Building Bylaws and Codes-6
Building Bylaws and Codes-6
Class -6
B.Arch Vii sem
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS
and the buildings which are of 15 mt. and above in height and low
Educational (more than two storeyed and built-up area exceeds 1000
sq. mt., Business (where plot area exceeds 500 sq. mt., Mercantile
• The concerned Authority shall refer the building plans to the Chief Fire
identified as above.
• The Authority shall furnish three sets of complete building plans along
with prescribed fee to Chief Fire Officer, after ensuring that the
• The plans shall be clearly marked and indicate the complete fire
building with suitable legend along with standard signs and symbols on
the drawings.
PROCEDURE FOR CLEARANCE FROM FIRE SERVICE …
Consultant/Architect.
• The Chief Fire Officer shall examine these plans to ensure that they are in
accordance with the provisions of fire safety and means of escape as per
these bye- laws and shall forward two sets of plans duly signed for
building shall approach the Chief Fire Officer through the concerned
Authority for obtaining clearance from fire safety and means of escape point
of view.
• The concerned Authority shall ensure that clearance from Chief Fire Officer
has been obtained for the building before granting the completion certificate.
• On receipt of the above request, the Chief Fire Officer shall issue the
owner /builder.
RENEWAL OF FIRE CLEARANCE
Consultant, the Chief Fire Officer shall renew the fire clearance in respect
others.
GENERAL
• Type of Exits
• Number of Size of Exits
• Arrangements of Exits
• Occupant Load
• Capacity of Exit
• Staircase Requirements
• Minimum Width Provision for Stairways
• Minimum Width Provision for Passageway/Corridors
• Doorways
• Stairways
Fire Escapes or External Stairs:
a) Fire escape shall not be taken into account while calculating the number
c)Entrance to the fire escape shall be separate and remote from internal
staircase.
d)The route to fire escape shall be free of obstructions at all times except the
doorway leading to the fire escape which shall have the required fire
resistance.
f)Fire escape stairs shall have straight flight not less than 125 cm wide
case width of the same shall not be less than the width of the main
tower.
Spiral Stairs
b)A spiral stair shall not be less than 150 cm in diameter and
the R.C.C. construction having the fire resistance of not less than
two hours.
escape.
• The door shall be fitted with the check action door closers.
• The staircase enclosures on the external wall of the building shall be
• Permanent vent at the top equal to the 5% of the cross sectional area of
the enclosure and openable sashes at each floor level with area equal to
provided.
• The roof of the shaft shall be at least 1 mt. above the surrounding roof.
• There shall be no glazing or the glass bricks in any internal closing
wall of staircase.
facilities.
Ramps
greater than 1 in 8.
e)For building above 24.0 mt. in height access to ramps from any floor of the
f) In case of nursing homes, hospitals etc. area exceeding 300 sq.mt. at each
floor one of the exit facility shall be a ramp of not less than 2.4 mt. in
width.
PROVISION OF LIFTS
a)Provision of the lifts shall be made for all multi-storeyed building having a
b)All the floors shall be accessible for 24.0 hrs. by the lift. The lift provided in
emergency.
c)Grounding switch at ground floor level to enable the fire service to ground
installed therein.
Fire Lift
• The lift shall have a floor area of not less than 1.4 sq.mt, It shall have
a loading capacity of not less than 545 kg. (8 persons lift) with
mains in a building and the cables run in a route safe from fire, that
• Lights and fans in the elevator having wooden paneling or sheet steel
• The speed of the fire lift shall be such that it can reach to the
permitted for lifts and shall have solid doors with fire resistance of at least one
hour.
• A sign shall be posted and maintained on every floor at or near the lift
indicating that in case of fire, occupants shall use the stairs unless instructed
otherwise.
• The sign shall also contain a plan for each floor showing the location of the
stairways.
• Floor marking shall be done at each floor on the wall in front of the lift-landing
door.
danger of spread of fire, smokes of fumes thereby from one floor of fire area to
b) Air -Conditioning systems circulating air to more than one floor area should be
provided with dampers designed to closed automatically in case of fire and thereby
Such a system should also be provided with automatic controls to stop fans in case of fire,
unless arranged to remove smoke from a fire, in which case these should be designed
to remain in operation.
c) Air- conditioning system serving large places of assembly (over one thousand
persons), large departmental stores, or hostels with over 100 rooms in a single
smoke through the system in the case of fire in air filters or from other
sources drawn into the system even though there is insufficient heat to
corridor lighting circuits, lifts detection system, fire pumps, pressurization fans
and bowlers, P..A system, exit sign, smoke extraction system, in case of failure of
The generator shall be capable of taking starting current of all the machines and
If the stand by pump is driven by diesel engine, the generator supply need not be
The staircase and corridor lighting shall be on separate circuits and shall be
independently connected so that it could be operated by one switch
installation on the ground floor easily accessible to fire fighting staff at any
time irrespective of the position of the individual control of the light points,
if any. It should be of miniature circuit breaker type of switch so as to avoid
replacement of fuse in case of crisis.
b) Double throw switch shall be installed in the service room for terminating
the stand by supply.
rating. If ducts are larger than 10 sq.mt. the floor should seal them, but
provide suitable opening for the pipes to pass through, with the gaps sealed.
They shall not be located within the staircase enclosure or service shafts or air-
conditioning shafts. Inspection panel and door shall be tight fitting with 1
hour fire resistance; the chutes should be as far away as possible form exits.
c) Refuge chutes shall not be provided in staircase walls and A/C shafts etc.
PROVISION OF HELIPAD
1. Access
2. Wet Riser
3. Down Comer
4. Hose Reel
6. Yard Hydrant
8. Terrace Tanks
9. Fire Pump 17.Illuminated Exit Sign
per minute.
• The static storage water supply required for the above mentioned purpose
should entirely be accessible to the fire engines of the local fire service.
The slab need not been strengthened if the static tank is not located in
b) To prevent stagnation of water in the static water tank the suction tank of
the domestic water supply shall be fed only through an over flow
capacity.
c) The static water storage tank shall be provided with a fire
comer is provided.
AUTOMATIC SPRINKLERS
insisted.
residential buildings (Dwelling House, Boarding House and Hostels) above 24 mt.
height.
a) All residential buildings like dwelling housing (including flats) boarding houses and
hostels shall be equipped with manually operated electrical fire alarm system with one
b) The location of the call boxes shall be decided after taking into consideration their floor
b) The call boxes shall be of the break glass type without any moving parts. Where the call
is transmitted automatically to the control room without any other action on the part of
c) The circuit shall also include one or more batteries with a capacity of 48
ensure that all occupants of the floor shall be warned whenever any call
box is actuated.
e) The call boxes shall be so installed that they do not obstruct the exit ways
and yet their location can easily be noticed from either direction. The
base of the call box shall be at a height of 1.5 mt. from the floor level.
FIRE ALARM SYSTEM…
The guidelines for fire drill and evacuation etc. for high-rise building may be
seen in Appendix (B) of National Building Code part IV. All such
building shall prepare the fire orders duly approved by the Chief Fire
A qualified fire officer and trained staff shall be appointed for the following
buildings.
a)All high rise buildings above 30 mt. in height where covered area of one
Tourism Department and all hotels above 15 mt. in height with 150 beds
exceeding 100.
Any material giving out toxic gases/smoke if involved in the fire shall not be
The surface frames spread of the lining material shall conform to class-I of
The framework of the entire false ceiling would be provided with metallic sections
46
Basic Terminology used in Fire Safety Norms
• Combustible Material
• Down-comer
• Emergency Lighting
• Emergency Lighting System
• Escape Lighting
• Fire Door
• Fire Exit
• Fire Lift
• Fire Load
• Fire Resistance
• Fire Separation
• Fire Stop
• Fire Tower
than 100 mm internal diameter with landing valves on each
floor/landing. It is also fitted with inlet connections at ground
level for charging with water by pumping from fire service
appliances and air release valve at roof level to release trapped
air inside.