Chapter 1
Chapter 1
LECTURE NOTE of
ELECTRICAL POWER SYSTEMS
(EMEg - 3131 )
OUTLINE
AC and DC transmission
Single-phase and three-phase transmission
Complex power
Structure of a power system
Representation of power system components
Single-phase solution of balanced three-phase networks
One-line diagram and impedance or reactance diagram per unit (PU)
3
Chapter 1. Fundamentals of Power Systems
System – Refers to an interconnection of various elements to act together.
Electrical Elements
Voltage Source
Current Source
Resistive, Inductive and Capacitive elements and
Electrical control and protection elements 4
Fundamentals of Power Systems Cont’d
Power System – is an interconnected network, consisting of :
Major Generating Stations
Power Transmission Systems and
Distribution Systems
Loads
☞ Generating stations and Distribution Systems are connected through
transmission systems to supply electricity to consumers .
The six main components of a power system are:
Power Plant,
Power Transformer,
Transmission Line,
Substation,
Distribution Line and
5
Distribution Transformer.
Overview of Power Systems
6
Overview of Power Systems Cont’d
Generation Station: source of power, ideally with a specified voltage and
frequency.
The major source of primary energy are :-
Fossil fuels (coal, natural gas, oil), Hydro power, Nuclear power, Solar energy,
Geothermal energy, Wind energy, etc.
☞Power Transmission System :- refers to the bulk transfer of power by high-
voltage links between central generation and load centers. It consists of:
☞ Power Transformer - a static electrical device used to step up or step down a.c.
voltage from one level to another. (usually rated above 2500 kVA)
☞ Transmission lines - have resistance, inductance, capacitance and flow limitations.
Used to transmit power from generating stations to substation and sub-
transmission customers( Voltage level above 33kV). And
☞ Substations :- consists of switchyard, switchgear and control room components.
Used for controlling and switching of the supplied power, as well as for
protecting power equipment from damage. 7
Overview of Power Systems Cont’d
Distribution Systems :- connects all the loads in a particular area
to the transmission lines. It consists of:
Distribution Transformer - a static electrical device used to convert the
distribution voltage down to the final consumption level. (usually rated
below 500 kVA)
Distribution Lines - Used to transfer power from substation step down
transformers to distribution transformers and final consumers(Voltage
level < 33kV).
☞ Loads :- The major consumption groups are industrial, residential
(domestic) and commercial.
8
Structure of Power System
Generation, Transmission and Distribution systems are the main component
of an electric power system.
Generation stations and Distribution systems are connected through
transmission line.
Distribution system is mainly responsible for the conveyance of power to the
customer by means of lower power.
Electric power is generated at a specific voltage magnitude and stepped up
by step up transformers to transmits it in transmission network.
The network which receives all the generated power is called the super grid.
A grid can feed a sub station network.
9
Structure of Power System Cont’d
Part of typical power system
10
Structure of Power System Cont’d
Power Supply Network is divided in to Transmission and Distribution network.
Transmission Network
Primary System
Secondary (Sub-transmission) System
Distribution Network
Primary Distribution System
Secondary Distribution System
Distribution network contains
Higher number of branches
Higher number of sources
Several 3-phase Step-down transformer
3-phase 4-wire lines (220 V)
11
Structure of Power System Cont’d
Typical Distribution System
12
AC and DC Transmission
Two ways to transport electricity – Alternating current (AC) and Direct
current (DC).
DC transmission – is the first form of power transmission, but as
distances and loads increase, voltage problems were encountered. Then
The limitations of maximum distance and load were overcome with
development of ac transformer used in AC Transmission.
Later HVDC(High Voltage DC) transmission embedded in an ac system,
by using solid-state converters at both ends of the dc line operating as
rectifier and inverter.
Since the cost of an HVDC transmission line is less than that of an ac line
with the same capacity, but the additional cost of converters for dc
transmission is offset when the line is long enough.
Generally assumed that overhead HVDC transmission is economical for
transmission distances longer than about 600-800 km.
13
AC Transmission
AC (Alternating Current)- is a time varying quantity and it oscillates 60 (50)
times a second.
Advantages
It can deliver power to loads over vast distances using transformers.
AC generators are easier to build than DC generators.
Disadvantages
Very hazardous. Susceptible to voltage surges.
Complex system for analysis, computer with power system analysis software has saved
engineers.
Frequency disturbance in one system is transferred to other system
Power swing in one system may affect the other system. Major fault in one system may lead to the
complete failure of the system. 14
DC Transmission
DC (Direct Current)- is a time
constant quantity. Disadvantages
Advantages Generation of power at high DC voltage is difficult.
It needs fewer conductor than AC Needs extra power electronic equipment (rectifier and
inverter).
Voltage drop in DC is less than AC transmission for
the same load and transmission end
Dc lines have less corona loss and reduced
interference with communication systems
Stable than AC transmission.
Can interconnect two AC system of different
frequency.
Fast and reliable control of magnitude and direction of
power flow by controlling firing angle.
15
Instantaneous Power In Single-phase Ac Circuits for RLC Load
☞ The instantaneous power :- absorbed by an electrical load is the product of
the instantaneous voltage across the load in volts and the instantaneous
current into the load in amperes.
☞ For AC circuits, the voltage and current are
v(t) = VM cos(t+v)
i(t) = IM cos(t+i)
The instantaneous power is simply their product
17
General RLC circuit
Average power
To calculate average power (integrate power over one cycle and divide by period)
t 0 T t 0 T
1 1
P=
T
t0
p(t) dt =
T V
t0
M cost v I M cost + i dt
1
= VM I M cos v - i
2
Since, Irms = I = IM/2 and Vrms = V = VM/2
P = VI cos v - i
Recall that passive sign convention says:
P > 0, power is being absorbed
P < 0, power is being supplied
18
Real and Reactive Power
Real (or average) power (Watts) :- Which is the actual power absorbed by the element
P = VI cos v - i
Examples Electric Heater , Electric Stove , oven Toasters, Iron …etc
Reactive power (VAR) :- Which is the reactive power absorbed or delivered by the element
Q = VI sin v - i
Reactive power represents energy stored in reactive elements (inductors and capacitors). Its unit is
Volt Ampere Reactive (VAR)
19
Complex Power
Complex power is the complex sum of real power and reactive power
S = P JQ
We can compute the average and reactive power from the complex power (S)
complex power provide a geometric interpretation
P = Re al ( S ) ( S ) cos v - i Q = Im ag ( S ) ( S ) Sin v - i
S=I2rms Z
Z Re( Z ) j Im(Z ) Z cos Z j sin Z
V2 2
PR = VI R IR R W
R
VI R sin 2t
Purely Resistive Load Cont’d
Purely Capacitive Load
Driving voltage is
VC= = VMsin(t)
Differentiate to find current
q= CVMsin(t)
i=
Current “leads” voltage by
The instantaneous power absorbed by the capacitor is
1
PC t = V (t )iC t VM I M sint sin t 90 VM I M sin 2t 90 VI C cos2t W
2
The instantaneous power injected by a capacitor is also a double-frequency sinusoid with
zero average value.
Therefore, a purely Capacitive Load injects only Reactive Power
23
Purely Capacitive Load Cont’d
24
Purely Inductive Load
Voltage is
VL== VMsin(t)
Integrate to find current
sin(t)
i=
Current “lags” voltage by
The instantaneous power absorbed by the inductor is
1
PL t = V (t )i L t VM I M sin t sin t 90 VM I M sin 2t 90 VI L cos2t W
2 inductor is a double-frequency
The instantaneous power absorbed by the
sinusoid with zero average value.
Therefore, a purely Inductive Load absorbs only Reactive Power
25
Purely Inductive Load Cont’d
26
Time Phasor
V = IR
V = jLI
V =I/ jC
27
Power Factor
average power P
pf = =
apparent power V rms I rms
V rms I rms cos v i
=
= cos v i = cos Z L
V rms I rms
Power factor angle is v- i = ZL (the phase angle of the load impedance)
28
Power Factor Cont’d
☞ power factor (pf) special cases :
purely resistive load: ZL = 0° pf=1
purely reactive load: ZL = ± 90° pf=0
29
Example 1
Q1: Determine the average and reactive power delivered by the source.
10 30
The phasor current leaving the source is Î 1.86 98.2
2 j8 j3
The average power delivered by the source is:
1
PAV,source Re 10 30 1.86 98.2
*
2
1
Re 10 30 1.8698.2
2
9.28cos 30 98.2 3.45W
30
The reactive power delivered by the source is:
1
Qsource Im 10 30 1.86 98.2 *
2
1
Im 10 30 1.8698.2
2
31
Q2: Determine the average power and reactive power delivered to each
element
The voltage across the elements are: Î 1.86 98.2
ˆ 2Iˆ 2(1.86 98.2 ) 3.71 98.2 V
VR
32
Q3: Show that conservation of complex power, average power, and reactive power is
achieved.
Pˆsource Pˆ R Pˆ L PˆC
3.45 j8.62 3.45 j0 0 j13.79 0 j5.17
33
Power In Balanced Three-phase Circuits
• In the case of three-phase the same pattern exists, except that three-phase
consists of three separate and distinct single-phases with voltages of equal
amplitudes and phase differences of , which are combined so that they can be
transmitted over three wires.
Vc Ic
120º
Va
Ib Ia
Vb 120º
34
Power In Balanced Three-phase Circuits Cont’d
Assuming that the system is balanced which means that the three-phase
voltage and current magnitudes (V or I) are the same for all three phases and
they have a phase shift of -120 and 120. It can be expressed mathematically
as follows:
𝑉 𝑎=𝑉 𝑚 sin 𝜔 𝑡 𝑉 𝑏=𝑉 𝑚 sin ( 𝜔 𝑡 −120 ° ) 𝑉 𝑐 =𝑉 𝑚 sin ( 𝜔 𝑡 +120 ° )
𝑖𝑎= 𝐼 𝑚 sin ( 𝜔 𝑡 − ∅ ) 𝑖𝑏 = 𝐼 𝑚 sin ( 𝜔 𝑡 − ∅ −120 ° ) 𝑖𝑐 =𝑉 𝑚 sin ( 𝜔 𝑡 +120 ° )
Therefore, for balanced three phase system, the total instantaneous power is equal to average (real) power, which is constant.
35
That is one of the reasons for using three phase system in addition to a need for bulk power transfer compared to single phase.
Power In Balanced Three-phase Circuits Cont’d
Connection Types
There are two types of connections in three-phase circuits: Y(Wye) and
Δ(Delta) or Combined.
36
Power In Balanced Three-phase Circuits Cont’d
A three-phase circuit may be connected either in wye or in delta. In a balanced three-
phase circuit the phase and the line values of the current, power, and voltage are related
as follows (the subscripts p and l refer to phase and line values, respectively):
Y-connected sources are most common to avoid circulating currents when there is a
small imbalance
Δ-connected loads are most common to allow easy addition and removal of loads in
each phase
Power In Balanced Three-phase Circuits Cont’d
The delta and wye impedances are related by:
For both types of connections, the apparent and reactive powers are,
respectively,
From the above, it is clear that the phrase angle may be obtained as:
38
Example
For a 208-V three-phase ideally balanced system shown below,
Find:
a) The magnitude of the line current
b) The magnitude of the load’s line and phase voltages and ;
c) The real, reactive, and the apparent powers consumed by the load;
d) The power factor of the load.
39
Solution
Both, the generator and the load are Y connected, therefore, it’s easy to construct a per-phase equivalent circuit
a) Phase current
40
Solution Cont’d
c) The real power consumed by the load:
41
Representation of power system components
The basic components of a power system are generators, transformers,
transmission lines, and loads.
The following Figure shows the symbols used to represent the typical
components of a power system.
42
Representation of power system components Cont’d
The interconnections among these components in the power system
may be shown in a so-called one-line diagram.
47
The Per-Unit System Cont’d
48
The Per-Unit System Cont’d
Choice of Base values
For a connected circuit, it is obvious that the same bases should be
used for the whole network.
In a transformer, two circuits are not directly connected but
magnetically coupled. The voltages of the windings are in the ratio of
turns and currents in inverse ratio.
For the coupled circuit, we should then choose
»The same base power
»Base voltages in the ratio of turns
This will ensure Spu, Vpu, Ipu, to remain unchanged when passing through an
ideal transformer 49
The Per-Unit System Cont’d
50
The Per-Unit System Cont’d
If Different Base values are Given
If the per unit values are given based on SB1 and VB1which
are different from the chosen base SB2 and VB2 for analysis,
the given per unit values must be modified before they can be
used. Thus,
51
The Per-Unit System Cont’d
52
The Per-Unit System Cont’d
Advantages of per unit system
I. It deal with numerics near unity rather than over a wide range.
II. Provides a more meaningful comparison of parameters of machines
with different ratings.
III. Circuit analysis of systems containing transformers of various
transformation ratios is greatly simplified.
IV. The p.u systems are ideal for the computerized analysis and simulation
of complex power system problems.
V. The ohmic value of impedances are referred to secondary is different
from the value as referred to primary. However, if base values are
selected properly, the p.u impedance is the same on the two sides of
the transformer.
VI. The circuit laws are valid in p.u systems, and the power and voltages
53
Example
• A 300 MVA, 20 kV three-phase generator has a subtransient reactance of 20%. The generator
supplies a number of synchronous motors over 64-km transmission line having
transformers at both ends, as shown in Fig. below. The motors, all rated 13.2 kV, are
represented by just two equivalent motors. Rated inputs to the motors are 200 MVA and 100
MVA for M1 and M2, respectively. For both motors X” = 20%. The three phase transformer T1
is rated 350 MVA, 230/20 kV with leakage reactance of 10%. Transformer T2 is composed of
three single-phase transformers each rated 127/13.2 kV, 100 MVA with leakage
reactance of 10%. Series reactance of the transmission line is 0.5 Ω/km. Draw the impedance
diagram, with all impedances marked in per -unit. Select the generator rating as base in
the generator circuit.
54
Solution
55
Solution Cont’d
56
Solution Cont’d
57