Available in bulk length
• Cut to fit - easy to install
• Three year replacement life
• One temperature works for all
• Actuation Temp. 435°F
install in areas where the maximum ambient
temperature does not exceed 375°F.
PN 16860
Detection Tubing Cutter
KP 2-5, P
PRM Tube Support Clip
.25" DIAMETER
P/N 16506 END OF
LINE FITTING
P/N 16502 QUICKSEAL
FITTING 1/4"
• Required within one inch of the
end of the line fitting.
HOLE
KP 2-5, P
Teflon Backplate MRM & PRM
Original
Teflon Coated
Strike Control Unit
PN23826
C 10
Strike Control Unit
PN23826
C 10
Strike Control Unit
PN23826
C 11
Strike Detection
PN24168
C 13
Strike Cable
• Cables available in lead and extension segments
• A variety of lengths are available
• Color coded for easy identification; Blue-Pressure Switch,
Green-Detection, and Yellow-Actuation (page C 23 table 2.12)
C 13
Strike Actuation
PN24448
C 16
Strike End of Line Resistor
PN23474
• 470kΏ resistors
• 3 provided with the Strike unit
C 16
Strike Control Unit
• Two are required, not supplied with the unit
• 6 month in service life for the primary
PN24903
BATTERY REPLACEMENT LABEL
BATTERY IDENTIFICATION LABEL
C 17
Electric Actuation
• Used with the Strike Control Unit only
• Receives the #24448 Linear Actuator
• Threaded if additional enclosure is needed
KP 2-3a
Strike Release Module (SRM)
• Available with or without the
Amerex enclosure
• Receives the linear actuator #24448
• Can accommodate the gas trip
assembly #12740
PN26607 – w enclosure
PN26577
KP 2-4a
Nitrogen Actuation Cylinder
PN12856 Single cartridge actuation capabilities:
KP 2-6
Actuation Hose
KP 2-7
Amerex Nozzles
KP 2-7
Amerex Nozzles
• Original style
Fryer/Griddle
P/N 13729
Solid Fuel
Charbroiler
P/N 11983
Upright Broiler
P/N 11984
• Only 7 types
• Unique tip design for identification
Appliance & Plenum Range (4 Burner) Duct Nozzle
• Strainer – replaceable
P/N 11982 P/N 14178 P/N 16416
• No foil seal
• Metal nozzle cap
• Back shelf
P/N16853
KP 2-7
Amerex Nozzles
• New style
• Engraved for easy
identification
KP 2-7
Amerex Nozzle Swivel Adapter
PN 16440
To aim the nozzle at the
correct point on the hazard
KP 2-7
Detection System
Not a detector!
Detection System
JOB Links
Quick Response Links
They are constructed of two
metal struts held in tension
by a small, glass bulb that
ruptures at the appropriate
temperature rating.
Stationary load max = 55 lbs PN16226 - 286°
PN16227 - 360°
PN16445 - 450°
PN16446 - 500°
KP 2-9
Detection System
PN12327 - 280°
PN12328 - 360°
PN12329 - 450°
Globe K Link
• Fixed Temperature
• Bimetallic Solder
• 280° - 450°F
• Continuous Cable Run
• Globe Type K Only
Maximum Load = 50 lbs. (22.68 kg.)
KP 2-9
Detection System
NO ML Links!
KP 2-9
Detector Assembly
PN12508
• Detector Assembly
• Link Holder
• Detector Bracket
• Two EMT Connectors
• Test Link PN12891
KP 2-8
Detector Assembly
Amerex Conduit Offset
PN12507
Conduit Offset
KP 2-9
NO
KP 2-9
NO
KP 2-9
Amerex Corner Pulley
PN12309
• Used at Every Change in Direction
• Fits 1/2" EMT
• High Temperature Aluminum Alloy
• Integrated Mounting Holes
KP 2-8
Amerex Corner Pulley
PN16444
• Used at Every Change in Direction
• Fits 1/2" EMT
• Removable Pulley Wheel
• Compression Fitting
• Brooks Model CP-5
KP 2-8
Amerex Lanyard Network
•2’ Termination Segment
• Interconnection
Segments
• 22” or 11”
KP 2-9
Amerex Lanyard Network
KP 2-9
Amerex Lanyard Network
LINKSegment
Cable TO LINK–- PN17354
17354
KP 2-9
Amerex Lanyard Network
KP 2-9
Amerex Detection Cable
PN12553
• Cable
• Stainless Steel 7 x 7
480# Tensile Strength
• 500 Foot Spool
• 1/16” Cable Diameter
KP 2-8
Amerex Accessories
PN12276 - 3/8” NPT
PN12510 - 3/8” EMT
PN12512 - 1/2” EMT
PN14204 - 1/2” NPT
PN16502 – 1/4” TUBE
KP 2-10
Amerex Manual Pull Station
PN21481
KP 2-10
Amerex Gas Shutoff Valves
Amerex Mechanical Gas Valve
• 3/4" to 2“
• Heavy Duty Brass Body
• “Pull to Release” Actuation
• Can also be used with Strike
• Other Listed Valves with KP Sys.
- ASCO Mech. Gas Valve
- Ansul Mech. Gas Valve
KP 2-11
Amerex Gas Shutoff Valves
ASCO Electric
Gas Valve
• 1/2" to 3“
• 120 VAC Powered Open
• Manual Reset
Relay Required
KP 2-11
Amerex Manual Reset Relay
PN12526
For Use with an
Electric Gas Valve
KP 2-11
Amerex Vent Plug
PN10173
For Use in the Cylinder
Pneumatic Actuation Line.
• Prevents pressure build up in
the actuation line due to temp-
ature changes in the kitchen
• Required for each contained
actuation line
KP 2-14
Fastener
KP 2-16
Flexible Discharge Hose
KP 2-17
DESIGN
Section 3
Nozzles
PN11984 – .5 Flow Point (Upright Broiler, Single Burner)
KP 3-1
Duct Coverage
2 – PN 16416 51”- 84” Perimeter
P/N 16416
PERIMETER = 10” (25 cm)
+ 20” (51 cm)
10”
+ 10” (25 cm)
(25 cm)
+ 20” (51 cm)
PERIMETER = 60”(152 cm)
KP 3-2
Duct Coverage
2 - PN11983 1.5fp 100” Perimeter
• Unlimited length
• Unlimited changes
in direction
• Max. Diagonal dim.=37.2”
• 2 - PN11983 nozzles
total of 3 flow points
KP 3-2
Duct Coverage
3 - PN11983
150” Perimeter
• Unlimited length
• Unlimited changes
in direction
• Max. Diagonal dim.=55.9”
• 3 - PN11983 nozzles
Total of 4.5 flow points
KP 3-3
Plenum Coverage
KP 3-5
Plenum Coverage
KP 3-5
Appliance Specific Coverage
Single Vat Deep Fat Fryer
• PN13729 2fp Nozzle • Height 36" – 48”
• 19.5" x 25.38" Overall • Aimed at midpoint of hazard area
• 19" x 19.5" Cooking Area
KP 3-6
Appliance Specific Coverage
Single Vat Deep Fat Fryer
Low Prox. Coverage 36” MAX.
KP 3-7
Appliance Specific Coverage
Split Vat Deep Fat Fryer with Drip Board
• PN13729 2fp Nozzle • Nozzle Height 40” - 50"
• 14" x 21" Overall • Aimed at Midpoint of Hazard Area
• 14" x 15" Cooking Area
KP 3-8
Appliance Specific Coverage
Single Burner Range
18”
KP 3-9
Appliance Specific Coverage
Single Burner Range
KP 3-9
Appliance Specific Coverage
Range - 2 Burner
48”
• Nozzle placement directly over
44”
appliance center
KP 3-9
Appliance Specific Coverage
Range - 2 Burner
• 12" x 24" cooking area (2 burner)
• PN11982 1fp nozzle
• nozzle height 36” - 50"
• Nozzle placement directly over
appliance center
KP 3-10
Appliance Specific Coverage
•NFPA 96
10.2.7.3 – the addition of obstructions to spray
patterns from the cooking appliance nozzle (s)
such as baffle plates, shelves, or any
modification shall not be permitted.
Appliance Specific Coverage
SHELF
KP 3-11
Appliance Specific Coverage
BSM: Back Shelf Manifold Asy. – (P/N 17461 with nozzles)
KP 3-24-27
Appliance Specific Coverage
Range - 4 Burner
• 24" x 24" Cooking area (4 Burner)
• PN14178 2fp Nozzle
•Nozzle Height 18” - 50"
•Nozzle placement directly over
appliance center
KP 3-12
Appliance Specific Coverage
Griddle - Perimeter – 2fp - Low Proximity
KP 3-15
Appliance Specific Coverage
Wok
• 24" diameter maximum
• 14" diameter minimum
• PN11982 1fp nozzle
• Nozzle height 40” - 50"
• Nozzle located anywhere
within 1" diameter of center
of wok aimed at center of wok
KP 3-12
Appliance Specific Coverage
Griddle Aiming - Perimeter Nozzle
KP 3-13
Appliance Specific Coverage
KP 3-13
Appliance Specific Coverage
Griddle - Overhead – 2fp
KP 3-14
Appliance Specific Coverage
KP 3-15
Appliance Specific Coverage
KP 3-16
Appliance Specific Coverage
24”
• Maximum 2 layers of rock
•
24”
44”
• Nozzle Height 18” - 44"
18”
• Nozzle located anywhere over
the appliance aimed at the
center of hazard area
KP 3-16
Appliance Specific Coverage
Module Coverage for Larger Appliances
KP 3-11-14
Appliance Specific Coverage
6” MAX.. DEPTH
KP 3-17
Appliance Specific Coverage
Mesquite Chip & Chunks Charbroiler
• 24" x 28.5" Cooking Area
• PN11983 1.5fp Nozzle
• Maximum Depth 6"
• Nozzle Height 16” - 48"
• Nozzle located anywhere
48
6” MAX.. DEPTH
KP 3-17
Appliance Specific Coverage
Mesquite Logs Charbroiler
• 24" x 28.5" Cooking Area
• PN11983 1.5fp Nozzle
44 • Maximum Depth 11"
•Nozzle Height 19” - 44"
24 28.5 19
•Nozzle located anywhere
over the appliance aimed at
midpoint of hazard area
KP 3-17
Appliance Specific Coverage
• 30.5" Width
• 28.5" Depth
• 2 - 11984 .5fp Nozzle
• Upper nozzle located in the center of
the space above the grate, aimed to opposite corner
• Lower nozzle located below the grate aimed
toward the center of drip pan opening
KP 3-18
Appliance Specific Coverage
Salamanders & Cheese Melters
OPTION 1
• Up to 38” in length
• PN11982 1fp Nozzle
• Nozzle should be located in the
middle of the opening and aimed
at the rear opposite corner
KP 3-18
Appliance Specific Coverage
12"-36" NOZZLE
HEIGHT ABOVE
NOZZLE LOCATED IN THE APPLIANCE
CENTER OF THE IN-LET
OPENING
12"-36"NOZZLE
HEIGHT ABOVE
The nozzles are to be located
CATALYST
NEICO 9025
CHAIN BROILER
the catalyst.
KP 3-20
Model Specific Coverage
Duke Char-broiler
2 – PN13729 2fp
KP 3-21
AMCAD
PIPING
Section 3
Piping
TYPICAL DISTRIBUTION NETWORK FOR SINGLE CYLINDER SYSTEM
Duct
4 Feet Max. Supply Line Supply Branch
Nozzle
Plenum Branch
10 Feet Max.
Distributor
KP 3-31
Piping
TYPICAL DISTRIBUTION NETWORK FOR SINGLE CYLINDER SYSTEM
4 Feet Max.
Nozzle
Wok Branch
Fryer
Plenum Nozzle
10 Feet Max.
Supply Line Branch
Griddle
(Overhead)
Range
Distributor
KP 3-31
Piping
KP 3-31
Piping
KP 3-33
Piping Minimum
When designing a KP system to protect a kitchen containing a Fryer, Wok
or Range, the following MINIMUM TOTAL SYSTEM PIPING must be used in
accordance with the chart below:
PIPING REQUIREMENTS
Minimum Minimum total Minimum Flow Points
Appliance Linear Ft. Equivalent per System
Fryer 6.5 10 2
Wok 9 22.1 6
Range 7 16.4 4
KP 3-33
Piping Supply Line
ALL PIPE AND FITTINGS RUNNING FROM THE DISTRIBUTOR BLOCK
OR THE DISCHARGE FITTING TO THE FIRST SPLITTING TEE
CYLINDER MAX. LINEAR MAX.QTY. MAX. QTY. MAX. QTY.
FLOW POINTS PIPE SIZE FEET OF PIPE TEES ELBOWS BUSHINGS
KP 275 = 8 3/8 20 1 5 0
KP 475 = 14 1/2 25 1 5 2
KP 600 = 18 1/2 25 1 5 2
KP 3-33
Piping
KP 3-33
Piping
KP 3-33
Piping Supply Line
ALL PIPE AND FITTINGS RUNNING FROM THE DISTRIBUTOR BLOCK
OR THE DISCHARGE FITTING TO THE FIRST SPLITTING TEE
CYLINDER MAX. LINEAR MAX.QTY. MAX. QTY. MAX. QTY.
FLOW POINTS PIPE SIZE FEET OF PIPE TEES ELBOWS BUSHINGS
KP 275 = 8 3/8 20 1 5 0
KP 475 = 14 1/2 25 1 5 2
KP 600 = 18 1/2 25 1 5 2
KP 3-33
Piping Supply Branch
ALL PIPE AND FITTINGS LEAVING THE FIRST/SPLITTING TEE IN THE SYSTEM AND ENDING WITH
THE LAST NOZZLE IN THE LAST BRANCH LINE. WHILE THE LAST NOZZLE BRANCH IS INCLUDED IN
THE PIPING LIMITATIONS FOR THE SUPPLY BRANCH LINE, THE LIMITATION (PIPE SIZE AND
MAXIMUM LENGTH) FOR NOZZLE BRANCH LINES APPLY TO THIS PORTION OF THE SUPPLY
BRANCH LINE.
CYLINDER MAX. MAX. QTY.
MAX. FEET OF MAX. FEET OF MAX. QTY.
FLOW PIPE SIZE QTY. REDUCING
PIPE STRAIGHT PIPE SPLIT ELBOWS
POINTS TEES BUSHINGS
KP 275 = 8 3/8 20 25 7 8 0
KP 375 = 11 3/8 OR 1/2 27 30 10 8 2
KP 475 = 14 3/8 27 30 12 8 2
50’- 3/8" PIPE
KP 600 = 18 AS NOTED 35’ - 3/8" OR 1/2" 14 8 2
ONLY
40’ of ½” 45 of ½”
2KP 375=22 AS NOTED 18 8 0
(*30’ of 3/8”) (*30’ of 3/8”)
NOTE: IN A SINGLE KP 3.75 GALLON STRAIGHT PIPE SYSTEM, 5’ OF PIPE MAY
BE TRANSFERRED FROM THE SUPPLY LINE TO THE SUPPLY BRANCH LINE. *2.
THE USE OF 3/8” PIPE WITH TWO MANIFOLD KP375’S IS ONLY PERMITTED
WHEN THE SUPPLY LINE LENGTH IS EQUAL TO OR LESS THAN 20 FEET.
KP 3-33
Piping Nozzle Branch
ALL PIPE AND FITTINGS LEADING FROM THE SUPPLY BRANCH TEE TO A
SYSTEM NOZZLE.
CYLINDER FLOW TOTAL LINEAR MAX. QTY. MAX. QTY. MAX. QTY.
PIPE SIZE
POINTS FEET OF PIPE TEES ELBOWS BUSHINGS
KP275 = 8 3/8 32 5 10 0
KP375 = 11 3/8 OR 1/2 32 8 12 11
KP475=14 3/8 32 10 15 0
KP600 = 18 3/8 32 11 18 15
2-KP375 = 22 3/8 32 18 18 20
MAX. PER NOZZLE BRANCH 7 3 6 4
KP 3-33
Piping General Limitations
• Maximum of (4) flow points on each nozzle branch line
• Nozzles may be mixed on a nozzle branch
• Cylinder discharge fitting, hose and distribution block are not included in
the piping calculations. (old 375)
• A flex distribution hose is used in a nozzle branch line only
• When used, 48” of piping shall be subtracted from the overall allowable
pipe for a nozzle branch line (4’ of hose + 3’ of pipe = 7’ Max. nozzle branch
length)
• Any fitting (s) associated with the installation of a flex distribution hose
shall be counted against the overall nozzle branch piping limitations.
• No mixing of pipe sizes within a piping category (supply line, supply
branch line, nozzle branch line) is allowed. (i.e. one nozzle branch line is ½”
pipe – all nozzle branches are to be 1/2” pipe.
KP 3-15
Design Question
11982 •What size cylinder is this?
•Is this split or straight?
16416
11982
11984
13729
11982
13729
11982
11984
11983
14178
Design Question
•What size cylinder is this?
11982 •Is this split or straight?
16416
11984 11982
14178
14178
11982
13729
11982
13729
Design Question
•Griddle 30”X94”
•How many nozzles, what part
numbers, and how many flow
points to cover this?
Design Question
KP 3-44
Zone Defense
KP 3-44
Zone Defense
• The protected rectangular area is 34” (17” from the centerline of the
nozzles) x length of the hood.
KP 3-44
Zone Defense
•LENGTH OF HOOD
•HOOD DEPTH
•6” MAX.
•34” DEPTH
•20” MAX •20” MAX
ZONE of
PROTECTION •CENTERLINE
TOTAL FLOOD
NOZZLES
•17”
KP 3-44
Zone Defense
•6” •6”
MAX. MAX.
•20” MAX.
•ZD Nozzles •6” MAX.
•PN14178 (2xR)
•TOP OF APPLIANCE
•TOP OF APPLIANCE
KP 3-45
Zone Defense
The ZD nozzles cannot protect cooking appliances with an enclosed
cooking area such as an upright broiler or salamander.
• Enclosed appliances must be covered by the standard KP appliance
specific protections outlined in section 3 of this manual.
• No ZD nozzles are required above the appliance protected by a
dedicated nozzle.
• The location of appliance specific protection is fixed and the appliance
must remain in this location.
KP 3-44
Zone Defense Piping
KP 3-47
Zone Defense Piping
KP 3-47
Zone Defense Piping
KP 3-49
Zone Defense Piping
KP 3-49
Zone Defense Piping
KP 3-49
Zone Defense Piping
KP 3-49
DETECTION
Section 3
Detection
MRM
• Spot Detection
• Lanyard
PRM
Strike
• Linear
• Spot
MRM Spot Detection
Standard Spot Detection. A detector must be placed
over every protected appliance & hood duct opening.
KP 3-34
Detection MRM
MRM
• Maximum of 30 corner pulleys/either style
• Maximum of 30 detectors
• Maximum of 200 feet of cable
• No pulley tees allowed
• No manual pulls on the detection network
• One conduit offset may be used
(located only at the MRM)
KP 3-35
MRM Lanyard Detection
KP 3-36
MRM Lanyard Detection
Lanyard Network
• Cable segments are pre-fabricated to specific length placing detectors
every 12” or 24”
• Installation is faster and easier
• Allows movement of appliances under the protected area
• Eliminates the use of conduit, link holders and mounting brackets
under the hood in the plenum area
KP 3-36
MRM Lanyard Detection
KP 3-36
MRM Lanyard Detection
KP 3-36
MRM Spot Detection Lanyard Style
EXHAUST
DUCT
HOOD
MRM I
KP 3-35
Detection PRM
PN16506
KP 3-37
Detection PRM
KP 3-37
Detection Strike
PN23826
C
Detection Strike
• 2 detection circuits
• Uses spot heat detectors, linear detection wire, or both
• Maximum length of each detection circuit, 100’
• Can address single or multiple hazards
• Detection circuits may be used independently or in tandem
• It is permissible to integrate a manual device in the detection circuit
• Multiple layout options described in the Strike manual pages 26-30
C 26-30
Detection Strike
C 38-41
Detection Strike
C 38-41
Detection Strike
• Spot detectors may be placed every 24”
• Integrated quick seal
C 42,43
Detection Strike
C 26-30
Manual Pull Network
NFPA 96
10.5.1.1
At least one manual pull activation device shall be
located in a means of egress or at an alternate
location acceptable to the AHJ
Manual Pull Network
KP 3-38
Strike Manual Pull Network
C 30-32
Manual Pull Network
Accessible?
Manual Pull Network
Accessible?
Manual Pull Network
Accessible?
Manual Pull Network
Accessible?
Mechanical Gas Valve
KP 3-39-41
Strike Relay Module
OPTIONAL AC
DEVICES
(AUX ALARMS,
HORNS, FANS,
MOTORS, PUMPS,
APPLIANCES, ETC.)
C 39-41
Strike Relay Module
• 2 types; electric gas shut off only and gas shut off with
auxiliary relays
• For use with the Strike when a mechanical gas shut off is
not needed
C 39-41
INSTALLATION
Section 4
Installation PRM
KP 4-4
Installation PRM
KP 4-4
Installation PRM
KP 4-5
Installation PRM
KP 4-5
Installation PRM
1. Remove knurled nut from plated tube fitting
and slide over end of tubing.
2. Cut tubing square without collapsing
3. Firmly push the end of the tube over the end
of the fitting, it must go all the way over the
fitting
4. Tighten the fitting until you feel the resistance
of the nut bottoming out.
5. Do not over tighten.
KP 4-6
Installation Detection Bracket
Position link holder and link
in center (or slightly off center
away from MRM) in bracket`
Terminal Clamp
(P/N 12859)
KP 4-8
ACTUATION
Section 4
Actuation Network
Actuation Network
KP 4-11
Actuation Network
PN10173
KP 3-29,4-14
Actuation Network
KP 3-29,4-14
Actuation Network
KP
Actuation Network
KP 3-29,4-15
Actuation Network
KP 3-29,4-15
Actuation Network
Pipe must be fitted tight (three turns past hand tight recommended).
All threaded connections in the actuation network must be sealed with
Teflon tape (applied to male threads only).
Starting with the third thread from the pipe opening, wrap the Teflon tape
clockwise around the threads moving away from the pipe opening.
Make certain that tape does not extend past the end of the pipe – it could
dislodge and possibly block the actuation network.
KP 4-15
Actuation Network
Actuation circuit from
Strike to cylinder is Strike Actuation
housed in conduit Strike to
cylinder only
KP 4-2a,b
Actuation Network
Actuation circuit from
Strike to cylinder is Strike Actuation
housed in conduit
Strike to
cylinder with J
Box
KP 4-2a,b
Actuation Network
Strike Actuation
Actuation circuit from Strike to Strike to pneumatic
SRM is housed in conduit
nitrogen line
Regular KP
actuation
network and
Cylinder
capability
KP 4-7a
Installation Cable Lines
KP 4-11
Installation Manual Device
KP 4-12
Installation T Pulley
Manual Pull Stations
Cable Connector is Farthest
From Pulleys in Set Position
KP 4-13
Installation T Pulley
KP 4-13
DISCHARGE
Section 4
Installation Actuation/Distribution
KP 4-14
Installation Actuation/Distribution
For pneumatic actuation, secure the pneumatic line into
each cylinder
For electric actuation, ensure actuator #24448 is threaded
all the way and is fully bottomed out against the assembly
KP 4-14-15
Installation Actuation/Distribution
KP 4-15,16
Installation Actuation/Distribution
• Gas valve cable limitations are the same as manual pull; 130’
maximum and 20 corner pulleys
• Install the Gas Trip Assembly, 12740
• Gas valves cable requires a travel of 1/2” to close the valve
• If a tee pulley is used, set position of connector in the tee pulley
should be as close as possible to the pulley bearings
• Gas valve listings and limitations apply to Strike SRM use and
MRM PRM use
KP 4-17
Installation Gas Valve
• Gas valve trip assembly p/n 12740 must be purchased when using
an Ansul gas valve or an ASCO “pull to release” valve
• Both a gas valve trip assembly p/n 12740 and a conversion kit p/n
13622 must be purchased when using ASCO valves
• Make certain that the gas line is free of debris, shavings, pipe dope
etc. Contaminants in the line may prevent the gas valve from
sealing properly
KP 4-17-19
Installation Gas Valve
C
TESTING
Section 5
Testing and Commissioning
KP 5-1,3
Testing and Commissioning
KP 5-1,3
Testing and Commissioning
KP 5-1,3
Testing and Commissioning
• Offer-training-whenever-possible
KP 5-1,3
Testing and Commissioning
Testing and Commissioning
Strike Testing and Commissioning
C 68-72
MAINTENANCE
Section 6
Maintenance
Maintenance
Maintenance
Owner Maintenance
• Do not add, delete, move or change any part of the hood & duct,
appliances, or fuel source without contacting your Amerex KP
systems distributor
Semi Annual Maintenance
Always Remember
systems distributors
KP 6-1
Semi Annual Maintenance
KP 6-1
Semi Annual Maintenance
KP 6-1-3
Semi Annual Maintenance
Function test control devices;
KP 6-1-3
Semi Annual Maintenance
Function test control devices;
KP 6-1-3
Semi Annual Maintenance
• Agent cylinder - first test at 12 years, 480 psi, tester must have
DOT RIN number. Volumetric or proof pressure testing determines
the next testing date.
• Actuation hoses - 12 years 3500 psi
• Distribution hose - 12 years 480 psi
• Nitrogen cylinder - not required per DOT and NFPA 17a
• PRM accumulator to be replaced every 12 years
KP 6-1-3
Semi Annual Maintenance
• Ensure that owner or end user has a copy of the owners manual and
understand the instructions in the owners manual
KP 6-3
Semi Annual Maintenance
NFPA 17A
KP 7-1-4
Reset & Recharge
• Repeat all the same steps listed for semi annual maintenance
• Reset all devices to functioning
• Recharge agent cylinders and nitrogen actuation cartridges
• Have enough agent on hand at all times
• See instructions for charging nitrogen cylinder
(in the KP manual and online at training.Amerex-fire.com)
• Use only Amerex KP agent
KP 7-1-4
Reset & Recharge
KP 7-7
Reset & Recharge
KP 7-7
EXAM
Section _
Exam
• Write your name and company name legibly on the answer sheet
• Open book exam
• Return the answer sheet and feedback form from the back of
your book.
• Leave